4 Mounting and wiring................................................................................................................................72
4.1Installation on mounting rails ...........................................................................................................72
4.2Installation instructions for enhanced mechanical load capacity .....................................................74
6.4.5Simultaneous updating of several EtherCAT devices.................................................... 161
6.5Restoring the delivery state ...........................................................................................................162
6.6Support and Service ......................................................................................................................163
EL20xx, EL21244Version: 5.2
1Foreword
1.1Product overview, digital output terminals
Foreword
EL2002 [}17]
EL2004 [}17]
EL2008 [}17]
EL2014 [}23]
EL2022, EL2024 [}43]
EL2024-0010 [}43]
EL2032, EL2034 [}47]
EL2042 [}51]
EL2084, EL2088 [}54]
EL2124 [}58]
2 channels, 24VDC, 0.5A
4 channels, 24VDC, 0.5A
8 channels, 24VDC, 0.5A
4 channels, 24VDC, 0.5A, diagnostics
2 and 4 channels, 24VDC, 2A
4 channels, 12VDC, 2A
2 and 4 channels, 24VDC, 2A, diagnostics
2 channels, 24VDC; 2 x 4A/1 x 8A
4 and 8 channels, 24VDC, 0.5A
4 channels, 5VDC, CMOS-outputs
1.2Notes on the documentation
Intended audience
This description is only intended for the use of trained specialists in control and automation engineering who
are familiar with the applicable national standards.
It is essential that the documentation and the following notes and explanations are followed when installing
and commissioning these components.
It is the duty of the technical personnel to use the documentation published at the respective time of each
installation and commissioning.
The responsible staff must ensure that the application or use of the products described satisfy all the
requirements for safety, including all the relevant laws, regulations, guidelines and standards.
Disclaimer
The documentation has been prepared with care. The products described are, however, constantly under
development.
We reserve the right to revise and change the documentation at any time and without prior announcement.
No claims for the modification of products that have already been supplied may be made on the basis of the
data, diagrams and descriptions in this documentation.
Trademarks
Beckhoff®, TwinCAT®, EtherCAT®, EtherCATP®, SafetyoverEtherCAT®, TwinSAFE®, XFC® and XTS® are
registered trademarks of and licensed by Beckhoff Automation GmbH.
Other designations used in this publication may be trademarks whose use by third parties for their own
purposes could violate the rights of the owners.
Patent Pending
The EtherCAT Technology is covered, including but not limited to the following patent applications and
patents: EP1590927, EP1789857, DE102004044764, DE102007017835 with corresponding applications or
registrations in various other countries.
The TwinCAT Technology is covered, including but not limited to the following patent applications and
patents: EP0851348, US6167425 with corresponding applications or registrations in various other countries.
EL20xx, EL21245Version: 5.2
Foreword
EtherCAT® is registered trademark and patented technology, licensed by Beckhoff Automation GmbH,
Germany.
Please note the following safety instructions and explanations!
Product-specific safety instructions can be found on following pages or in the areas mounting, wiring,
commissioning etc.
Exclusion of liability
All the components are supplied in particular hardware and software configurations appropriate for the
application. Modifications to hardware or software configurations other than those described in the
documentation are not permitted, and nullify the liability of Beckhoff Automation GmbH & Co. KG.
Personnel qualification
This description is only intended for trained specialists in control, automation and drive engineering who are
familiar with the applicable national standards.
Description of instructions
In this documentation the following instructions are used.
These instructions must be read carefully and followed without fail!
DANGER
Serious risk of injury!
Failure to follow this safety instruction directly endangers the life and health of persons.
WARNING
Risk of injury!
Failure to follow this safety instruction endangers the life and health of persons.
CAUTION
Personal injuries!
Failure to follow this safety instruction can lead to injuries to persons.
NOTE
Damage to environment/equipment or data loss
Failure to follow this instruction can lead to environmental damage, equipment damage or data loss.
Tip or pointer
This symbol indicates information that contributes to better understanding.
EL20xx, EL21247Version: 5.2
Foreword
1.4Documentation issue status
Version Comment
5.2- Update structure
- Chapter “Non-reactive Bus Terminals” updated
5.1- Update structure
- Chapter “Non-reactive Bus Terminals” updated
5.0- Update structure
- Chapter “Technical data” updated
4.9- Chapter “Non-reactive Bus Terminals” updated
4.8- Chapter “Introduction” updated
- Chapter “LEDs and connection” updated
- Update structure
4.7- Chapter “Non-reactive Bus Terminals” updated
- Update structure
4.6- Chapter “Non-reactive Bus Terminals” updated
- Chapter “Technical data” updated
4.5- Chapter “Introduction” Notes updated
- Chapter “Technical data” updated
4.4- Chapter “Foreword” – “Notes on the documentation“ updated
- Technical data corrected
- Chapter “TwinCAT Quickstart” added
- Chapter “EtherCAT slave process data settings” removed
2.2- Technical data amended, watchdog documentation amended
2.1- Terminals EL2022, EL2024, EL2034 added
2.0- Terminals EL2002, EL2008 added, technical data amended
1.0- Technical data amended
0.1- Provisional documentation for EL20xx
EL20xx, EL21248Version: 5.2
Foreword
1.5Version identification of EtherCAT devices
Designation
A Beckhoff EtherCAT device has a 14-digit designation, made up of
• family key
• type
• version
• revision
ExampleFamilyTypeVersionRevision
EL3314-0000-0016EL terminal
(12 mm, nonpluggable connection
level)
ES3602-0010-0017 ES terminal
(12 mm, pluggable
connection level)
CU2008-0000-0000 CU device2008 (8-port fast ethernet switch) 0000 (basic type) 0000
3314 (4-channel thermocouple
terminal)
3602 (2-channel voltage
measurement)
0000 (basic type) 0016
0010 (highprecision version)
0017
Notes
• The elements mentioned above result in the technical designation. EL3314-0000-0016 is used in the
example below.
• EL3314-0000 is the order identifier, in the case of “-0000” usually abbreviated to EL3314. “-0016” is the
EtherCAT revision.
• The order identifier is made up of
- family key (EL, EP, CU, ES, KL, CX, etc.)
- type (3314)
- version (-0000)
• The revision -0016 shows the technical progress, such as the extension of features with regard to the
EtherCAT communication, and is managed by Beckhoff.
In principle, a device with a higher revision can replace a device with a lower revision, unless specified
otherwise, e.g. in the documentation.
Associated and synonymous with each revision there is usually a description (ESI, EtherCAT Slave
Information) in the form of an XML file, which is available for download from the Beckhoff web site.
From 2014/01 the revision is shown on the outside of the IP20 terminals, see Fig. “EL5021 EL terminal,standard IP20 IO device with batch number and revision ID (since 2014/01)”.
• The type, version and revision are read as decimal numbers, even if they are technically saved in
hexadecimal.
Identification number
Beckhoff EtherCAT devices from the different lines have different kinds of identification numbers:
Production lot/batch number/serial number/date code/D number
The serial number for Beckhoff IO devices is usually the 8-digit number printed on the device or on a sticker.
The serial number indicates the configuration in delivery state and therefore refers to a whole production
batch, without distinguishing the individual modules of a batch.
Structure of the serial number: KKYYFFHH
KK - week of production (CW, calendar week)
YY - year of production
FF - firmware version
HH - hardware version
EL20xx, EL21249Version: 5.2
Foreword
Example with
Ser. no.: 12063A02: 12 - production week 12 06 - production year 2006 3A - firmware version 3A 02 hardware version 02
Exceptions can occur in the IP67 area, where the following syntax can be used (see respective device
documentation):
Syntax: D ww yy x y z u
D - prefix designation
ww - calendar week
yy - year
x - firmware version of the bus PCB
y - hardware version of the bus PCB
z - firmware version of the I/O PCB
u - hardware version of the I/O PCB
Example: D.22081501 calendar week 22 of the year 2008 firmware version of bus PCB: 1 hardware version
of bus PCB: 5 firmware version of I/O PCB: 0 (no firmware necessary for this PCB) hardware version of I/O
PCB: 1
Unique serial number/ID, ID number
In addition, in some series each individual module has its own unique serial number.
See also the further documentation in the area
• IP67: EtherCAT Box
• Safety: TwinSafe
• Terminals with factory calibration certificate and other measuring terminals
Examples of markings
Fig.1: EL5021 EL terminal, standard IP20 IO device with serial/ batch number and revision ID (since
2014/01)
EL20xx, EL212410Version: 5.2
Fig.2: EK1100 EtherCAT coupler, standard IP20 IO device with serial/ batch number
Foreword
Fig.3: CU2016 switch with serial/ batch number
Fig.4: EL3202-0020 with serial/ batch number 26131006 and unique ID-number 204418
EL20xx, EL212411Version: 5.2
Foreword
Fig.5: EP1258-00001 IP67 EtherCAT Box with batch number/ date code 22090101 and unique serial
number 158102
Fig.6: EP1908-0002 IP67 EtherCAT Safety Box with batch number/ date code 071201FF and unique serial
number 00346070
Fig.7: EL2904 IP20 safety terminal with batch number/ date code 50110302 and unique serial number
00331701
Fig.8: ELM3604-0002 terminal with unique ID number (QR code) 100001051 and serial/ batch number
44160201
EL20xx, EL212412Version: 5.2
Foreword
1.6Non-reactive Bus Terminals
Use of non-reactive Bus or EtherCAT Terminals in safety applications
If a Bus or EtherCAT Terminal is described as non-reactive, this means that the consecutive terminal behaves passively in a safety application (e.g. in the case of the all-pole switch-off of a potential
group).
In this case the terminals do not represent an active part of the safety controller and do not affect
the Safety Integrity Level (SIL) or Performance Level (PL) attained in the safety application.
For details, please refer to chapter 2.17f in the TwinSAFE application manual.
NOTE
Pay attention to the hardware version
Please pay attention to the information about the hardware version and non-reactivity of the respective Bus
Terminal in the chapters "Technical Data" or "Firmware Compatibility"!
Only terminals with the appropriate hardware version may be used without the attained SIL/PL being affected!
The Bus or EtherCAT Terminals regarded as non-reactive at the time of preparing this document are listed in
the following tables together with their respective hardware versions.
Terminal name
Bus Terminal
KL240805
KL280902
KL213409
KL242405
KL911007
Terminal name
EtherCAT terminal
EL200415
EL200807
EL202209
EL202406
EL203406
EL280901
EL287201
EL2878-000500
EL911013
EL941016
from hardware version
from hardware version
External wiring
The following requirements are to be ensured by the system manufacturer and must be incorporated into the
user documentation.
• Protection class IP54
The terminals must be installed in IP54 control cabinets to ensure the necessary protection class IP54.
• Power supply unit
The standard terminals must be supplied with 24V by an SELV/PELV power supply unit with an output
voltage limit U
• Prevention of feedback
Feedback can be prevented through different measures. These are described below. In addition to
mandatory requirements there are also optional requirements, of which only one needs to be selected.
EL20xx, EL212413Version: 5.2
of 60V in the event of a fault.
max
Foreword
◦ No switching of loads with a separate power supply
Loads that have their own power supply must not be switched by standard terminals, since in this
case feedback via the load cannot be ruled out.
Fig.9: Negative example – active load
◦ The control of an STO input of a frequency converter could serve here as a negative example.
Exceptions to the general requirement are allowed only if the manufacturer of the connected load
guarantees that feedback to the control input cannot occur. This can be achieved, for example,
through adherence to load-specific standards.
◦ Option 1: Ground feedback and all-pole disconnection
The ground connection of the connected load must be fed back to the safely switched ground of
the respective output terminal.
EL20xx, EL212414Version: 5.2
Foreword
Fig.10: Ground connection of the load: correct (K1) and incorrect (K2)
◦ If either
a) the ground of the load is not fed back to the terminal or
b) the ground is not safely switched but connected permanently
then fault exclusions are necessary with regard to a short-circuit with external potential in order to
be able to achieve Cat. 4 PLe according to EN ISO 13849-1:2007 or SIL3 according to IEC
61508:2010 (refer here to the overview in the chapter "Effect of options on the safety level").
◦ Option 2: Cable short-circuit fault exclusion
If solution option 1 is not feasible, the ground feedback and all-pole disconnection can be
dispensed with if the danger of feedback due to a cable short-circuit can be excluded by other
measures. These measures, which can be implemented alternatively, are described in the
following sections.
