Single-, Two- and Four-Channel Analog Input Terminals
for Thermocouples
Version: 3.4
Date: 2008-05-19
Table of contents
Table of contents
1. Foreword 1
Notes on the documentation 1
Safety Instructions 2
2. Technical data 3
3. Connection 3
KL3311 3
KL3312 (KL3302) 4
KL3314 4
4. Functional description 5
5. Terminal configuration 8
6. Register Description 9
General Description of Registers 9
Terminal-specific register description 12
Control and Status byte 14
Register communication 15
7. Appendix 17
Mapping 17
Register Table 20
Support and Service 21
KL3311, KL3312, KL3314 and KL3302
Foreword
Foreword
Notes on the documentation
This description is only intended for the use of trained specialists in control and automation engineering
who are familiar with the applicable national standards. It is essential that the following notes and
explanations are followed when installing and commissioning these components.
Liability Conditions
The responsible staff must ensure that the application or use of the products describe d satisfy all the
requirements for safety, including all the relevant laws, regulations, guidelines and standards.
The documentation has been prepared with care. The products described are, however, constantly under
development. For that reason the documentation is not in every case checked for consistency with
performance data, standards or other characteristics. None of the statements of this manual represent s a
guarantee (Garantie) in the meaning of § 443 BGB of the German Civil Code or a statement about the
contractually expected fitness for a particular purpose in the meaning of § 434 par. 1 sentence 1 BGB. In
the event that it contains technical or editorial errors, we retain the right to make alterations at any time
and without warning. No claims for the modification of products that have already been supplied may be
made on the basis of the data, diagrams and descriptions in this documentation.
Delivery conditions
In addition, the general delivery conditions of the company Beckhoff Automation GmbH apply.
This documentation is copyrighted. Any reproduction or third party use of this publication, whether in
whole or in part, without the written permission of Beckhoff Automation GmbH, is forbidden.
KL3311, KL3312, KL3314 and KL3302 1
Foreword
Safety Instructions
State at Delivery
All the components are supplied in particular hardware and software configurations appropriate for the
application. Modifications to hardware or software configurations other than those described in the
documentation are not permitted, and nullify the liability of Beckhoff Automation GmbH.
Description of safety symbols
The following safety symbols are used in this documentation. They are intended to alert the reader to the
associated safety instructions..
This symbol is intended to highlight risks for the life or health of personnel.
Danger
This symbol is intended to highlight risks for equipment, materials or the
Attention
environment.
This symbol indicates information that contributes to better understanding.
i
Note
2 KL3311, KL3312, KL3314 and KL3302
Technical data
Technical data
Technical data KL3311 KL3302* KL3312 KL3314
Number of inputs
Power supply
Thermocouple sensor type
Connection
Temperature range within the respective defined range of the sensor
Resolution
Broken lead detection
Conversion time
Meas. error (total meas.
range)
Electrical isolation
Current consumption from
K-Bus
Bits width in process
image
Configuration
Weight
Operating temperature
Storage temperature
Relative humidity
Vibration / shock
resistance
EMC resistance burst / ESD
Installation position
Protection class
1 2 2 4
via the K-Bus
Types J, K, L, B, E, N, R, S, T, U (default setting type K), mV measurement
2 wire
(Default: type K; -100° ... 1370°C)
0.1°C per digit
yes no yes yes
~ 200 ms ~ 250 ms
< ± 0.5% (of the full scale value)
500 V
typically 65 mA
Input: 1 x 16 bits of data
(1 x 8 bits control/status
optional)
no address setting, configuration via bus coupler or controller
approx. 70 g
0°C ... +55°C
-25°C ... +85°C
95 % no condensation
according to EN 60068-2-6 / EN 60068-2-27, EN 60068-2-29
according to EN 61000-6-2 / EN 61000-6-4
any
IP20
(K-Bus/signal voltage)
rms
Input: 2 x 16 bits of data
(2 x 8 bits control/status
optional)
Input: 4 x 16 bits of data
(4 x 8 bits control/status
optional)
*) KL3302 is no longer available and was replaced with KL3312.
