Beijer Electronics CAN J1939 User Manual

Expansion Module for CAN J1939
Installation
MAEN962 2009 -02
English
Installation of Expansion Module for CAN J1939
The expansion module is used for the operator panel to communicate via CAN J1939. The correct driver must be installed in the operator panel.

Important

Read the entire installation instructions prior to installing and using this equip­ment. Only qualified personnel may install, operate or repair this equipment. Users must acquire the appropriate knowledge to use the equipment properly. The manufacturer does not assume any responsibility for modified, altered or renovated equipment.
THE MANUFACTURER SHALL NOT BE LIABLE TO ANYONE FOR ANY DIRECT, INDIRECT, SPECIAL, INCIDENTAL, OR CONSEQUEN­TAL DAMAGES RESULTING FROM THE INSTALLATION, USE OR RE­PAIR OF THIS EQUIPMENT, WHETHER ARISING IN TORT, CONTRACT, OR OTHERWISE. BUYER’S SOLE REMEDY SHALL BE THE REPAIR, REPLACEMENT, OR REFUND OF PURCHASE PRICE, AND THE CHOICE OF THE APPLICABLE REMEDY SHALL BE AT THE SOLE DISCRETION OF THE MANUFACTURER.
Attention:
Observe pr ecautions for handling electrostatic sen sitive device s.

Technical Data

Size, W x H x D 87 x 70 x 30 mm Weight 0.12 kg
Installation of Expansion Module for CAN J1939Installation of Expansion Module for CAN J1939

Space Requirements

70 mm
30 mm

Installation

1. Unpack and check the delivery. If damage is found, notify the supplier.
M3x6 - 4 pcs
Note:
Place the panel on a stable surface during installation. Dropping it or letting it fall may cause damage.
2. Disconnect the operator panel from the power supply.
3. Remove the plastic cover from the expansion port.
4. Secure the expansion module in position, using the provided screws.
5. Connect the operator panel to the power supply.

Cable Connection

The pins for the CAN connection are used according to the description below.
12345
Pin Description
1Not used 2 Connection to CAN High 3 Connection to CAN Low 4Not used 5 Connection to CAN Shield
Note:
The last user on the CAN bus must be terminated with R120
Ω.

Settings in the Configuration Tool

Double-click on the Peripherals folder in the Project Manager in the configuration tool for the operator panel.
Right-click on Expansion Port and select Fieldbus. Then drag Controller 1 or Controller 2 with the corresponding driver to the Fieldbus icon. To change the se­lected driver, select Properties from the Project menu.
For further information, please see the information for the driver.
Loading...