EL20xx, EL212415Version: 5.2
Foreword
Fig.11: Short circuit fault exclusion through protected cable laying
◦ a) Possibility 1: Load connection via separate sheathed cables
The non-safely switched potential of the standard terminal may not be conducted together with
other potential-conducting cores inside the same sheathed cable. (Fault exclusion, see EN ISO
13849-2:2013, Table D.4)
◦ b) Possibility 2: Wiring only inside the control cabinet
All loads connected to the non-safe standard terminals must be located in the same control
cabinet as the terminals. The cables are routed entirely inside the control cabinet. (Fault exclusion,
see EN ISO 13849-2:2013, Table D.4)
◦ c) Possibility 3: Dedicated earth connection per conductor
All conductors connected to the non-safe standard terminals are protected by their own earth
connection. (Fault exclusion, see EN ISO 13849-2:2013, Table D.4)
◦ d) Possibility 4: Cable permanently (fixed) installed and protected against external damage
All conductors connected to the non-safe standard terminals are permanently fixed and, e.g.
protected against external damage by a cable duct or armored pipe.
• Effect of the options on the safety level
In principle, standard terminals in safely switched potential groups are not an active part of the safety
controller. Accordingly, the safety level attained is defined only by the higher-level safetycontroller, i.e. the standard terminals are not included in the calculation! However, the wiring of the
standard terminals can lead to limitations in the maximum attainable safety level.
Depending on the solution selected for the avoidance of feedback and the safety standard considered
(see Option 1 and Option 2), different maximum attainable safety levels result, which are summarized
in the following table:
Summary of safety classifications
Feedback avoidance measures
Fault exclusion
Cable short-circuit
Ground feedback and allpole disconnection
DIN EN ISO 13849-1IEC 61508EN 62061
max.
Cat. 4
PLe
max. SIL3max. SIL2 *
max. SIL3
EL20xx, EL212416Version: 5.2
Product overview, digital output terminals
2Product overview, digital output terminals
2.1EL2002, EL2004, EL2008 - Introduction
Fig.12: EL2002, EL2004
Fig.13: EL2008
Two-, four-, and eight-channel digital output terminals 24VDC, 0.5A
The EL200x digital output terminals relay binary control signals of the automation device in an electrically
isolated manner to the actuators of the process level. They are protected against reverse polarity at the
power contacts. The digital output terminals of the EL200x series indicate their signal state through an LED
for each channel.
EL20xx, EL212417Version: 5.2
Product overview, digital output terminals
CAUTION
Watchdog settings
Please refer to section "Notes for setting the watchdog [}62]".
EL20xx, EL212418Version: 5.2
Product overview, digital output terminals
2.1.1EL2002, EL2004, EL2008 - Technical data
Technical dataEL2002EL2004EL2008
Number of outputs248
Non-reactive outputs-yes
(see notice [}13])
Load typeohmic, inductive, lamp load
Nominal output voltage24VDC (-15%/ +20%)
Switching timesTON: 60µs typ.; T
Output current per channelmaximum 0.5A (short-circuit proof)
Switch-off energy (inductive)max. 150mJ/channel
Current consumption from load
voltage (power contacts)
Supply voltage for electronicvia the E-Bus
Current consumption via E-bustyp. 100mAtyp. 100mAtyp. 110mA
Electrical isolation500V (E-bus/field voltage)
Bit width in the process image2 output bits4 output bits8 output bits
Configurationno address setting, configuration via TwinCAT System Manager
Weightapprox. 55g
Permissible ambient temperature
range during operation
Permissible ambient temperature
range during storage
Permissible relative humidity95%, no condensation
Dimensions (W x H x D)approx. 15 mm x 100 mm x 70 mm (width aligned: 12 mm)
Mounting [}72]
Vibration/shock resistanceaccording to EN 60068-2-6/EN 60068-2-27,
EMC resistance burst/ESDconforms to EN 61000-6-2 / EN 61000-6-4
Protection classIP20
Installation positionvariablevariable
ApprovalCE
typ. 15mA
-25°C ... +60°C (extended temperature
range)
-40°C ... +85°C
on 35 mm mounting rail conforms to EN 60715
see also Installation instructions for terminals with increased mechanical load capacity [}74]
cULus [}150]
ATEX [}82]
: 300µs typ.
OFF
yes
(see notice [}13])
Aligned in horizontal installation position:
-25°C ... +60°C (extended temperature range)
All other installation positions, see note[}78]:-25°C... +45°C
see note [}78]
EL20xx, EL212419Version: 5.2
Product overview, digital output terminals
2.1.2EL2002 - LEDs and connection
Fig.14: EL2002
EL2002 - LEDs
LEDColorMeaning
OUTPUT 1
OUTPUT 2
greenoffNo output signal
on24VDC output signal at the respective output
EL2002 - Connection
Terminal pointDescription
NameNo.
Output 11Output 1
+24V2+24V (internally connected to terminal point6 and positive power contact)
0V3Ground for output1 (internally connected to terminal point7 and negative power contact)
PE4PE (internally connected to terminal point8)
Output 25Output 2
+24V6+24V (internally connected to terminal point2 and positive power contact)
0V7Ground for output2 (internally connected to terminal point3 and negative power contact)
PE8PE (internally connected to terminal point4)
EL20xx, EL212420Version: 5.2
2.1.3EL2004 - LEDs and connection
Product overview, digital output terminals
Fig.15: EL2004
EL2004 - LEDs
LEDColorMeaning
OUTPUT 1- 4greenoffNo output signal
on24VDC output signal at the respective output
EL2004 - Connection
Terminal pointDescription
NameNo.
Output 11Output 1
0V2Ground for output1 (internally connected to terminal point3, 6, 7 and negative power contact)
0V3Ground for output3 (internally connected to terminal point2, 6, 7 and negative power contact)
Output 34Output 3
Output 25Output 2
0V6Ground for output2 (internally connected to terminal point2, 3, 7 and negative power contact)
0V7Ground for output4 (internally connected to terminal point2, 3, 6 and negative power contact)
Output 48Output 4
EL20xx, EL212421Version: 5.2
Product overview, digital output terminals
2.1.4EL2008 - LEDs and connection
Fig.16: EL2008
EL2008 - LEDs
LEDColorMeaning
OUTPUT 1- 8greenoffNo output signal
on24VDC output signal at the respective output
EL2008 - Connection
Terminal pointDescription
NameNo.
Output 11Output 1
Output 32Output 3
Output 53Output 5
Output 74Output 7
Output 25Output 2
Output 46Output 4
Output 67Output 6
Output 88Output 8
EL20xx, EL212422Version: 5.2
2.2EL2014
2.2.1EL2014 - Introduction
Product overview, digital output terminals
Fig.17: EL2014
Four-channel digital output terminal, 24VDC, 0.5A, with diagnostics
The EL2014 digital output terminal connects the binary control signals from the automation device on to the
actuators at the process level with electrical isolation. The EL2014 is protected against polarity reversal and
processes load currents with outputs protected against overload and short-circuit. The integrated diagnosis
can be evaluated in the controller and is indicated by the LEDs. Overtemperature and the lack of a voltage
supply to the terminal are supplied as diagnostic information. Beyond that each channel can among other
things signal a short circuit individually. The output behavior of the channels in the case of a bus error can be
parameterized. The switching state and any error of the output are indicated by the LED. Maintenance of the
application is simplified by the diagnosis. The power contacts are continuous; reference potential of the
outputs is the 0V power contact.
The outputs are fed via the 24V power contact in the EL2014.
NOTE
Watchdog settings
Please refer to section "Notes for setting the watchdog [}62]".
EL20xx, EL212423Version: 5.2
Product overview, digital output terminals
2.2.2EL2014 - Technical data
Technical dataEL2014
Connection technology1-wire
digital outputs4
Rated load voltage24VDC (-15%/ +20%)
Load typeohmic, inductive, lamp load
Distributed clocksNo
Max. output current0.5A (short-circuit-proof) per channel
Short circuit current< 1A typ.
Breaking energy< 150mJ/channel
Output stagepush (high-side switch)
Reverse voltage protectionYes
Switching timesTON: 50µs typ., T
Supply voltage for electronicVia the power contacts
Current consumption via E-bustyp. 60mA
Recommended cycle time≥ 200µs; with cycle times < 200µs the process data is not
updated in each cycle.
Current consumption of power contacts typ. 15mA + load
Electrical isolation500V (E-bus/field voltage)
Bit width in process image4-bit output and 20-bit diagnostics
Supports NoCoeStorage [}68] function
Yes
Configurationvia System Manager
Conductor typessolid wire, stranded wire and ferrule
Special featuresdiagnostics via process data and LED: overtemperature,
PowerFail, short circuit (per channel)
Weightapprox. 70g
Permissible ambient temperature range
0 °C ... +55 °C
during operation
Permissible ambient temperature range
-25 °C ... +85 °C
during storage
Permissible relative humidity95%, no condensation
Dimensions (W x H x D)approx. 15mm x 100mm x 70mm (width aligned: 12mm)
Mounting [}72]
on 35mm mounting rail conforms to EN 60715
Vibration/shock resistanceconforms to EN 60068-2-6 / EN 60068-2-27
EMC immunity/emissionconforms to EN 61000-6-2 / EN 61000-6-4
0V2Ground for output1 (internally connected to terminal point3, 6, 7 and negative power
0V3Ground for output3 (internally connected to terminal point2, 6, 7 and negative power
Output 34Output 3
Output 25Output 2
0V6Ground for output2 (internally connected to terminal point2, 3, 7 and negative power
0V7Ground for output4 (internally connected to terminal point2, 3, 6 and negative power
Output 48Output 4
No.
contact)
contact)
contact)
contact)
ERROR: Open Load
EL20xx, EL212425Version: 5.2
Product overview, digital output terminals
2.2.4Overload protection
Technical data
Please note the information in the technical data regarding load type, max. output current and short
circuit current.
When switching on lamp loads, high starting currents occur that are limited by the output circuit of the
terminals (see fig. Overload current limitation).
Fig.19: Overload current limitation
Fig.20: Schematic illustration of the thermal switch-off in case of overload
In case of a long-term overload and/or short-circuit, the output is protected by the thermal switch-off of the
channel.
The output circuit of the terminal limits the current. The terminal maintains this current until important selfheating of the channel occurs.
On exceeding the upper temperature limit, the terminal switches the channel off.
The channel is switched on again after it has cooled down to below the lower temperature limit.
The output signal is clocked until the output is switched off by the controller or the short-circuit is eliminated
(see fig. Schematic illustration of the thermal switch-off in case of overload). The clock frequency depends
on the ambient temperature and the load of the other terminal channels.
EL20xx, EL212426Version: 5.2
Product overview, digital output terminals
Short-circuit or prolonged overload on a channel leads to an increase in the device temperature. If several
channels are overloaded, this leads to a rapid increase in the device temperature. The overloaded channels
are switched off when the upper limit for the device temperature is exceeded. The channels are only
switched on again if the temperature falls below the lower limit values for both the device and the channel.
The non-overloaded channels continue operating properly.
When switching off inductive loads, high induction voltages result from interrupting the current too quickly.
These are limited by an integrated free-wheeling diode (breaking energy see Technical data). Since the
current reduces only slowly, a delayed switch-off can occur in many control applications. For example, a
valve remains open for many milliseconds. Switch-off times are realized that correspond, for instance, to the
switch-on time of the coil.
Protection against high induction voltages
To protect against voltage peaks such as can occur when switching inductive loads, we recommend
to provide suitable protective circuits (e.g. with the free-wheeling diode, RC combination or varistor)
directly at the actuator.
Fig.21: Switch-off of inductive loads
EL20xx, EL212427Version: 5.2
Product overview, digital output terminals
2.2.5Operating modes and settings
2.2.5.1Process data
Parameterization
An EL2014 is parameterized via 2 tabs in the TwinCAT System Manager: the Process Data tab (A) for the
communication-specific settings and the CoE directory (B) for the settings in the slave.
Fig.22: EL2014 “Process Data” tab
• Changes to the process data-specific settings are generally only effective after a restart of the
EtherCAT master:
Restart TwinCAT in RUN or CONFIG mode; RELOAD in CONFIG mode
• Changes to the online CoE directory
◦ are in general immediately effective
◦ are generally stored in non-volatile memory in the terminal/slave. They should be entered in the
CoE StartUp list so that the settings are accepted after a replacement of the terminal. The CoE
StartUp list is processed at each EtherCAT start and the settings are loaded into the slave.
Illustration of the process data and structural contents
The EL2014 provides three different process data for transmission:
• the diagnostics per channel “DIG Diag Inputs” (16-bit),
• the device diagnostics “DIG Inputs Device” (4-bit),
• The switching state of the outputs “DIG output” (4-bit)
EL20xx, EL212428Version: 5.2
Product overview, digital output terminals
Fig.23: EL2014 Online illustration of the process data and structural contents in the System Manager
The plain text display of the bit meanings is particularly helpful not only in commissioning but also for linking
to the PLC program.
