Operating Manual
Pressure Transmitter for Shipbuilding and Offshore
Applications
EP 500
www.bdsensors.com
Headquarter Western Europe / International
BD SENSORS GmbH
BD-Sensors-Str. 1
D - 95199 Thierstein
Germany
Tel: +49 (0) 92 35 / 98 11-0
Fax: +49 (0) 92 35 / 98 11-11
Headquarter Eastern
Europe
BD SENSORS s.r.o.
Hradištská 817
CZ - 687 08 Buchlovice
Czech Republic
Tel: +42 (0) 5 72 / 4 11Fax: +42 (0) 5 72 / 4 11-
further agencies in:
• Belgium
• Denmark
• France
• Greece
• Italy
• Lithuania
• Luxemburg
• Netherlands
• Norway
The addresses of our distribution partners are listed on our
homepage www.bdsensors.com. It is possible to download
data sheets, operating manuals, ordering codes and certificates, as well.
1. General information
1.1 Information on the operating manual
This operating manual contains important information on
proper usage of the device. Read this operating manual
carefully before installing and starting up the pressure
measuring device.
Adhere to the safety notes and operating instructions which
are given in the operating manual. Additionally applicable
regulations regarding occupational safety, accident prevention as well as national installation standards and engineering rules must be complied with!
This operating manual is part of the device, must be kept
nearest its location, always accessible to all employees.
This operating manual is copyrighted. The contents of this
operating manual reflect the version available at the time of
printing. It has been issued to our best knowledge. However,
errors may have occurred. BD SENSORS is not liable for
any incorrect statements and their effects.
– Technical modifications reserved –
Russia
BD SENSORS RUS
39a, Varshavskoe shosse
RU - Moscow 117105
Russia
Tel: +7 (0) 9 59 81 / 09 63
Fax: +7 (0) 9 57 95 / 07 21
• Poland
• Romania
• Sweden
• Switzerland
• Slovakia
• Spain
• Turkey
• UK
• Ukraine
• Iran
• Israel
• Kazakhstan
• Taiwan
• Thailand
AUSTRALIA
1.2 Symbols used
DANGER! – dangerous situation, which may result in
death or serious injuries
WARNING! – potentially dangerous situation, which
may result in death or serious injuries
CAUTION! – potentially dangerous situation, which may
result in minor injuries
!
CAUTION! – potentially dangerous situation, which may
result in physical damage
NOTE – tips and information to ensure a failure-free
operation
1.3 Target group
WARNING! To avoid operator hazards and damages of
the device, the following instructions have to be worked
out by qualified technical personnel.
1.4 Limitation of liability
By non-observance of the operating manual, inappropriate
use, modification or damage, no liability is assumed and
warranty claims will be excluded.
The conformity of the produced end device has to be ensured by the responsible design engineer or developer.
1.5 Intended use
- The pressure transmitter EP 500 has been designed for
hard conditions especially in shipbuilding and offshore
applications. The EP 500 is intended, depending on the
ordered pressure range, for the pressure measurement
of gauge or absolute pressure. A typical application is
e.g. level measurement via air bubbling. The EP 500 fulfil the requirements of Germanischer Lloyd (GL) as
standard. The certificate is available for download on
our homepage: http://www.bdsensors.com/proucts/
download/certificates
- It is the operator's responsibility to check and verify the
suitability of the device for the intended application. If
any doubts remain, please contact our sales department
in order to ensure proper usage. BD SENSORS is not
liable for any incorrect selections and their effects!
- Permissible media are gases or liquids, which are compatible with the media, wetted parts of the device.
- The technical data listed in the current data sheet are
engaging and must be complied with. If the data sheet is
not available, please order or download it from our
homepage: http://www.bdsensors.com/products/download/datasheets
WARNING! Danger through improper usage!
1.6 Package contents
Please verify that all listed parts are undamaged included in
the delivery and check for consistency specified in your
order:
- pressure transmitter EP 500
- mounting instructions
2. Product identification
The device can be identified by its manufacturing label. It
provides the most important data. By the ordering code the
product can be clearly identified.
nominal
pressure
Fig. 1 manufacturing label
!
type designation
range
signal
supply
The manufacturing label must not be removed from the
device!
ordering code
connector pinout
serial
number
3. Mechanical installation
3.1 Mounting and safety instructions
WARNING! Install the device only when depressurized
and currentless!
WARNING! This device may only be installed by
qualified technical personnel who has read and understood the operating manual!
!
Handle this high-sensitive electronic precision
measuring device with care, both in packed and
unpacked condition!
!
There are no modifications/changes to be made on the
device.
!
Do not throw the package/device!
!
To avoid damaging the diaphragm, remove packaging
and protective cap directly before starting assembly.
The delivered protective cap has to be stored!
!
Place the protective cap on the pressure port again
immediately after disassembling.
!
Handle the unprotected diaphragm very carefully - it is
very sensitive and may be easily damaged.
!
Do not use any force when installing the device to
prevent damage of the device and the plant!
!
