Beijer Electronics BoX2 pro Installation Manual

Page 1
BoX2pro
InstallationManual
English
MAEN275,2018-03
Page 2
Page 3
Foreword
Installationmanual forBoX2pro
All operator panelsare developed to satisfy the demands of human-machine communication. Built-in functions such as displaying and controlling text, dynamic indication, time channels, alarm and recipe handling are included.
The operator panel works primarily in an object-oriented way, making it easy to understand and use. Configuration is carried out on a PC using iX Developer software. The project can then be transferred and stored in the operator panel itself.
Various types of automation equipment such as PLCs, servos or drives can be connected to the operator panels. In this manual, t he term “thecontroller” refers to the connected equipment.
This manual explains how to install the operator panel. Please refer to the iX Developer reference manual for further information.
Order no: MAEN275
Copyright © 2018-03 Beijer Electronics AB. All rights reserved.
The information in this document is subject to changewithoutnoticeandisprovidedasavailableatthe
time of printing. Beijer Electronics AB, including all its group companies, reserves the right to change any
information without updating this publication. Beijer Electronics A B,includingallits group companies,
assumesnoresponsibilityforanyerrorsthatmayappear in this document. Read the entire installation
manual prior to installing and using this equipment. Only qualified personnel may install, operate or repair
this equipment. Beijer Electronics AB, including all its group companies, are not responsible for modified,
altered or renovatedequipment. Because the equipment has a wide range of applications, users must acquire
the appropriate knowledge to use the equipment properly in their specific applications. Persons responsible
for the application and the equipment must themselves ensure that each application is in compliance with
all relevant requirements,standardsandlegislationinrespecttoconfigurationandsafety. Onlypartsand
accessoriesmanufacturedaccording to specifications set by Beijer Electronics AB, including all its group
companies, may be used.
BEIJER ELECTRONICS AB, INCLUDING ALL ITS GROUP COMPANIES,SHALL NOT BE LIABLE TO ANYONE FOR ANY DIRECT, INDIRECT, SPECIAL, INCIDENTALOR CONSEQUENTIAL DAMAGES RESULTINGFROMTHE I NSTALLATION,USE OR REPAIROF THIS EQUIPMENT, WHETHER ARISING IN TORT, CONTRACT, OR OTHERWISE. BUYER'S SOLE REMEDY SHALL BE THE REPAIR, REPLACEMENT, OR REFUND OF PURCHASE PRICE, AND THE CHOICE OF THE APPLICABLE REMEDY SHALL BE AT THE SOLE DISCRETION OF BEIJER ELECTRONICS AB, INCLUDING ALL ITS GROUP COMPANIES.
BeijerElectronics, MAEN275
Page 4
Foreword
BeijerElectronics, MAEN275
Page 5
Contents
Contents
1 Safety Precautions ....................................................... 7
1.1 General ...........................................................
7
1.2 Hazardous Materials .... . ........................................
7
1.3 Disposal RequirementsUnder WEEE Regulations ...........
8
1.4 UL and cUL Installation .........................................
8
1.5 During Installation ..............................................
9
1.6 During Use .......................................................
10
1.7 Service and Maintenance ........................................
10
1.8 Dismantling and Scrapping .....................................
10
2 Installation ............................................................... 11
2.1 InstallationProcess ..............................................
11
2.1.1 Connectionsto the Controller ......... .........................
12
2.1.2 OtherConnectionsandPeripherals .............................
13
3 TechnicalData ........................................................... 15
4 ChemicalResistance .................................................... 17
4.1 Metal Casing .....................................................
17
5 OperatorPanel Drawings .............................................. 19
5.1 Connectors .......................................................
19
5.1.1 CommunicationPorts ...........................................
19
5.2 BoX2 pro Outline ................................................
20
6 Additional Installation Tips . . .......................................... 21
6.1 Grounding the operator panel ..................................
21
6.2 Ethernet Connection in the OperatorPanel ...................
22
6.3 To Achieve Better EMC Protection .............................
23
6.4 Ambient Temperature ...........................................
24
6.5 Safety .............................................................
25
6.6 Galvanic Isolation ................................................
26
6.7 Cable and Bus Termination RS-485 ............................
27
BeijerElectronics, MAEN275
Page 6
Contents
BeijerElectronics, MAEN275
Page 7
Safety Precautions
1SafetyPrecautions
Both the installer and the owner and/or operator of the operator panel must read and understand this installation manual.
