Beko CLEARPOINT L 215 V, CLEARPOINT L 220 V, CLEARPOINT L 205 V, CLEARPOINT L 210 V, CLEARPOINT L 225 V Instructions For Installation And Operation Manual
Beko CLEARPOINT L 215 V, CLEARPOINT L 220 V, CLEARPOINT L 205 V, CLEARPOINT L 210 V, CLEARPOINT L 225 V, CLEARPOINT L 230 V, CLEARPOINT L 250 V, CLEARPOINT L 240 V, CLEARPOINT L 260 V, CLEARPOINT L 275 V, CLEARPOINT L 295 V Instructions For Installation And Operation Manual
Specifications and Main Features
Frequently Asked Questions
User Manual
EN - english
Instructions for installation and operation
Activated-carbon adsorber without dust filter
CLEARPOINT®L 205 – L295 V
Dear customer,
Thank you for deciding in favour of the CLEARPOINT®V activated-carbon adsorber. Please read these
installation and operating instructions carefully before mounting and starting up the CLEARPOINT®V
activated-carbon adsorber and follow our directions. Perfect functioning of the activated-carbon adsorber
can only be guaranteed when the provisions and notes stipulated here are strictly adhered to.
2CLEARPOINT® L 205 – L295 V
Type plate CLEARPOINT® V activated-carbon adsorber
17Dismantling and disposal ................................................................................................................46
18List of spare parts............................................................................................................................47
19EC Declaration of Conformity..........................................................................................................47
CLEARPOINT® L 205 – L295 V5
General advice
3General advice
Prior to starting up the CLEARPOINT®V activated carbon adsorber, it must be ensured that
the operating staff are instructed and skilled according to these instructions for installation and
operation with regard to the set-up, monitoring, operation and maintenance of the plant, as well
as to the safety measures to be observed.
The operating instructions must be accessible at all times at the place of application of the
device.
Non-observance of the installation and operating instructions involves risks for persons and
systems.
If you have any queries regarding these instructions, please contact BEKO TECHNOLOGIES
GMBH.
6CLEARPOINT® L 205 – L295 V
Safety instructions
4Safety instructions
4.1Safety labelling
Safety instructions whose non-observance represents a threat to life and physical condition or can lead to
property damage are labelled in accordance with DIN 4844 and ANSI Z535.
4.1.1Safety pictograms in accordance with DIN 4844
General danger symbol
Quickly escaping compressed air
Note
Observe operating instructions
Use eye protection
Wear light breathing protection
Use protective gloves
Wear ear protectors
CLEARPOINT® L 205 – L295 V7
Safety instructions
4.1.2Signal words in accordance with ANSI
Danger!
Warning!
Caution!
Notice!
Important!
Imminent hazard
Consequences of non-observance: serious injury or death
Potential hazard
Consequences of non-observance: possible serious injury or death
Imminent hazard
Consequences of non-observance: possibly injury or property damage
Potential hazard
Consequences of non-observance: possibly injury or property damage
Additional advice, info, hints
Consequences of non-observance: disadvantages during operation and maintenance, no
danger
8CLEARPOINT® L 205 – L295 V
4.2General safety instructions
Installation works must exclusively be carried out by authorised and qualified skilled
personnel. Prior to undertaking any measures on the CLEARPOINT®V, the skilled personnel
shall read up on the device by carefully studying the operating instructions. The operator is
responsible for the adherence to these provisions. The respective directives in force apply to
the qualification and expertise of the skilled personnel.
For safe operation, the device must only be installed and operated in accordance with the
indications in the operating instructions. In addition, the national and operational statutory
provisions and safety regulations, as well as the accident prevention regulations required for
the respective case of application, need to be observed during employment. This applies
accordingly when accessories are used.
Danger!
Compressed air!
Risk of serious injury or death through contact with quickly or suddenly escaping
compressed air or through bursting and/or unsecured plant components.
All types of installation, maintenance and repair works must only be carried out when the
CLEARPOINT®V is pressureless.
Safety instructions
It is the operator’s duty to ensure that the connected pressure generator is secured against
exceeding of the maximum operating overpressure and the temperature limits at the
CLEARPOINT®V.
Pressure relief valves used need to be arranged in such a manner that endangering of
persons is excluded. Where required, observe the manufacturer's additional advice. Suitable
and permissible arming devices need to be provided in accordance with the local regulations.
The max. permissible operating parameters, such as the operating overpressure,
temperature and volume flow must not be exceeded. The max. permissible operating
parameters are specified on the type plate and in the technical data (see "Technical data"
section).
Never make structural modifications to the plant!
Use suitable tools and genuine spare parts and accessories only!
Only use fittings and connecting elements that are approved for this application. It is of vital
importance to observe the specifications of the respective manufacturer. Ensure that the
connections are installed according to good professional practice.
Only use pipes, valves and fittings which are suitable for the pressure and temperature
range. It is of vital importance to observe the specifications of the manufacturer.
Sudden impact through pressure build-up can cause damage and escape of compressed air.
Avoid a sudden pressure build-up by operating the valves slowly.
