Belimo EPF+MP, EP065F+MP, EP080F+MP, EP100F+MP, EP125F+MP Technical Data Sheet

...
Page 1
Characterised control valve with sensor-operated flow control, 2-way, Flange, PN 16 (EPIV)
• Nominal voltage AC/DC 24 V
• Control modulating, communicative
• For closed cold and warm water systems
• Communication via Belimo MP-Bus or conventional control
• Conversion of active sensor signals and switching contacts
Type overview
Technical data sheet EP..F+MP
Type DN
[ ]DN[“]
EP065F+MP 65 2 1/2 8 480 EP080F+MP 80 3 11 660 EP100F+MP 100 4 20 1200 EP125F+MP 125 5 31 1860 EP150F+MP 150 6 45 2700
kvs theor.: Theoretical kvs value for pressure drop calculation
V’nom
[ l/s]
V’nom
[ l/min]
kvs theor.
[ m³/h]
50
74 126 195 254
PN
n(gl)
[ ]
16 3.2 16 3.2 16 3.2 16 3.2 16 3.2
[ ]
Technical data
Electrical data Nominal voltage AC/DC 24 V
Nominal voltage frequency 50/60 Hz Nominal voltage range AC 19.2...28.8 V / DC 21.6...28.8 V Power consumption in operation 9.5 W Power consumption in rest position 6.5 W Power consumption for wire sizing 13 VA Connection supply / control Cable 1 m, 4 x 0.75 mm² Parallel operation Yes (note the performance data)
Functional data
Torque Motor 20 Nm (DN 65...80)
40 Nm (DN 100...150)
Operating range Y DC 2...10 V Input Impedance 100 kΩ Operating range Y variable Start point DC 0.5...24 V
End point DC 8.5...32 V Options positioning signal Modulating (DC 0...32 V) Position feedback U DC 2...10 V Position feedback U note Max. 1 mA Position feedback U variable Start point DC 0.5...8 V
End point DC 2...10 V Sound power level Motor 45 dB(A) Adjustable flow rate V’max 30...100% of Vnom Control accuracy
Media
Medium temperature -10...120°C
Close-off pressure ∆ps 690 kPa Differential pressure ∆pmax 340 kPa
Flow characteristic equal percentage (VDI/VDE 2178), optimised in
Leakage rate air-bubble tight, leakage rate A (EN 12266-1) Pipe connectors Flange PN 16 according to EN 1092-2 Installation position upright to horizontal (in relation to the stem) Servicing maintenance-free Manual override with push-button, can be locked
±5% (of 25...100% Vnom) @ 20°C / Glycol 0%
vol.
Cold and warm water, water with glycol up to
max. 60% vol.
the opening range (switchable to linear)
www.belimo.com
EP..F+MP • en-ap • 2019-06-03 • subject to changes
1
Page 2
!
α
EP..F+MP
Technical data
Safety notes
Electr. 2-way PI-CCV EPIV, Flange, PN 16
Flow measurement Measuring principle Ultrasonic volumetric flow measurement
±2% (of 25...100% Vnom) @ 20°C / Glycol 0% vol.
Safety
Materials
Measuring accuracy flow
Min. flow measurement 1% of V’nom
Protection class IEC/EN III Safety Extra-Low Voltage (SELV) Degree of protection IEC/EN IP54 EMC CE according to 2014/30/EU Mode of operation Type 1 Rated impulse voltage supply / control 0.8 kV Control pollution degree 3 Ambient temperature -30...50°C Storage temperature -20...80°C Ambient humidity Max. 95% r.H., non-condensing
Flow measuring pipe EN-GJL-250 (GG 25), with protective paint Closing element stainless steel AISI 316 Stem seal EPDM Ball seat PTFE, O-ring Viton
• This device has been designed for use in stationary heating, ventilation and air conditioning systems and must not be used outside the specified field of application, especially in aircraft or in any other airborne means of transport.
• Outdoor application: only possible in case that no (sea)water, snow, ice, insolation or aggressive gases interfere directly with the actuator and that is ensured that the ambient conditions remain at any time within the thresholds according to the data sheet.
• Only authorised specialists may carry out installation. All applicable legal or institutional installation regulations must be complied during installation.
• The connection between the control valve and the measuring tube should not be separated.
• The device contains electrical and electronic components and must not be disposed of as household refuse. All locally valid regulations and requirements must be observed.
Product features
Mode of operation
The final controlling device is comprised of three components: characterised control valve (CCV), measuring pipe with volumetric flow sensor and the actuator itself.
The adjusted maximum flow (max) is assigned to the maximum positioning signal
(typically 10 V / 100%). The final controlling device can be controlled communicative or analogue. The medium is detected by the sensor in the measuring pipe and is applied as the flow value. The measured value is balanced with the setpoint. The
actuator corrects the deviation by changing the valve position. The angle of rotation α
varies according to the differential pressure through the final controlling element (see volumetric flow curves).