1.1 General
Read the safety precautions carefully.
Check the delivery for transportationdamage. If damage is found, notify the
supplier as soon as possible.
Do not use the operator panel i n an environment with high explosive hazards.
The supplier is not responsible for modified, altered or reconstructed
equipment.
Use only parts and accessories manufactured according to specifications of
the supplier.
Read the installation and operating instructions carefully before installing,
using or repairing the operator panel.
Neverallowfluids,metalfilingsorwiringdebristoenteranyopeningsinthe
operator panel. This may cause fire or electrical shock.
Only qualified personnel may operate the operator panel.
Thefiguresinthismanualserveanillustrativepurpose. Becauseofthemany
variables associated with any particular installation, the supplier cannot assume responsibility for actual use based on the figures.
The supplier neither guarantees that the operator panel is suitable for your
particular application, nor assumes responsibility for your product design, installation or operation.
It is recommended to turn on and shut down the operator panel at least once
before installing any components/cards or before connecting the operator panel to external devices; for example serial devices.
ForMarine panels only:
The operator panelmust be installed and operated as described in this
document to meet thiscertification.
Observe precautions for handling electrostatic discharge sensitive devices
1.2 HazardousMaterials
Toxic andhazardousmaterialsor elements
有毒和有害的材料或元素
Partdescription
零件描述
Pb Hg Cd Cr6+ PBB PBDE
PCBandelectronic components
PCB和电子元件
XOO O O O
O:Indicatesthattheconcentration ofthehazardoussubstanceinallhomogeneous materialsinthepartsisbelowtherelevantthresholdof theGB/T26572-2011 standard.
O: 表示该有害物质在该部件所有均质材料中的含量均在 GB/T26572-2011规定的限 量要求以下。
X:Indicatesthattheconcentrationofthehazardoussubstanceof atleastoneof allhomogeneousmaterialsinthepartsisabovetherelevantthresholdof theGB/T
BeijerElectronics, MAEN275
7
Page 8
Safety Precautions
26572-2011standard. But stillcomplieswiththeEU RoHSDirective2011/65/EU.
X:表明该有害物质至少在部件的某一均质材料中的含量超出GB/T26572-2011规定 的限量要求。但仍然符合EURoHS 指令2011/65/EU
1.3 DisposalRequirementsUnder WEEERegulations
Forprofessional users in the European Union: If you wish to discard electrical and electronic equipment (EEE), please contact your dealer or supplier for further information.
Fordisposal in countries outside of the European Union: If you wish to discard this product please contact your local authorities or dealer and ask for the correct method of disposal.
1.4 ULandcULInstallation
Caution:
Thissectionisonlyvalidfor ULlabeledX2panels.
This equipment is suitable for use in Class 2 non-hazardous locations only.
[Combinations of equipment in your system are subject to investigation by the local authority havingjurisdiction at the time of installation].
All devices have to be supplied by a Class 2 power supply.
Warning:
OnlyULandcUL approvedexpansionunitsareallowedtobeconnected to theportdesignated“EXPANSION”. Atthemoment therearenosuch units evaluatedorallowed.
SEULESLESUNITÉSD'E XTENSIONCERTIFIÉESULET cULPEUVENTÊTRE RACCORDÉESAUPORTDÉSIGNÉ«EXPANSION». ÀL'HEUREACTUELLE,AUCUNE UNITÉDECETYPE N'AÉTÉTESTÉE OUAUTORISÉE.
This equipment is suitable for use in Class 2 non-hazardous locations only.
[combinations of equipment in your system are subject to investigation by the local authority having jurisdiction at the time of installation].
All devices have to be supplied by a Class 2 power supply.
Warning:
OnlyULandc
ULapprovedexpansionunits areallowedtobeconnected to
theportde
signated“EXPANSION”. Atthemomentthereare nosuchunits
evaluate
dorallowed.
SEULESL
ESUNITÉSD'EXTENSIONCERTIFIÉESULET
cULPE
UVENTÊTRERACCORDÉESAUPORTDÉSIGNÉ«EXPANSION».
ÀL'HE
UREACTUELLE,AUCUNEUNITÉDE CETYPEN'AÉTÉ TESTÉE
OUAU
TORISÉE
8
BeijerElectronics, MAEN275
Page 9
Safety Precautions
Warning:
Batterymayexplodeifmistreated. Do notrecharge,disassembleor dispose ofinre.
