Installation and Operating Instruction for B.E.G. - Occupancy detector PD4-M-2C-C-SM/FC/ FM
GB
1. Mounting preparation
Work on the 230V mains supply
may only be carried out by qualified professionals or by instructed
persons under the direction and
supervision of qualified skilled
electrical personnel in accordance
with electrical regulations.
Disconnect supply before installing!
The device is not suited for safe
disconnection of the mains supply.
When in Master/ Slave mode of
operation, the Master-appliance must
always be installed at the location
where there is least daylight.
3a. Hardware configuration SM
Position LED’s
Potentiometer 3 Time Channel2
Potentiometer 2 Time Channel1
Potentiometer 1 Lux Channel1
A
5
120
15
60
30
40
50
123
16
15
TEST
10
30
1
5
2
40
x
LED 1 green
LED 2 red
LED 3 white
2a. Installation LUXOMAT®
PD4-M-2C-C-SM
CAUTION:
For maximum
sensitivity the
open
closed
The detector must be installed on a solid and level
surface. The circular cover ring must be removed
prior to assembly. To do this, twist the lens anticlockwise through approximately 5° and lift off.
Having connected up the wires in accordance
with regulations, secure the detector with 2
screws. After installation replace the lens and lock
(turn clockwise). Mains to be connected.
closed
open
detector-,lens- and
corridor-axis must
match
C
3b. Hardware configuration FC
Position LED’s and potentiometers
LED 1 green
LED 2 white
LED 3 red
2b. Installation LUXOMAT®
PD4-M-2C-C-FC
A circular opening of diameter 68mm must
first of all be produced in the ceilin
Having connected up the cables in accordance with regulations, the detector is inserted
into the opening as shown in the drawing
opposite and fixed into position with the assistance of the spring clip.
3c. Hardware configuration FM
Potentiometer 1 Lux Channel1
Potentiometer 2 Time Channel1
Potentiometer 3 Time Channel2
2c. Installation LUXOMAT®
PD4-M-2C-C-FM
B.I.T.
PASSED
Q.C.
1
( For connections please see pt. 21!)
Position LED’s and potentiometers
LED 1 green
LED 2 white
LED 3 red
The detector can be installed
in conventional inlet-sockets
mounted on the ceiling. The
assembly plate enclosed must
be stripped off prior to installation and secured to the
ceiling using 4 screws.
Having connected up the
cables in accordance with
regulations, the detector can
be placed in position as
shown in the drawing opposite and, applying a little
pressure, can then be locked
into position with the assistance of the spring clips.
Potentiometer 1 Lux Channel1
Potentiometer 2 Time Channel1
Potentiometer 3 Time Channel2
4a. Position potentiometers DIP-Switch SM
A
5
120
15
60
30
40
50
123
16
15
TEST
10
30
1
5
2
40
x
OFF
ON
VA
Surface mounting
HA
LED
COR
DIP
DIP 1 Fully automatic/semi automatic mode
DIP 2 LED ON/OFF
DIP 3 Change between corridor mode and standard mode
The DIP switch settings are overriden using the remote control.
5. DIP switch functions
DIPswitch
ONOFF
1Semi automatic mode Fully automatic mode
2LED OFF LED ON
3Corridor mode Standard mode
4b. Position DIP-Switch FC
50-60Hz
230VAC ±10%
N
Rel1
Rel2
S L L
R
123
ONOFF
False ceiling mounting
DIP 1 Fully automatic/semi automatic mode
DIP 2 LED ON/OFF
DIP 3 Change between corridor mode and standard mode
The DIP switch settings are overriden using the remote control.
Corridor function: After deactivation by an external push
button, the detector switches off and returns to automatic
mode after 5 sec.
The DIP settings are enabled again by:
DIP
1
2
3
OFF ON
• Adjusting the DIP switches when closed
• Reset with test sun setting at the potentiometers
• Reset when open
4c. Position DIP-Switch FM
DIP
50-60Hz
230VAC ±10%
N
Rel1
Rel2
S L L
R
123
OFF
ON
Flush mounting
DIP 1 Fully automatic/semi automatic mode
DIP 2 LED ON/OFF
DIP 3 Change between corridor mode and standard mode
The DIP switch settings are overriden using the remote control.
