LUXOMAT® LC-plus 280
Operating and mounting instructions for motion detector LUXOMAT® LC-plus 280
1. Mounting preparations |
2. Mounting types |
|
1 |
1 |
|
2 |
|
2
1)Caution: have all work involving the 230 V mains supply carried out by a qualified electrician! Before starting disconnect the mains! Please be aware, that the LUXOMAT® LC-plus 280 is not suitable as an intrusion detector, since it is not equipped with a tamper contact.
2)Socket base corner mounting
|
1) |
Wall mounting |
Important: The LUXOMAT® LC-plus 280 has |
2) |
Outside corner mountable with plug-in |
to be mounted in such a way, that the adjusting |
|
socket (included) |
elements /rotary regulators are always pointed |
|
|
downward. |
|
|
5. Putting into operation / Settings
Self test cycle
After mounting and connecting the 230 VAC supply voltage, the LED flashed for 1min. to show a self testing unit. Then the unit is ready for operation and the settings can be made manually or with remote control (see point 11).
86 |
4 2 1 |
30s |
|
|
15s |
T |
|
10 |
|
|
|
12 |
|
|
|
16 |
|
|
Follow-up time Lux value
3. Plug-in socket |
4. Inserting of the connection cable |
|
1 |
1 |
1 |
2
|
|
2 |
2 |
1) |
Connection cable from top down |
2) |
Connection cable from below |
|
|
3) |
Terminal markings |
|
|
(Wiring diagrams see point 16) |
1) Press here for separation of terminal case |
3 |
|
|
|
|
|
|
||||
|
|
|
|
|
|
|
|
|
|
||
and plug-in socket |
|
|
|
|
|
|
|
|
|
|
|
2) Mount the plug-in socket with two screws |
|
|
|
|
|
|
|
|
|
|
|
and the enclosed seal rings on a firm base |
|
|
|
|
|
|
|
|
|
|
|
(Pay attention to inserting of the connection |
|
|
|
|
|
|
|
|
|
|
|
cable, see point 4) |
|
|
|
|
|
|
|
|
|
|
|
LED Functional display |
6. Factory settings |
||||||||||
|
|
|
& “TEST” |
||||||||
Slow flashing: EEPROM empty |
|
|
|
||||||||
280 will only react to commands “RESET” and |
|
|
|
||||||||
Fast flashing: EEPROM is written |
|
|
|
|
|
|
|
|
|
|
|
During the self-testing cycle, the LUXOMAT® LC-plus |
|
|
|
|
|
|
|
|
|
|
|
“LIGHT OFF” |
On delivery the potentiometers are adjusted in |
||||||||||
|
|||||||||||
Follow-up time |
position “TEST” and “SUN” symbol (daytime |
||||||||||
Test operation, 15 sec. ... 16 min., Pulse operation |
operation). With this adjustments the following |
||||||||||
(Test operation: range testing, detector switches |
regular values are active: |
||||||||||
on/off the lighting at any recognized movement) |
Follow-up accommodation: 3 min. |
||||||||||
|
Lux value: approx. 20 Lux |
||||||||||
Lux value |
Reset: The adjusting into “Factory settings” from |
||||||||||
any other position causes a “Reset” of the device. |
|||||||||||
Night operation...Dusk...Day operation |
|||||||||||
That means all parameters are resetted into factory |
|||||||||||
(Day operation: light sensor inactive, switching at |
|||||||||||
settings (fast LED-flashing). |
|||||||||||
any brightness value) |
|||||||||||
|
|
|
|
|
|
|
|
|
|
7. Sensor head optics
By swinging the sensor head horizontally (approx. ±45°) and vertically (approx. ±15°) the detection area can be changed.
10. Mounting place
1
1)If possible mount unit on a safe place (wall or ceiling mount).
8.Sensitivity adjustment (mounting height 2.50m); mounting height min. = 2.00m
(Sensor head justified horizontally, see point 7)
2,50 m
|
200° |
m |
280° |
|
|
|
|
m |
|
|
|
|
|
|
16 |
16 |
|
|
m |
|
|
|
|
|
2 |
||
1) |
Range walking across: approx. 16 m |
|
280° |
9 |
m |
|
|
|
m |
||||
|
|
|
|
|
||
2) |
Range walking towards: approx. 9 m |
|
16 |
|||
3) |
Anti-creep: approx. 2 m |
|
20 m |
|
|
|
2
2)Influence of weather reduces the lifetime of the unit. Please take care to mount correctly.
3
> 1m
4
3)Minimum distance to switched lighting, frontally or laterally to device: 1m
4)Never mount the connected lights below the motion detector!
9. Exclude sources of interference
2 |
3 |
|
|
|
60˚ |
1
1)Blind for limiting creep-under protection and backward detection
2)Blinds for reduction of far-away and close-by areas by 60° each
3)Blinds for reduction of far-away areas by 60° each
11. Settings of remote control
1 |
|
IR-LCmini |
|
LUXOMAT® IR-LC-plus |
PARTY |
TEST |
|
|
|
COMFORT |
RESET |
|
|
LUXOMAT |
|
|
|
|
® |
IR-RC mini
2
1)LUXOMAT® IR-LC-plus (accessory, see point 20)
2)LUXOMAT® IR-LCmini (accessory, see point 20)
Caution: Settings with remote control subscribe the settings by courtesy of potentiometers (see point 5) (for description see point 12).