LABATTERIEP E UT EXPLOSERENCAS DEMAUVAISEMANIPULATION. NELARECHARGEZPAS,NELADÉMONTEZ PAS ETNELA JETEZ PAS DANS LE FEU.
This product contains a battery; this must only be changed in an area known
to be non-hazardous.
Replace the battery with a BR 2032 battery. Useof another type of battery
may present a risk of fire or explosion.
Foruse on a flat surface of a type 4X enclosure indoor use only.
Use minimum 75°C copper conductors only.
To make wiring connections to the power supply connector, follow the table
with cable and torque specifications below:
Terminal BlockConnector WireSizeAWG Torque (Lb.In.)
X1/X100Phoenixconnectors AWG30– 12 5–7 X1/X100Anytek connectors AWG24– 12 3.5 X1/X100DECA connectors AWG24–12 7
ThesedevicesareClass2suppliedprogrammablecontrollers(industrialPCs)
for the use in industrial control equipment and are intended to be (front) panel mounted (Type 12 and 4x for indoor use only).
Caution:
TheenclosureprovidesadegreeofprotectionofatleastIP20,butwheninstalledinan apparatus,itshouldmeetIP65..
LEBOÎTIEROFFREUN DEGRÉDEPROTECTIOND'AUMOINSIP20,MAIS LORSQU'ILESTINSTALLÉDANSUNAPPAREIL,ILDOITÊTRE DECLASSEIP65.
1.5 DuringInstallation
The operator pane
l is designed for stationary installation on a planar surface,
where the followi
ng conditions are fulfilled:
no high explosiv
erisks
no strong magne
tic fields
no direct sunl
ight
no large, su
dden temperature changes
Install the operator panel according to the accompanying installation
instructions.
Ground the operator panel according to the accompanying installation
instructions.
Only qualified personnel may install the operator panel.
Separate the high voltage, signal, and supply cables.
Make sure that the voltage and polarity of the power source is correct before
connecting the operator panel to the power outlet.
BeijerElectronics, MAEN275
9
Page 10
Safety Precautions
Peripheralequipment must be appropriate for the application and location.
1.6 DuringUse
Keep the operator panel clean.
Emergency stop and other safety functions may not be controlled from the
operator panel.
1.7 ServiceandMaintenance
Only qualified personnel should carry out repairs.
The agreed warranty applies.
Before carrying out any cleaning or maintenance operations, disconnect the
equipment from the electrical supply.
Replacing the battery incorrectly may result in explosion. Only use batteries
recommended by the supplier. During the warranty period, the battery needs to be replaced by an authorized Beijer Electronics service center.
1.8 DismantlingandScrapping
The operator panel or parts thereof shall be recycled acco
rding to local
regulations.
The following components contain substances th
at might be hazardous to
health and the environment: lithium batteryan
d electrolytic capacitor.
10
BeijerElectronics, MAEN275
Page 11
Installation
2Installation
2.1 InstallationProcess
5.5
11.7
63
5.5
63
11.7
127.6 M4 x 0.7
8
1 (6x)
63
5.5
TheBoX2procanbeusedasabenc
h top device or clipped onto a DIN rail. For
custom mounting, the DIN rail m
ount can be moved from the standard position,
opposite the connection, to a
side. The mount can be removed for access to all the
mounting points shown ab
ove.
The following is needed:
No tools required - stand
ard usage
A Phillips screwdriver
for movement or removal of the DIN rail mounting
bracket
1.
Unpackand check the delivery. If damage is found,notify the supplier.
Note:
Placetheoperatorpanelo n astablesurfaceduring installation. Droppingtheoperatorpanelorlettingitfallmay causedamage.
BeijerElectronics, MAEN275
11
Page 12
Installation
2.
Connect the cables in thespecified order, according to the drawing and steps below.
Caution:
Theoperatorpanelmustbebroughtto ambienttemperaturebeforeitisstarted
up. Ifcondensationforms,ensurethat theoperatorpanelisd ry beforeconnecting ittothepoweroutlet.
Ensurethattheoperatorpaneland thecontrollersystemhavethe sameelectrical
grounding(referencevoltagelevel),otherwiseerrors incommunicationmay occur.
Ensurethatthe voltageandpolarityofthepowersourceiscorrect.