DIP
OFF
ON
120
60
50
4030
15
10
A
16
10
5
21
30
15
TEST
2000
1200
600
200
40
5
120
60
50
40
30
15
10
A
16
10
5
2
1
30
15
TEST
5
6. Putting into operation / Settings
120
60
50
4030
15
10
A
16
10
5
21
30
15
2000
1200
600
200
40
5
120
60
50
40
30
15
10
A
16
10
5
2
1
30
15
TEST
5
120
60
50
40
30
15
10
A
5
Self test cycle
After an initial 60-second self-test cycle, the LUXOMAT® PD4-M-2C-C
is ready for operation.
Potentiometer 1 - Adjustment twilight-switch for channel1
“Light“
The switch-on value for the light can be set at between 10 and
2000 Lux. Using the potentiometer, the luminance set points
can be set as desired.
Symbol : Night operation
Symbol : Day/Night operation
Determining the current brightness
Set potentiometer 2 to the „Test“ setting. The green LED lights
up permanently as soon as the value set at the potentiometer
exceeds the current measured brightness.
Potentiometer 2 - Adjustment follow-up time channel 1 “Light“
Symbol TEST: Test mode, reacts on motion only. Every movement switches on the light for a period of 2 seconds, switching
it off for a period of 2 seconds. The time can be set infinitely
variably at between 15sec. and 16 minutes.
Potentiometer 3 - Follow-up time for appliance-control
The time can be set infinitely variably at between 5 minutes and
120 minutes. After 15 minutes the
This is around 5min. If there are not detected any further movements within this period, the switch-on delay starts again.
switch-on delay is activated.
Symbol : Impulse = 2,5 sec.
Symbol A: Alarm impulse = 2sec.
Alarm impulse
In order to set off an alarm impulse, at least 3 movements
within 9sec. have to be detected.
The potentiometer settings are overriden using the remote control.
Pulse spacing PD-Slave
9s2s
2 or 9 seconds can be set for the pause
between 2 pulses sent to the master. The
setting can be made with activated ( ) or
LED ON
deactivated ( ) LED indicator.
LED OFF
For devices with a separate slave input, 2 sec.
can be set.
7. Reset and default settings
12
1. Default settings
If the potentiometers are in the “Test“
and “Sun“ position and the detector is unprogrammed, the factory
program is activated: 500 lux and
10min and corridor operation
mode active.
2. Reset
If both potentiometers are returned to
the ”Test“ and “Sun“ setting from any
other position, a reset is executed. All
values programmed with the remote
control are deleted.
8. Putting into operation of the remote
control IR-PD-2C (optional)
Check Battery:
Open battery compartment
by pressing the plastic springs
together and removing the
battery-holder.
Caution: Settings with remote control supersede
the settings by potentiometers.
Option: Remote control IR-PD
®
®
LUXOMAT
LUXOMAT
LUXOMAT
IR-PD-2C-S
®
PD3
500
200
120
®
400
100 20
HA
ON/OFF
B.E.G.
B.E.G.
B.E.G.
B.E.G.
LUXOMAT
R1
R1
R2
min30min60min
Folie IR-PD-2C-SIR-PD-2C - 92475
Wallbracketforremotecontrol
An adhesive film for the surface of the IR-PD-2C-S
is included with the device. If required, this can be
used for any B.E.G. remote control with 27 keys.
In order to benefit from the whole range of functions of the PD4-M-2C-C, please order separately
the remote control IR-PD-2C.
9. Settings by remote control IR-PD-2C10. Key functions in closed state
Resetting when
open
: Deletes
all values set
with the remote
control, light OFF.
