Optically Isolated RS-422/485 Repeaters
485OP, 485OPB
PRODUCT FEATURES
• 2KVisolation
• Addupto32nodestoRS-485network
• RS-4222-wire,RS-4852or4-wire
• Modbus
• ULRecognized
SPECIFICATIONS
serial ProtoCols
Model 485OP is an optically isolated RS-422/485 signal repeater. In
addition to 2KV isolation on the data lines, it can be used to extend RS422/485 circuits an additional 1.2 km (4,000 ft.), thereby doubling the
range. An added benefit is the ability to add another 32 nodes to an RS-485
network and join 2 and 4 wire systems.
The compact design fits almost anywhere. Terminal blocks allow easy
installation. Wiring schematic on the label eliminates guesswork. A 12 VDC
power supply is required.
ORDERING INFORMATION
Model
nuMber
485OP RS-422/485 Fiber Optic Isolated Repeater USA (included)
485OPB RS-422/485 Fiber Optic Isolated Repeater
ACCESSORIES
PS1EU-1000 - 220-240 VAC to 12 VDC power supply, jack, Euro CEE7/7 plug
PS1UK-1000 - 220-240 VAC to 12 VDC power supply, jack, UK BS-1363 plug
485HESP - RS-485 surge protector
485PS4 - 12VDC @ 500 mA, wall power supply, tinned stripped leads
desCriPtion Power suPPly
EU or UK
(sold separately)
www.bb-elec.com
orders@bb-elec.com
support@bb-elec.com
International Office: 707 Dayton Road PO Box 1040 Ottawa, IL 61350 USA 815-433-5100 Fax 433-5104
European Office: Westlink Commercial Park Oranmore Co. Galway Ireland +353 91 792444 Fax +353 91 792445
isolation
Lines Protected Data lines
Method Optical
Rating 2000 V
surge suPPression
Lines Protected Data lines
Method TVS
Rating
industrial bus
Power
Connector Terminal block
Voltage 10 to 14 VDC
Power Consumption 1.0 W
Source Included wall transformer or other 10 to 14 VDC source
Power suPPly
Input Voltage 120 VAC (USA); 220-240 VAC (EU, UK)
Output Voltage 12 VDC
Output Connection
terMinal bloCks
Wire Size 22 to 14 AWG
Torque 0.5 Nm
led indiCators
2 x DATA (RED) Flashes when data received
enClosure
Material Plastic
IP Rating 30
Dimensions 9.7 x 6.1 x 2.5 cm (3.8 x 2.4 x 1.0 in)
Mounting In line
environMental
Operating Temperature 0 to 55 °C (32 to 131 °F)
Operating Humidity 0 to 95% non-condensing
MTBF 453103 hours
MTBF Calculation Method Parts Count Reliability Prediction
agenCy aPProvals
RS-422 4-wire
RS-485 2-wire
RS-485 4-wire
6.5V bi-directional
600W peak power dissipation
Modbus ASCII/RTU
USA: Stripped and tinned leads
EU: UK BS-1363 plug, jack
UK: Euro CEE7/7 plug, jack
CE, FCC
cULus Recognized, File E222870
Declaration of Conformity available
for download at www.bb.elec.com
485OP, 485OPB_3713ds