Flow characteristic
Flow rate curves
∆p
∆p
∆p
3
2
1
www.belimo.com
∆p1 < ∆p2 < ∆p
2
EP..F+MP • en-ap • 2019-06-03 • subject to changes
3
Page 3
Y
EP..F+MP
Product features
Transmission behaviour HE
Electr. 2-way PI-CCV EPIV, Flange, PN 16
Heat exchanger transmission behaviour Depending on the construction, temperature spread, medium and hydraulic circuit,
the power Q is not proportional to the water volumetric flow  (Curve 1). With the
classical type of temperature control, an attempt is made to maintain the control signal Y proportional to the power Q (Curve 2). This is achieved by means of an equal­percentage valve characteristic curve (Curve 3).
1
2
3
www.belimo.com
EP..F+MP • en-ap • 2019-06-03 • subject to changes
3
Page 4
100%
U5 [V]
U5 [V]
[V]
PP/MP
EP..F+MP
Product features
Control characteristics
Electr. 2-way PI-CCV EPIV, Flange, PN 16
The velocity of the medium is measured in the measuring component (sensor electronics) and converted to a flow rate signal. The positioning signal Y corresponds to the power Q via the exchanger, the volumetric flow is regulated in the EPIV. The control signal Y is converted into an
equal-percentage characteristic curve and provided with the Vmax value as the new
reference variable w. The momentary control deviation forms the positioning signal Y1 for the actuator. The specially configured control parameters in connection with the precise flow rate sensor ensure a stable quality of control. They are however not suitable for rapid control processes, i.e. for domestic water control. U5 displays the measured volumetric flow as voltage (factory setting). As an alternative, U5 can be used for displaying the valve opening angle. It is always in
reference to the respective Vnom, i.e. if Vmax is e.g. 50% of Vnom, then Y = 10 V, U5 = 5 V.
1. Standard equal percentage Vmax = Vnom / 2. effect Vmax < Vnom
1
nom
100%
2
nom
50%
50%
max
25%
0
100%
Y
A
A
1)
DN
w
k
max
D
D
Y [V]
0
Y
100%80% 80%
D
U
1)
Y
1
5
A
M
4
EP..F+MP • en-ap • 2019-06-03 • subject to changes
www.belimo.com
Page 5
100%
m
x
1%
Y
EP..F+MP
Product features
Definition
Electr. 2-way PI-CCV EPIV, Flange, PN 16
Flow control
Vnom is the maximum possible flow.
Vmax is the maximum flow rate which has been set with the greatest positioning signal. Vmax can be set between 30% and 100% of Vnom.
Vmin 0% (non-variable).
no
Creep flow suppression
100%
ma
Y
30%
0
Given the very low flow speed in the opening point, this can no longer be measured by the sensor within the required tolerance. This range is overridden electronically.
Opening valve The valve remains closed until the volumetric flow required by the positioning signal Y
corresponds to 1% of Vnom. The control along the valve characteristic curve is active
after this value has been exceeded.
Closing valve The control along the valve characteristic curve is active up to the required flow rate of
1% of Vnom. Once the level falls below this value, the flow rate is maintained at 1% of Vnom. If the level falls below the flow rate of 0.5% of Vnom required by the reference
variable Y, then the valve will close.
www.belimo.com
Converter for sensors
Configurable actuators
Positioning signal inversion
Hydraulic balancing
Manual override
High functional reliability
0
0.5%
1%
100%
Connection option for a sensor (active sensor or switching contact). The MP actuator serves as an analogue/digital converter for the transmission of the sensor signal via MP-Bus to the higher level system.
The factory settings cover the most common applications. Single parameters can be
modified with the Belimo Service Tools MFT-P or ZTH AP.
This can be inverted in cases of control with an analogue positioning signal. The inversion causes the reversal of the standard behaviour, i.e. at a positioning signal of
0%, regulation is to max, and the valve is closed at a positioning signal of 100%.
With the Belimo tools, the maximum flow rate (equivalent to 100% requirement) can be adjusted on-site, simply and reliably, in a few steps. If the device is integrated in the management system, then the balancing can be handled directly by the management system.
Manual override with push-button possible (the gear is disengaged for as long as the button is pressed or remains locked).
The actuator is overload protected, requires no limit switches and automatically stops when the end stop is reached.
EP..F+MP • en-ap • 2019-06-03 • subject to changes
5
Page 6
!