Potentiometer
and DIP switches
are enabled for
setting.
when choosing CdS
min
20
min
Unlocking device - Activation of the programming mode
Daytime operation, detector only activated by motion
or
Automatic reading in the current light value as new
luminance set point
or
Luminance set point for channel 1
to
+
PI R
CdS
5
to
5
or
HA
ON/OFF
20 - 1000Lux
1000
Increase the current light level by
20 resp 50 Lux
Change between motion detector and photo electric
switch
Follow-up time ch1 (light)/
ch2 (HVAC) 5 - 30 min. resp.
120min. or impulse
120
min
(
switch-on delay ch 2:5min.
)
Detection sensitivity reduced or normal
Change between fully automatic
and semi automatic mode (HA)
Permanent protection against sabotage
This function blocks the unit permanently. This operating mode can only be activated during the period of
t < 5 sec
5 seconds (white LED flash) after pressing the “lock“
button. The procedure for leaving this mode is as
follows:
1. Switch off the current
2. Apply current for 31 - 59 seconds
3. Switch of the current again
4. Apply current, wait for selftest cycle
5. Open detector
Light ON/OFF during the detection of motion plus
follow-up time;
Activation of the 12h-ON/OFF-function by holding
down the push button
Activation/Deactivation of the test function
After 3 minutes the test mode will be automatically
closed.
Switches channel off and is immediately active again,
exits all timers, interruption of light measurement
Conrmation
Changes to “open“ state
Light ON/OFF
LED ON/OFF (by holding down the push button)
Locking device - Exit programming mode
If there is not reaction for about 3 minutes the programming mode will be deactivated.
t < 5 sec
White LED ashes
Permanent protection against sabotage
11. Explanation of the remote control button functions
11a. In the initialisation period
12h Light ON/OFF (party function)
Activated by “Light“ - push button
Deactivated by “Reset“- push button (default)
Corridor function
Activated by “outside“- push button
Deactivate by “inside“- push button (default)
Forced shutdown
Activated by “sun“ - push button
Deactivate by “moon“- push button (default)
11b. In opened state
This push button opens the detector and the following functions
can then be programmed.
Attention: The detector is closed automatically:
• after every voltage recovery
• after 3 minutes
The state changes to “closed“.
In the first 5 seconds, the white LED flashes every 0.5 seconds.
During this time, sabotage protection can be activated.
The device distinguishes between 2 procedures:
• Reading in with lighting switched on:
The switch-on value is determined automatically.
Determining the switch-on value:
1. Press the “eye“ push button
2. Switch off the light (2 seconds later)
3. Read in the brightness
4. Switch-on value = Read brightness
• Reading in with lighting switched off:
When the push button is pressed, the current brightness
is specified as the switch-on value. The switch-off value is
determined automatically.
20
If the brightness has been modified, the switch-off threshold is
recalculated.
1000
Each time the push button is pressed, the device increases the
+
current switch-on value in increments of 20 lux for a current
switch-on value of < 100lux and in increments of 50 lux for a
current switch-on value of > 100lux.
Standard sensitivity for most applications
Reduced sensitivity for outdoor applications
When the pulse function of channel1 is active, a pulse of 1sec.
is generated every 9sec. If the pulse function is activated via
remote control, the pause between 2 pulses can be modified.
After activating the function via the “Pulse“ push button, select
the desired time within 5sec.:
5
= 9 sec.,
min
The impulse function of channel 2 depends only on motion !
After each movement the HVAC channel is activated for
2.5sec.; time delay starts afterwards for 9sec.
The “Test“ push button can be used to set the LED ON/OFF
function. To do this, hold down the push button for 3sec.
Please note that in the open state and in test mode, the LED
indicators are always ON.
Twilight switch function (CdS)
PI R
If the CdS function is active, the detector acts as a simple
CdS
twilight switch. Only the brightness can be set in this mode.
Movements are no longer indicated by the red LED.
Push button acknowledgement:
Each push of a button is indicated by lamp acknowledgement
and by the white LED.
“Light ON“ status: OFF/ON (approx. 0.5sec. each)
“Light OFF“ status: ON/OFF (approx. 0.5sec. each)
10
= 10sec.,
min
15
= 15sec.,
min
30
min
= 30sec.