Connection
KL3311
KL3311, KL3312, KL3314 and KL3302 3
Connection
KL3312 (KL3302)
KL3314
4 KL3311, KL3312, KL3314 and KL3302
Functional description
Functional description
The thermocouple terminals KL3311, KL3302 (without broken wire
detection), KL3312 and KL3314 can evaluate type J, K, B, E, N, R, S, T, U
and L thermocouples. The characteristic curves are linearized and the
reference temperature determined directly within the terminal.
Temperatures are output in 1/10°C. The terminal is fully configurable via
the Bus Coupler or the control. Different output formats may be selected or
own scaling activated. In addition, linearization of the characteristic curve
and determination and calculation of the reference temperature
(temperature at the terminal connection contacts) can be switched off.
Functioning Thermocouples can be classified as active measuring sensors. They
exploit the thermo-electric effect (Seebeck, Peltier, Thomson). Where two
electrical conductors of different materials (e.g. iron and constantan) make
contact, charge is transferred across the contact surface. A contact
potential develops, and is strongly dependent on temperature. The
thermally generated voltage is both a function of the temperature being
measured, T, and of the reference temperature, T
, at the point where
v
contact is made with the thermocouple. Since the coefficients are
determined at a reference temperature of 0°C, it is necessary to
compensate for the effect of the reference temperature. This is done by
converting the reference temperature into a reference voltage that depends
on the type of thermocouple, and adding this to the measured thermal
voltage. The temperature is found from the resulting voltage and the
corresponding curve.
U
= U
k
meas
+ U
ref
T
= f(Uk)
aus
Process data output format In the delivery state, the measured value is displayed in increments of
1/10 °C in two's complement format (integer). Other display types can be
selected via the feature register (e.g. sign/amount representation, Siemens
output format).
Measured value Hexadecimal output Signed integer output
: Bits 1 and 6 (over range and error bits) in the status byte are
kmax
set. The linearization of the characteristic curve is continued with the
coefficients of the upper range limit up to the limit stop of the A/D converter
or to the maximum value of 0x7FFF.
KL3311, KL3312, KL3314 and KL3302 5
Functional description
U
k
< U
: Bits 0 and 6 (under range and error bits) in the status byte are
kmin
set. The linearization of the characteristic curve is continued with the
coefficients of the lower range limit up to the limit stop of the A/D converter
or to the minimum value of 0x8000.
For over range or under range the red error LED is switched on.
LED display The four LEDs indicate the operating state of the associated terminal
channels.
Green LEDs: RUN (not applicable for KL3314)
• On: normal operation
• Off: Watchdog-timer overflow has occurred. If no process data are
transmitted by the Bus Coupler for 100 ms, the green LEDs go out.
Red LEDs: ERROR
•On: Wire breakage. The resistance is in the invalid range of the
characteristic curve of the respective thermocouple.
•Off: The resistance is in the valid range of the characteristic curve.
Process data The process data that are transferred to the terminal bus are calculated
using the following equations:
X_ref: ADC value of the reference point
: Temperature of the reference point
T
ref
U
: Voltage value of the reference point
ref
X_R: ADC value of the temperature sensor
U
: Voltage value of the temperature sensor
m1
A_a, B_a: Manufacturer gain and offset compensation (R17, R18)
A_h, B_h: Manufacturer scaling
A_w, B_w: User scaling
U
: Sum of U
k
and Um1
ref
T: Measured temperature in 1/16 °C
T
: Tempe rature after manufacturer scaling (1/10 °C)
h
T
: Tempe ratu re after user scaling
a
T_AUS: Process data to PLC
a) Voltage value of the reference point:
T
= A00 * X_ (1.0)
ref
= a1 * T
U
ref
2
+ b1 * T
ref
+ c1 (1.1)
ref
b) Measured temperature in 1/16°C:
U
= A_a * X_m + B_a (1.2)
m1
U
= U
+ Um1 (1.3)
k
ref
T = a
2
* U
+ b0 * Uk + c0 (1.4)
0
k
c) Neither user nor manufacturer scaling are active:
T_AUS = T (1.5)
d) Manufacturer scaling active (factory setting):
T
= A_h * T + B_h (1.6)
h
Y_AUS = T
h
e) User scaling active:
Ta = A_w * T + B_w (1.7)
Y_AUS = T
a
f) Manufacturer and user scaling active: (1.8)
Y_1 = A_h * T + B_h
Y_2 = A_w * Y_1 + B_w
Y_AUS = Y_2
6 KL3311, KL3312, KL3314 and KL3302
Functional description
1
LM334
X_vglTvgl
a1,b1,c
TThTa
Ta us
Output: microV
Tvgl
ADC
A00,B00
Uvgl
1:11:11:1
Output: Tvgl in °C
X_m
Um1
T
Uk
amount
rep.
