B.E.G. LUXOMAT PD1-M-DIM Installation And Operating Instruction

Installation and Operating Instruction for B.E.G. - Occupancy detectors PD2-Master-DIM-SM/-FC/-FM
LUXOMAT®PD1-M-DIM
1
1
2
2
25
22
18
10
TEST
30
R1
120
60
50
40 30
15
10
A
16
10
5
2 1
30
15
TEST
2000
1200
600
200
40
5
25
22
18
10
TEST
30
R1
2000
1200
600
200
40
GB
2a.
Installation of the LUXOMAT® PD1-M-DIM-SM
2b. Installation of the LUXOMAT
®
PD1-M-DIM-FC
1. Mounting preparations
Work on the 230V mains supply may only be carried out by quali­fied professionals or by instructed persons under the direction and supervision of qualified skilled elec­trical personnel in accordance with electrotechnical regulations.
Disconnect supply before installing!
When in Master/ Slave mode of operation, the Master-appliance must always be installed at the location where there is least daylight.
2c.
Installation of the LUXOMAT® PD1-M-DIM-FM
The detector can be installed in conventional inlet­sockets mounted on the ceiling.
The assembly plate enclosed must be stripped off prior to instal­lation and secured to the ceiling using 4 screws and ensuring that it is not laterally transposed.
For surface-mounting, an inwall sensor unit is combined with a surface-mounted receptacle as a housing base.
Before mounting the base, the enclosed mounting plate must be mounted true to side, i.e. the writing must be legible.
Now fix the base on ceiling or wall, but first put the cable through one of the cable openings provided. The detector must be mounted on a flat, solid surface.
Next prepare the sensor part by screwing in both fixing screws, then connect the cable as per the wiring diagram.
Now insert the sensor part and check for matching positioning of the two markings. Press beyond the spring housing pressure so that the sensor part firmly locks in place. Now turn the sensor part counter-clockwise for about 10° to the stop.
The detector has been designed and developed specifically for installation in sus­pended ceilings.
A circular opening of diameter 68 – 70mm must be produced in the ceiling.
Having connected up the cables in accor dance with regulations, the detector is inserted into the opening as shown in the drawing opposite and fixed into position with the assistance of the spring clips.
B.I.T.
Q.C.
PASSED
1
6 mm
Having connected up the cables in ac­cordance with regulations, the detector can be placed in position as shown in the drawing opposite and, applying a little pressure, can then be locked into position with the assistance of the spring clips.
B.I.T.
Q.C.
PASSED
1
6 mm
4. Settings carried out using remote control (optional)
Remote control LUXOMAT® IR-PDim
1. Check Battery:
open battery compartment by pressing the plastic springs together and removing the battery-holder.
2. IMPORTANT
Please pay attention, that the setting is Potentio­meter 1 at “TEST” and Potentiometer 2 not at “SUN”. All values which have been programmed using the remote control will be deleted in the event of power failure in the position “TEST/ SUN”. Please switch Potentiometer 2 over to “MOON” or any other value.
Caution: Settings with remote control supersede the settings by courtesy of potentiometers.
3. Putting into operation / Settings
Self test cycle
The product enters an initial 60-second self-test cycle, when the supply is first connected. The occupancy detector is ready for operation.
Follow-up time for light control
The time can be set infinitely variably at between 1 and 30 minutes.
Symbol TEST: Test mode (Every movement switches on the light for a period of 1 second, switching it off for a period of 2 seconds after that regardless of the level of brightness.)
Twilight-switch for light control (relay 1)
The switch-on value for the light can be set at between 10 and 2000 Lux. Using the rotary control, the luminance set points can be set as desired.
Symbol
: Night-time operation
Symbol
: Daytime/ Night-time operation
Orientation lighting
This rotary controller serves to determine the working time of the orientation lighting (fixed to 20%). “ON” for permanent orientation lighting. “OFF” for deactiviation of orientation lighting.
25
22
18
1
6
10
3
1
TEST
6
30
R1
120
60
50
40
30
15
10
A
16
10
5
2
1
30
15
2000
1200
600
200
40
5
60
5
10
30
50
ON
OFF
Unlocking device
Lock device
Luminance set point for constant light regulation
Dimming
The following approach will prove useful when setting a command value (example workplace): Place a luxmeter flat on the desk, then, using the remote control IR-PDim, adjust the light up or down by pressing the keys max or min until the desired command value which best suits your require­ments has been reached.