By right-clicking on the Status variable in the configuration tree (A), the structure can be opened for linking
(B).
Activation of the “Show Sub Variables” button (C) displays all subvariables and links to the PLC (D) in the
online view.
The process data to be transmitted (PDO, ProcessDataObjects) can be selected by the user
• for all TwinCAT versions via the “Predefined PDO Assignment” selection dialog (see fig. “EL2014
Process Data tab” A) or
• selectively for individual PDOs (see fig. “EL2014 Process Data tab” B)
. These changes become effective after activation and an EtherCAT restart or a reload.
EL20xx, EL212429Version: 5.2
Product overview, digital output terminals
Fig.24: EL2014 “Process Data” tab
A Selection of the diagnostic scope via the selection dialog “Predefined PDO Assignment”
B Display of (optional) PDOs (process data objects)
C Selection of the required Sync Manager
D Display of the PDOs available for selection
Three pre-defined PDO assignments can be selected:
• Full Diagnostics:
Inputs: Selection of the PDOs 0x1A00 (diagnostics per channel) and 0x1A02 (device diagnostics). Both
the diagnostic data for each channel and the data for the device diagnostics are displayed and
transmitted.
Outputs: PDO 0x1600 (switching state of the outputs) is displayed and transmitted.
• Compact Diagnostics:
Inputs: Selection of the PDO 0x1A02 (device diagnostics). Only the diagnostic data for the device are
displayed in the System Manager and transmitted to the control system.
Outputs: PDO 0x1600 (switching state of the outputs) is displayed and transmitted.
• No Diagnostics: Neither 0x1A00 nor 0x1A02 is selected. No diagnostic data are displayed in the
System Manager and none are transmitted to the control system.
Outputs: PDO 0x1600 (switching state of the outputs) is displayed and transmitted.
Compact Diagnostics, No Diagnostics
When converting from “Full Diagnostics” to “Compact Diagnostics” or “No Diagnostics”, or when deactivating the PDO 0x1600, links already established to the deactivated objects are deleted.
EL20xx, EL212430Version: 5.2
Product overview, digital output terminals
2.2.5.2Diagnostics per channel
Open Load (Index 0x60n1:02 [}36])
The open load detection shows that no load is connected when the output is switched on.
The “open load” bit (index 0x60n1:02) is set to TRUE if the output is TRUE and the output current is less
than typ. 0.2 mA.
Short Circuit to 24V (Index 0x60n1:04 [}36])
A short circuit to 24 V is detected if the output is FALSE, but nevertheless a voltage of more than typ. 10 V is
present. The “Short Circuit to 24V” bit (index 0x60n1:04) is set to TRUE. The corresponding LED flashes red.
The “Overcurrent” bit (index: 0x60n1:03) is set in case of an overload. The LED lights up red. The channel
heats up, so that the “Overtemperature” bit (index: 0x60n1:01) is set on reaching an upper limit temperature
(see fig. Overload current limitation [}27]).
In the case of a short-circuit the channel overheats very quickly, leading to it being switched off. Once the
temperature has cooled down to below a lower limit value following the switch-off, the output is switched on
again. The temperature, however, is then still so high that the “Overtemperature” bit (index: 0x60n1:01)
remains set. Thus the LED remains red as long as the short-circuit is present.
Overcurrent diagnostics is no longer possible once the output is switched off. The “Overcurrent” bit (index:
0x60n1:03) is only set to TRUE when the output is switched on again (see fig. Schematic illustration of thethermal switch-off in case of overload [}27]).
2.2.5.3Device diagnostics
General error (index 0xF600:11 [}36])
If the “Common Fault” bit (index 0xF600:11) is set, there is an error on one or more channels.
It is thus possible in the “Compact Diagnostics” process mode to determine that errors have occurred on one
or more channels.
Device overtemperature (index 0xF600:12 [}36])
The device temperature rises due to an overload, a short-circuit or excessively high ambient temperature. If
the device temperature exceeds the upper limit value, the overloaded channels are switched off. The
“Overtemperature Device” bit (index 0xF600:12) is set. All other channels continue to operate properly.
If the device temperature falls below the lower limit value the “Overtemperature Device” bit (index
0xF600:12) is reset. If the channel temperature also falls below the lower limit value, the respective channels
are switched on again.
Undervoltage (index 0xF600:13 [}36])
If the “Undervoltage” bit (index 0xF600:13) is set, the supply voltage of the terminal has fallen below typically
17 V.
Voltage loss (index 0xF600:14 [}36])
If the error bit in “Missing Voltage” (index 0xF600:14) is set, the supply voltage of the terminal has fallen
below typically 14 V.
EL20xx, EL212431Version: 5.2
Product overview, digital output terminals
2.2.5.4Settings via the CoE directory
CoE online directory
Fig.25: EL2014 CoE directory
The online data are accessible (A) if the terminal is online, i.e. connected to the EtherCAT Master TwinCAT
and in an error-free RUN state (WorkingCounter = 0). The entries “DIG Safe State Active Ch.n (index
0x80n0) (D) and “DIG Safe State Value Ch.n” (index 0x80n1) (E) can be changed online; please also
observe the Notes on the CoE interface [}67] and on the StartUp-List [}68].
The diagnostic data of the channels can be read under “DIG Diag Inputs Ch.n” (index 0x60n1) (B).
The diagnostic data of the terminal can be read under “DIG Inputs Device” (index 0xF600).
The state of the outputs can be read under “DIG Outputs Ch.n” (index 0x70n0) (C).
The display in TwinCAT is continuously updated if (F) has been activated.
EL20xx, EL212432Version: 5.2
Product overview, digital output terminals
DIG Safe State Active (index 0x80n0:01 [}35]) / DIG Safe State Value (index 0x80n1:01 [}35])
The setting in “DIG Safe State Active” (index 0x80n0:01) defines whether the outputs should assume a safe
state in the case of a bus error. The safe state of the output in the case of a bus error is defined with “DIG
Safe State Value” (index 0x80n1:01).
1. “DIG Safe State Active“ = TRUE and
◦ “DIG Safe State Value“ = TRUE: the output is switched on.
2. “DIG Safe State Active“ = TRUE and
◦ “DIG Safe State Value“ = FALSE: the output is switched off
3. “DIG Safe State Active“ = FALSE
◦ The state of the output is retained. Entries in “DIG Safe State Value” (index 0x80n1:01) have no
effect.
Flow-chart illustration of the sequence in case of a bus error
Fig.26: Change of state of the outputs in the case of a bus error
EL20xx, EL212433Version: 5.2
Product overview, digital output terminals
Tabular example:
DIG Safe State Active
Index 0x80n0:01
TRUETRUEFALSETRUEFALSE
TRUEFALSEFALSEFALSEFALSE
FALSEFALSE / TRUEFALSEFALSEFALSE
Graphical example:
DIG Safe State Value
Index 0x80n1:01
Output before
bus error
TRUETRUETRUE
TRUEFALSETRUE
TRUETRUETRUE
Output during
bus error
Output after bus
error
Fig.27: Graphical illustration of the channel state during a bus error
2.2.6Object description and parameterization
EtherCAT XML Device Description
The display matches that of the CoE objects from the EtherCAT XML Device Description. We recommend downloading the latest XML file from the download area of the Beckhoff website and in-
stalling it according to installation instructions.
Parameterization
The terminal is parameterized via the CoE Online tab (double-click on the respective object), or the
PDOs are allocated via the Process Data tab.
Introduction
The CoE overview contains objects for different intended applications:
EL20xx, EL212434Version: 5.2
Product overview, digital output terminals
2.2.6.1Restore object
Index 1011 Restore default parameters
Index (hex) NameMeaningData typeFlagsDefault value
1011:0
1011:01SubIndex 001If this object is set to "0x64616F6C" in the set value
Restore default parameters [}162]
Restore default parametersUINT8RO0x01 (1
dialog, all backup objects are reset to their delivery
state.
UINT32RW0x00000000
(0
)
dec
)
dec
2.2.6.2Configuration data
Index 80n0 DIG Safe State Active Ch.n
(n=0 for Ch.1 to n=3 for Ch.4)
Index (hex) NameMeaningData typeFlagsDefault value
80n0:0DIG Safe State Active
80n0:01
Ch.n
Active [}33]
Maximum subindexUINT8RO0x01 (1
Enabling of the output state defined in index 0x80n1:01
in case of a bus error
0: output retains its current state.
1: output is switched to the state defined in index
0x80n1.
BOOLEANRW0x01 (1
)
dec
)
dec
Index 80n1 DIG Safe State Value Ch.n
(n=0 for Ch.1 to n=3 for Ch.4)
Index (hex) NameMeaningData typeFlagsDefault value
80n1:0DIG Safe State Value
80n1:01
Ch.n
Value [}33]
Maximum subindexUINT8RO0x01 (1
Defines the state of the output in case of a bus error:
0: output off
1: output on
BOOLEANRW0x00 (0
)
dec
)
dec
2.2.6.3Command object
Index FB00 DIG Command
Index (hex) NameMeaningData typeFlagsDefault value
FB00:0DIG CommandMaximum subindexUINT8RO0x03 (3
FB00:01RequestreservedOCTET -
STRING[2]
FB00:02StatusreservedUINT8RO0x00 (0
FB00:03ResponsereservedOCTET -
STRING[4]
RW{0}
RO{0}
)
dec
)
dec
EL20xx, EL212435Version: 5.2
Product overview, digital output terminals
2.2.6.4Input data
Index 60n1 DIG Diag Inputs
(n=0 for Ch.1 to n=3 for Ch.4)
Index (hex) NameMeaningData typeFlagsDefault value
60n1:0DIG Diag Inputs Ch.n Maximum subindexUINT8RO0x04 (4
60n1:01
60n1:02
Overtemperature
[}31]
Open Load [}31]
The overtemperature bit is set if the max. permissible
temperature of the channel is exceeded.
Wire break detection
The Open Load bit is set if the channel is switched on
BOOLEANRO0x00 (0
BOOLEANRO0x00 (0
and the load current is ≤ typically 0.2 mA.
60n1:03
Overcurrent [}31]
Overcurrent and short-circuit detection
The overcurrent bit is set if an overload is detected
BOOLEANRO0x00 (0
when the channel is switched on.
No overload can be detected if the channel is switched
off (e.g. thermal switch-off).
Short-circuit current detection: typ. 1A
60n1:04
Short Circuit to 24V
[}31]
The Short Circuit to 24V bit is set if voltage is present
when the channel is switched off.
BOOLEANRO0x00 (0
Index F600 DIG Inputs Device
)
dec
)
dec
)
dec
)
dec
)
dec
Index (hex) NameMeaningData typeFlagsDefault value
• Bit 1 = 1: synchronous with SM 2 event is
supported (outputs available)
• Bit 1 = 1: synchronous with SM 3 event is
supported (no outputs available)
• Bit 2-3 = 01: DC mode is supported
• Bit 4-5 = 01: input shift through local event
(outputs available)
• Bit 4-5 = 10: input shift with SYNC1 event (no
outputs available)
• Bit 14 = 1: dynamic times (measurement by
writing 0x1C32:08 [}40]) (for revision no.: 17 –
25)
1C33:05Minimum cycle time
as 0x1C32:05 [}40]
1C33:06Calc and copy timeTime between reading of the inputs and availability of
the inputs for the master (in ns, only DC mode)
UINT32RO0x00002710
(10000
UINT32RO0x00000000
(0
dec
1C33:07Minimum delay timeUINT32RO0x00000384
(900
1C33:08Command
as 0x1C32:08 [}40]
1C33:09Maximum Delay time Time between SYNC1 event and reading of the inputs
(in ns, only DC mode)
1C33:0BSM event missed
counter
1C33:0CCycle exceeded
counter
1C33:0DShift too short counter
1C33:20Sync error
as 0x1C32:11 [}40]
as 0x1C32:12 [}40]
as 0x1C32:13 [}40]
as 0x1C32:32 [}40]
UINT16RW0x0000 (0
UINT32RO0x00000384
(900
UINT16RO0x0000 (0
UINT16RO0x0000 (0
UINT16RO0x0000 (0
BOOLEANRO0x00 (0
)
dec
dec
)
dec
)
dec
)
dec
)
)
dec
dec
)
dec
dec
dec
dec
)
dec
)
dec
)
)
)
)
)
Index F000 Modular device profile
Index (hex) NameMeaningData typeFlagsDefault value
F000:0Modular device profile General information for the modular device profileUINT8RO0x02 (2
)
dec
F000:01Module index distance Index spacing of the objects of the individual channels UINT16RO0x0010 (16
F000:02Maximum number of
modules
Number of channelsUINT16RO0x0004 (4
dec
EL20xx, EL212441Version: 5.2
)
dec
)
Product overview, digital output terminals
Index F008 Code word
Index (hex) NameMeaningData typeFlagsDefault value
F008:0Code word
NoCoeStorage function:
The input code of the code word 0x12345678 activates
UINT32RW0x00000000
(0
)
dec
the NoCoeStorage function:
Changes to the CoE directory are not saved if the function is active. The function is deactivated by:
1.) changing the code word or
2.) restarting the terminal.