A_h,B_h
A_a, B_a
Gain, Offset adjust.
Output: microVOutput: T in 1/16°C
Connection Due to the differential inputs of the terminals, different connection types are
recommended depending on the type of thermocouple used.
For earthed thermocouples, ground is connected to the screen. If the
thermocouple has no earth connection, the ground, screen and -TC1 or TC2 contacts are connected with each other.
a0, b0, c0
temperature
manuf. scal.
Siemensformat
A_w,B_w
userscaling
MM
MM
ShieldShield
Earthed thermocouple Floating thermocouple
The examples show the situation for KL3312. For the KL3314, the screen
should be connected to an additional screen terminal (KL9195).
KL3311, KL3312, KL3314 and KL3302 7
Terminal configuration
The terminals can be configured and parameterized via the internal register
BK2000 Lightbus Coupler In the BK2000 Lightbus coupler, the control and status byte is mapped in
Example for KL3312 (KL3302):
Terminal configuration
structure. Each terminal channel is mapped in the Bus Coupler. Depending
on the type of the Bus Coupler and the mapping configuration (e.g.
Motorola/Intel format, word alignment etc.) the terminal data are mapped in
different ways to the Bus Coupler memory. For parameterizing a terminal,
the control and status byte also has to be mapped.
addition to the data bytes. This is always located in the low byte at the
offset address of the terminal channel.
Beckhoff-Lightbus
bus coupler
BK2000
The terminal is
mapped in the
bus coupler.
C/S
Data H Data L
C/S
Data LData H
C/S
D1 - 1
D1 - 0
0Offset Terminal1 Channel1 = 0
D0 - 1
C/S - 1
D0 - 0
C/S - 0
Offset Terminal2 Channel2 = 8
User data allocation depending
on mapping
Offset Terminal2 Channel1 = 4
KL3302, KL3312
LH
K-Bus
To the bus terminal
BK3000 PROFIBUS
coupler
Example for KL3312 (KL3302):
For the BK3000 PROFIBUS coupler, the master configuration should
specify for which terminal channels the control and status byte is to be
inserted. If the control and status byte are not evaluated, the terminals
occupy 2 bytes per channel:
• KL3311: 2 bytes of input data
• KL3312 (KL3302): 4 bytes of input data
• KL3314: 8 bytes of input data
Profibus bus coupler
BK3000
The terminal is
mapped in the
bus coupler.
0
Data L
Data H
C/S
D0 - 1
D1 - 1
C/S - 1
D0 - 0
D1 - 0
C/S - 0
The control-/status byte
must be inserted for
parameterization.
BK4000 Interbus Coupler The BK4000 Interbus Coupler maps the terminals in the delivery state with
2 bytes per channel:
• KL3311: 2 bytes of input data
• KL3312 (KL3302): 4 bytes of input data
• KL3314: 8 bytes of input data
Parameterization via the fieldbus is not possible. If the control and status
byte is to be used, the KS2000 configuration software is required.
Example for KL3312 (KL3302):
Interbus bus coupler
BK4000
The terminal is
mapped in the
bus coupler.
Data H
Data L
Data H
Data L
Data H
D0 - 1
D1 - 1
D0 - 0
D1 - 0
0
The control/status byte
must be inserted for
parameterization (KS2000).
Offset Terminal2 Channel1 = 6
Offset Terminal2 Channel1 = 4
Offset Terminal1 Channel2 = 2
Offset Terminal1 Channel1 = 0
K-Bus
Other Bus Couplers and
further information
i
Note
Parameterization with
KS2000
To the bus terminal
Further information about the mapping configuration of Bus Couplers can
be found in the Appendix of the respective Bus Coupler manual under
Master configuration.
The Appendix contains an overview of possible mapping configurations
depending on the parameters that can be set.