T
~
T
~
EP..F+MP
Accessories
Gateways
Electrical accessories
Service Tools
Electr. 2-way PI-CCV EPIV, Flange, PN 16
Description Type
Gateway MP zu BACnet MS/TP UK24BAC Gateway MP to Modbus RTU UK24MOD Gateway MP to LonWorks UK24LON Gateway MP to KNX UK24EIB
Description Type
Stem heating flange ISO 5211, F05 (30 W) ZR24-F05 Connection cable 5 m, A: RJ11 6/4, B: 6-pin New Generation for ZTH
AP
Connection cable 5 m, A: RJ11 6/4, B: free wire end for ZTH AP Connecting board MP-Bus for wiring boxes EXT-WR-FP20-MP (IP20) and EXT-WR-FP65-MP (IP65) MP-Bus power supply for MP actuators
Description Type
Service tool for configurable and communicative Belimo actuators / VAV controller and HVAC performance devices
Belimo PC-Tool, Software for adjustments and diagnostics, for MF/MP/ MOD/LON/KNX actuators incl. fire protection, CD with Software and instructions (de/en), for Windows operating systems
Adapter for Service-Tool ZTH MFT-C Level converter USB/MP ZIP-USB-MP
ZK1-GEN
ZK2-GEN ZFP2-MP
ZN230-24MP
ZTH AP
MFT-P
Electrical installation
Notes • Connection via safety isolating transformer.
• Parallel connection of other actuators possible. Observe the performance data.
Wiring diagrams
AC/DC 24 V, modulating Operation on the MP-Bus
+
1 32 5
Y
U
DC (0)2…10 V
2…10 V
DC
Cable colours:
1 = black 2 = red 3 = white 5 = orange
+
1 32 5
Y
Sensor
U
MP
Functions
Cable colours:
1 = black 2 = red 3 = white 5 = orange
6
EP..F+MP • en-ap • 2019-06-03 • subject to changes
www.belimo.com
Page 7
de
de
EP..F+MP
Electr. 2-way PI-CCV EPIV, Flange, PN 16
Functions
Functions when operated on MP-Bus
Connection on the MP-Bus Network topology
T
~
MP
+
A)
There are no restrictions for the network topology (star, ring, tree or
1235
U
Y
A) more actuators and sensors (max.8)
mixed forms are permitted). Supply and communication in one and the same 3-wire cable
• no shielding or twisting necessary
• no terminating resistors required
Connection of active sensors Connection of external switching contact
T
~
MP
+
T
~
MP
+
p
1235
U
Y
A)
A) more actuators and sensors (max.8)
• Supply AC/DC 24 V
• Output signal DC 0...10 V (max. DC 0...32 V)
• Resolution 30 mV
1235
Y
A)
A) more actuators and sensors (max.8)
• Switching current 16 mA @ 24 V
• Start point of the operating range
U
must be parameterised on the MP
actuator as ≥ 0.5 V
Functions for actuators with specific parameters (Configuration necessary)
Override control and limiting with AC 24 V with relay contacts Override control and limiting with DC 24 V with relay contacts
T
T
~
abd
5123
~
U
Y
e
e.g. 1N 4007
Y (DC 0 ... 10 V)
Close 
max
Open Y
ab
-
T
+
ab
~
Y
e
5123
U
Y (DC 0 ... 10 V)
ab
Close 
max
Y
Control 3-point
T
~
ab
1235
YU
www.belimo.com
U
e.g. 1N 4007
Position control: 90° = 100s Flow control: Vmax = 100s
EP..F+MP • en-ap • 2019-06-03 • subject to changes
7
Page 8
°9
EP..F+MP
Operating controls and indicators
Adaption
4
5
Installation notes
Recommended installation positions
2
Power
3
Status
Electr. 2-way PI-CCV EPIV, Flange, PN 16
2
Push-button and LED display green
Off: On: Press button:
3
Push-button and LED display yellow
Off: Flickering: On: Press button:
4
Gear disengagement button
Press button: Release button:
5
Service plug
For connecting parameterisation and service tools
Check power supply connection
2
Off and 3 On
No power supply or malfuntion In operation Triggers angle of rotation adaptation, followed by standard mode
Standard mode without MP bus MP communication active Adaptation or synchronising process active Confi rmation of the addressing
Gear disengages, motor stops, manual override possible Gear engages, synchronisation starts, followed by standard mode
Possible wiring error in power supply
The ball valve can be installed upright to horizontal. The ball valve may not be installed in a hanging position, i.e. with the stem pointing downwards.
Mounting position in the return
Water quality requirements
Stem heating
Servicing
90
Installation in the return is recommended.
The water quality requirements specified in VDI 2035 must be adhered to. Belimo valves are regulating devices. For the valves to function correctly in the long term, they must be kept free from particle debris (e.g. welding beads during installation work). The installation of suitable strainer is recommended.
