Building Regulations and the Benchmark
Commissioning Checklist
Building Regulations (England & Wales) require notification of
the installation of a heating appliance to the relevant Local
Authority Building Control Department. From 1 April 2005 this
can be achieved via a Competent Persons Self Certification
Scheme as an option to notifying the Local Authority directly.
Similar arrangements will follow for Scotland and will apply in
Northern Ireland from 1 January 2006.
The Health & Safety Executive operates the ‘Gas Safe Register’,
a self-certification scheme for gas heating appliances.
These arrangements represent a change from the situation
whereby compliance with Building Regulations was accepted as
being demonstrated by completion of the Benchmark Logbook
(which was then left on site with the customer).
With the introduction of Self Certification Schemes, the
Benchmark Logbook is being withdrawn. However, a similar
document in the form of a commissioning checklist and service
interval record is incorporated at the back of these instructions.
The Benchmark Scheme
Benchmark places responsibilities on both manufacturers and installers. The
purpose is to ensure that customers are provided with the correct equipment for
their needs, that it is installed, commissioned and serviced in accordance with the
manufacturer’s instructions by competent persons and that it meets the
requirements of the appropriate Building Regulations. The Benchmark Checklist
can be used to demonstrate compliance with Building Regulations and should be
provided to the customer for future reference.
Installers are required to carry out installation, commissioning and servicing work
in accordance with the Benchmark Code of Practice which is available from the
Heating and Hotwater Industry Council who manage and promote the Scheme.
Visit www.centralheating.co.uk for more information.
Applications for the copyright owner’s permission to reproduce or make other
use of any part of this publication should be made, giving details of the proposed
use, to the following address:
The Company Secretary, Baxi Heating UK Ltd,
Brooks House, Coventry Road, Warwick. CV34 4LL
Full acknowledgement of author and source must be given.
This company is a member of the Benchmark initiative and fully
supports the aims of the programme. Its aim is to improve the
standards of installation and commissioning of central heating
systems in the UK and to encourage the regular servicing of all
central heating systems to ensure safety and efficiency.
Building Regulations require that installations should comply
with manufacturer's instructions. It is therefore important that
the commissioning checklist is completed by the installer. The
relevant section of Building Regulations only relates to
dwellings. Therefore the checklist only applies if the appliance is
being installed in a dwelling or some related structure.
The flowchart opposite gives guidance for installers on the
process necessary to ensure compliance with Building
Regulations.
WARNING: Any person who does any unauthorised act in relation to a
copyright work may be liable to criminal prosecution and civil claims for damages.
IMPORTANT - Installation, Commissioning, Service & Repair
This appliance must be installed in accordance with the manufacturer’s instructions and
the regulations in force. Read the instructions fully before installing or using the
appliance.
In GB, this must be carried out by a competent person as stated in the Gas Safety
(Installation & Use) Regulations.
Definition of competence: A person who works for a Gas Safe registered company
and holding current certificates in the relevant ACS modules, is deemed competent.
In IE, this must be carried out by a competent person as stated in I.S. 813 “Domestic
Gas Installations”.
The addition of anything that may interfere with the normal operation of the appliance
without express written permission from the manufacturer or his agent could invalidate
the appliance warranty. In GB this could also infringe the Gas Safety (Installation and
Use) Regulations.
Warning - Check the information on the data plate is compatible with local supply
conditions.
All Gas Safe registered engineers carry an ID card with their licence number and a
photograph. You can check your engineer is registered by telephoning
0800 408 5500 or online at www.gassaferegister.co.uk
This company declare that no substances harmful to
health are contained in the appliance or used during
appliance manufacture.
The appliance is suitable only for installation in GB and IE
and should be installed in accordance with the rules in
force, and only used in a suitably ventilated location.
In GB, the installation must be carried out by a Gas Safe
Registered Installer. It must be carried out in accordance
with the relevant requirements of the:
• Gas Safety (Installation & Use) Regulations.