Index F010 Module list
Index (hex) NameMeaningData typeFlagsDefault value
F010:0Module listMaximum subindexUINT8RW0x04 (4
F010:01SubIndex 001Profil 280 (Extended Digital Input and Output with Di-
agnostics)
F010:02SubIndex 002Profil 280 (Extended Digital Input and Output with Di-
agnostics)
F010:03SubIndex 003Profil 280 (Extended Digital Input and Output with Di-
agnostics)
F010:04SubIndex 004Profil 280 (Extended Digital Input and Output with Di-
agnostics)
UINT32RW0x00000118
(280
UINT32RW0x00000118
(280
UINT32RW0x00000118
(280dec)
UINT32RW0x00000118
(280
)
dec
)
dec
)
dec
)
dec
EL20xx, EL212442Version: 5.2
Product overview, digital output terminals
2.3EL2022, EL2024, EL2024-0010 - Introduction
Fig.28: EL2022
Fig.29: EL2024, EL2024-0010
Two- and four-channel digital output terminals, 24VDC, 2A (EL2022, EL2024)
The EL2022 and EL2024 digital output terminals connect the binary control signals from the automation
device on to the actuators at the process level with electrical isolation. These devices feature short-circuit
protection of the outputs. Two channels (EL2022) or four channels (EL2024) are available, which indicate
their signal state via LEDs. The EL2024 enables direct connection of four 2-wire actuators. It features four
earth connecting points.
The EL2024-0010 is a version with 12VDC output.
CAUTION
Watchdog settings
Please refer to section "Notes for setting the watchdog [}62]".
Output current max. per channelmax. 2A (short-circuit-proof)
Switch-off energy (inductive)< 1,7J/channel
Current consumption from load voltagetyp. 9mA + loadtyp. 13mA + load
Supply voltage for electronicvia the E-Bus
Current consumption via E-bustyp. 100mAtyp. 120mA
Electrical isolation500V (E-bus/field voltage)
Bit width in the process image2 output bits4 output bits
Configurationno address setting, configuration via TwinCAT System Manager
Weightapprox. 55g
Permissible ambient temperature range
during operation
Permissible ambient temperature range
during storage
Permissible relative humidity95%, no condensation
Dimensions (W x H x D)approx. 15mm x 100mm x 70mm (width aligned: 12mm)
Mounting [}72]
Vibration/shock resistanceaccording to EN 60068-2-6/EN 60068-2-27,
EMC resistance burst/ESDconforms to EN 61000-6-2 / EN 61000-6-4
Protection classIP20
Installation positionvariable
ApprovalCE
-25°C ... +60°C (extended temperature range)**0°C ... + 55°C*
-40°C ... +85°C-25°C ... + 85°C
on 35mm mounting rail conforms to EN 60715
see also Installation instructions for terminals with increased mechanical load capacity
[}74]
cULus [}150]
ATEX [}82]
IECEx
: 200µs typ.
OFF
CE
cULus [}150]
ATEX [}82]
-
CE
cULus [}150]
ATEX [}81]
EL20xx, EL212444Version: 5.2
2.3.2EL2022 - LEDs and connection
Product overview, digital output terminals
Fig.30: EL2022
EL2022 - LEDs
LEDColorMeaning
OUTPUT 1
OUTPUT 2
greenoffNo output signal is present.
onA 24VDC output signal is present.
EL2022 - Connection
Terminal pointDescription
NameNo.
Output 11Output 1
+24V2+24V (internally connected to terminal point6 and positive power contact)
0V3Ground for output1 (internally connected to terminal point7 and negative power contact)
PE4PE contact (internally connected to terminal point8 and PE power contact)
Output 25Output 2
+24V6+24V (internally connected to terminal point2 and positive power contact)
0 V7Ground for output2 (internally connected to terminal point3 and negative power contact)
PE8PE contact (internally connected to terminal point4 and PE power contact)
EL20xx, EL212445Version: 5.2
Product overview, digital output terminals
2.3.3EL2024, EL2024-0010 - LEDs and connection
Fig.31: EL2024, EL2024-0010
EL2024, EL2024-0010 - LEDs
LEDColorMeaning
OUTPUT 1- 4greenoffNo output signal is present.
onA 24VDC output signal (EL2024) or 12VDC output signal (EL2024-0010) is present
EL2024, EL2024-0010 - Connection
NOTE
12 V DC at the power contacts of the EL2024-0010
During configuration of the Bus Terminal block, please note that the power contacts of the EL2024-0010
carry a voltage of 12VDC (provided e.g. by an EL9512 power supply terminal).
If 24V terminals are to operate in the terminal block simultaneously, measures must be implemented for
electrical isolation (e.g. through the EL9190 power feed terminal or the EL9080 separation terminal).
Terminal pointDescription
NameNo.
Output 11Output 1
0V2Ground for output1 (internally connected to terminal point3, 6, 7 and negative power contact)
0V3Ground for output3 (internally connected to terminal point2, 6, 7 and negative power contact)
Output 34Output 3
Output 25Output 2
0V6Ground for output2 (internally connected to terminal point2, 3, 7 and negative power contact)
0V7Ground for output4 (internally connected to terminal point2, 3, 6 and negative power contact)
Output 48Output 4
EL20xx, EL212446Version: 5.2
2.4EL2032, EL2034 - Introduction
Product overview, digital output terminals
Fig.32: EL2032, EL2034
Two- and four-channel digital output terminals with diagnostics, 24 VDC, 2A
The EL2032 and EL2034 digital output terminals connect the binary 24 V control signals electrically isolated
with the actuators. Two channels or four channels are available, which indicate their signal state via LEDs.
The direct connection of wire-wire actuators is possible. The EL2032 enables direct connection of two 3-wire
actuators.
The EL2032 and EL2034 include additional diagnostic LEDs and input bits, which indicate short circuit and
broken wire. Broken wire is reported, if the output current is less than the limit value when the output is
connected. The limit value is typically between 2 and 900mA. The application of the "broken wire detection"
function therefore makes sense for regular output currents of approx. 1A or higher.
CAUTION
Watchdog settings
Please refer to section "Notes for setting the watchdog [}62]".
EL20xx, EL212447Version: 5.2
Product overview, digital output terminals
2.4.1EL2032, EL2034 - Technical data
Technical dataEL2032EL2034
Number of outputs24
Reverse voltage protectionyes
Load typeohmic, inductive, lamp load
Rated voltage of the outputs24VDC (-15%/ +20%)
Switching timesTON: 40µs typ.; T
Output current max. per channelmax. 2A (short-circuit-proof)
Short circuit and open circuit detection
Switch-off energy (inductive)< 1,7J/channel
Current consumption from load voltagetyp. 12mA + loadtyp. 14mA + load
Supply voltage for electronicvia E-Bus
Current consumption via E-bustyp. 100mAtyp. 120mA
Electrical isolation500V (E-bus/field voltage)
Bit width in the process image2 output bits, 2 input bits (diagnostic)4 output bits, 4 input bits (diagnostic)
Configurationno address setting, configuration via TwinCAT System Manager
Weightapprox. 55g
Permissible ambient temperature range during operation
Permissible ambient temperature range during storage
Permissible relative humidity95%, no condensation
Dimensions (W x H x D)approx. 15 mm x 100 mm x 70 mm (width aligned: 12 mm)
Mounting [}72]
Vibration/shock resistanceaccording to EN 60068-2-6/EN 60068-2-27,
EMC resistance burst/ESDconforms to EN 61000-6-2 / EN 61000-6-4
Protection classIP20
Installation positionvariable
ApprovalCE
yes;open circuit detection [}47] from approx. 1A regular output current
-25°C ... +60°C (extended temperature range)
-40°C ... +85°C
on 35 mm mounting rail conforms to EN 60715
see also Installation instructions for terminals with increased mechanical load capacity
[}74]
cULus [}150]
ATEX [}82]
: 200µs typ.
OFF
EL20xx, EL212448Version: 5.2
2.4.2EL2032 - LEDs and connection
Product overview, digital output terminals
Fig.33: EL2032
EL2032 - LEDs
LEDColorMeaning
OUTPUT 1
OUTPUT 2
ERROR 1
ERROR 2
greenoffNo output signal is present.
onA 24VDC output signal is present.
redFault indication in the event of interruption or overload of the output voltage
EL2032 - Connection
Terminal pointDescription
NameNo.
Output 11Output 1
+24 V2+24V (internally connected to terminal point6 and positive power contact)
0V3Ground for output1 (internally connected to terminal point7 and negative power contact)
PE4PE contact (internally connected to terminal point8 and PE power contact)
Output 25Output 2
+24V6+24V (internally connected to terminal point2 and positive power contact)
0V7Ground for output2 (internally connected to terminal point3 and negative power contact)
PE8PE contact (internally connected to terminal point4 and PE power contact)
EL20xx, EL212449Version: 5.2
Product overview, digital output terminals
2.4.3EL2034 - LEDs and connection
Fig.34: EL2034
LEDs
LEDColorMeaning
OUTPUT 1- 4greenoffNo output signal is present.
onA 24VDC output signal is present.
ERROR 1 - 4redFault indication in the event of interruption or overload of the output voltage
EL2034 pin assignment
Terminal pointDescription
NameNo.
Output 11Output 1
0V2Ground for output1 (internally connected to terminal point3, 6, 7 and negative power contact)
0V3Ground for output3 (internally connected to terminal point2, 6, 7 and negative power contact)
Output 34Output 3
Output 25Output 2
0V6Ground for output2 (internally connected to terminal point2, 3, 7 and negative power contact)
0V7Ground for output4 (internally connected to terminal point2, 3, 6 and negative power contact)
Output 48Output 4
EL20xx, EL212450Version: 5.2
2.5EL2042 - Introduction
Product overview, digital output terminals
Fig.35: EL2042
Two-channel digital output terminals, 24V
The EL2042 digital output terminals connect the binary 24V control signals electrically isolated with the
actuators. Two channels are available in each case, which indicate their signal state via LEDs. The EL2042
enables connection of loads with current consumption up to 8A if the outputs are connected in parallel.
2x4A/1x8A
DC;
CAUTION
Watchdog settings
Please refer to section "Notes for setting the watchdog [}62]".
EL20xx, EL212451Version: 5.2
Product overview, digital output terminals
2.5.1EL2042 - Technical data
Technical dataEL2042
Number of outputs2
Reverse voltage protectionyes
Load typeohmic, inductive, lamp load
Nominal output voltage24VDC (-15%/ +20%)
Switching timesTON: 40µs typ.; T
Output current max. per channelmax. 4A (short-circuit-proof) per channel, 8A with parallel connec-
Supply voltage for electronicvia the E-Bus
Current consumption of power contactstyp. 13mA + load
Current consumption via E-bustyp. 120 mA
Electrical isolation500V (E-bus/field voltage)
Bit width in the process image2 output bits
Configurationno address setting, configuration via TwinCAT System Manager
Weightapprox. 55g
Permissible ambient temperature range during operation0°C ... + 55°C
Permissible ambient temperature range during storage-25°C ... + 85°C
Permissible relative humidity95%, no condensation
Dimensions (W x H x D)approx. 15mm x 100mm x 70mm (width aligned: 12mm)
Mounting [}72]
Vibration/shock resistanceaccording to EN 60068-2-6/EN 60068-2-27,
EMC resistance burst/ESDconforms to EN 61000-6-2 / EN 61000-6-4
Protection classIP20
Installation positionvariable
ApprovalCE
tion
on 35mm mounting rail conforms to EN 60715
see also Installation instructions for terminals with increased me-
chanical load capacity [}74]
200µs typ.
OFF
EL20xx, EL212452Version: 5.2
2.5.2EL2042 - LEDs and connection
Product overview, digital output terminals
Fig.36: EL2042
EL2042 - LEDs
LEDColorMeaning
OUTPUT 1
OUTPUT 2
greenoffNo output signal is present.
onA 24VDC output signal is present.
EL2042 - Connection
Terminal pointDescription
NameNo.