Check all pipe connections subsequent to the installation and retighten them if necessary!
The general safety and accident prevention regulations apply!
Prior to the start-up, a leak test needs to be carried out. This test shall only be effected by
correspondingly qualified skilled personnel in compliance with the safety regulations.
Caution!
Unauthorised intervention!
Unauthorised interventions may endanger persons and plants and lead to
malfunction.
CLEARPOINT® L 205 – L295 V9
Safety instructions
Unauthorised interventions, modification and abuse of the pressure device are prohibited.
Operators of the devices must observe the local and national pressure equipment
regulations in the country of installation.
Danger!
High pressure!
Subsequent to the start-up, components of the plant are under pressure.
Risk of serious injury or death through contact with quickly or suddenly escaping
compressed air or through bursting and/or unsecured plant components.
Any installation, repair and maintenance works must only be carried out when the plant is
disconnected, pressureless and de-energised.
Warning!
Improper use and application!
Improper use and application can lead to injury and damage to plants.
The following use is considered improper and is therefore prohibited:
Exceeding the max. permissible operating pressure
Exceeding the max. permissible operating temperature
Exceeding the max. permissible volume flow
All individual cases of application which are described as improper
Caution!
Improper transport!
Improper transport can lead to injury and damage to plants.
The CLEARPOINT®V must only be transported and installed by qualified and authorised
skilled personnel.
Only use suitable and technically unobjectionable lifting tools!
Only use lifting tools with a sufficient carrying capacity!
The respective national regulations and directives in force must be adhered to. Otherwise,
personal injuries may occur.
NOTE!
Damage through defective components!
Under no circumstances should you start up a damaged CLEARPOINT®V. Defective
components can impair the operational reliability and cause further damage.
Caution!
Incorrect installation!
Incorrect installation of the CLEARPOINT V®may endanger persons.
Ensure that the personnel in charge of the installation of the CLEARPOINT®V are sufficiently
instructed and competent for this task.
10CLEARPOINT® L 205 – L295 V
Safety instructions
Danger!
Incorrect start-up!
The incorrect start-up of the CLEARPOINT®V may endanger persons.
Prior to starting up the CLEARPOINT®V, it must be ensured that the operating staff are
instructed according to these instructions for installation and operation with regard to the setup, monitoring, operation and maintenance of the plant, as well as to the safety measures to
be observed.
CAUTION!
Operational reliability at risk!
Overloading the CLEARPOINT®V can compromise the operational reliability!
Observe the permissible temperature range!
Do not exceed the permissible volume flow!
NOTE!
Operational reliability at risk!
Incorrect installation can compromise the operational reliability and affect service measures.
The clear diameter of the pipe joint must be at least as large as the mounting dimension of
the CLEARPOINT®V.
It is strongly recommended to install a shut-off valve both upstream and downstream of the
CLEARPOINT®V for the implementation of service measures.
To maintain the supply of compressed air during service failures, maintenance and repair
works on the CLEARPOINT®V, the installation of a bypass line around the CLEARPOINT®V
is advisable. This bypass line must have a shut-off valve.
Danger!
Mishandling!
Mishandling of the CLEARPOINT®V may endanger persons.
Prior to starting up the CLEARPOINT®V, it must be ensured that the operating staff are
instructed according to these instructions for installation and operation with regard to the setup, monitoring, operation and maintenance of the plant, as well as to the safety measures to
be observed.
CLEARPOINT® L 205 – L295 V11
Safety instructions
Danger!
Incorrect maintenance!
The incorrect maintenance of the CLEARPOINT®V may endanger persons.
Ensure that the personnel in charge of the operation, monitoring and maintenance of the
CLEARPOINT®V are sufficiently instructed and competent for this task.
Caution!
Activated-carbon dust!
Eyes and respiration are endangered through quickly or suddenly escaping activated-
carbon dust.
Activated carbon can produce dust and wear debris!
Use eye protection!
During the start-up of the activated-carbon adsorber, compressed air might escape and
cause a very loud expansion noise. Wear silencing ear protectors.
Wear personal protective clothing!
Wear light breathing protection at strong dust development!
Caution!
Activated carbon produces dust and wear debris!
Endangering through dust explosion.
Use suitable tools and ex-protection-tested suction plants and accessories. Observe the
safety instructions.
12CLEARPOINT® L 205 – L295 V
Safety instructions
4.3Special advice for plants under pressure in accordance with the 97/23/EC
Pressure Equipment Directive
The CLEARPOINT®V activated-carbon adsorber is a pressure device in the sense of the 97/23/EC
Pressure Equipment Directive. Therefore, the plant needs to be registered with the supervisory authority
in accordance with the local regulations, and requires the approval of the latter.
For the examination prior to the start-up and for periodic inspections, the national regulations need to be
observed, such as the industrial safety regulation in the Federal Republic of Germany. In countries
outside the EU, the respective regulations in force there need to be adhered to.
The proper use of pressure devices is the basic requirement for safe operation. As regards pressure
devices, the following needs to be observed:
The CLEARPOINT®V must only be employed within the pressure and temperature range limits
indicated by the manufacturer on the type plate.