Separatehighvoltagecablesfromsignalandsupplycables.
Shieldedcommunicationcablesarerecommended.
24V DC
RS232/ RS422/ RS485
24V DC
A
D
Controller
Power
B
Ethernet
C
The image is ill ustrative only and may differ slightly from the actual panel.
Connect cable A. Connect cable B, using 14-20 AWG (2.08–0.52 mm
2
), 180–220 N-cm
torque.
Connect cable C. Connect cable D. The recommended cross-section of the cable is 1.5
mm
2
.
2.1.1 ConnectionstotheController
Forinformation about the cablesto be used when connecting the operator panel to the controller, please refer to the help file for the driver in question.
12
BeijerElectronics, MAEN275
Page 13
Installation
2.1.2 OtherConnectionsandPeripherals
Cables, peripheralequipment and accessories must be suitable for the application and its environment. For further details or recommendations, please refer to the supplier.
BeijerElectronics, MAEN275
13
Page 14
Installation
14
BeijerElectronics, MAEN275
Page 15
Technical Data
3TechnicalData
Parameter BoX2 pro
Dimensions,W×H×D 128×101×39mm Sealing IP20 Framematerial Powder-coatedaluminum Weight 0.4 kg CPU i.MX6DualLite
DualARMCortex-A9Core
1.0GHz 512kBL2cache
Serialports StandardD-sub(9Pin,female)
COM1: RS-232withRTS/CTS COM2: RS-422/RS-485 COM3: RS-485
EthernetLANA 10/100MbitBase-T(shieldedRJ45withLEDs) EthernetLANB 10/100MbitBase-T(shieldedRJ45withLEDs) USB 1×USBHost 2.0,maxoutputcurrent500 mA
SupportsuptoUSB 2.0HighSpeed
Externalstorage media
1×SDcard
Flashmemory (application memory)
1.5GBSSD(eMMC)
MemoryRAM 1GBDDR3 NVRAM 128kB Real timeclock Yes Battery BR2032lithiumbattery,
replaceable
Powerconsumption atratedvoltage
5W
Fuse InternalDCfuse,3.14AT,5×20mm Powersupply +24VDC(18–32VDC)
CE:Thepowersupplymustconformw ith therequirements accordingtoEN/IEC60950andEN/IEC61558-2-4. ULandcUL:Thepowersupplymustconformwiththe requirementsforclass2power supplies.
Operating temperature
-10°Cto+60°C
Storagetemperature -20°Cto+70°C Relativehumidityin
operation
5%–85%non-condensation
Vibration 1g,accordingtoEN/IEC 60068-2-6,Test Fc Mechanicalshock 15g,half-sine,11msaccordingtoEN/IEC60068-2-27 Approvalsand
certications
CE/FCC/KC Informationisavailableon www.beijerelectronics.com
BeijerElectronics, MAEN275
15
Page 16
Technical Data
Parameter BoX2 pro
ULapproval Yes, informationavailableatUL.com Marinecerticates Informationisavailableonwww.beijerelectronics.com
16
BeijerElectronics, MAEN275
Page 17
Chemical Resistance
4 ChemicalResistance
4.1 MetalCasing
The frame and c asing material is powder-coated aluminum. This powder paint withstands exposure to the following chemicalswithout visible change:
Aceticacid10% Phosphoricacid4% Citricacid10% Phosphoricacid10% Diesel Seawater Distilledwater Sodiumchloride2% Edibleoil Sodiumchloride20% Fueloil Sulphuricacid20% Hydrogenperoxide3% Tapwater
The powder paint shows limited resistance to the f
ollowing chemicals at room
temperature:
Butanol Nitricacid3% Hydrochloricacid5% Nitricacid10% Isopropylalcohol Phosphoricacid43% Sodiumhypochlorite10% Turpentine
Note:
Ifexposure toanyof theabovechemicalsisdemanded, itisrecommendedtorsttest thechemicalinahidden spotofthemetalcasing.