• The appropriate Building Regulations either The Building
Regulations, The Building Regulations (Scotland), Building
Regulations (Northern Ireland).
• The Water Fittings Regulations or Water Byelaws in
Scotland.
• The Current I.E.E. Wiring Regulations.
Where no specific instructions are given, reference should
be made to the relevant British Standard Code of Practice.
In IE, the installation must be carried out by a competent
Person and installed in accordance with the current edition
of I.S. 813 ‘Domestic Gas Installations’, the current Building
Regulations and reference should be made to the current
ETCI rules for electrical installation.
All systems must be thoroughly flushed and treated
with inhibitor (see section 6.2).
The boiler meets the requirements of Statutory Instrument “ The Boiler (Efficiency)
o
Regulations 1993 N
3083” and is deemed to meet the requirements of Directive
92/42/EEC on the energy efficiency requirements for new hot water boilers fired with
liquid or gaseous fuels:-
Type test for purpose of Regulation 5 certified by:
Notified Body 0086.
Product/Production certified by:
Notified Body 0086.
For GB/IE only.
Codes of Practice, most recent version should be used
In GB the following Codes of Practice apply:
StandardScope
BS 6891Gas Installation.
BS 5546Installation of hot water supplies for domestic
purposes.
BS EN 12828Heating systems in buildings.
BS EN 12831Heating systems in buildings - calculations of load
BS EN 14336Installation & commissioning of water based
heating systems.
BS 6798Installation of gas fired hot water boilers.
BS 5440 Part 1Flues.
BS 5440 Part 2Ventilation.
BS 7074Expansion vessels and ancillary equipment for
sealed water systems.
BS 7593Treatment of water in domestic hot water
central heating systems.
In IE the following Codes of Practice apply:
StandardScope
I.S. 813Domestic Gas Installations.
The following BS standards give valuable additional information;
BS 5546Installation of hot water supplies for domestic
purposes.
BS EN 12828Heating systems in buildings.
BS EN 12831Heating systems in buildings - calculations of load
BS EN 14336Installation & commissioning of water based
heating systems.
BS 7074Expansion vessels and ancillary equipment for
sealed water systems.
BS 7593Treatment of water in domestic hot water
The following advice should be adhered to, from when first handling the boiler to the final stages of installation, and also during maintenance.
Most injuries as a result of inappropriate handling and lifting are to the back, but all other parts of the body are vulnerable, particularly shoulders, arms and
hands. Health & Safety is the responsibility of EVERYONE.
There is no ‘safe’ limit for one man - each person has different capabilities. The boiler should be handled and lifted by TWO PEOPLE.
Do not handle or lift unless you feel physically able.
Wear appropriate Personal Protection Equipment e.g. protective gloves, safety footwear etc.
Preparation
Co-ordinate movements - know where, and when, you are both going.
Minimise the number of times needed to move the boiler - plan ahead.
Always ensure when handling or lifting the route is clear and unobstructed. If possible avoid steps, wet or slippery surfaces, unlit areas etc. and take special
care on ladders/into lofts.
Technique
When handling or lifting always use safe techniques - keep your back straight, bend your knees. Don’t twist - move your feet, avoid bending forwards and
sideways and keep the load as close to your body as possible.
Where possible transport the boiler using a sack truck or other suitable trolley.
Always grip the boiler firmly, and before lifting feel where the weight is concentrated to establish the centre of gravity, repositioning yourself as necessary.
See section 8.3 of these instructions for recommended lift points.
Remember
The circumstances of each installation are different. Always asses the risks associated with handling and lifting according to the individual conditions.
If at any time when installing the boiler you feel that you may have injured yourself STOP !!
DO NOT ‘work through’ the pain - you may cause further injury.
IF IN ANY DOUBT DO NOT HANDLE OR LIFT THE BOILER - OBTAIN ADVICE OR ASSISTANCE BEFORE PROCEEDING !!
1. The Baxi Solo HE A range are gas fired room sealed fan
assisted condensing central heating boilers.