Automatic reading in the current light value as new luminance set point
Individual light value 2 - 2500Lux
Follow-up time
1 up to 30min.
Orientation lighting and its follow-up time OFF button: No orientation light. Grey button: Programming the switch-off delay time. On button: Orientation light is permanently activated.
Note: During the orientation light phase, the constant light regulation is also active: if there is sufficient brightness, dimming occurs < 2V and, if applicable, the lighting is switched off.
Preset/ user mode => (see page 2, point 6)
Fully automatic/semi automatic mode => (see page 2, point 5)
Semi automatic: green LED, Fully automatic: red LED on for approx. 3sec.
Resetting when open
All values which have been programmed using the remote control IR-PDim are deleted, and those values which have been set by potentiometer are activated.
Lock device
Test mode
Reset to deactivate
Resetting when closed
The lighting relay is switched off, i.e. opened and the follow-up times reset.
Permanent protection against sabotage
This function blocks the unit permanently (green LED is illuminated). This operating mode can only be activated during the period of 5 seconds after pressing the “lock“ button. This status will only permit actuating the function “Light on/ Light off”.
The procedure for leaving this mode is as follows:
1. Switch off the current
2. Apply current for 31 – 59 seconds
3. Switch of the current again
4. Apply current
5. Open detector
Light on/ off
The light will remain switched on/ off for as long as movements are detected in the areas of coverage. Once the last movement has been detected, the light will remain on for the duration of the follow-up time as per setting. The appliance will then return independently to the mode selected (Fully or Semi-automatic).
Option:
Wall bracket for remote control IR-PDim
max
50
Lux
1500
Lux
50
Lux
1500
Lux
50
Lux
1500
Lux
50
Lux
1500
Lux
50
Lux
1500
Lux
1500
Lux
max
50 Lux
1500
Lux
ON
OFF
max
50
Lux
1500
Lux
ON
20 %
1500
Lux
Sensor and power supply in one case for onwall-, ceiling­and flushmounting
Power supply: 230V~ +6 %/-10% Power consumption: < 1W Ambient temperature: -25°C to +50°C Degree of protection/class: SM IP54, FC and FM IP20, FC
with accessory IP23 / II
Settings: manually and by remote control Light values: 50 - 1500Lux (Remote control) Extension of the detection area: with Slaves Area of coverage: square 4 x 90° Range of coverage Ø H 2,50m / T= 18°C:
seated 4.20m / tangential 7.50m / radial 4.50 m
Recommended height for mounting: 2 - 3 m Light measurement: mixed light, daylight + artificial light Lux values: 10 - 2000Lux (Potentiometer)
• Relay/Channel 1 for light-connection
Type of contact: dry contact type NO Contact load: 2300W cos (ϕ)=1 / 1150VA cos (ϕ) =0.5 DIM-Output: 1 x (1 -10 V) Max. no. of series-connected electronic ballasts:
max. 50 electronic ballasts by one single supply with max. 100m cable run and a conductur cross-section of
0.75mm²
Time-settings: 1 - 30 min. / Test Dimensions
H x Ø [mm]
SM FC FM
PD1-M-DIM 80 x 98 103 x 97 84 x 97 Visible portion when built into ceiling: 30 x 97mm
Technical data PD1-Slave
Electrical data same as above, but just one channel for signaling motion detection.
Declaration of Conformity: The product complies with
the low voltage recommendation 2006/95/EC and the EMV recommendation 2004/108/EC.
12.