Thepowderpaintshowslittleornoresistancetothefollowingchemicalsatroom temperature:
Aceticacid,conc. Methyl-ethylketone Toluene Acetone Nitricacid30% Trichlorethylene Ammonia5% Phenol Xylene Ammonia,conc. Sodiumhydroxide5% 97octaneunleadedpetrol Ethylacetate Sodiumhydroxide30% 98octaneleadedpetrol
BeijerElectronics, MAEN275
17
Page 18
Chemical Resistance
18
BeijerElectronics, MAEN275
Page 19
Operator PanelDrawings
5 OperatorPanelDrawings
5.1 Connectors
1
2
34
Pos. Connector Description
1 Powersupply +24VDC(18–32V DC) 2 LANA 1×10/100Base-T(shieldedRJ45) 3 LANB 1×10/100Base-T (shieldedRJ45) 4 COM Serialcommunication port
5.1.1 CommunicationPorts
Serialport,9-pin female
Pin
COM1 COM2 COM 3
1-
RS-422Tx+
RS-485Tx+/Rx+
-
2RS-232RxD - ­3RS-232TxD - ­4 - RS-422Rx+ RS-485T x+/Rx+ 5GND GND -
6-
RS-422Tx-
RS-485Tx-/Rx-
-
7RS-232RTS - ­8RS-232CTS - ­9 - RS-422Rx- RS-485Tx-/Rx-
Note:
Inordertoutilizetwocommunication ports,theY-split cableCAB109mustbeused. InordertoutilizethreecommunicationportsthesplitcableCAB150 mustbeused. TouseRS-232andRS-422,useCAB 109. TouseRS-232andRS-485,useCAB 150.
BeijerElectronics, MAEN275
19
Page 20
Operator PanelDrawings
5.2 BoX2proOutline
128
86
78
14
39
Note:
AStepCADle isavailableonthewebsitewww.beijerelectronics.com
20
BeijerElectronics, MAEN275
Page 21
Additional Installation Tips
6 AdditionalInstallationTips
When experiencingcommunication problemsin noisy environments or when operating close to temperature limits, the following recommendations are to be noticed.
6.1 Groundingtheoperatorpanel
1
2
3
4
5
6
5350
Door
Operator panel
Ferrite core
Mounting plate in the cabinet
Power supply
24 V DC
The mounting clamps of the operator panel do not provide a secure grounding connection between the panel and the device cabinet, see 1 in drawing above.
1.
Connect a wire, that is sized correctly according to local electrical codes, between the quick-connect terminal connector on the operator panel and the chassis of the panel, see 2 in drawing above.
2.
Connect a wire or grounding braid, that is sized correctly according to local electrical codes, between the chassis of the operator panel and the closest grounding point on the door, see 3 in drawing above.
3.
Connect a strong but short grounding braidbetween the door and the device cabinet,see 4 in drawing above.
4.
Twist the cables onto the24
V DC feed, see 5 in drawing above. 2 turns around the ferrite core provide 4 times the suppression of 1 turn. 3 turns around the ferrite
core provide 9 times the suppression of 1 turn.
Connect a wire or grounding braid, that is sized correctly according to local electrical codes, between the chassis of the operator panel and the closest grounding point.
BeijerElectronics, MAEN275
21
Page 22
Additional Installation Tips
Note:
Thegroundingwiresshouldbeshortandtheconductor shouldhavealargearea. Along,thingroundingwire hasaveryhigh impedance(resistance)athighfrequencies anddoesnot guidedisturbancestotheground. Multi-wireconductorsarebetterthan singlewireconductorswiththesamearea. Abraidedconductorwire withthesameareais evenbetter. Thebest isashort,thick groundingbraid.
6.2 EthernetConnectioninthe OperatorPanel
1
2
3
4
5
RJ45
RJ45
RJ45
RJ45
RJ45
RJ45
RJ45
RJ45
Industrial Ethernet
Operator panel
Operator panel
Operator panel
Operator panel
Shielded
Short and unshielded
0.1 μF 250 V
1-1 3-3
8-8
2-2
In some industrial unitsfor Ethernet, the RJ45 contact’sshield is connected to the chassis via a capacitor, see 1 in drawing above.
The operator panel’sEthernet shield is directly connected to the chassis, see 2 in drawing above.
1.
Check whether the other Ethernet unit has its shield directly grounded or grounded via a capacitor.
Note:
Inmanycases,connectingtheshieldedEthernetcablingtothechassisat bothendsis inappropriate. Humorgroundingloops canoccur. Unshieldedcablingmayevenresult infewercommunicationerrors.
22
BeijerElectronics, MAEN275
Page 23
Additional Installation Tips
A good solution may be to use a shielded Ethernet cable, but to connect the shield at one end only.