The parameterizations can be carried out independently of the fieldbus
system with the KS2000 configuration software via the serial configuration
interface in the Bus Coupler.
Register Description
Different operating modes or functionalities may be set for the complex
terminals. The General Description of Registers explains those register
contents that are the same for all complex terminals.
The terminal-specific registers are explained in the following section.
Access to the internal terminal registers is described in the Register
Communication section.
Complex terminals that possess a processor are able to exchange data bi-
General Description of Registers
directionally with the higher-level controller. These terminals are referred to
below as intelligent Bus Terminals. These include analog inputs, analog
outputs, serial interface terminals (RS485, RS232, TTY etc.), counter
terminals, encoder interface, SSI interface, PWM terminal and all other
parameterizable terminals.
KL3311, KL3312, KL3314 and KL3302 9
Register Description
The main features of the internal data structure are the same for all the
intelligent terminals. This data area is organized as words and comprises
64 registers. The important data and parameters of the terminal can be
read and set through this structure. It is also possible for functions to be
called by means of corresponding parameters. Each logical channel in an
intelligent terminal has such a structure (4-channel analog terminals
therefore have 4 sets of registers).
This structure is divided into the following areas:
(A detailed list of all registers can be found in the Appendix.)
Register Application
0 to 7
8 to 15
16 to 30
31 to 47
48 to 63
Process variables
Type register
Manufacturer parameters
User parameters
Extended user area
Process variables
R0 to R7: Registers in the internal RAM of the terminal
The process variables can be used in addition to the actual process image.
Their function is specific to the terminal.
R0 to R5: Terminal-specific registers
The function of these registers depends on the respective terminal type
(see terminal-specific register description).
R6: Diagnostic register
The diagnostic register can contain additional diagnostic information. Parity
errors, for instance, that occur in serial interface terminals during data
transmission are indicated here.
R7: Command register
High-Byte_Write = function parameter
Low-Byte_Write = function number
High-Byte_Read = function result
Low-Byte_Read = function number
Type register
R8 to R15: Registers in the internal ROM of the terminal
The type and system parameters are hard programmed by the
manufacturer, and the user can read them but cannot change them.
R8: Terminal type
The terminal type in register R8 is needed to identify the terminal.
R9: Software version (X.y)
The software version can be read as a string of ASCII characters.
R10: Data length
R10 contains the number of multiplexed shift registers and their length in
bits.
The Bus Coupler sees this structure.
R11: Signal channels
Related to R10, this contains the number of channels that are logically
present. Thus for example a shift register that is physically present can
perfectly well consist of several signal channels.
R12: Minimum data length
The particular byte contains the minimum data length for a channel that is
to be transferred. If the MSB is set, the control and status byte is not
necessarily required for the terminal function and is not transferred to the
control, if the Bus Coupler is configured accordingly.
10 KL3311, KL3312, KL3314 and KL3302
Register Description
R13: Data type register
Data type register
0x00
0x01
0x02
0x03
0x04
0x05
0x06
0x07
0x08
0x11
0x12 Structure 1 byte n bytes with variable l ogical channel
0x13
0x14 Structure 1 byte n words with variable l ogical channel
0x15
0x16 Structure 1 byte n double words with variable logical
Terminal with no valid data type
Byte array
Structure 1 byte n bytes
Word array
Structure 1 byte n words
Double word array
Structure 1 byte n double words
Structure 1 byte 1 double word
Structure 1 byte 1 double word
Byte array with variable logical channel length
length (e.g. 60xx)
Word array with variable logical channel length
length
Double word array with variable logical channel length
channel length
R14: Reserved
R15: Alignment bits (RAM)
The alignment bits are used to place the analog terminal in the Bus
Coupler on a byte boundary.
Manufacturer parameters
R16 to R30: Manufacturer parameter area (SEEROM)
The manufacturer parameters are specific for each type of terminal. They
are programmed by the manufacturer, but can also be modified by the
controller. The manufacturer parameters are stored in a serial EEPROM in
the terminal, and are retained in the event of voltage drop-out.
These registers can only be altered after a code-word has been set in R31.
User parameters
R31 to R47: User parameter area (SEEROM)
The application parameters are specific for each type of terminal. They can
be modified by the programmer. The application parameters are stored in a
serial EEPROM in the terminal, and are retained in the event of voltage
drop-out. The user area is write-protected by a code-word.