Output 11Output 1
+24 V2+24V (internally connected to terminal point6 and positive power contact)
0 V3Ground for output1 (internally connected to terminal point7 and negative power contact)
-4-
Output 25Output 2
+24 V6+24V (internally connected to terminal point2 and positive power contact)
0V7Ground for output2 (internally connected to terminal point3 and negative power contact)
-8-
EL20xx, EL212453Version: 5.2
Product overview, digital output terminals
2.6EL2084, EL2088 - Introduction
Fig.37: EL2084, EL2088
Four- and eight-channel digital output terminals, 24 VDC, 0.5A (EL2084, EL2088)
The EL2084 and EL2088 digital output terminals connect the binary control signals from the automation unit
on to the actuators at the process level with electrical isolation.
The EtherCAT Terminals have 0V (ground) switching outputs and generate load currents with outputs that
are resistant to overload and short-circuit. They include four or eight channels, whose signal state is
indicated by LEDs.
CAUTION
Watchdog settings
Please refer to section "Notes for setting the watchdog [}62]".
EL20xx, EL212454Version: 5.2
Product overview, digital output terminals
2.6.1EL2084, EL2088 - Technical data
Technical dataEL2084EL2088
Number of outputs48
Load typeohmic, inductive, lamp load
Nominal voltage of the outputs24VDC (-15%/ +20%)
Output current max. per channelmax. 0.5A (short-circuit-proof)max. 0.5A (total current 3A)
Current consumption from load voltagetyp. 30mA + load
Supply voltage for electronicvia the E-Bus
Current consumption via E-bustyp. 100mAtyp. 110mA
Electrical isolation500V (E-bus/field voltage)
Bit width in the process image4 output bits8 output bits
Configurationno address setting, configuration via TwinCAT System Manager
Weightapprox. 70g
Permissible ambient temperature range during operation
Permissible ambient temperature range during storage
Permissible relative humidity95%, no condensation
Dimensions (W x H x D)approx. 15mm x 100mm x 70mm (width aligned: 12mm)
Mounting [}72]
Vibration/shock resistanceaccording to EN 60068-2-6/EN 60068-2-27,
EMC resistance burst/ESDconforms to EN 61000-6-2 / EN 61000-6-4
Protection classIP20
Installation positionvariable
ApprovalCE
0°C ... + 55°C0°C ... + 55°C
(aligned in horizontal installation position)
0°C ... + 45°C
(all other installation positions,
see Note [}78])
-25°C ... + 85°C
on 35mm mounting rail conforms to EN 60715
see also Installation instructions for terminals with increased mechanical load capacity
[}74]
see note [}78]
cULus [}150]
ATEX [}81]
EL20xx, EL212455Version: 5.2
Product overview, digital output terminals
2.6.2EL2084 - LEDs and connection
Fig.38: EL2084
EL2084 - LEDs
LEDColorMeaning
OUTPUT 1- 4greenoffNo output signal is present at the respective output
onA 0V output signal is present at the respective output
EL2084 - Connection
Terminal pointDescription
NameNo.
Output 11Output 1 (0V)
24V2+24V for output 1 (internally connected to terminal points 3, 6, 7 and positive power contact)
24V3+24V for output 3 (internally connected to terminal points 2, 6, 7 and positive power contact)
Output 34Output 3 (0V)
Output 25Output 2 (0V)
24V6+24V for output 2 (internally connected to terminal points 2, 3, 7 and positive power contact)
24V7+24V for output 4 (internally connected to terminal points 2, 3, 6 and positive power contact)
Output 48Output 4 (0V)
EL20xx, EL212456Version: 5.2
2.6.3EL2088 - LEDs and connection
Product overview, digital output terminals
Fig.39: EL2088
EL2088 - LEDs
LEDColorMeaning
OUTPUT 1- 8greenoffNo output signal is present at the respective output
onA 0V output signal is present at the respective output
EL2088 - Connection
Terminal pointDescription
NameNo.
Output 11Output 1 (0V)
Output 32Output 3 (0V)
Output 53Output 5 (0V)
Output74Output 7 (0V)
Output 25Output 2 (0V)
Output 46Output 4 (0V)
Output 67Output 6 (0V)
Output 88Output 8 (0V)
EL20xx, EL212457Version: 5.2
Product overview, digital output terminals
2.7EL2124 - Introduction
Fig.40: EL2124
Four-channel digital output terminal 5 VDC, CMOS output
The digital output terminal EL2124 connects the binary control signals of the automation device in an
electrically isolated manner to the actuators at the process level and generates load currents with outputs
that are protected against overload and short-circuit. The EtherCAT Terminal contains four channels whose
signal state is indicated by LEDs.
CAUTION
Watchdog settings
Please refer to section "Notes for setting the watchdog [}62]".
EL20xx, EL212458Version: 5.2
Product overview, digital output terminals
2.7.1EL2124 - Technical data
Technical dataEL2124
Number of outputs4
Load typeohmic, inductive, lamp load
Nominal output voltage5VDC (CMOS output)
Switching timesTON: < 1µs typ.; T
Output current max. per channel±20mA (short-circuit-proof) per channel, 8mA signal current, type
Supply voltage for electronicvia the E-Bus
Current consumption via E-bustyp. 130mA
Current consumption from load voltage (power contacts)typ. 12mA + load
Electrical isolation500V (E-bus/field voltage)
Bit width in the process image4 output bits
Configurationno address setting, configuration via TwinCAT System Manager
Weightapprox. 70g
Permissible ambient temperature range during operation0°C ... + 55°C
Permissible ambient temperature range during storage-25°C ... + 85°C
Permissible relative humidity95%, no condensation
Dimensions (W x H x D)approx. 15mm x 100mm x 70mm (width aligned: 12mm)
Mounting [}72]
Vibration/shock resistanceaccording to EN 60068-2-6/EN 60068-2-27,
EMC immunity/emissionconforms to EN 61000-6-2 / EN 61000-6-4
Protection classIP 20
Installation positionvariable
ApprovalCE
CMOS output
on 35mm mounting rail conforms to EN 60715
see also Installation instructions for terminals with increased me-
chanical load capacity [}74]
cULus [}150]
ATEX [}81]
: < 1µs typ.
OFF
EL20xx, EL212459Version: 5.2
Product overview, digital output terminals
2.7.2EL2124 - LEDs and connection
Fig.41: EL2124
LEDs
LEDColorMeaning
OUTPUT 1- 4greenoffNo output signal
on5 VDC output signal at the respective output
EL2124 - Connection
NOTE
5 V DC at the power contacts
During configuration of the Bus Terminal block, please note that the power contacts of the EL2124 carry a
voltage of 5 VDC (provided e.g. by an EL9505 power supply terminal).
If 24V terminals are to operate in the terminal block simultaneously, measures must be implemented for
electrical isolation (e.g. through the EL9190 power feed terminal or the EL9080 separation terminal).
Terminal pointDescription
NameNo.
Output 11Output 1
+5V2+5V (internally connected to terminal point6 and positive power contact)
0V30V (internally connected to terminal point 7 and negative power contact)
Output 34Output 3
Output 25Output 2
+5V6+5V (internally connected to terminal point2 and positive power contact)
0V70V (internally connected to terminal point 3 and negative power contact)
Output 48Output 4
EL20xx, EL212460Version: 5.2
Basics communication
3Basics communication
3.1EtherCAT basics
Please refer to the EtherCAT System Documentation for the EtherCAT fieldbus basics.
3.2EtherCAT cabling – wire-bound
The cable length between two EtherCAT devices must not exceed 100 m. This results from the FastEthernet
technology, which, above all for reasons of signal attenuation over the length of the cable, allows a maximum
link length of 5 + 90 + 5 m if cables with appropriate properties are used. See also the Designrecommendations for the infrastructure for EtherCAT/Ethernet.
Cables and connectors
For connecting EtherCAT devices only Ethernet connections (cables + plugs) that meet the requirements of
at least category 5 (CAt5) according to EN 50173 or ISO/IEC 11801 should be used. EtherCAT uses 4 wires
for signal transfer.
EtherCAT uses RJ45 plug connectors, for example. The pin assignment is compatible with the Ethernet
standard (ISO/IEC 8802-3).
PinColor of conductorSignalDescription
1yellowTD +Transmission Data +
2orangeTD -Transmission Data -
3whiteRD +Receiver Data +
6blueRD -Receiver Data -
Due to automatic cable detection (auto-crossing) symmetric (1:1) or cross-over cables can be used between
EtherCAT devices from Beckhoff.
Recommended cables
Suitable cables for the connection of EtherCAT devices can be found on the Beckhoff website!
E-Bus supply
A bus coupler can supply the EL terminals added to it with the E-bus system voltage of 5V; a coupler is
thereby loadable up to 2A as a rule (see details in respective device documentation).
Information on how much current each EL terminal requires from the E-bus supply is available online and in
the catalogue. If the added terminals require more current than the coupler can supply, then power feed
terminals (e.g. EL9410) must be inserted at appropriate places in the terminal strand.
The pre-calculated theoretical maximum E-Bus current is displayed in the TwinCAT System Manager. A
shortfall is marked by a negative total amount and an exclamation mark; a power feed terminal is to be
placed before such a position.
EL20xx, EL212461Version: 5.2
Basics communication
Fig.42: System manager current calculation
NOTE
Malfunction possible!
The same ground potential must be used for the E-Bus supply of all EtherCAT terminals in a terminal block!
3.3General notes for setting the watchdog
ELxxxx terminals are equipped with a safety feature (watchdog) that switches off the outputs after a
specifiable time e.g. in the event of an interruption of the process data traffic, depending on the device and
settings, e.g. in OFF state.
The EtherCAT slave controller (ESC) in the EL2xxx terminals features 2 watchdogs:
• SM watchdog (default: 100 ms)
• PDI watchdog (default: 100 ms)
SM watchdog (SyncManager Watchdog)
The SyncManager watchdog is reset after each successful EtherCAT process data communication with the
terminal. If no EtherCAT process data communication takes place with the terminal for longer than the set
and activated SM watchdog time, e.g. in the event of a line interruption, the watchdog is triggered and the
outputs are set to FALSE. The OP state of the terminal is unaffected. The watchdog is only reset after a
successful EtherCAT process data access. Set the monitoring time as described below.
The SyncManager watchdog monitors correct and timely process data communication with the ESC from the
EtherCAT side.
PDI watchdog (Process Data Watchdog)
If no PDI communication with the EtherCAT slave controller (ESC) takes place for longer than the set and
activated PDI watchdog time, this watchdog is triggered.
PDI (Process Data Interface) is the internal interface between the ESC and local processors in the EtherCAT
slave, for example. The PDI watchdog can be used to monitor this communication for failure.
The PDI watchdog monitors correct and timely process data communication with the ESC from the
application side.
The settings of the SM- and PDI-watchdog must be done for each slave separately in the TwinCAT System
Manager.
• each watchdog has its own timer setting, the outcome of this in summary with the multiplier is a
resulting time.
• Important: the multiplier/timer setting is only loaded into the slave at the start up, if the checkbox is
activated.
If the checkbox is not activated, nothing is downloaded and the ESC settings remain unchanged.
Multiplier
Multiplier
Both watchdogs receive their pulses from the local terminal cycle, divided by the watchdog multiplier:
1/25 MHz * (watchdog multiplier + 2) = 100 µs (for default setting of 2498 for the multiplier)
The standard setting of 1000 for the SM watchdog corresponds to a release time of 100 ms.
The value in multiplier + 2 corresponds to the number of basic 40 ns ticks representing a watchdog tick.
The multiplier can be modified in order to adjust the watchdog time over a larger range.
EL20xx, EL212463Version: 5.2
Basics communication
Example "Set SM watchdog"
This checkbox enables manual setting of the watchdog times. If the outputs are set and the EtherCAT
communication is interrupted, the SM watchdog is triggered after the set time and the outputs are erased.
This setting can be used for adapting a terminal to a slower EtherCAT master or long cycle times. The
default SM watchdog setting is 100 ms. The setting range is 0..65535. Together with a multiplier with a range
of 1..65535 this covers a watchdog period between 0..~170 seconds.
Calculation
Multiplier = 2498 → watchdog base time = 1 / 25MHz * (2498 + 2) = 0.0001seconds = 100µs
SM watchdog = 10000 → 10000 * 100µs = 1second watchdog monitoring time
CAUTION
Undefined state possible!
The function for switching off of the SM watchdog via SM watchdog = 0 is only implemented in terminals
from version -0016. In previous versions this operating mode should not be used.
CAUTION
Damage of devices and undefined state possible!
If the SM watchdog is activated and a value of 0 is entered the watchdog switches off completely. This is
the deactivation of the watchdog! Set outputs are NOT set in a safe state, if the communication is interrupted.