Technical data
PD1-Master-DIM
11. PD1-M-DIM - Connections
Type SM FC FM
PD1-M-DIM (Master) 92179 92176 92173
PD1-S (Slave) 92178 92175 92172
LUXOMAT
®
Remote control:
IR-PDim (incl. wall bracket) 92200
Accessory:
BSK Ball basket guard 92199 Wall bracket for remote control as replacement
92100 Occupancy detectors - Covering IP23 92206 Socket IP54 92161 SM-Socket for PD1-FM 92171
9. Article / Part nr. / Accessory
MAN 6320 – 211209–1
8. Range of Coverage
13. LED-functional indicators, fault-finding
The functional indicators in the case of the LUXOMAT® PD1-M-DIM (red and green LED‘s)
Red LED indicating self-checking mode (over a period of 60 seconds following mains‘-supply lock-on)
Flashing at intervals of 1 second EEPROM/ memory empty
Flashing rapidly
EEPROM/ memory contains information
Red LED as an indicator of status
Flashing irregularly
Movements are detected within the area of coverage
Flashing regularly
Detector identifies bright, light off (dependent upon operating mode)
Not illuminated
Detector identifies dark, light on (dependent upon operating mode)
Flashing extremely rapidly
Too bright / Too dark / Undefined
Red LED as an acknowledgement of receipt for commands from the remote control
Illuminated for 2 seconds
Signal validly received
Illuminated for 0.5 seconds
Not-accepted command, detector blocked Flashing extremely rapidly
Not-accepted command, occurs, for example, when an attempt is made to input twilight-value are too bright or too dark
Green LED as an acknowledgement of receipt for commands from the remote control
Lights up for 3 seconds
Semi automatic or user signal correctly received
Green LED as an indicator of status (only for status “Permanent protection against sabotage”)
Flashing irregularly
Movement are detected within the area of coverage
Flashing regularly
Detector identifies bright, light off (dependent upon operating mode)
Not illuminated
Detector identifies dark, light on (dependent upon operating mode)
lluminated for 2 seconds
Signal validly received (dependent upon operating mode)
1 2
quer zum Melder gehen frontal zum Melder gehen Unterkriechschutz
Walking across Walking towards Seated
1500
Lux
1500
Lux
7.50 m
4.20 m
7.50 m
4 x 90°
2.50 m
1
2
Connections PD1-M-DIM
+
NR
+
L S
SLAVE
L'
1-10V
3
3
6. Manual Dimming - Preset / User
(for IR-PDim functions see page 1)
You can dim manually by pressing the pushbutton for a long time (> 2sec). When the button is released, the current dimming value is retained. Upon renewed dimming, the dimming direction is reversed.
PRESET – the luminance set point is set during start-up operation by the installer and remains unchanged. The luminance set-point congured through manual dim­ming is only applied for the time being. Caution: The constant light regulation is now deactivated!
The currently set articial light is retained independent
of the ambient/daylight brightness! After switching off and then back on, the originally set luminance set-point is reset = constant light regulation is activated.
USER - can only be activated via the remote control! The luminance set-point is changed upon each manual dimming and re-adjusted by the user (Conformation through relay clicking!). The constant light regulation remains activated!
5. Fully / Semi automatic mode
(for IR-PDim functions see page 1)
Fully automatic operation
In this operating mode, the lighting switches automati­cally on and off for increased comfort, depending on presence and brightness.
Semiautomatic operation (Semiautomatic can only be activated via the remote control!)
In this operating condition, in order to gain increased savings, the lighting is energized only after being manu­ally switched on. Switch-off takes place automatically.
The semiautomatic mode basically behaves like the fully automatic one. However, the difference is that switching­on must always be carried out manually!
As many (closer-contact) buttons as desired can be wired in parallel on the “S” button input (ON/ OFF Dimm).
7. Manual Switching
You can switch the lighting on and off manually by pressing the pushbutton for a short time. It will stay on or off as long as people are detected plus the
congured follow up time.
10. Wiring diagrams
Push button operation For manual switching push the button only a short time (0.2 - 0.5 sec.)! To dim push the button until the wished light level is arrived.
Master-/Slave-operation. The Master is the only one to read the light level and to switch the connected loads. Independant of the light level the Slave units react to movements only by sending impulsions via the dry contact.
No load can be connected to the dry con­tact. The Master-dim-occupancy detectors can not be switched into parallel. For that application please prefer the Master-/ Slave-installation. It is recommended to put the Master the furthest possible postion away from the natural light source.
1-10 VDC
Terminal connection for push button operation
MASTER
+
R L' N L S
1-10 VDC
Terminal connection for Master-/Slave-operation
MASTER
SLAVE
R R N N L L
R
L' N L S + -