R31: Code-word register in RAM
i
Note
The code-word 0x1235 must be entered here so that parameters in the
user area can be modified. If any other value is entered into this register,
the write-protection is active. When write protection is not active, the code
word is returned when the register is read. If the write protection is active,
the register contains a zero value.
R32: Feature register
This register specifies the terminal's operating modes. Thus, for instance, a
user-specific scaling can be activated for the analog I/Os.
R33 to R47 Terminal-specific Registers
The function of these registers depends on the respective terminal type
(see terminal-specific register description).
Extended application region
R47 to R63
Extended registers with additional functions.
KL3311, KL3312, KL3314 and KL3302 11
Register Description
Process variables
Manufacturer parameters
Terminal-specific register description
R0: Raw ADC value (X_R)
This register contains the unfiltered ADC value of the connected element
according to (Eq. 0.1)
(0x0000 corresponds to approx. -125mV, 0x8000 to approx. 0V, 0xFFFF to
approx. 125 mV, i.e. gain and offset errors are present)
R1 to R5: Reserved
R6: Diagnostic register
High byte: reserved
Low byte: status byte
R17: Hardware compensation - offset (B_a)
16 bit signed integer
This register is used for offset compensation of the terminal (Eq. 1.2).
Register value approx. 0x0000
R18: Hardware compensation - gain (A_a)
This register is used for gain compensation of the terminal (Eq. 1.2).
Register value approx. 0x3D4X
R19: Manufacturer scaling - offset (B_h)
16 bit signed integer [0x0000]
This register contains the offset of the manufacturer's equation of the
straight line (1.6). The straight-line equation is activated via register R32.
R20: Manufacturer scaling - gain (A_h)
16 bits signed integer *2
This register contains the scale factor of the manufacturer's equation of the
straight line (1.6). The straight-line equation is activated via register R32.
R21: Manufacturer gain compensation for reference voltage
[approx. 0x01XX]
-8
[0x00A0]
12 KL3311, KL3312, KL3314 and KL3302
Register Description
User parameters
R32: Feature register
[0x1006]
The feature register specifies the terminal's operating mode.
- reserved, do not change!
1 Reference temperature off [0]
- reserved, do not change!
1
Element
Type: L -25°C to 900°C
Type: J -100°C to 1,200°C
Type: E -100°C to 1,000°C
Type: T -100°C to 400°C
Type: N -100°C to 1,300°C
Type: U -25°C to 600°C
Type: B 600°C to 1,800°C
Type: R 0°C to 1,700°C
Type: S 0°C to 1,700°C
In the delivery state, the watchdog
timer is switched on.
Sign / amount representation is active
instead of two's-complement
representation. (-1 = 0x8001)
This bit is used for inserting status
information on the lowest 3 bits (see
below).
Deactivates the measuring current for
broken wire detection
Checking of the lower measuring range
limit not applicable. [0]
Valid measuring range
-100°C to 1,370°C
Valid measuring range
*) no scaling active
**) only manufacturer scaling active
Examples Bit 15 to 12: 1111, no scaling active:
The output format is as follows: 1 digit corresponds to 1/16 °C or to 4 μV
Bit 15 to 12: 1111, manufacturer scaling activated via bit 1 of the feature
register:
The output format is as follows: 1 digit corresponds to 1/10 °C or to 6.4 μV
KL3311, KL3312, KL3314 and KL3302 13
Register Description
If the Siemens output format is selected, the lowest three bits are used to
assess the status. The process data is represented in bits 3 to 15, with bit
15 representing the sign bit. Scaling of the measurement reading according
to the Siemens standard has to be done via user scaling.
Measured
value
out of range
in range
Bit 15 ... 3
0 0 1
Process data 0 0 0
Bit 2
X
Bit 1
Error
Bit 0
Overflow
R33: User scaling - offset (B_w)
16 bit signed integer
This register contains the offset of the user straight-line equation (1.7). The
straight-line equation is activated via register R32.
R34: User scaling - gain (A_w)
16 bits signed integer* 2
-8
This register contains the scale factor of the user straight-line equation (1.7)
The straight-line equation is activated via register R32.