3.4EtherCAT State Machine
The state of the EtherCAT slave is controlled via the EtherCAT State Machine (ESM). Depending upon the
state, different functions are accessible or executable in the EtherCAT slave. Specific commands must be
sent by the EtherCAT master to the device in each state, particularly during the bootup of the slave.
A distinction is made between the following states:
• Init
• Pre-Operational
• Safe-Operational and
• Operational
• Boot
The regular state of each EtherCAT slave after bootup is the OP state.
EL20xx, EL212464Version: 5.2
Fig.44: States of the EtherCAT State Machine
Basics communication
Init
After switch-on the EtherCAT slave in the Init state. No mailbox or process data communication is possible.
The EtherCAT master initializes sync manager channels 0 and 1 for mailbox communication.
Pre-Operational (Pre-Op)
During the transition between Init and Pre-Op the EtherCAT slave checks whether the mailbox was initialized
correctly.
In Pre-Op state mailbox communication is possible, but not process data communication. The EtherCAT
master initializes the sync manager channels for process data (from sync manager channel 2), the FMMU
channels and, if the slave supports configurable mapping, PDO mapping or the sync manager PDO
assignment. In this state the settings for the process data transfer and perhaps terminal-specific parameters
that may differ from the default settings are also transferred.
Safe-Operational (Safe-Op)
During transition between Pre-Op and Safe-Op the EtherCAT slave checks whether the sync manager
channels for process data communication and, if required, the distributed clocks settings are correct. Before
it acknowledges the change of state, the EtherCAT slave copies current input data into the associated DPRAM areas of the EtherCAT slave controller (ECSC).
In Safe-Op state mailbox and process data communication is possible, although the slave keeps its outputs
in a safe state, while the input data are updated cyclically.
Outputs in SAFEOP state
The default set watchdog [}62] monitoring sets the outputs of the module in a safe state - depending on the settings in SAFEOP and OP - e.g. in OFF state. If this is prevented by deactivation of the
watchdog monitoring in the module, the outputs can be switched or set also in the SAFEOP state.
Operational (Op)
Before the EtherCAT master switches the EtherCAT slave from Safe-Op to Op it must transfer valid output
data.
In the Op state the slave copies the output data of the masters to its outputs. Process data and mailbox
communication is possible.
EL20xx, EL212465Version: 5.2
Basics communication
Boot
In the Boot state the slave firmware can be updated. The Boot state can only be reached via the Init state.
In the Boot state mailbox communication via the file access over EtherCAT (FoE) protocol is possible, but no
other mailbox communication and no process data communication.
EL20xx, EL212466Version: 5.2
Basics communication
3.5CoE Interface
General description
The CoE interface (CANopen over EtherCAT) is used for parameter management of EtherCAT devices.
EtherCAT slaves or the EtherCAT master manage fixed (read only) or variable parameters which they
require for operation, diagnostics or commissioning.
CoE parameters are arranged in a table hierarchy. In principle, the user has read access via the fieldbus.
The EtherCAT master (TwinCAT System Manager) can access the local CoE lists of the slaves via
EtherCAT in read or write mode, depending on the attributes.
Different CoE parameter types are possible, including string (text), integer numbers, Boolean values or larger
byte fields. They can be used to describe a wide range of features. Examples of such parameters include
manufacturer ID, serial number, process data settings, device name, calibration values for analog
measurement or passwords.
The order is specified in 2 levels via hexadecimal numbering: (main)index, followed by subindex. The value
ranges are
• Index: 0x0000 …0xFFFF (0...65535
• SubIndex: 0x00…0xFF (0...255
dez
)
dez
)
A parameter localized in this way is normally written as 0x8010:07, with preceding "x" to identify the
hexadecimal numerical range and a colon between index and subindex.
The relevant ranges for EtherCAT fieldbus users are:
• 0x1000: This is where fixed identity information for the device is stored, including name, manufacturer,
serial number etc., plus information about the current and available process data configurations.
• 0x8000: This is where the operational and functional parameters for all channels are stored, such as
filter settings or output frequency.
Other important ranges are:
• 0x4000: In some EtherCAT devices the channel parameters are stored here (as an alternative to the
0x8000 range).
• 0x6000: Input PDOs ("input" from the perspective of the EtherCAT master)
• 0x7000: Output PDOs ("output" from the perspective of the EtherCAT master)
Availability
Not every EtherCAT device must have a CoE list. Simple I/O modules without dedicated processor
usually have no variable parameters and therefore no CoE list.
If a device has a CoE list, it is shown in the TwinCAT System Manager as a separate tab with a listing of the
elements:
EL20xx, EL212467Version: 5.2
Basics communication
Fig.45: "CoE Online" tab
The figure above shows the CoE objects available in device "EL2502", ranging from 0x1000 to 0x1600. The
subindices for 0x1018 are expanded.
Data management and function "NoCoeStorage"
Some parameters, particularly the setting parameters of the slave, are configurable and writeable. This can
be done in write or read mode
• via the System Manager (Fig. "CoE Online " tab) by clicking
This is useful for commissioning of the system/slaves. Click on the row of the index to be
parameterised and enter a value in the "SetValue" dialog.
• from the control system/PLC via ADS, e.g. through blocks from the TcEtherCAT.lib library
This is recommended for modifications while the system is running or if no System Manager or
operating staff are available.
Data management
If slave CoE parameters are modified online, Beckhoff devices store any changes in a fail-safe
manner in the EEPROM, i.e. the modified CoE parameters are still available after a restart.
The situation may be different with other manufacturers.
An EEPROM is subject to a limited lifetime with respect to write operations. From typically 100,000
write operations onwards it can no longer be guaranteed that new (changed) data are reliably saved
or are still readable. This is irrelevant for normal commissioning. However, if CoE parameters are
continuously changed via ADS at machine runtime, it is quite possible for the lifetime limit to be
reached. Support for the NoCoeStorage function, which suppresses the saving of changed CoE values, depends on the firmware version.
Please refer to the technical data in this documentation as to whether this applies to the respective
device.
• If the function is supported: the function is activated by entering the code word 0x12345678 once
in CoE 0xF008 and remains active as long as the code word is not changed. After switching the
device on it is then inactive. Changed CoE values are not saved in the EEPROM and can thus
be changed any number of times.
• Function is not supported: continuous changing of CoE values is not permissible in view of the
lifetime limit.
EL20xx, EL212468Version: 5.2
Startup list
Changes in the local CoE list of the terminal are lost if the terminal is replaced. If a terminal is replaced with a new Beckhoff terminal, it will have the default settings. It is therefore advisable to link
all changes in the CoE list of an EtherCAT slave with the Startup list of the slave, which is processed whenever the EtherCAT fieldbus is started. In this way a replacement EtherCAT slave can
automatically be parameterized with the specifications of the user.
If EtherCAT slaves are used which are unable to store local CoE values permanently, the Startup
list must be used.
Recommended approach for manual modification of CoE parameters
• Make the required change in the System Manager
The values are stored locally in the EtherCAT slave
• If the value is to be stored permanently, enter it in the Startup list.
The order of the Startup entries is usually irrelevant.
Basics communication
Fig.46: Startup list in the TwinCAT System Manager
The Startup list may already contain values that were configured by the System Manager based on the ESI
specifications. Additional application-specific entries can be created.
Online/offline list
While working with the TwinCAT System Manager, a distinction has to be made whether the EtherCAT
device is "available", i.e. switched on and linked via EtherCAT and therefore online, or whether a
configuration is created offline without connected slaves.
In both cases a CoE list as shown in Fig. “’CoE online’ tab” is displayed. The connectivity is shown as offline/
online.
• If the slave is offline
◦ The offline list from the ESI file is displayed. In this case modifications are not meaningful or
possible.
◦ The configured status is shown under Identity.
◦ No firmware or hardware version is displayed, since these are features of the physical device.
◦ Offline is shown in red.
EL20xx, EL212469Version: 5.2
Basics communication
Fig.47: Offline list
• If the slave is online
◦ The actual current slave list is read. This may take several seconds, depending on the size and
cycle time.
◦ The actual identity is displayed
◦ The firmware and hardware version of the equipment according to the electronic information is
displayed
◦ Online is shown in green.
Fig.48: Online list
EL20xx, EL212470Version: 5.2
Basics communication
Channel-based order
The CoE list is available in EtherCAT devices that usually feature several functionally equivalent channels.
For example, a 4-channel analog 0..10 V input terminal also has 4 logical channels and therefore 4 identical
sets of parameter data for the channels. In order to avoid having to list each channel in the documentation,
the placeholder "n" tends to be used for the individual channel numbers.
In the CoE system 16 indices, each with 255 subindices, are generally sufficient for representing all channel
parameters. The channel-based order is therefore arranged in 16
dec
/10
steps. The parameter range
hex
0x8000 exemplifies this:
• Channel 0: parameter range 0x8000:00 ... 0x800F:255
• Channel 1: parameter range 0x8010:00 ... 0x801F:255
• Channel 2: parameter range 0x8020:00 ... 0x802F:255
• ...
This is generally written as 0x80n0.
Detailed information on the CoE interface can be found in the EtherCAT system documentation on the
Beckhoff website.
3.6Distributed Clock
The distributed clock represents a local clock in the EtherCAT slave controller (ESC) with the following
characteristics:
• Unit 1 ns
• Zero point 1.1.2000 00:00
• Size 64 bit (sufficient for the next 584 years; however, some EtherCAT slaves only offer 32-bit support,
i.e. the variable overflows after approx. 4.2 seconds)
• The EtherCAT master automatically synchronizes the local clock with the master clock in the EtherCAT
bus with a precision of < 100 ns.
For detailed information please refer to the EtherCAT system description.
EL20xx, EL212471Version: 5.2
Mounting and wiring
4Mounting and wiring
4.1Installation on mounting rails
WARNING
Risk of electric shock and damage of device!
Bring the bus terminal system into a safe, powered down state before starting installation, disassembly or
wiring of the bus terminals!
Assembly
Fig.49: Attaching on mounting rail
The bus coupler and bus terminals are attached to commercially available 35mm mounting rails (DIN rails
according to EN60715) by applying slight pressure:
1. First attach the fieldbus coupler to the mounting rail.
2. The bus terminals are now attached on the right-hand side of the fieldbus coupler. Join the components with tongue and groove and push the terminals against the mounting rail, until the lock clicks
onto the mounting rail.
If the terminals are clipped onto the mounting rail first and then pushed together without tongue and
groove, the connection will not be operational! When correctly assembled, no significant gap should
be visible between the housings.
Fixing of mounting rails
The locking mechanism of the terminals and couplers extends to the profile of the mounting rail. At
the installation, the locking mechanism of the components must not come into conflict with the fixing
bolts of the mounting rail. To mount the mounting rails with a height of 7.5mm under the terminals
and couplers, you should use flat mounting connections (e.g. countersunk screws or blind rivets).
EL20xx, EL212472Version: 5.2
Mounting and wiring
Disassembly
Fig.50: Disassembling of terminal
Each terminal is secured by a lock on the mounting rail, which must be released for disassembly:
1. Pull the terminal by its orange-colored lugs approximately 1cm away from the mounting rail. In doing
so for this terminal the mounting rail lock is released automatically and you can pull the terminal out of
the bus terminal block easily without excessive force.
2. Grasp the released terminal with thumb and index finger simultaneous at the upper and lower grooved
housing surfaces and pull the terminal out of the bus terminal block.
Connections within a bus terminal block
The electric connections between the Bus Coupler and the Bus Terminals are automatically realized by
joining the components:
• The six spring contacts of the K-Bus/E-Bus deal with the transfer of the data and the supply of the Bus
Terminal electronics.
• The power contacts deal with the supply for the field electronics and thus represent a supply rail within
the bus terminal block. The power contacts are supplied via terminals on the Bus Coupler (up to 24V)
or for higher voltages via power feed terminals.
Power Contacts
During the design of a bus terminal block, the pin assignment of the individual Bus Terminals must
be taken account of, since some types (e.g. analog Bus Terminals or digital 4-channel Bus Terminals) do not or not fully loop through the power contacts. Power Feed Terminals (KL91xx, KL92xx
or EL91xx, EL92xx) interrupt the power contacts and thus represent the start of a new supply rail.
PE power contact
The power contact labeled PE can be used as a protective earth. For safety reasons this contact mates first
when plugging together, and can ground short-circuit currents of up to 125A.