2. The maximum outputs of the Baxi Solo models are:-
A - 11.82 kW (Non Condensing)
12 HE
12.81 kW (Condensing)
A - 15.24 kW (Non Condensing)
15 HE
16.49 kW (Condensing)
A - 17.81 kW (Non Condensing)
18 HE
19.27 kW (Condensing)
A - 22.0 kW (Non Condensing)
24 HE
23.8 kW (Condensing)
A - 30.18 kW (Non Condensing)
30 HE
32.61 kW (Condensing)
Note: 30 HE
adjustment details. All boilers automatically adjust output
according to system load.
A is pre-set at 22.0/23.8 kW - see section 10.8 for
Air Box Door
Fig. 2
Lower Door Panel
Position of Label
Data Badge
3. The boiler is designed for use on Natural Gas (G20).
4. The boiler is suitable for fully pumped open vented central
heating and domestic hot water systems and sealed systems.
5. A label giving details of the model, serial number and Gas
Council number is situated on the rear of the lower door panel
(Fig. 1).
6. The boiler data badge is positioned on the air box door
(Fig. 2).
7. The boiler is intended to be installed in residential / domestic
environments on a governed meter supply only.
8. The boiler must be installed with one of the purpose designed
flues such as the standard horizontal flue kit, part no 236921.
1.2Important Information
Man-made mineral fibre
• Some component parts of this appliance (insulation pads,
gaskets and rope seals) are manufactured from man-made
mineral fibre.
• Prolonged or excessive exposure to this material may result in
some irritation to the eyes, skin or respiratory tract.
• It is advisable to wear gloves when handling these items.
• Irritant dust will only be released from the items if they are
broken up or subjected to severe abrasion. In these instances a
suitable dust mask and goggles should be worn.
• Always thoroughly wash hands after installation, servicing or
changing components.
• When disposing of any items manufactured from man-made
mineral fibre care must be exercised.
• If any irritation of the eyes or severe irritation of the skin is
experienced seek medical attention.
1. Switched Live On: When the switched live switches
on if the flow temperature is less than the set point
then pump overrun occurs. When the switched live
switches on if the flow temperature is greater than the
set point then pump overrun occurs.
2. Pump On: The pump is on while the fan, spark
generator and gas valve are off. After 10 seconds if the
flow switch has made then fan pre-purge occurs. After
10 seconds if the flow switch has not made then anticycle occurs.
3. Fan Pre-Purge: The pump and fan are on while the
spark generator and gas valve are off. After 5 seconds
ignition occurs.
4. Ignition: The pump, fan, spark generator and gas
valve are on. If a flame is detected then burner on
occurs. If a flame is not detected within 5 seconds and
less than 5 ignition attempts have been made then fan
purge occurs. If a flame is not detected within 5
seconds and 5 ignition attempts have been made then
ignition lockout occurs.
Flame Detected ?
shut or Flow temperature
greater than set point ?
Fan Post Purge.
YES
YES
Burner On.
All TRVs
YES
5 second
All TRVs
shut down ?
NO
Ignition done and
5 attempts made ?
YES
Ignition
Lockout.
5. Burner On: The pump, fan and gas valve are on
while the spark generator is off. Flow temperature is
controlled by varying the fan speed (and thereby the
gas rate) to achieve optimum operation. If the flow
temperature is greater than the set point or the TRVs
all shut down then fan post purge occurs.
6. Fan Post Purge: The pump and fan are on while the
spark generator and gas valve are off. After 5 seconds if
the TRVs are not shut down then pump overrun
occurs. After 5 seconds if the TRVs are shut down then
anti-cycle occurs.
7. Pump Overrun: The pump is on while the fan, spark
generator and gas valve are off. After 1 minute anticycle occurs.
8. Anti-cycle: The pump, fan, spark generator and gas
valve are off. After 3 minutes if the flow temperature is
less than the set point then pump on occurs. After 3
minutes if the flow temperature is greater than the set
point then pump overrun occurs.
9. Ignition Lockout: The pump, fan, spark generator
and gas valve are off. The boiler can only be reset by
manually using the reset button.