12. Switch-off threshold brightness
1. If the switch-on threshold has been modified by the poten-
tiometer or remote control, the switch-off threshold stored in
the EEPROM is deleted and is then recalculated on the next
activation.
Determining the switch-off value
1. Switch on for 5min. with dark and motion
2. Light OFF for 2 sec.
3. Internal calculation of the switch-off value
2. If the eye push button is pressed, the switch-off threshold is
recalculated. See also Remote control –> Eye section
3. Switch-off delay
If the determined switch-off threshold is exceeded during
operation, the detector only switches off after a delay of approx.
15 minutes. This compensates for any brief fluctuations in the
brightness.
13a. Behaviour of external push button/IR “Light“
The “Corridor“ and “Light ON/OFF“ functions are mutually
exclusive. If both are activated, the detector performs the corridor
function.
The behaviour when the push button is pressed is defined as follows:
Corridor function activated
Light ON:
Push button pressed briefly: Light OFF -> Active after 5sec.
Push button held down: Light OFF -> Active after 5sec.
Light OFF:
Push button pressed briefly: Light ON as long as motion + Lag time
Push button held down: Light ON as long as motion + Lag time
13b. Behaviour of external push button/IR “Light“
12h Light ON/OFF activated
Light ON:
Push button pressed briefly: Light OFF -> Active after 5sec.
Push button held down: 12h OFF
Light OFF:
Push button pressed briefly: Light ON as long as motion + Lag time
Push button held down: 12h ON
12h Light ON/OFF deactivated
Light ON:
Push button pressed briefly: Light OFF as long as motion + Lag time
Push button held down: Light OFF as long as motion + Lag time
Light OFF:
Push button pressed briefly: Light ON as long as motion + Lag time
Push button held down: Light ON as long as motion + Lag time
13c. Behaviour of external push button/IR
“Forced shutdown“
Forced shutdown active
Light OFF:
Light OFF: Push button pressed briefly: Light ON for approx.
30min., then forced shutdown if the set brightness is still exceeded.
14. Other functions
Activation of light for 12 h via mains interruption
1. Interrupt current
2. Apply current for 2 to 5sec.
3. Interrupt current again
4. Apply current
5. Detector is now ON for 12h
Exiting sabotage
1. Interrupt current
2. Apply current for 30 to 60sec.
3. Interrupt current again
4. Apply current
5. Detector is in simple closed state
230V AC permanently at the slave input
If 230V AC is applied at the slave input for longer than 10 sec., the
light is switched on permanently. When the 230V is removed, the
light is switched off and automatic mode is activated.
230 V AC for 1 - 3sec. at push button connection S
If 230 V AC is applied for 1 - 3sec. at push button connection
S, this is interpreted as a slave signal at slave connection R. This
ensures that the detector is compatible with previous versions.
15. Fully automatic and semi automatic mode
(see functions IR-PD-2C)
Fully automatic operation
In this operating mode, the lighting switches automatically on and off
for increased comfort, depending on presence and brightness.
Channel 1 switches on in the event of motion if “dark“ is detected.
Semi automatic operation
In this operating condition, in order to gain increased savings, the
lighting is energized only after being manually switched on.
Switch-off takes place automatically or manually.
The semi automatic mode basically behaves like the fully automatic
one. However, the difference is that switching-on must always be
carried out manually!
As many (NO-contact) buttons as desired can be wired in parallel on
the “S” button input (ON/ OFF).
Triggering in semi automatic mode: If the detector switches off in semi
automatic mode (lag timer elapsed), the detector is switched on again
within 10sec. by motion (despite semi-automatic mode).
HA
ON/OFF
16. Range of Coverage
2,50 m
5 m
3 m
1
2
10 m20 m
walking towards
1
walking across
2
20 m
40 m
PD4-M-2C-C
17. Exclude sources of interferences
SM
FC
FM
In case the sensing area of the LUXOMAT®
PD4-M-2C-C is too large or areas are being covered
that should not be monitored, the range can be
reduced or limited through use of the enclosed
masking clips.