One option is tobreak the shield, see 3 in drawing above. A more elegant methodis to expand the shielded Ethernet cabling with a pieceof
unshielded Ethernet cable, see 4 in drawing above. The shield can be grounded via an external 0.1 μF/250 V film capacitor,see 5 in
drawing above. This connects the HF transients to ground.
6.3 ToAchieveBetterEMCProtection
Initially, use the original cabling from Beijer Electronics primarily.
Useshielded cables for RS-232 communication.
Usetwisted pair and shielded cabling for RS-422 and RS-485.
Usethe cabling intended for the bus type; Ethernet, Profibus, CC-Link,
CAN, Device Net etc.
Install and connect according to applicable specifications for the relevant bus
standard.
Useshielded cabling for Ethernet,preferably with foil and a braided shield.
D-sub covers should be shielded, and the shield should be connected to the
cover 360° where the cable enters.
Connect the shield at bothends.
Shielded cable
Not same potential
Ground plane 1 Ground plane 2
Ground plate Ground plate in another building
0.1 μF/250 V
With longer distances, there is a risk that the ground potential may be different. In that case, the shield should only be connectedat one end. A good alternative is to connect the other end of the shield to the ground via a 0.1 μF/250 V film capacitor. Both ends are then connected to the ground in terms of HF, but only connected to the ground at one end in terms of LF, thus avoiding the 50/60 Hz grounding loops.
Metal cabinet Metal cabinet
Terminal or connector Terminal or connector
EMC cable gland
Plastic cable gland
Shielded cable
Short distance
Cable clamp in steel
Shielded cable
1.
Usean EMCcable gland or regular plastic cable gland, remove the outer jacket andconnecttheshieldtotheinstallation plate with a 360° metal cable clamp.
BeijerElectronics, MAEN275
23
Page 24
Additional Installation Tips
2.
Place the 24 V DC and communicationscabling in one cable trunk/cable duct and 230/380 V AC in another. If the cables need to be crossed, cross them at 90° only. Avoid combining the cabling for stronger 24 V DC outputs with the communication cabling.
Ferritecores that are snapped onto the shielded cabling may remove minor disturbances. Large ferrite pieces that are snapped onto unshielded cabling and where the wires go 2-4 times around the cores are approximately 5-25 times more efficient.
6.4 AmbientTemperature
The maximum ambient temperature for the operator panel is provided in the specifications. The ambient temperature refers to the temperature in the device cabinet which cools the operator panel’selectronics.
Operator panel
Powe r
Powe r
Powe r
30 °C outside
To p 50 °C inside
Bottom 40 °C inside
Middle 45 °C inside
Airflow
Axial fan 120 x 120 mm
Inmostcases,theambienttemperaturefortheoperatorpanelissignificantly higher than the device cabinet’s ambient temperature.
If the cabinet is tall and there a re a
number of heat-generating devices, the
temperature at the top of the cabin
et is considerably higher than the temperature
increase that would be expect
ed. All electronics are sensitive to heat. The lifespan
of an electrolytic capacito
r is cut in half with an 8-10 °C increase in temperature. A
15-20 °C temperature incre
ase results in a quarter of the lifespan etc.
Rittal has a go od program for estimating the anticipated average temperature in the cabinet as well as a large program for controlling the temperature in the device cabinet.
An enamel-coated stee
l cabinet has a radiant heat value of 5.5 W/m
2
per degrees C.
Installing a fan inside the cabinet evens out the temperature, while moving air provides considerably better cooling than still air.
Install the fan so tha
t it sits in a cooler area and b lows cold air against the operator
panel. If the fan is m
ounted at the topand sucks warm air upwards, the ambient
temperature of the
fan becomes higher, resulting in a shorter lifespan.
An approximate value of the net power consumption for the operator panel can be calculated by multiplyingthe supply voltage with the current drawn by the operator panel. This is assuming that all supplied power is transformed to heat.
24
BeijerElectronics, MAEN275
Page 25
Additional Installation Tips
6.5 Safety
4
1
2
4
3
4
Power supply 230 V AC to 24 V DC
Power supply 230 V AC to 24 V DC
Power supply 230 V AC to 24 V DC
Operator panel
Operator panel
Operator panel
Distance?
Small controller with expansion unit
+24 V
+24 V
+24 V
0 V
0 V
0 V
230 V AC
COM1
COM100
Ch0
Ch1
Ch100
Ch101
5355
If a power supply that meets safety standardsis used and only powers the operator panel, there is no problem. See 1 in drawing above.
