B.E.G. LUXOMAT PD3-1C, LUXOMAT PD3-2C, LUXOMAT PD3-1C-Micro, LUXOMAT PD3-1C-SM, LUXOMAT PD3-1C-FC Installation And Operating Instruction

...
B.I.T.
Q.C.
PASSED
1
Installation and Operating Instruction for B.E.G. - Occupancy detectors PD3-1C-SM/-FC/-FM and PD3-2C-FC/-FM
2a.
Installation of the LUXO­MAT® PD3-SM
2c.
Installation of the
LUXO-
MAT® PD3-FM
LUXOMAT®PD3-1C(-Micro)/-2C
2b.
Installation of the
LUXO-
MAT® PD3-FC
Sensor and power supply in one case
Power supply: 230V~ + 6 %/-10 % Power consumption: < 1W Ambient temperature: -25°C to +50°C Degree of protection/class: SM IP54, FC and FM IP20,
FC with accessory IP23 / II
Settings: locally Area of coverage: circular 360° Range of coverage Ø H 2.50m / T= 18°C:
seated 2.50m / tangential 10m / radial 6 m
Recommended height for mounting: 2 - 3 m Light measurement: mixed light, daylight + artificial light Lux values - Potentiometer: 10 - 2000Lux
• Channel 1 for light-connection
Type of contact: NOC/with pretravel tungsten contact Contact load: 2000 W, 230V~, cos (ϕ) =1 /
1000VA cos (ϕ) = 0.5 Time-settings: 30 sec. - 30 min. / Test
• Channel 2 for HVAC (only PD3-2C)
Contact load: 230V~, 3 A cos(ϕ) =1 Time-settings: 5 min. - 120min. with time delay of 5 min.
for follow-up time > 15min. Dimensions H x Ø [mm] SM FC FM PD3 52x 106 84,5 x 80 65x 98 Visible portion when built into ceiling: 34 x 74mm
Declaration of Conformity: The product complies with
the low voltage recommendation 2006/95/EC and the EMV recommendation 2004/108/EC.
4.
Technical data
PD3
5. Trouble shooting
1. Lamp does not light up
Lamp may be defect:
Replace lamps
No mains connection/power:
Check connection and mains fuse by qualied electrician
Incorrect setting of CDS twilight threshold:
Correct setting of CDS threshold
Lens of sensor unit obstructed by dirt or other objects:
Clean lens, remove objects
2. Lamp turns ON too late or detection range too small LUXOMAT
®
PD3 is mounted too high:
See table of mounting heights. Correct mounting if required.
3. Lamp stays ON continuously
Continuous thermal activity detected ie fan, central heat­ing ducts, animals within detection area:
Remove heatsource. Check proper function of LUXOMAT® PD3 by covering the fresnel-lens. After expiry of delay timer, PD3 has to turn OFF lighting.
LUXOMAT
®
PD3 connected in parallel to a manual over-
ride switch:
Connect switch correctly
4. Unintended switching of light
Movement of heat source within detection area:
Check on presence of animals, fans or heaters
The detector can be installed in conventional inlet-sockets mounted on the ceiling. The assembly plate enclosed must be stripped off prior to installation and secured to the ceiling using 4 screws.
Having connected up the cables in accordance with regulations, the detector can be placed in position as shown in the drawing opposite and, applying a little pressure, can then be locked into position with the assist­ance of the spring clips.
The detector must be in­stalled on a solid and level surface. There is no need for frames.
For mounting remove lens (C) (turn anticlockwise). Fasten the mounting base
to the ceiling.
Having connected up the wires in accordance with regulations, secure the detector with 2 screws as per the illustration above.
1. Mounting preparations
Work on the 230V mains supply
may only be carried out by qualified professionals or by instructed persons under the direction and supervision of qualified skilled electrical person­nel in accordance with electrotechni­cal regulations.
Disconnect supply before installing!
The detector has been designed and developed specifically for instal­lation in suspended ceilings.
A circular opening of diameter 65mm must be cut into ceiling.