EL20xx, EL212473Version: 5.2
Mounting and wiring
Fig.51: Power contact on left side
NOTE
Possible damage of the device
Note that, for reasons of electromagnetic compatibility, the PE contacts are capacitatively coupled to the
mounting rail. This may lead to incorrect results during insulation testing or to damage on the terminal (e.g.
disruptive discharge to the PE line during insulation testing of a consumer with a nominal voltage of 230V).
For insulation testing, disconnect the PE supply line at the Bus Coupler or the Power Feed Terminal! In order to decouple further feed points for testing, these Power Feed Terminals can be released and pulled at
least 10mm from the group of terminals.
WARNING
Risk of electric shock!
The PE power contact must not be used for other potentials!
4.2Installation instructions for enhanced mechanical load
capacity
WARNING
Risk of injury through electric shock and damage to the device!
Bring the Bus Terminal system into a safe, de-energized state before starting mounting, disassembly or
wiring of the Bus Terminals!
Additional checks
The terminals have undergone the following additional tests:
VerificationExplanation
Vibration10 frequency runs in 3 axes
6 Hz < f < 60 Hz displacement 0.35 mm, constant amplitude
For terminals with enhanced mechanical load capacity, the following additional installation instructions apply:
• The enhanced mechanical load capacity is valid for all permissible installation positions
• Use a mounting rail according to EN 60715 TH35-15
• Fix the terminal segment on both sides of the mounting rail with a mechanical fixture, e.g. an earth
terminal or reinforced end clamp
• The maximum total extension of the terminal segment (without coupler) is:
64 terminals (12 mm mounting with) or 32 terminals (24 mm mounting with)
• Avoid deformation, twisting, crushing and bending of the mounting rail during edging and installation of
the rail
• The mounting points of the mounting rail must be set at 5 cm intervals
• Use countersunk head screws to fasten the mounting rail
• The free length between the strain relief and the wire connection should be kept as short as possible. A
distance of approx. 10 cm should be maintained to the cable duct.
4.3Connection
4.3.1Connection system
WARNING
Risk of electric shock and damage of device!
Bring the bus terminal system into a safe, powered down state before starting installation, disassembly or
wiring of the bus terminals!
Overview
The Bus Terminal system offers different connection options for optimum adaptation to the respective
application:
• The terminals of ELxxxx and KLxxxx series with standard wiring include electronics and connection
level in a single enclosure.
• The terminals of ESxxxx and KSxxxx series feature a pluggable connection level and enable steady
wiring while replacing.
• The High Density Terminals (HD Terminals) include electronics and connection level in a single
enclosure and have advanced packaging density.
Standard wiring (ELxxxx / KLxxxx)
Fig.52: Standard wiring
The terminals of ELxxxx and KLxxxx series have been tried and tested for years.
They feature integrated screwless spring force technology for fast and simple assembly.
EL20xx, EL212475Version: 5.2
Mounting and wiring
Pluggable wiring (ESxxxx / KSxxxx)
Fig.53: Pluggable wiring
The terminals of ESxxxx and KSxxxx series feature a pluggable connection level.
The assembly and wiring procedure is the same as for the ELxxxx and KLxxxx series.
The pluggable connection level enables the complete wiring to be removed as a plug connector from the top
of the housing for servicing.
The lower section can be removed from the terminal block by pulling the unlocking tab.
Insert the new component and plug in the connector with the wiring. This reduces the installation time and
eliminates the risk of wires being mixed up.
The familiar dimensions of the terminal only had to be changed slightly. The new connector adds about 3
mm. The maximum height of the terminal remains unchanged.
A tab for strain relief of the cable simplifies assembly in many applications and prevents tangling of individual
connection wires when the connector is removed.
Conductor cross sections between 0.08mm2 and 2.5mm2 can continue to be used with the proven spring
force technology.
The overview and nomenclature of the product names for ESxxxx and KSxxxx series has been retained as
known from ELxxxx and KLxxxx series.
High Density Terminals (HD Terminals)
Fig.54: High Density Terminals
The Bus Terminals from these series with 16 terminal points are distinguished by a particularly compact
design, as the packaging density is twice as large as that of the standard 12mm Bus Terminals. Massive
conductors and conductors with a wire end sleeve can be inserted directly into the spring loaded terminal
point without tools.
Wiring HD Terminals
The High Density (HD) Terminals of the ELx8xx and KLx8xx series doesn't support pluggable
wiring.
It is also possible to connect the Standard and High Density Terminals with ultrasonically
"bonded" (ultrasonically welded) conductors. In this case, please note the tables concerning the
wire-size width below!
EL20xx, EL212476Version: 5.2
Mounting and wiring
4.3.2Wiring
WARNING
Risk of electric shock and damage of device!
Bring the bus terminal system into a safe, powered down state before starting installation, disassembly or
wiring of the Bus Terminals!
Terminals for standard wiring ELxxxx/KLxxxx and for pluggable wiring ESxxxx/KSxxxx
Fig.55: Connecting a cable on a terminal point
Up to eight terminal points enable the connection of solid or finely stranded cables to the Bus Terminal. The
terminal points are implemented in spring force technology. Connect the cables as follows:
1. Open a terminal point by pushing a screwdriver straight against the stop into the square opening
above the terminal point. Do not turn the screwdriver or move it alternately (don't toggle).
2. The wire can now be inserted into the round terminal opening without any force.
3. The terminal point closes automatically when the pressure is released, holding the wire securely and
permanently.
See the following table for the suitable wire size width.
Wire size width (conductors with a wire end sleeve)0.14 ... 1.5mm
2
2
2
0.08 ... 2.5mm
0,08 ... 2.5mm
0.14 ... 1.5mm
2
2
2
Wire stripping length8 ... 9mm9 ... 10mm
High Density Terminals (HD Terminals [}76]) with 16 terminal points
The conductors of the HD Terminals are connected without tools for single-wire conductors using the direct
plug-in technique, i.e. after stripping the wire is simply plugged into the terminal point. The cables are
released, as usual, using the contact release with the aid of a screwdriver. See the following table for the
suitable wire size width.
Wire size width (conductors with a wire end sleeve)0.14 ... 0.75mm
Wire size width (ultrasonically “bonded" conductors) only 1.5mm
2
2
2
2
Wire stripping length8 ... 9mm
4.3.3Shielding
Shielding
Encoder, analog sensors and actors should always be connected with shielded, twisted paired
wires.
4.4Installation positions
NOTE
Constraints regarding installation position and operating temperature range
Please refer to the technical data for a terminal to ascertain whether any restrictions regarding the installation position and/or the operating temperature range have been specified. When installing high power dissipation terminals ensure that an adequate spacing is maintained between other components above and below the terminal in order to guarantee adequate ventilation!
Optimum installation position (standard)
The optimum installation position requires the mounting rail to be installed horizontally and the connection
surfaces of the EL/KL terminals to face forward (see Fig. “Recommended distances for standard installationposition”). The terminals are ventilated from below, which enables optimum cooling of the electronics through
convection. "From below" is relative to the acceleration of gravity.
EL20xx, EL212478Version: 5.2
Mounting and wiring
Fig.56: Recommended distances for standard installation position
Compliance with the distances shown in Fig. “Recommended distances for standard installation position” is
recommended.
Other installation positions
All other installation positions are characterized by different spatial arrangement of the mounting rail - see
Fig “Other installation positions”.
The minimum distances to ambient specified above also apply to these installation positions.
EL20xx, EL212479Version: 5.2
Mounting and wiring
Fig.57: Other installation positions
4.5Positioning of passive Terminals
Hint for positioning of passive terminals in the bus terminal block
EtherCAT Terminals (ELxxxx / ESxxxx), which do not take an active part in data transfer within the
bus terminal block are so called passive terminals. The passive terminals have no current consumption out of the E-Bus.
To ensure an optimal data transfer, you must not directly string together more than 2 passive terminals!
Examples for positioning of passive terminals (highlighted)
Fig.58: Correct positioning
EL20xx, EL212480Version: 5.2
Mounting and wiring
Fig.59: Incorrect positioning
4.6ATEX - Special conditions (standard temperature
range)
WARNING
Observe the special conditions for the intended use of Beckhoff fieldbus components with
standard temperature range in potentially explosive areas (directive 94/9/EU)!
• The certified components are to be installed in a suitable housing that guarantees a protection class of at
least IP54 in accordance with EN 60529! The environmental conditions during use are thereby to be
taken into account!
• If the temperatures during rated operation are higher than 70°C at the feed-in points of cables, lines or
pipes, or higher than 80°C at the wire branching points, then cables must be selected whose temperature data correspond to the actual measured temperature values!
• Observe the permissible ambient temperature range of 0 to 55°C for the use of Beckhoff fieldbus components standard temperature range in potentially explosive areas!
• Measures must be taken to protect against the rated operating voltage being exceeded by more than
40% due to short-term interference voltages!
• The individual terminals may only be unplugged or removed from the Bus Terminal system if the supply
voltage has been switched off or if a non-explosive atmosphere is ensured!
• The connections of the certified components may only be connected or disconnected if the supply voltage has been switched off or if a non-explosive atmosphere is ensured!
• The fuses of the KL92xx/EL92xx power feed terminals may only be exchanged if the supply voltage has
been switched off or if a non-explosive atmosphere is ensured!
• Address selectors and ID switches may only be adjusted if the supply voltage has been switched off or if
a non-explosive atmosphere is ensured!
Standards
The fundamental health and safety requirements are fulfilled by compliance with the following standards:
• EN 60079-0:2012+A11:2013
• EN 60079-15:2010
Marking
The Beckhoff fieldbus components with standard temperature range certified for potentially explosive areas
bear one of the following markings:
EL20xx, EL212481Version: 5.2
Mounting and wiring
II 3GKEMA 10ATEX0075 X Ex nA IIC T4 GcTa: 0…55°C
or
II 3GKEMA 10ATEX0075 X Ex nC IIC T4 GcTa: 0…55°C
4.7ATEX - Special conditions (extended temperature
range)
WARNING
Observe the special conditions for the intended use of Beckhoff fieldbus components with
extended temperature range (ET) in potentially explosive areas (directive 94/9/EU)!
• The certified components are to be installed in a suitable housing that guarantees a protection class of at
least IP54 in accordance with EN 60529! The environmental conditions during use are thereby to be
taken into account!
• If the temperatures during rated operation are higher than 70°C at the feed-in points of cables, lines or
pipes, or higher than 80°C at the wire branching points, then cables must be selected whose temperature data correspond to the actual measured temperature values!
• Observe the permissible ambient temperature range of -25 to 60°C for the use of Beckhoff fieldbus components with extended temperature range (ET) in potentially explosive areas!
• Measures must be taken to protect against the rated operating voltage being exceeded by more than
40% due to short-term interference voltages!
• The individual terminals may only be unplugged or removed from the Bus Terminal system if the supply
voltage has been switched off or if a non-explosive atmosphere is ensured!
• The connections of the certified components may only be connected or disconnected if the supply voltage has been switched off or if a non-explosive atmosphere is ensured!
• The fuses of the KL92xx/EL92xx power feed terminals may only be exchanged if the supply voltage has
been switched off or if a non-explosive atmosphere is ensured!
• Address selectors and ID switches may only be adjusted if the supply voltage has been switched off or if
a non-explosive atmosphere is ensured!
Standards
The fundamental health and safety requirements are fulfilled by compliance with the following standards:
• EN 60079-0:2012+A11:2013
• EN 60079-15:2010
Marking
The Beckhoff fieldbus components with extended temperature range (ET) certified for potentially explosive
areas bear the following marking:
II 3GKEMA 10ATEX0075 X Ex nA IIC T4 GcTa: -25…60°C
or
EL20xx, EL212482Version: 5.2
II 3GKEMA 10ATEX0075 X Ex nC IIC T4 GcTa: -25…60°C
4.8ATEX Documentation
Notes about operation of the Beckhoff terminal systems in potentially explosive areas (ATEX)
Pay also attention to the continuative documentation
Notes about operation of the Beckhoff terminal systems in potentially explosive areas (ATEX)
that is available in the download area of the Beckhoff homepage http:\\www.beckhoff.com!
Mounting and wiring
EL20xx, EL212483Version: 5.2
Commissioning
5Commissioning
5.1TwinCAT Quick Start
TwinCAT is a development environment for real-time control including multi-PLC system, NC axis control,
programming and operation. The whole system is mapped through this environment and enables access to a
programming environment (including compilation) for the controller. Individual digital or analog inputs or
outputs can also be read or written directly, in order to verify their functionality, for example.