The water must exhibit a conductivity ≥ 20 μS/cm during operation for correct
functioning. It should be noted that, under normal circumstances, even filling water with a lower conductivity will experience an elevation of its conductivity to above the minimum required value during filling and that the system can thus be put into operation. Elevation of conductivity during filling caused by:
- untreated residual water from pressure test or pre-rinsing
- metal salts (e.g. surface rust) dissolved out of the raw material
In cold water applications and warm humid ambient air can cause condensation in the actuators. This can lead to corrosion in the gear box of the actuator and causes a breakdown of it. In such applications, the use of a stem heating is provided. The stem heating must be enabled only when the system is in operation, because it does not have temperature control.
Ball valves, rotary actuators and sensors are maintenance-free.
8
Before any service work on the final controlling device is carried out, it is essential to isolate the rotary actuator from the power supply (by unplugging the electrical cable if necessary). Any pumps in the part of the piping system concerned must also be switched off and the appropriate slide valves closed (allow all components to cool down first if necessary and allways reduce the system pressure to ambient pressure level). The system must not be returned to service until the ball valve and the rotary actuator have been correctly reassembled in accordance with the instructions and the pipeline has been refilled by professionally trained personnel.
EP..F+MP • en-ap • 2019-06-03 • subject to changes
www.belimo.com
Page 9
∆p
2
∆p
: kPa
∆p
EP100F+MP kvs theor nom = 1200 l/min 50% * 1200 l/min = 600 l/min = 36 m /h
EP..F+MP
Installation notes
General notes
Minimum differential pressure
Flow direction
Inlet section
Valve selection
(pressure drop)
Electr. 2-way PI-CCV EPIV, Flange, PN 16
The direction of flow, specified by an arrow on the housing, is to be complied with, since otherwise the flow rate will be measured incorrectly.
In order to achieve the specified measuring accuracy, a flow-calming section or inflow section in the direction of the flow is to be provided upstream from the flow sensor. Its dimensions should be at least 5x DN.
DN L min.
65 5 x 65 mm = 325 mm
80 5 x 80 mm = 400 mm 100 5 x 100 mm = 500 mm 125 5 x 125 mm = 625 mm 150 5 x 150 mm = 750 mm
L
5 x DN
The valve is determined using the maximum required flow rate Vmax.
A calculation of the kvs value is not required.
Vmax = 30…100% of Vnom
If no hydraulic data are available, then the same valve DN can be selected as the heat exchanger nominal diameter.
The minimum required differential pressure (pressure drop through the valve) for
achieving the desired volumetric flow max can be calculated with the aid of the
theoretical kvs value (see type overview) and the below-mentioned formula. The
calculated value is dependent on the required maximum volumetric flow max. Higher
differential pressures are compensated for automatically by the valve.
Formula
= 100 x
min
max
k
vs theor.
max
k
vs theor.
min
: m3/h
: m3/h
Behaviour of sensor failure
www.belimo.com
Example (DN100 with the desired maximum flow rate = 50% nom)
= 100 x
min
. = 115 m /h
max
k
vs theor.
3
3
2
= 100 x = 10 kPa
36 m3/h
115 m3/h
2
In case of a flow sensor error, the EPIV will switch from flow control to position control. Once the error disappears, the EPIV will switch back to the normal control setting.
EP..F+MP • en-ap • 2019-06-03 • subject to changes
9
Page 10
EP..F+MP
Service
Service Tools connection
Electr. 2-way PI-CCV EPIV, Flange, PN 16
The actuator can be parameterised by ZTH AP via the service socket. For an extended parameterisation the PC tool can be connected.
Connection ZTH AP / PC-Tool
T
~
AC 24 V DC 24 V
– +
Dimensions / Weight
Dimensional drawings
Y U
1 32 5
UY
min. Y
min. X
H
D
d
K
If Y <180 mm, the extension of the hand crank must be demounted as necessary.
MP USB
ZTH AP
esc OK
i
USB
L
BELIMO PC-Tool
Type DN
Weight
[ ]L[ mm]H[ mm]D[ mm]d[ mm]K[ mm]X[ mm]Y[ mm]
EP065F+MP 65 379 205 185 4 x 19 145 220 150
26 kg
EP080F+MP 80 430 205 200 8 x 19 160 220 160 35 kg EP100F+MP 100 474 221 229 8 x 19 180 240 175 52 kg EP125F+MP 125 579 249 252 8 x 19 210 260 190 70 kg EP150F+MP 150 651 249 282 8 x 23 240 260 200 90 kg
Further documentation
Overview MP Cooperation Partners
• Tool connections
• Introduction to MP-Bus Technology
• General notes for project planning
10
EP..F+MP • en-ap • 2019-06-03 • subject to changes
www.belimo.com