NOTE: The maximum output of the 30
model is factory set at 22.0kW. This can
be altered to 30.18kW - see section 10 .8.
SEDBUK Declaration
For 12 model - The efficiency is 90.5%
For 15 model - The efficiency is 91.3%
For 18 model - The efficiency is 90.4%
For 24 model - The efficiency is 90.9%
For 30 model - The efficiency is 90.9%
This value is used in the UK Government’s Standard
The 1.5° fall provided by the elbow
is to allow condensate to run back to
the boiler, for disposal through the
Tube Ø 110mm
condensate discharge pipe.
Fig. 7
Fig. 8
F
Y
X
At least
1.5°
SIDE FLUE (left and right)
For every 1m of horizontal flue
length, the clearance above the top
of the flue elbow should be 27.5mm
to incorporate the 1.5° fall in the flue
from the terminal to the elbow.
1. The appliance is suitable for use with open vent fully
pumped systems and sealed systems .
The following conditions should be observed on all
systems:
• The static head must not exceed 30m (100ft) of water.
• The boiler must not be used with a direct cylinder.
• Drain cocks should be fitted to all system low points.
• All gas and water pipes and electrical wiring must be
installed in a way which would not restrict the servicing
of the boiler.
• Position isolating valves as close to circulating pump as
possible.
• It is recommended that the return pipe is fitted with an
automatic air vent as close to the boiler as is practical.
6.2Treatment of Water Circulating
Systems
• All recirculatory water systems will be subject to
corrosion unless an appropriate water treatment is
applied. This means that the efficiency of the system will
deteriorate as corrosion sludge accumulates within the
system, risking damage to pump and valves, boiler noise
and circulation problems.
• When fitting new systems flux will be evident within the
system, which can lead to damage of system components.
• All systems must be thoroughly drained and flushed out
using, for example, Sentinel X300 or X400 or Fernox F3.
They should be used following the flushing agent
manufacturer’s instructions.
• System additives - corrosion inhibitors and flushing
agents/descalers should comply to BS7593 requirements,
e.g. Sentinel X100 and Fernox MB-1 which should be used
following the inhibitor manufacturer’s instructions.
• Full instructions are supplied with the products, for
further information contact Sentinel (0800 389 4670) or
Fernox (0870 870 0362)
Failure to flush and add inhibitor to the system will
invalidate the appliance warranty.
• It is important to check the inhibitor concentration after
installation, system modification and at every service in
accordance with the manufacturer’s instructions. (Test kits
are available from inhibitor stockists.)
• For information or advice regarding any of the above
contact Technical Enquiries.
Boiler
Fig. 9
Copper
0.5m
Copper
1m
Copper
0.5m
Flow
Return
6.0System Details
6.3Pipework
1. The sizes of flow and return pipes from the boiler
should be determined by normal methods, according to
the requirements of the system. The connection on the
boiler are 22mm.
Fig. 10
Automatic Air
Boiler
500mm
45°
1000mm
Min
150mm
Max
Boiler
Return
Typical Low Head Installation
500mm
45°
Vent
1000mm
Min
15mm
Cold
Feed
15mm
Cold
Feed
150mm
Max
22mm
Open Vent
400mm
Min Head
Pump
22mm
Open Vent
400mm
Min Head
Return
Pump
Flow
Flow
2. A 20 °C (36°F) drop in temperature across the system
is recommended for condensing boilers. Existing radiators
may be oversized and so allow this, but where radiator
sizing is marginal it may be advisable to retain a system
temperature drop of 11°C (20°F).
NOTE: On Solo 30 HE
A models 28mm pipe should
be used to connect to the boiler flow and return.
3. In systems using non-metallic pipework it is necessary
to use copper pipe for the boiler Flow and Return. The
copper must extend at least 1 metre from the boiler and
include any branches (Fig. 9).
