1. General information
1.1 Information on the operating manual
This operating manual contains important information on proper usage of the device. Read this operating manual carefully before installing and starting up the pressure measuring device.
Adhere to the safety notes and operating instructions which are given in the operating manual. Additionally applicable regulations regarding occupational safety, accident preven­tion as well as national installation standards and engineer­ing rules must be complied with!
This operating manual is part of the device, must be kept nearest its location, always accessible to all employees.
This operating manual is copyrighted. The contents of this operating manual reflect the version available at the time of printing. It has been issued to our best knowledge. However, errors may have occurred. BD SENSORS is not liable for any incorrect statements and their effects.
– Technical modifications reserved –
Russia
BD SENSORS RUS 39a, Varshavskoe shosse RU - Moscow 117105 Russia
Tel: +7 (0) 9 59 81 / 09 63 Fax: +7 (0) 9 57 95 / 07 21
Poland
Romania
Sweden
Switzerland
Slovakia
Spain
Turkey
UK
Ukraine
Iran
Israel
Kazakhstan
Taiwan
Thailand
AUSTRALIA
1.2 Symbols used
DANGER! – dangerous situation, which may result in death or serious injuries
WARNING! – potentially dangerous situation, which may result in death or serious injuries
CAUTION! – potentially dangerous situation, which may result in minor injuries
!
CAUTION! – potentially dangerous situation, which may result in physical damage
NOTE – tips and information to ensure a failure-free operation
1.3 Target group
WARNING! To avoid operator hazards and damages of the device, the following instructions have to be worked out by qualified technical personnel.
1.4 Limitation of liability
By non-observance of the operating manual, inappropriate use, modification or damage, no liability is assumed and warranty claims will be excluded.
The conformity of the produced end device has to be en­sured by the responsible design engineer or developer.
1.5 Intended use
- The pressure transmitter EP 500 has been designed for hard conditions especially in shipbuilding and offshore applications. The EP 500 is intended, depending on the ordered pressure range, for the pressure measurement of gauge or absolute pressure. A typical application is e.g. level measurement via air bubbling. The EP 500 ful­fil the requirements of Germanischer Lloyd (GL) as standard. The certificate is available for download on our homepage: http://www.bdsensors.com/proucts/ download/certificates
- It is the operator's responsibility to check and verify the suitability of the device for the intended application. If any doubts remain, please contact our sales department in order to ensure proper usage. BD SENSORS is not liable for any incorrect selections and their effects!
- Permissible media are gases or liquids, which are com­patible with the media, wetted parts of the device.
- The technical data listed in the current data sheet are engaging and must be complied with. If the data sheet is not available, please order or download it from our homepage: http://www.bdsensors.com/products/down­load/datasheets
WARNING! Danger through improper usage!
1.6 Package contents
Please verify that all listed parts are undamaged included in the delivery and check for consistency specified in your order:
- pressure transmitter EP 500
- mounting instructions
2. Product identification
The device can be identified by its manufacturing label. It provides the most important data. By the ordering code the product can be clearly identified.
nominal
pressure
Fig. 1 manufacturing label
!
type designation
range
signal
supply
The manufacturing label must not be removed from the device!
ordering code
connector pinout
serial
number
3. Mechanical installation
3.1 Mounting and safety instructions
WARNING! Install the device only when depressurized and currentless!
WARNING! This device may only be installed by qualified technical personnel who has read and under­stood the operating manual!
!
Handle this high-sensitive electronic precision measuring device with care, both in packed and unpacked condition!
!
There are no modifications/changes to be made on the device.
!
Do not throw the package/device!
!
To avoid damaging the diaphragm, remove packaging and protective cap directly before starting assembly. The delivered protective cap has to be stored!
!
Place the protective cap on the pressure port again immediately after disassembling.
!
Handle the unprotected diaphragm very carefully - it is very sensitive and may be easily damaged.
!
Do not use any force when installing the device to prevent damage of the device and the plant!
!
For the installation following points have to be ob­served:
- By factory, the device has an ingress protection of IP 00. Therefore the mounting / installation has to be performed carefully. Additionally the device has to be protected from the environmental effects by the installation in a ventilated housing, with a much higher ingress protection than the device. Check, if the desired ingress protection is sufficiently for your application. (recommendation: IP 65 at least)
- Install the device in such a way that it is protected from direct solar irradiation. Direct solar irradiation can lead to the permissible operating temperature being overstepped in the worst case. Through this, the operability of the device can be affected or damaged. If the internal pressure increases due to solar irradiation, temporary measurement errors may occur.
- Install the device in such a way, that the gauge reference, which is necessary for measuring, is protected from dirt and moisture.
- Take note that no assembly stress occurs at the pressure port, since this may cause a shifting of the characteristic curve.
Provide a cooling line when using the device in steam piping.
If there is any danger of damage by lightning or overpressure when the device is installed outdoor, we suggest putting a sufficiently dimensioned overpressure protection between the supply or switch cabinet and the device.
3.2 General installation steps
- Carefully remove the pressure measuring device from the package and dispose of the package properly.
- Go ahead as detailed in the specific instructions below.
3.3 Installation steps for tube nozzle
- Slip your flexible tubes (4 mm) onto the tube nozzles as far as possible.
3.4 Installation steps for G 1/4" acc. to EN 837
- Use a suitable seal, corresponding to the medium and the pressure input (e. g. a cooper gasket).
- Ensure that the sealing surface of the taking part is perfectly smooth and clean.
- Screw the device into the corresponding thread by hand.
- Tighten it with a wrench (approx. 20 Nm).
4. Electrical installation
WARNING! Install the device in currentless environ­ments only!
Establish the electrical connection of the device according to the technical data shown on the manufacturing label, the following table and the wiring diagram.
Pin configuration:
Electrical connection
Supply Supply
Shield
Wiring diagram:
supply +
p
terminal
clamps
1 2
3
VS
I
supply –
For the electrical connection a shielded and twisted multicore cable has to be used.
5. Function display
Malfunction
Possible cause
Error detection / corrective
By information flow through the transmitter lights a green SMD-LED.
6. Initial start-up
WARNING! Before start-up, the user has to check for proper installation and for any visible defects.
WARNING! The device can be started and operated by authorized personnel only, who have read and under­stood the operating manual!
WARNING! The device has to be used within the technical specifications, only (compare the data in the data sheet)!
7. Placing out of service
WARNING! When dismantling the device, it must always be done in the depressurized and currentless condition! Check also if the medium has to be drained off before dismantling!
WARNING! Depending on the medium, it may cause danger for the user. Comply therefore with adequate precautions for purification.
8. Maintenance
In principle, this device is maintenance-free. If desired, the housing of the device can be cleaned when switched of using a damp cloth and non-aggressive cleaning solutions.
!
An incorrect cleaning can cause irreparable damages on diaphragm. Never use spiky objects or pressured air for cleaning the diaphragm.
9. Service / Repair
9.1
Recalibration
During the life-time of a transmitter, the value of offset and span may shift. As a consequence, a deviating signal value in reference to the nominal pressure range starting point or end point may be transmitted. If one of these two phenom­ena occurs after prolonged use, a recalibration is recom­mended to ensure furthermore high accuracy.
9.2
Return
Before every return of your device, whether for recalibration, decalcification, modifications or repair, it is necessary to contact us to ensure a fast handling of your request. Please inform us by sending an email to: return@bdsensors.de. Include the number of devices sent and request a RMA. Then clean the device and pack it shatterproof before send it to BD SENSORS indicating the RMA.
10. Disposal
The device must be disposed according to the European Directives 2002/96/EG and 2003/108/EG (on waste electrical and electronic equipment) Waste of electrical and electronic equipment may not be disposed by domestic refuse!
WARNING! Depending on the measuring medium, deposit on the device may cause danger for the user and the environment. Comply with adequate precau­tions for purification and dispose of it properly.
11. Warranty conditions
The warranty conditions are subject to the legal warranty period of 24 months from the date of delivery. In case of improper use, modifications of or damages to the device, we do not accept warranty claims. Damaged diaphragms will also not be accepted. Furthermore, defects due to normal wear are not subject to warranty services.
12. Declaration of conformity / CE
The delivered device fulfils all legal requirements. The applied directives, harmonised standards and docu­ments are listed in the EC declaration of conformity, which is available online at: http://www.bdsensors.com/products/ download/certificates. Additionally, the operational safety is confirmed by the CE sign on the manufacturing label.
13. Error handling
wrong connected inspect the connection
no output signal
analogue output signal too low
small shift of output signal
large shift of output signal
If you detect an error, please try to eliminate it by using this table or send the device to our service address for repair.
!
Improper action and opening can damage the device. Therefore repairs on the device may only be executed by the manufacturer!
line break
defective amperemeter (signal input)
load resistance too high verify the value of the load resistance supply voltage too low verify the output voltage of the power supply defective energy supply inspect the power supply and the applied supply voltage at the device
diaphragm is calcified or coated with deposit
diaphragm is damaged (caused by overpressure or manually)
inspect all line connections necessary to supply the device (including the connector plugs) inspect the amperemeter (fine-wire fuse) or the analogue input of the PLC
if possible it is recommended to send the device to BD SENSORS for decalcification or cleaning
it is recommended to send the device to BD SENSORS for repair