For further information please refer to http://infosys.beckhoff.com:
• EtherCAT Systemmanual:
Fieldbus Components → EtherCAT Terminals → EtherCAT System Documentation → Setup in the
TwinCAT System Manager
• TwinCAT2 → TwinCAT System Manager → I/O - Configuration
• In particular, TwinCAT driver installation:
Fieldbus components → Fieldbus Cards and Switches → FC900x – PCI Cards for Ethernet →
Installation
Devices contain the terminals for the actual configuration. All configuration data can be entered directly via
editor functions (offline) or via the "Scan" function (online):
• "offline": The configuration can be customized by adding and positioning individual components.
These can be selected from a directory and configured.
◦ The procedure for offline mode can be found under http://infosys.beckhoff.com:
TwinCAT2 → TwinCAT System Manager → IO - Configuration → Adding an I/O Device
• "online": The existing hardware configuration is read
◦ See also http://infosys.beckhoff.com:
Fieldbus components → Fieldbus cards and switches → FC900x – PCI Cards for Ethernet →
Installation → Searching for devices
The following relationship is envisaged from user PC to the individual control elements:
EL20xx, EL212484Version: 5.2
Commissioning
Fig.60: Relationship between user side (commissioning) and installation
The user inserting of certain components (I/O device, terminal, box...) is the same in TwinCAT2 and
TwinCAT3. The descriptions below relate to the online procedure.
Sample configuration (actual configuration)
Based on the following sample configuration, the subsequent subsections describe the procedure for
TwinCAT2 and TwinCAT3:
• Control system (PLC) CX2040 including CX2100-0004 power supply unit
• Connected to the CX2040 on the right (E-bus):
EL1004 (4-channel digital input terminal 24 V DC)
• Linked via the X001 port (RJ-45): EK1100 EtherCAT Coupler
• Connected to the EK1100 EtherCAT coupler on the right (E-bus):
EL2008 (8-channel digital output terminal 24VDC;0.5A)
• (Optional via X000: a link to an external PC for the user interface)
EL20xx, EL212485Version: 5.2
Commissioning
Fig.61: Control configuration with Embedded PC, input (EL1004) and output (EL2008)
Note that all combinations of a configuration are possible; for example, the EL1004 terminal could also be
connected after the coupler, or the EL2008 terminal could additionally be connected to the CX2040 on the
right, in which case the EK1100 coupler wouldn’t be necessary.
EL20xx, EL212486Version: 5.2
Commissioning
5.1.1TwinCAT2
Startup
TwinCAT basically uses two user interfaces: the TwinCAT System Manager for communication with the
electromechanical components and TwinCAT PLC Control for the development and compilation of a
controller. The starting point is the TwinCAT System Manager.
After successful installation of the TwinCAT system on the PC to be used for development, the TwinCAT2
System Manager displays the following user interface after startup:
Fig.62: Initial TwinCAT2 user interface
Generally, TwinCAT can be used in local or remote mode. Once the TwinCAT system including the user
interface (standard) is installed on the respective PLC, TwinCAT can be used in local mode and thereby the
next step is "Insert Device [}89]".
If the intention is to address the TwinCAT runtime environment installed on a PLC as development
environment remotely from another system, the target system must be made known first. In the menu under
"Actions" → "Choose Target System...", via the symbol "" or the "F8" key, open the following window:
EL20xx, EL212487Version: 5.2
Commissioning
Fig.63: Selection of the target system
Use "Search (Ethernet)..." to enter the target system. Thus a next dialog opens to either:
• enter the known computer name after "Enter Host Name / IP:" (as shown in red)
• perform a "Broadcast Search" (if the exact computer name is not known)
• enter the known computer IP or AmsNetID.
Fig.64: Specify the PLC for access by the TwinCAT System Manager: selection of the target system
Once the target system has been entered, it is available for selection as follows (a password may have to be
entered):
After confirmation with "OK" the target system can be accessed via the System Manager.
EL20xx, EL212488Version: 5.2
Commissioning
Adding devices
In the configuration tree of the TwinCAT2 System Manager user interface on the left, select "I/ODevices”
and then right-click to open a context menu and select "ScanDevices…", or start the action in the menu bar
via . The TwinCAT System Manager may first have to be set to "Configmode" via or via menu
“Actions" → "Set/Reset TwinCAT to Config Mode…" (Shift + F4).
Fig.65: Select "Scan Devices..."
Confirm the warning message, which follows, and select "EtherCAT" in the dialog:
Fig.66: Automatic detection of I/O devices: selection the devices to be integrated
Confirm the message "Find new boxes", in order to determine the terminals connected to the devices. "Free
Run" enables manipulation of input and output values in "Config mode" and should also be acknowledged.
Based on the sample configuration [}85] described at the beginning of this section, the result is as follows:
EL20xx, EL212489Version: 5.2
Commissioning
Fig.67: Mapping of the configuration in the TwinCAT2 System Manager
The whole process consists of two stages, which may be performed separately (first determine the devices,
then determine the connected elements such as boxes, terminals, etc.). A scan can also be initiated by
selecting "Device ..." from the context menu, which then reads the elements present in the configuration
below:
Fig.68: Reading of individual terminals connected to a device
This functionality is useful if the actual configuration is modified at short notice.
Programming and integrating the PLC
TwinCAT PLC Control is the development environment for the creation of the controller in different program
environments: TwinCAT PLC Control supports all languages described in IEC 61131-3. There are two textbased languages and three graphical languages.
• Text-based languages
◦ Instruction List (IL)
EL20xx, EL212490Version: 5.2
◦ Structured Text (ST)
• Graphical languages
◦ Function Block Diagram (FBD)
◦ Ladder Diagram (LD)
◦ The Continuous Function Chart Editor (CFC)
◦ Sequential Function Chart (SFC)
The following section refers to Structured Text (ST).
After starting TwinCAT PLC Control, the following user interface is shown for an initial project:
Commissioning
Fig.69: TwinCAT PLC Control after startup
Sample variables and a sample program have been created and stored under the name "PLC_example.pro":
EL20xx, EL212491Version: 5.2
Commissioning
Fig.70: Sample program with variables after a compile process (without variable integration)
Warning 1990 (missing "VAR_CONFIG") after a compile process indicates that the variables defined as
external (with the ID "AT%I*" or "AT%Q*") have not been assigned. After successful compilation, TwinCAT
PLC Control creates a "*.tpy" file in the directory in which the project was stored. This file (*.tpy) contains
variable assignments and is not known to the System Manager, hence the warning. Once the System
Manager has been notified, the warning no longer appears.
First, integrate the TwinCAT PLC Control project in the System Manager via the context menu of the PLC
configuration; right-click and select "Append PLC Project…":
Fig.71: Appending the TwinCAT PLC Control project
EL20xx, EL212492Version: 5.2
Commissioning
Select the PLC configuration "PLC_example.tpy" in the browser window that opens. The project including the
two variables identified with "AT" are then integrated in the configuration tree of the System Manager:
Fig.72: PLC project integrated in the PLC configuration of the System Manager
The two variables "bEL1004_Ch4" and "nEL2008_value" can now be assigned to certain process objects of
the I/O configuration.
Assigning variables
Open a window for selecting a suitable process object (PDO) via the context menu of a variable of the
integrated project "PLC_example" and via "Modify Link..." "Standard":
Fig.73: Creating the links between PLC variables and process objects
In the window that opens, the process object for the variable “bEL1004_Ch4” of type BOOL can be selected
from the PLC configuration tree:
EL20xx, EL212493Version: 5.2
Commissioning
Fig.74: Selecting PDO of type BOOL
According to the default setting, certain PDO objects are now available for selection. In this sample the input
of channel 4 of the EL1004 terminal is selected for linking. In contrast, the checkbox "All types" must be
ticked for creating the link for the output variables, in order to allocate a set of eight separate output bits to a
byte variable. The following diagram shows the whole process:
Fig.75: Selecting several PDOs simultaneously: activate "Continuous" and "All types"
Note that the "Continuous" checkbox was also activated. This is designed to allocate the bits contained in the
byte of the variable "nEL2008_value" sequentially to all eight selected output bits of the EL2008 terminal. In
this way it is possible to subsequently address all eight outputs of the terminal in the program with a byte
corresponding to bit 0 for channel 1 to bit 7 for channel 8 of the PLC. A special symbol () at the yellow or
red object of the variable indicates that a link exists. The links can also be checked by selecting a "Goto Link
Variable” from the context menu of a variable. The object opposite, in this case the PDO, is automatically
selected:
EL20xx, EL212494Version: 5.2
Commissioning
Fig.76: Application of a "Goto Link" variable, using "MAIN.bEL1004_Ch4" as a sample
The process of assigning variables to the PDO is completed via the menu selection "Actions" → "Generate
Mappings”, key Ctrl+M or by clicking on the symbol in the menu.
This can be visualized in the configuration:
The process of creating links can also take place in the opposite direction, i.e. starting with individual PDOs
to variable. However, in this example it would then not be possible to select all output bits for the EL2008,
since the terminal only makes individual digital outputs available. If a terminal has a byte, word, integer or
similar PDO, it is possible to allocate this a set of bit-standardised variables (type "BOOL"). Here, too, a
"Goto Link Variable” from the context menu of a PDO can be executed in the other direction, so that the
respective PLC instance can then be selected.
Activation of the configuration
The allocation of PDO to PLC variables has now established the connection from the controller to the inputs
and outputs of the terminals. The configuration can now be activated. First, the configuration can be verified
via (or via "Actions" → "Check Configuration”). If no error is present, the configuration can be
activated via (or via "Actions" → "Activate Configuration…") to transfer the System Manager settings
to the runtime system. Confirm the messages "Old configurations are overwritten!" and "Restart TwinCAT
system in Run mode" with "OK".
A few seconds later the real-time status is displayed at the bottom right in the System Manager.
The PLC system can then be started as described below.
Starting the controller
Starting from a remote system, the PLC control has to be linked with the Embedded PC over Ethernet via
"Online" → “Choose Run-Time System…":
EL20xx, EL212495Version: 5.2
Commissioning
Fig.77: Choose target system (remote)
In this sample "Runtime system 1 (port 801)" is selected and confirmed. Link the PLC with the real-time
system via menu option "Online" → "Login", the F11 key or by clicking on the symbol .The control
program can then be loaded for execution. This results in the message "No program on the controller!
Should the new program be loaded?", which should be acknowledged with "Yes". The runtime environment
is ready for the program start:
EL20xx, EL212496Version: 5.2
Commissioning
Fig.78: PLC Control logged in, ready for program startup
The PLC can now be started via "Online" → "Run", F5 key or .
5.1.2TwinCAT 3
Startup
TwinCAT makes the development environment areas available together with Microsoft Visual Studio: after
startup, the project folder explorer appears on the left in the general window area (cf. "TwinCAT System
Manager" of TwinCAT2) for communication with the electromechanical components.
After successful installation of the TwinCAT system on the PC to be used for development, TwinCAT3
(shell) displays the following user interface after startup:
EL20xx, EL212497Version: 5.2
Commissioning
Fig.79: Initial TwinCAT3 user interface
First create a new project via (or under "File"→“New"→ "Project…"). In the
following dialog make the corresponding entries as required (as shown in the diagram):
Fig.80: Create new TwinCAT project
The new project is then available in the project folder explorer:
EL20xx, EL212498Version: 5.2
Commissioning
Fig.81: New TwinCAT3 project in the project folder explorer
Generally, TwinCAT can be used in local or remote mode. Once the TwinCAT system including the user
interface (standard) is installed on the respective PLC, TwinCAT can be used in local mode and thereby the
next step is "Insert Device [}100]".
If the intention is to address the TwinCAT runtime environment installed on a PLC as development
environment remotely from another system, the target system must be made known first. Via the symbol in
the menu bar:
expand the pull-down menu:
and open the following window:
Fig.82: Selection dialog: Choose the target system
EL20xx, EL212499Version: 5.2
Commissioning
Use "Search (Ethernet)..." to enter the target system. Thus a next dialog opens to either:
• enter the known computer name after "Enter Host Name / IP:" (as shown in red)
• perform a "Broadcast Search" (if the exact computer name is not known)
• enter the known computer IP or AmsNetID.
Fig.83: Specify the PLC for access by the TwinCAT System Manager: selection of the target system
Once the target system has been entered, it is available for selection as follows (a password may have to be
entered):
After confirmation with "OK" the target system can be accessed via the Visual Studio shell.
Adding devices
In the project folder explorer of the Visual Studio shell user interface on the left, select "Devices" within
element “I/O”, then right-click to open a context menu and select "Scan" or start the action via in the
menu bar. The TwinCAT System Manager may first have to be set to "Config mode" via or via the
menu "TwinCAT" → "Restart TwinCAT (Config mode)".
Fig.84: Select "Scan"
Confirm the warning message, which follows, and select "EtherCAT" in the dialog:
EL20xx, EL2124100Version: 5.2
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.