Having connected up the cables in accor­dance with regulations, the detector is inserted into the opening as shown in the drawing above and fixed into position with the assistance of the spring clips.
e.g. 65mm
GB
Type SM FC FM
PD3-1C 92190 92196 92186
PD3-1C-Micro 92219 92184 –
PD3-2C 92198 92188
Accessory:
BSK Ball basket guard 92199 FC-Covering IP23 92206 SM-Blinds 92260
7. Article / Part nr. / Accessory
6. Range of Coverage
quer zum Melder gehen frontal zum Melder gehen Unterkriechschutz
walking across walking towards seated
1 2
10 m
6 m
2.50 m
10 m
360°
2.50 m
1
2
3. Putting into operation / Settings
Follow-up time for device control (PD3-2C)
The time can be set infinitely variably at between 5 and 120 minutes.
Follow-up time for light control
The time can be set infinitely variably at between 30 seconds and 30 minutes.
Symbol
: impulse < 1sec.
Symbol
TEST: Test mode
(Every movement switches on the light for a period of 1 second, switching it off for a period of 2 seconds after that regardless of the level of brightness.)
Twilight-switch for light control
The switch-on value for the light can be set at between 10 and 2000Lux. Using the rotary control, the luminance set points can be set as desired.
Symbol
: Night-time operation
Symbol
: Daytime/ Night-time operation
Adjusting sensitivity (PD3-1C)
For sensitivity adjustment of the detector, both in the interior and the exterior range, the PD3-1C-SM/-FC is equipped with an additional knob (see pictures) for excluding sources of interference, e.g. bad weather conditions or draught air.
Max: for interior use
(recognition of the slightest movements)
Min: for exterior use
(exclusion of sources of interference)
Sound (PD3-1C-Micro)
Max: highest sensitivity Min: microphone switched off Intermediate values to be adjusted accordingly to local conditions. Lighting of the LED means the noise­detector is functioning and triggers the timer again. The microphone is active for 9 seconds after the last movement and time delay completed.
120
60
50
40 30
15
10
A
16
10
5
2
1
30
15
2000
1200
600
200
40
5
max.
min.
max.
min.
2 4 6
8
12
30
secs
30
mins
1
min
TEST
40
50 60 90
120
5
mins
30
10
15
N
L
'
L
N
'
L
~6 m
6 m 7 m
18m
6 m
~6 m
6 m
12m
6 m
6 m
4 m
6 m
8. Wiring diagrams
MAN 5789 – 161209-4
9. PD3 - Connections
Connection PD3-1C-SM
NL L'
Connection PD3-1C-FC/-FM
NL L'N
Connection PD3-2C-FC/-FM
N LL'
+
R2
10. PD3 - Dimensions
PD3-SM
PD3-FC
PD3-FM
11. Installation examples
Parallel-operation together with stairwell switch.
Alternatively switching by either motion detector or stairwell switch.
L' N L
Parallel-operation with stairwell switch
Standby,
additionally manual switching is possible.
N
L
L' N L L' N L
Terminal connection voor parallel operation
L' N L
Switching with external switch PD3-1C-FC
L' N L
Permanent light operation with external switch
Standby
Switching is manually possible (permanent light operation)
L' N L L' N L
Terminal connection for parallel-operation
Parallel switching
Max. 8 occupancy detectors keep settings (Lux and time) the same.
L' N L
Standard operation with opt. arc extinctions kit
Arc
extinction kit
Standby
Optional extension for switching of parallel inductors, rocker switches, uorescent lamps etc.
L
N
Terminal connection for parallel-operation PD3-2C-FC
+
dry
contact
Circuit like PD3-1C-FC, but additional with two dry contact (relay 2).
645
5
15
R L' N L L NO NO
3A
230VAC 50-60Hz
Slave / Remote
84.5
74
R L' N L L NO NO
3A
230VAC 50-60Hz
Slave / Remote
98
72
13
13
35
65
16
48x4825 25
14
52
106
Loading...