B&B Electronics 485OPDRI-PH User Manual

11.. CChheecckk ffoorr RReeqquuiirreedd HHaarrddwwaarree
ILinx 485OPDRI-PH Isolated Repeater This Quick Start Guide Additional Items Required but not included
o A 10 to 48 VDC Power Supply. Repeater draws
2.3W Max.
22.. IInnffoorrmmaattiioonn
UULL CCllaassss 11 DDiivv 22
1. Refer to Nonincendive Field Wiring Apparatus Control Drawing. for important information.
2. Power, Input / output (I/O) wiring for the end use enclosure must be in accordance with Class 1 Division 2 wiring methods (Article 501.10(B) of the National Electric Code, NFPA 70) and in accordance with the local authority having jurisdiction.
3. Maximum ambient air temperature 85°C.
4. Temperature rating of field installed conductors 105°C. Use Copper Wire Only.
5. These devices must be installed in end use enclosure suitable for the location.
6. WARNING – EXPLOSION HAZARD SUBSTITUTION OF COMPONENTS MAY IMPAIR SUITABILITY FOR CLASS 1, DIVISION 2.
7. WARNING – EXPLOSION HAZARD: DO NOT DISCONNECT EQUIPMENT UNLESS POWER HAS BEEN SWITCHED OFF OR THE AREA IS KNOWN TO BE NON-HAZARDOUS.
8. WARNING – THIS APPARATUS IS SUITABLE FOR USE IN CLASS 1 DIVISION 2, GROUPS A, B, C, AND D OR NONHAZARDOUS LOCATIONS ONLY.
Quick Start Guide
ILinx 485OPDRI-PH
Triple Isolated RS-422/485
Repeater
33.. FFrroonntt && BBaacckk PPaanneell
A
Power LED
Red, ON When Power Applied
B
Data LEDs
Green. LEDs Flash When Data is on
Port. C 422/485 TB
5 Position, Removable
D
Ground Lug
Chassis Ground to Earth Ground
E
DIP Switch
Used to Configure
F
Power TB
2 Position, Removable
44.. CCoonnffiigguurraattiioonn DDIIPP SSwwiittcchh
SWITCH POSITION 8 IS NOT USED
Highlighted settings indicate factory default. Switch functions are identical for each port.
Communications Mode
Switch
1 2 3 4
RS-485
2-Wire
Half Duplex
ON
ON
ON
ON
RS-485
4-Wire
Full Duplex
ON
OFF
OFF
OFF
RS-422
Full Duplex
OFF
OFF
OFF
OFF
Built-in Termination Resistor
Switch 5
Use the 120Ω Built-in Termination
ON
Use External or No Termination
OFF
Built-in Transmit Bias Resistor
Switch 6
Use External or No Bias Resistor
ON
Use the 1.2K Ω Transmit Bias Resistor
OFF
Built-in Receive Bias Resistor
Switch 7
Use External or No Bias Resistor
ON
Use the 1.2K Ω Receive Bias Resistor
OFF
For an explanation of RS-485 termination and biasing requirements, refer to B&B Electronics’ RS-485 application note. This publication can be downloaded at: www.bb-elec.com
International Headquarters: 815-433-5100 www.bb-elec.com
Documentation Number – p/n 8932r001 485OPDRI-PH-1712qsg
©2010 B&B Electronics Manufacturing Company
European Headquarters:
+353 91 792444
www.bb-europe.com
66.. PPoowweerr CCoonnnneeccttiioonn
1. Connect Power. Power Requirements: 10 to 48 VDC,
2.3W Maximum.
2. The terminal block will accept 28 to 12 AWG Wire.
88.. RRSS--442222//448855 TTeerrmmiinnaall BBlloocckkss
RS-422 / 4-Wire RS-485
1100.. OOppeerraattiioonn
1. During normal operation, the Power LED should be illuminated.
2. When data is sent or received on either port, the corresponding Data LED should flash.
99.. WWiirriinngg EExxaammpplleess
2-Wire RS-485
See Section One for wire recommendation.
55.. GGrroouunndd CCoonnnneeccttiioonn
1. It is recommended that the chassis be grounded.
2. Connect a grounding wire from the ground lug to a good source of Earth Ground.
Documentation Number – p/n 8932r001 485OPDRI-PH-1712qsg