6.4Low Head Installation
1. Using a close couple arrangement the minimum head is
as shown in the diagrams (Figs. 10 & 11) subject to the
following conditions:
a) The pump being adjusted to give a 20°C drop across
the boiler.
b) The pump must be fitted on the flow.
c) The pump must be fitted in accordance with the
pump manufacturer's instructions.
d) The open vent pipe must be taken up from a tee in a
horizontal section of the flow pipe.
An alternative Low Head Installation (Fig. 12)
2. For heads below 400mm then a combined vent and
feed pipe may be connected. This must be a minimum of
22mm diameter. It is recommended that an air separator
is fitted when using a combined feed and vent pipe.
1. Providing that the cold feed and open vent pipe are
positioned correctly (e.g. the system is not prone to
pumping over, air entrainment etc.) the pump may be
fitted on the primary return pipe.
Flow
13
Y Plan
Diverter
Valve
Cylinder
Stat
Room
Stat
Boiler
Pump
Timer
230V
50Hz
LNE
L
N
CH on
HW on
HW off
LNE
LN P/FE
b
g/y
w
o
gr
1
C2
g/y
S Plan
Valve
Cylinder
Stat
Room
Stat
Boiler
Pump
Timer
230V
50Hz
LNE
L
N
CH on
HW on
LNE
LN P/FE
Motor
S Plan
Valve
Motor
o
o
gr
b
g/y
b
gr
br
br
Y Plan
Diverter
Valve
Cylinder
Stat
Boiler
Pump
Timer
230V
50Hz
LNE
L
N
CH on
HW on
HW off
LNE
LN P/FE
b
g/y
o
gr
1
C2
w
g/y
S Plan
Valve
Cylinder
Stat
Boiler
Pump
Timer
230V
50Hz
LNE
L
N
CH on
HW on
LNE
LN P/FE
Motor
S Plan
Valve
Motor
o
o
gr
b
g/y
b
gr
br
br
Y Plan, Room Thermostat System, CH Interlocked By Room Thermostat
At least the Radiator(s) near the Room Thermostat not TRV’d
Pump run from Switched Live
By-pass permitted but not required for Part L1 compliance
Key to colours
b-Blue
br - Brown
w- White
o- Orange
gr- Grey
g/y - Green/Yellow
6.0System Details
6.5System Controls
This boiler does not require a bypass.
This boiler does not require a permanent live.
The pump only needs wiring directly to the boiler for
fully TRV’d systems.
1. To comply with Part L1 of the Building Regulations the
heating system into which the boiler is installed should
include the following:
a) zone controls
b) timing controls
c) boiler control interlocks
2. Such a system needs to be fully pumped and must
provide independent temperature and time control to
both the heating and hot water circuits and have a boiler
interlock.
S Plan, Room Thermostat System, CH Interlocked By Room Thermostat
At least the Radiator(s) near the Room Thermostat not TRV’d
Pump run from Switched Live
By-pass permitted but not required for Part L1 compliance
3. The boiler should be controlled so that it operates on
demand only. Where it is proposed to effect control by
thermostatic radiator valves, a room thermostat (or
other device such as a flow switch - a flow switch is
integral to this boiler) should also be provided to switch
off the boiler when there is no demand for heating or
hot water.
4. The interlock for the CH circuit can be provided by
either a Room Thermostat or a fully TRV’d system with
the pump wired back to the boiler without a bypass.
Connection diagrams for both options for Y and S plan
systems are shown.