No welding must be carried out on the pressure vessel of the device.
The CLEARPOINT®V must neither be installed in insufficiently ventilated rooms nor near heat
sources or inflammable substances.
To avoid fractures resulting from material fatigue, the CLEARPOINT®V should not be exposed
to vibrations during operation.
The maximum operating pressure indicated by the manufacturer on the type plate must not be
exceeded. It is the operator's responsibility to install the appropriate safety and control devices.
Prior to the start-up of the CLEARPOINT®V, the connected pressure generator (compressor
etc.) must be safeguarded against exceeding of the max. permissible operating pressure. The
integrated safeguard needs to be checked by an approved inspection agency.
The documents related to the CLEARPOINT®V (manual, operating instructions, manufacturer's
declaration etc.) must be kept safe for future reference.
No objects whatsoever must be installed or placed on the CLEARPOINT®V and the connecting
lines.
Installation of the plant in frost-free places only.
WARNING!
Unauthorised intervention!
Unauthorised interventions may endanger persons and plants and lead to malfunction.
Unauthorised interventions, modification and abuse of the pressure devices are prohibited.
Operators of the devices must observe the local and national pressure equipment
regulations in the country of installation.
Warning!
High pressure!
Subsequent of the start-up of the CLEARPOINT®V components of the plant are under
pressure. Serious injuries are possible.
Any installation, repair and maintenance works on the CLEARPOINT®V must only be carried
out when the plant is pressureless.
CLEARPOINT® L 205 – L295 V13
Residual risk
5Residual risk
The plant offers state-of-the-art technology. However, certain residual risks remain.
Risk through disregard of the safety instructions.
The safety instructions included in these operating instructions point to further residual risks. It is,
therefore, of vital importance to observe all safety instructions.
6Field of application and proper use of the CLEARPOINT®V activated-carbon
adsorber
These operating instructions apply exclusively to the tank variants of the CLEARPOINT®L205 V to L295
V activated-carbon adsorbers from BEKO TECHNOLOGIES GMBH and refer to the device type without
dust filter and internal tubing.
The CLEARPOINT V®activated-carbon adsorber must only be applied under the conditions described in
this user manual, and only in connection with the components recommended or approved by the
manufacturer.
The field of application comprises the reduction of oil vapours and odorous substances from compressed
air or nitrogen. The system is intended for the use under industrial conditions inside buildings.
Any other use is considered improper. The manufacturer shall not be liable for problems occurring as a
consequence of improper use. The operator alone is responsible for any hazard resulting from that.
Please check, prior to reading the operating instructions, whether or not these instructions
correspond to the device.
Read these installation and operating instructions carefully prior to any intervention regarding
the CLEARPOINT®V.
The operating instructions must be accessible at all times at the place of application of the
device.
If you have any queries regarding these instructions, please contact BEKO TECHNOLOGIES
GMBH.
To ensure safe operation, the device must only be operated and maintained in accordance
with the indications in the operating instructions. In addition, the national and operational
statutory provisions and safety regulations, as well as the accident prevention regulations
required for the respective case of application, need to be observed during employment. This
applies accordingly when accessories are used.
Non-observance of the installation and operating instructions involves risks for persons and
systems.
Proper functioning and trouble-free operation of the activated-carbon adsorber is only ensured when the
transport, storage, set-up, installation, operation and maintenance are carried out in accordance with the
advice included in this user manual.
To handle the plant, the personnel must be trained to deal with devices of the compressed-air technology
and need to know the contents of this user manual as far as handling is concerned.
To start up and maintain the plant, the personnel must be familiar with the safety concepts of the
compressed-air technology. The personnel must be authorised and trained in such a manner that they
are capable of starting up and maintaining such facilities.
The proper employment and use of the CLEARPOINT®V according to the directions requires the exact
compliance with the installation instructions, in particular in respect of:
14CLEARPOINT® L 205 – L295 V
Applied EU directives and harmonised standards
The place of installation, installation conditions
The pressure and temperature of the inlet air
The ambient temperature
The device is supplied as accepted in the factory. The operator only needs to establish the connections
with the compressed-air system, which is described in the following chapters.
WARNING!
Improper use!
The following is considered as improper use and is prohibited:
Exceeding the max. permissible operating pressure
Exceeding the max. permissible operating temperature
Exceeding the max. permissible volume flow
Employment of the CLEARPOINT®V in hazardous areas
All individual cases of application which are not described as proper us
7Applied EU directives and harmonised standards
Applied EU directives:
97/23/ECPressure Equipment Directive
Harmonised standards applied:
EN 10216-2:Seamless steel tubes for pressure purposes. Technical delivery conditions -
Part 2: Non-alloy and alloy steel tubes with specified elevated temperature
properties
EN 10028-2:Flat products made of steels for pressure purposes - Part 2: Non-alloy and alloy
steels with specified elevated temperature properties
EN 10242:Threaded pipe fitting in malleable cast iron
AD-2000 bulletins
CLEARPOINT® L 205 – L295 V15