However, if a 24 V unitthat also powers other
unitsisused,thereisreasontobe
cautious, see 2 indrawing above. The opera
tor panel does not have insulation
that meets safety requirements in the eve
nt of a potential short circuit between
230 V AC and 24 V DC. It is assumed that the 2
4 V power supply is secure, for
example, SELVaccording to EN 6095
0 (protection against electric shock) and
UL 950.
Note:
Hereisanexample thatexplainswhyasecure 24VDCpowers upply canberuinedby mixing24V relaycontacts with230V ACrelaycontacts inasmallercontroller. Check thattheclearancesandcreepage distancesbetween24VDC and230VACfulll EN60950orUL950. Ifnot, inputaseparate24Vunit intotheoperatorpanel.
If there is a substantial distance between the relay contactsfor 24 V DC and 230VAC,itisOKtousethesame24Vdevicesforallfeeds. See3indrawing above.
Connect 0 V on the 24 V power supply to the ground, see 4 in drawing above. This offers three advantages:
Safety is increased. The 24 V power supply is not live in the event of a faulty
connection or short circuit between 0 V (24 V) and 230 V phase.
Transients on the 24 V feed are connectedto theground.
No risk that the 24 V feed is at a high level in relationship to the ground. This
is not unusual since there is high static electricity.
BeijerElectronics, MAEN275
25
Page 26
Additional Installation Tips
6.6 GalvanicIsolation
USB
USB
RS232RS422/485
+24 V DC
0 V
Filter
DC/DC galvanic isolation
VCC
0 V (GND)
DC/AC
CFL
Ethernet
Internal electronics
1.5 m
The operator panel has galvanic isolation against the 24 V DC power supply but no galvanic isolation between the communication ports for RS-232, RS-422/RS-485 and USB. Only the Ethernet connection has galvanic isolation.
* *
*
***
**
*
Operator panel Modular controller Printe
r
PCPC
Different ground potential
*
= Internal 0 V (GND) connection
Power CPU COM COM2
RS422 RS232 USB
When a PC is connected to the operator panel, the internal 0 V (GND) of the panel is connected to the protective ground via the PC.
A number of USB devices can have the shield connected together with the protective ground. Here,the 0 V (GND) of the operator panel is connected to the protective ground when, for example, a USB memory stick, keyboard, or similar device is plugged in.
If a number ofunits are connected that have a 0 V and a ground connection, and these are connected to various grounding points, there is a substantial risk of problems. Grounding currents go through communication cables, the rear plate of the controller,internally in the operator panel, and can cause errors.
Use external units to improve communication and achieve galvanic isolation. Westermo has good industry-standard insulators that are also insulated from the 24 V DC feed.
Note:
Itisveryimportanttomakesurethatt he 24Vfeedintheexternalinsulationunitis not connectedtooneo f thecommunicationoutlets. Ifitdoesnothave100%insulation againstthe24Vf eed, disturbancesandgroundingcurrentsfromthe 0Vonthe24 V sidedisruptthecommunication. Usingthistypeofunit solvesoneproblembut createsalargerp roblem! Asubstandard installationmayworknow,butproblemsmayarisewhenother devicesareconnected.
26
BeijerElectronics, MAEN275
Page 27
Additional Installation Tips
6.7 CableandBusTerminationRS-485
If maximum transfer distance and maximum transfer speed is needed,
shielded and twisted pair cable should be used. The mutual capacitance may not exceed 52.5 pF/m, and the cable area should be at least 0.25 mm
2
(AWG 24).
0 V, the reference voltage for communication should be included in
the cabling. With two-way communication use two pairs; one pair for communication and one pair for 0 V.
The shield must be g roundedat one end. The other end is usually grounded,
but with longer distancesor when there is a difference in the ground potential, theshieldshouldbeconnectedtothegroundvia0.1μF/250Vfilmcapacitor to prevent ground current in the braided shield. A number of manufacturers recommendthattheshieldbegroundedateachnode. Variousmanufacturers have different systems for bus termination.
Depending on the recipients’ design, the bus wires may be on the same level or require pull-up or pull-down to ensure that no faulty signals are detected when the bus is in resting mode (all transmitters are disconnected).
BeijerElectronics, MAEN275
27