R35 and R36: reserved
R37: Filter constant
[0x0000]
This documentation applies to all terminals from software version 3x. The
i
Note
version number can be found within the serial number on the right-hand
side face of the terminal: xxxx3xxx
Example: 52983A2A ⇒ The firmware version is 3A.
Filter constants: First notch [Hz] Conversion time [ms]
The control byte is transmitted from the controller to the terminal. The
control byte is not used for KL331x and KL3302.
The status byte is transmitted from the terminal to the controller. The status
byte contains various status bits for the analog input channel:
status byte:
Bit 7 = 0
Bit 6 = 1
bin
: ERROR - general error bit
bin
Bit 5 to bit 2: reserved
Bit 1 = 1
Bit 0= 1
: Over range
bin
: Under range
bin
Compensation The terminals are compensated when delivered.
In order to compensate tolerances of the external components, gain and
offset registers for compensating the thermocouple voltage are
implemented for each channel, i.e. R17 (thermocouple voltage offset) and
R18 (thermocouple voltage gain). For compensating the reference point
temperature (temperature at the transition between the thermocouple and
14 KL3311, KL3312, KL3314 and KL3302
Register Description
the terminal contacts), a gain register (R21) is implemented, which is
identical for both sets of registers.
Compensation can be carried out as follows:
First, the offset is carried out with 0V input voltage, reference temperature
deactivated and linearization switched off. 0xF100 is entered in the feature
register. This is followed by gain compensation with a maximum voltage of
125 mV (typical value: 70 mV). For this terminal setting with deactivated
manufacturer scaling, the voltage is displayed with 4 μV per digit.
Gain and offset compensation of the thermocouple voltage is carried out
separately for each channel.
In the next step, the temperature of the reference point is compensated. To
this end, a thermocouple has to be selected via the feature register, and
reference point temperature compensation must be active (R32 0x1006
type K). With short-circuited inputs (0 V), the temperature of the terminal
contacts is determined, and the temperature output by the terminal
(measured via an internal temperature sensor) is set accordingly (via R21).
The reference point temperature only has to be calibrated once for each
terminal, i.e. R21 is identical for both channels.
Register communication
Register access via
process data exchange
Bit 7=1
: Register mode
bin
If bit 7 of the control byte is set, then the first two bytes of the user data are
not used for exchanging process data, but are written into or read from the
terminal's register set.
Bit 6=0
Bit 6=1
: read
bin
: write
bin
Bit 6 of the control byte specifies whether a register should be read or
written. If bit 6 is not set, then a register is read out without modifying it.
The value can then be taken from the input process image.
If bit 6 is set, then the user data is written into a register. As soon as the
status byte has supplied an acknowledgement in the input process image,
the procedure is completed (see example).
Bit 0 to 5: Address The address of the register that is to be addressed is entered into bits 0 to
5 of the control byte.
Control byte in
register mode
MSB
REG=1 W/R A5 A4 A3 A2 A1 A0
REG = 0
REG = 1
W/R = 0
W/R = 1
: Process data exchange
bin
: Access to register structure
bin
: Read register
bin
: Write register
bin
A5...A0 = register address
Address bits A5 to A0 can be used to address a total of 64 registers.
KL3311, KL3312, KL3314 and KL3302 15
Register Description
To the bus coupler
K-Bus
Control-/
status byte
C/S-bit 7
If control bit 6=0: read
If control bit 6=1: write
Complex bus te rmina l
Example 1 Reading of register 8 in the BK2000 with a KL3312 and the end terminal:
Example 2 Writing of register 31 in the BK2000 with an intelligent terminal and the end
The control or status byte occupies the lowest address of a logical channel.
The corresponding register values are located in the following 2 data bytes.
(The BK2000 is an exception: here, an unused (reserved) data byte is
automatically inserted after the control or status byte, and the register
value is therefore placed on a word boundary).
If the following bytes are transferred from the control to the terminal,
Byte
Name
Value
Byte 3 Byte 2 Byte 1 Byte 0
DataOUT 1 DataOUT 0 Not used Control byte
0xXX 0xXX 0xXX 0x88
the terminal returns the following type identifier (0x0CF0 corresponds to
unsigned integer 3312).