Y Plan, Fully TRV’d System, CH Interlocked By Boiler Flow Switch
Room Thermostat should not be fitted
Pump must be run from Boiler P/F connection for Part L1 compliance
By-pass not permitted (must be valved off) for Part L1 compliance
S Plan, Fully TRV’d System, CH Interlocked By Boiler Flow Switch
Room Thermostat should not be fitted
Pump must be run from Boiler P/F connection for Part L1 compliance
By-pass not permitted (must be valved off) for Part L1 compliance
Table. 1
Safety
Valve
Fig. 13
Air
Vent
Pressure
Gauge
Boiler
System Drains at
Low Point
Filling
Point
Pump
Expansion
Vessel
Max Boiler Flow
Temp = 82° C
Method of determining minimum valve of
expansion vessel volume for sealed systems
using Baxi Boilers
Vessel Charge
Pressure (Bar)
Initial System
Pressure (Bar)
0.5
0.5
1.0
1.5
2.0
1.0
1.0
1.5
2.0
1.5
Example :-
System Volume = 75 litres
1.5
2.0
Vessel Charge Pressure = 1.0 bar
Initial System Pressure = 1.5 bar
Then :-
75 x 0.152 = 11.4 litres
Expansion Vessel Volume
NOTE
Where a vessel of the calculated size is not obtainable then
the next available larger size should be used.
3 Litre
Top Up Bottle
(if required)
Radiator
Circuit
Multiply Total
Water Content Of
System By (Litres)
0.067
0.112
0.207
0.441
0.087
0.152
0.330
0.125
0.265
6.0System Details
6.7Sealed Systems (Fig. 13)
1. SAFETY VALVE - A safety valve complying with the
requirements of BS 6750 Part 1 must be fitted close to
the boiler on the flow pipe by means of a horizontal or
vertically upward connection with no intervening valve
or restrictions and should be positioned to facilitate
testing. The valve should be pre-set and non-adjustable
to operate at a pressure of 3 bar (45 Ibf/in
arranged to discharge any water or steam through a pipe
to a safe outlet position.
2. PRESSURE GAUGE - A pressure gauge of minimum
range 0-4 bar (0-60 Ibf/in
2
) with a fill pressure indicator
must be fitted to the system, preferably at the same
point as the expansion vessel in an easily visible position.
3. EXPANSION VESSEL - An expansion vessel
complying with the requirements of BS 4814 must be
fitted to the system by means of a connection close to
the inlet side of the circulating pump in accordance with
the manufacturers instructions, the connecting pipe being
unrestricted and not less than 15mm (
The volume of the vessel should be suitable for the
system water content and the nitrogen or air charge
pressure should not be less than the system static head
(See Table. 1).
Further details of sealed system design can be obtained
from BS 5449 and the British Gas publication entitled
'Specifications for Domestic Wet Central Heating
Systems'.
4. FILLING POINT - A filling point connection on the
central heating return pipework must be provided to
facilitate initial filling and pressurising and also any
subsequent water loss replacement / refilling. The sealed
primary circuits may be filled or replenished by means of
a temporary connection between the primary circuit and
a supply pipe provided a ‘Listed’ double check valve or
some other no less effective backflow prevention device
is permanently connected at the inlet to the circuit and
the temporary connection is removed after use. The
filling method adopted must be in accordance with all
relevant water supply regulations and use approved
equipment.
Your attention is drawn to, for GB: Guidance G24.2 and
recommendation R24.2 of the Water Regulations Guide.
for IE: the current edition of I.S. 813 “Domestic Gas
Installations”.
5. MAKE UP SYSTEM - A method of replacing water
lost from the system should be provided either by
means of a make up vessel of not more than 3 litres (5
pints) capacity, mounted above the highest point of the
system, or by re-pressurisation of the system.
6. VENTING - A method of venting the system during
filling and commissioning must be provided by fitting
automatic air vents or by venting manually.
7. HOT WATER STORAGE - The hot water storage
vessel must be of the indirect coil type. All components
used in the system must be suitable for operation at
110°C (230°F) and at the pressure allowed by the safety
valve.
CH
Return
15
Zone 1
Zone 2
Window
Recess
Zone 2
7.0Site Requirements
7.1Location
NOTE: Due to the high efficiency of the boiler a
plume of water vapour will be discharged from the
flue. This should be taken into account when siting
the flue terminal.
1. The boiler may be fitted to any suitable wall with the
flue passing through an outside wall or roof and
discharging to atmosphere in a position permitting
satisfactory removal of combustion products and
providing an adequate air supply. The boiler should be
fitted within the building unless otherwise protected by a
suitable enclosure i.e. garage or outhouse. (The boiler
may be fitted inside a cupboard - see Section 7.2).