For the installation following points have to be observed:
- By factory, the device has an ingress protection of
IP 00. Therefore the mounting / installation has to
be performed carefully. Additionally the device has
to be protected from the environmental effects by
the installation in a ventilated housing, with a much
higher ingress protection than the device. Check, if
the desired ingress protection is sufficiently for
your application. (recommendation: IP 65 at least)
- Install the device in such a way that it is protected
from direct solar irradiation. Direct solar irradiation
can lead to the permissible operating temperature
being overstepped in the worst case. Through this,
the operability of the device can be affected or
damaged. If the internal pressure increases due to
solar irradiation, temporary measurement errors
may occur.
- Install the device in such a way, that the gauge
reference, which is necessary for measuring, is
protected from dirt and moisture.
- Take note that no assembly stress occurs at the
pressure port, since this may cause a shifting of
the characteristic curve.
Provide a cooling line when using the device in steam
piping.
If there is any danger of damage by lightning or
overpressure when the device is installed outdoor, we
suggest putting a sufficiently dimensioned overpressure
protection between the supply or switch cabinet and the
device.
3.2 General installation steps
- Carefully remove the pressure measuring device from
the package and dispose of the package properly.
- Go ahead as detailed in the specific instructions below.
3.3 Installation steps for tube nozzle
- Slip your flexible tubes (∅ 4 mm) onto the tube nozzles
as far as possible.
3.4 Installation steps for G 1/4" acc. to EN 837
- Use a suitable seal, corresponding to the medium and
the pressure input (e. g. a cooper gasket).
- Ensure that the sealing surface of the taking part is
perfectly smooth and clean.
- Screw the device into the corresponding thread by
hand.
- Tighten it with a wrench (approx. 20 Nm).
4. Electrical installation
WARNING! Install the device in currentless environments only!
Establish the electrical connection of the device according to
the technical data shown on the manufacturing label, the
following table and the wiring diagram.
Pin configuration:
Electrical
connection
Supply
Supply −
Shield
Wiring diagram:
supply +
p
terminal
clamps
1
2
3
VS
I
supply –
For the electrical connection a shielded and twisted
multicore cable has to be used.
5. Function display
Error detection / corrective
By information flow through the transmitter lights a green
SMD-LED.
6. Initial start-up
WARNING! Before start-up, the user has to check for
proper installation and for any visible defects.
WARNING! The device can be started and operated by
authorized personnel only, who have read and understood the operating manual!
WARNING! The device has to be used within the
technical specifications, only (compare the data in the
data sheet)!
7. Placing out of service
WARNING! When dismantling the device, it must
always be done in the depressurized and currentless
condition! Check also if the medium has to be drained
off before dismantling!
WARNING! Depending on the medium, it may cause
danger for the user. Comply therefore with adequate
precautions for purification.
8. Maintenance
In principle, this device is maintenance-free. If desired, the
housing of the device can be cleaned when switched of
using a damp cloth and non-aggressive cleaning solutions.
!
An incorrect cleaning can cause irreparable damages
on diaphragm. Never use spiky objects or pressured air
for cleaning the diaphragm.
9. Service / Repair
9.1
Recalibration
During the life-time of a transmitter, the value of offset and
span may shift. As a consequence, a deviating signal value
in reference to the nominal pressure range starting point or
end point may be transmitted. If one of these two phenomena occurs after prolonged use, a recalibration is recommended to ensure furthermore high accuracy.
9.2
Return
Before every return of your device, whether for recalibration,
decalcification, modifications or repair, it is necessary to
contact us to ensure a fast handling of your request. Please
inform us by sending an email to: return@bdsensors.de.
Include the number of devices sent and request a RMA.
Then clean the device and pack it shatterproof before send it
to BD SENSORS indicating the RMA.
10. Disposal
The device must be disposed according to the
European Directives 2002/96/EG and
2003/108/EG (on waste electrical and electronic
equipment) Waste of electrical and electronic
equipment may not be disposed by domestic
refuse!
WARNING! Depending on the measuring medium,
deposit on the device may cause danger for the user
and the environment. Comply with adequate precautions for purification and dispose of it properly.
11. Warranty conditions
The warranty conditions are subject to the legal warranty
period of 24 months from the date of delivery. In case of
improper use, modifications of or damages to the device, we
do not accept warranty claims. Damaged diaphragms will
also not be accepted. Furthermore, defects due to normal
wear are not subject to warranty services.
12. Declaration of conformity / CE
The delivered device fulfils all legal requirements.
The applied directives, harmonised standards and documents are listed in the EC declaration of conformity, which is
available online at: http://www.bdsensors.com/products/
download/certificates.
Additionally, the operational safety is confirmed by the CE
sign on the manufacturing label.
13. Error handling
wrong connected inspect the connection
no output
signal
analogue
output signal
too low
small shift of
output signal
large shift of
output signal
If you detect an error, please try to eliminate it by using this table or send the device to our service address for repair.
!
Improper action and opening can damage the device. Therefore repairs on the device may only be executed by the
manufacturer!
line break
defective amperemeter (signal
input)
load resistance too high verify the value of the load resistance
supply voltage too low verify the output voltage of the power supply
defective energy supply inspect the power supply and the applied supply voltage at the device
diaphragm is calcified or coated
with deposit
diaphragm is damaged (caused
by overpressure or manually)
inspect all line connections necessary to supply the device (including
the connector plugs)
inspect the amperemeter (fine-wire fuse) or the analogue input of the
PLC
if possible it is recommended to send the device to BD SENSORS for
decalcification or cleaning
it is recommended to send the device to BD SENSORS for repair
EP500_E_110210