Byte
Name
Value
Byte 3 Byte 2 Byte 1 Byte 0
DataIN 1 DataIN 0 Not used Status byte
0x0C 0xF0 0x00 0x88
terminal:
If the following bytes (code word) are transferred from the control to the
terminal,
Byte
Name
Value
Byte 3 Byte 2 Byte 1 Byte 0
DataOUT 1 DataOUT 0 Not used Control byte
0x12 0x35 0xXX 0xDF
the code word is set, and the terminal returns the register address with bit
7 for register access as acknowledgement.
Byte
Name
Value
Byte 3 Byte 2 Byte 1 Byte 0
DataIN 1 DataIN 0 Not used Status byte
0x00 0x00 0x00 0x9F
Default mapping for:
Lightbus, Ethernet,
EtherCAT and
Bus Terminal Controller
(BCxxxx, BXxxxx)
Legend See KL3312 mapping.
Appendix
Mapping
As already described in the Terminal Configuration section, each Bus
Terminal is mapped in the Bus Coupler. In the delivery state, this mapping
occurs with the default settings of the Bus Coupler for this terminal. The
default setting can be changed with the KS2000 configuration software or
with a master configuration software (e.g. TwinCAT System Manager or
ComProfibus).
If the terminals are fully evaluated, they occupy memory space in the input
and output process image.
The following tables provide information about the terminal mapping,
depending on the conditions set in the Bus Coupler.
KL3311
Conditions Word offsetHigh byte Low byte
Complete evaluation: no 0 Ch0 D1 Ch0 D0
Motorola format: no 1 - Word alignment: any 2 - 3 - -
Conditions Word offsetHigh byte Low byte
Complete evaluation: no 0 Ch0 D0 Ch0 D1
Motorola format: yes 1 - Word alignment: any 2 - 3 - -
Conditions Word offsetHigh byte Low byte
Complete evaluation: yes 0 Ch0 D0 Ch0 CB/SB
Motorola format: no 1 - Ch0 D1
Word alignment: no 2 - 3 - -
Conditions Word offsetHigh byte Low byte
Complete evaluation: yes 0 Ch0 D1 Ch0 CB/SB
Motorola format: yes 1 - Ch0 D0
Word alignment: no 2 - 3 - -
Conditions Word offsetHigh byte Low byte
Complete evaluation: yes 0 res. Ch0 CB/SB
Motorola format: no 1 Ch0 D1 Ch0 D0
Word alignment: yes 2 - 3 - -
Multiplex shift register 0x0218/0130 R ROM
Signal channels 0x0218 R ROM
Minimum data length 0x0098 R ROM
Data structure 0x0000 R ROM
reserved 0x0000 R
Alignment register variable R/W RAM
Hardware version number 0x???? R/W SEEROM
Hardware compensation: Offset specific R/W SEEROM
Hardware compensation: Gain specific R/W SEEROM
Manufacturer scaling: Offset 0x0000 R/W SEEROM
Manufacturer scaling: Gain 0x00A0 R/W SEEROM
specific R/W SEEROM
temperature
reserved 0x0000 R/W SEEROM
...
... ... ... ...
reserved 0x0000 R/W SEEROM
Code word register variable R/W RAM
Feature register 0x1006 R/W SEEROM
User scaling: Offset 0x0000 R/W SEEROM
User scaling: Gain 0x0100 R/W SEEROM
reserved 0x0000 R/W SEEROM
reserved 0x0000 R/W SEEROM
reserved 0x0138 R/W SEEROM
...
... ... ... ...
reserved 0x0000 R/W SEEROM
20 KL3311, KL3312, KL3314 and KL3302
Appendix
Beckhoff and their partners around the world offer comprehensive service
Support and Service
and support, making available fast and competent assistance with all
questions related to Beckhoff products and system solutions.
Beckhoff's branch offices and representatives
Please contact your Beckhoff branch office or representative for local
support and service on Beckhoff products!
The addresses of Beckhoff's branch offices and representatives round the
world can be found on her internet pages: http://www.beckhoff.com
You will also find further documentation for Beckhoff components there.
Support offers you comprehensive technical assistance, helping you not
only with the application of individual Beckhoff products, but also with
other, wide-ranging services:
• world-wide support
• design, programming and commissioning of complex automation
systems
•and extensive training program for Beckhoff system components