Fig. A
Zone 1
Zone 0
Zone 0
Window
Recess
Zone 2
Fig. B
0.6 m
In GB Only
Window Recess
Zone 2
Zone 2
0.6 m
In GB Only
2.25 m
Ceiling
Outside Zones
2. If the boiler is sited in an unheated enclosure then it is
recommended to incorporate an appropriate device for
frost protection in the system controls.
3. If the boiler is fitted in a room containing a bath or
shower it MUST NOT BE fitted in zone 0, 1 or 2, ONLY
within the shaded area (Figs. A & B shows zone
dimensions for a bathtub. For other examples refer to
the Current I.E.E. Wiring Regulations) reference must be
made to the relevant requirements.
In GB this is the current I.E.E. Wiring Regulations and
Building Regulations.
In IE reference should be made to the current edition of
I.S. 813 “Domestic Gas Installations” and the current
ETCI rules.
4. If the boiler is to be fitted into a building of timber
frame construction then reference must be made to the
current edition of Institute of Gas Engineers Publication
IGE/UP/7 (Gas Installations in Timber Framed Housing).
7.2Ventilation of Compartments
1. Where the boiler is installed in a cupboard or
compartment, no air vents are required for cooling
purposes providing that the minimum dimensions below
are maintained.
Sides15mm
Top200mm
Bottom50mm
Front30mm
2. If the boiler is installed in a smaller cupboard or
compartment it must be ventilated according to
BS 5440 Part 2 and the minimum clearances given in
section 4.0 “Technical Data” maintained.
3. Any compartment should be large enough to house
the boiler only.
NOTE: The ventilation label on the front of the outer
case MUST NOT BE REMOVED when the appliance is
installed in a compartment or cupboard.
5mm Min
390mm
5mm Min
7.0Site Requirements
Fig. 15
200mm
600mm
50mm
7.3Clearances (Figs. 15 &16)
1. A flat vertical area is required for the installation of the
boiler.
2. These dimensions include the necessary clearances
around the boiler for case removal, spanner access and air
movement. Additional clearances may be required for the
passage of pipes around local obstructions such as joists
running parallel to the front face of the boiler.
3. For unventilated compartments see Section 7.2.
7.4Gas Supply
1. The gas installation should be in accordance with the
relevant standards. In GB this is BS 6891. In IE this is the
current edition of I.S. 813 “Domestic Gas Installations”.
2. The connection to the appliance is a
1
/2in BSPF.
3. Ensure that the pipework from the meter to the
appliance is of adequate size to ensure correct operation.
Do not use pipes of a smaller diameter than the boiler
gas connection.
Fig. 16
500mm
For Servicing
Purposes
5mm
In Operation
285mm
At least
1.5°
7.5Electrical Supply
1. External wiring must be correctly earthed, polarised and
in accordance with relevant regulations/rules. In GB this is
the current I.E.E. Wiring Regulations. In IE reference
should be made to the current edition of ETCI rules.
2. The mains supply is 230V ~ 50Hz fused at 3A.
NOTE: “The method of connection to the electricity
supply must facilitate complete electrical isolation of the
appliance”.
Note! There is no method of isolating the boiler, at the
user interface.
Connection may be via a fused double-pole isolator with a
contact separation of at least 3mm in all poles and servicing
the boiler and system controls only.
WARNING: The PCB Control and Fan
Assembly are 325 Vdc. Isolate at supply
before access.
Examples are shown of the following methods of termination:i) to an internal soil & vent pipe
ii) via an internal discharge branch (e.g. sink waste) downstream of the trap
iii) to a drain or gully
iv) to a purpose made soakaway
v) pumped into an internal discharge branch (e.g. sink waste) downstream of the trap
vi) pumped into an external soil & vent pipe
vii) to a drain or gully with extended external run & trace heating
It is strongly recommended to discharge internally into the household
drainage system. If connecting to a rain water drain, that drain MUST
discharge into a foul drain.
Insulation
Pipe must terminate above
water level but below
surrounding surface. Cut
end at 45°
*It is NOT RECOMMENDED
to connect upstream of the
sink or other waste water
receptacle !
50mm per metre of pipe run
2.5° Minimum fall
Boiler
Sink
Boiler
50mm per metre of pipe run
2.5° Minimum fall
iii) Termination to a drain or gully
50mm per metre of pipe run
2.5° Minimum fall
21.5mm
i) Termination to an internal soil and
vent pipe
450mm min*
ii) External termination via internal discharge branch
32mm
*450mm is applicable to properties
up to 3 storeys.
For multi-storey building installations
consult BS 6798.
e.g sink waste - downstream*
Pipe must terminate above
water level but below
surrounding surface. Cut
end at 45°
7.0Site Requirements
7.6Condensate Drain
FAILURE TO INSTALL THE CONDENSATE DISCHARGE
PIPEWORK CORRECTLY WILL AFFECT THE RELIABLE
OPERATION OF THE BOILER.
CAREFUL CONSIDERATION MUST BE GIVEN TO THE
POSSIBILITY OF THE PIPEWORK BEING SUBJECT TO
FREEZING CONDITIONS AND APPROPRIATE
MEASURES TAKEN TO PREVENT BLOCKAGE.
CORRECT INSTALLATION IN ACCORDANCE WITH
THIS SECTION WILL CONSIDERABLY MINIMISE THE
LIKELIHOOD OF BLOCKAGE AND SUBSEQUENT
BOILER LOCK-OUT.
A CONDENSATE DISCHARGE PUMP AND PIPE ‘TRACE
HEATING’ ARE AVAILABLE AS ACCESSORIES - see
paragraphs 7.7.12 to 7.715 for further details.
The condensate discharge pipe MUST NOT RISE at any
point along its length. There MUST be a fall of AT LEAST
2.5° (50mm per metre) along the entire run EXCEPT when
employing a suitable condensate pump in basement and
cellar or similar applications.
The boiler condensate trap incorporates a seal of 75mm,
therefore it is unnecessary to install an air break and trap in
the discharge pipework.
3
1. The condensate outlet will accept 21.5mm (
overflow pipe. It is strongly recommended that this dischargesinternally into the household drainage system.
Where this is not possible, discharge into an outside drain is
permissible providing every possible precaution is taken to
prevent freezing.
2. Ensure the discharge of condensate complies with any
national or local regulations in force. BS 6798 & Part H1 of the
Building Regulations give further detailed guidance.
3. The discharge pipe should be run in a proprietary drain pipe
material e.g. PVC, PVC-U, ABS, PVC-C or PP.
4. Metal pipework is NOT suitable for use in condensate
discharge systems.
5. The pipe should be a minimum of 21.5mm diameter and
must be supported using suitably spaced clips of the correct
design to prevent sagging.
6. It is advisable that the full length of condensate pipe is run
Further specific requirements for soakaway
design are referred to in BS 6798.
50mm per metre of pipe run
2.5° Minimum fall
500mm min
Holes in the soak-away must
face away from the building
7. Internal runs greater than 3 metres or runs in cold areas
should use 32mm waste pipe.
8. External runs MUST be a MINIMUM of 32mm and fully
insulated with material suitable for external use.
9. If the boiler is fitted in an unheated location the entire
condensate discharge pipe should be treated as an external run
and sized and insulated accordingly.
10. In all cases discharge pipe must be installed to aid disposal of
the condensate. To reduce the risk of condensate being
trapped, as few bends and fittings as possible should be used
and any burrs on cut pipe removed.
11. When discharging condensate into a soil stack or waste pipe
the effects of existing plumbing must be considered. If soil pipes
or waste pipes are subjected to internal pressure fluctuations
when WC's are flushed or sinks emptied then back-pressure
may force water out of the boiler trap and cause appliance
lockout.
Loading...
+ 42 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.