Product Overview
2
Wiring Example
Terminal Block
Connectors
A – F
DIP Switches
1 – 8
1
Connections
Terminal
Block
Signal
A OUT (+)
B OUT (-)
Signal
C
Ground
Power
D
Ground
E IN (+)
F IN (-)
A-F Side
Terminal Block
Connectors
G – M
DIP Switches
1 – 8
2-Wire RS-485 System
TD/RD(A)-
.
.
TD/RD(B)+
H In G In +
L Out -
K Out +
J
M IGND1
Cable is 2 twisted pairs
+ shield (not shown)
485OPDR-HS
10-30
VDC
Out - B
Out + A
In - F
In + E
GND D
IGND2 C
.
.
GND/REF
POWER
SUPPLY
-V NC +V
3
L N
DIP Switches
AC Power lines
or AC outlet
using plug
Signal
Ground
Set DIP switches for RS-422, 2-Wire RS-485
or 4-Wire RS-485. The sample settings shown
below are for 2-Wire RS-485 half duplex
operation.
Switches 1, 2, 3, 4, 5 = ON
Switch 6 = OFF
Switches 7, 8 = Not Used
Attention: Please follow proper ESD
protection procedures when configuring
this device.
G IN (+)
H IN (-)
+10 to 30
J
K OUT (+)
L OUT (-)
M
VDC
Signal
Ground
G-M Side
Echo
Off
Echo
On
2W 2W
4W 4W
RS-485
Switch 1 2 3 4 5 6 7 8
Position
ON ON ON ON ON ON *** ***
OFF OFF OFF OFF OFF OFF *** ***
RS-422
Bias
IN
Bias
OUT
IN
Term
OUT
Used
Not
Used
Not
Term
Not
Used
Not
Used
Troubleshooting
Q. What are the factory presets?
A. “2-Wire” RS-485 half duplex operation; echo off, bias in,
termination out.
Switches 1, 2, 3, 4, 5 = ON
Switche 6 = OFF.
Switches 7, 8 = Not used.
Q. I want to use “4-Wire” RS-485 but the “4-Wire” RS485
devices do not respond with data.
A. When this unit is used to talk to a “4-Wire” device that
does not have biasing across the RS-485 receiver lines it may
be necessary to set the Transmitter to RS-422 Transmit mode:
Switch 1 = OFF.
This setting can be used providing that the master is on the
opposite side of the repeater. No other 4-Wire device can
be connected to the transmit lines on the side set for RS-422
transmit. The 485OPDRI has switches to enable separate
Transmit bias & Receive bias.
Biasing
Bias is provided by 4.7kΩ pull-up/down
resistors on the Data In lines. This value
is adequate for most applications without
termination.
Recommended Accessories
DIN rail mount
power supply
MDR-20-24
http://www.bb-elec.com/Products/PowerSupplies-Accessories/DIN-Power-Supplies/
Industrial-Slimline-Power-Supplies.aspx
Dataline Surge
Suppressor
HESP4DR
http://www.bb-elec.com/Products/SerialConnectivity/Surge-Protection/Heavy-DutySurge- Protectors.aspx
Fast Easy Answers...
You can use your
smart phone to access
complete documentation
on our website. Simply
scan code to the right.
485OPDR-HS
High Speed, Isolated
RS-422/485 Repeater
Q
S
tart
G
uide
uick
Document number – pn9830_R1_485OPDR-HS_3213qsg
1-888-948-2248 | Europe: +353 91 792444
www.bb-elec.com
707 Dayton Road | PO Box 1040 | Ottawa, IL 61350
Phone: 815-433-5100 | Fax: 815-433-5109
www.bb-elec.com | E-mail: info@bb-elec.com
© 2011 B&B Electronics Manufac turing Compa ny
First Things First...
Before you begin, be sure you have
the following:
485OPDR-HS
Additional items required but not included:
Power Supply (10 to 30 VDC, 0.7 W)
RS-422/485 Cable
Fast and easy on the web: