Baxi Solo 2 RS Quick Start Manual

Please leave these Instructions with the User.
Baxi Solo 2 RS Range
Wall Mounted Room Sealed
Gas Fired Central Heating Boilers
Installation and Servicing Instructions
2
Baxi Solo 2 60 RS
G.C.No. 41 077 79
Baxi Solo 2 50 RS
G.C.No. 41 077 78
Baxi Solo 2 40 RS
G.C.No. 41 077 77
Baxi Solo 2 30 RS
G.C.No. 41 077 76
Baxi UK Limited is one of the leading manufacturers of domestic heating products in the U.K.
Our first priority is to give a high quality service to our customers. Quality is built into every Baxi product ­products which fulfil the demands and needs of customers, offering choice, efficiency and reliability.
To keep ahead of changing trends, we have made a commitment to develop new ideas using the latest technology - with the aim of continuing to make the products that customers want to buy.
Baxi is also the largest manufacturing partnership in the country. Everyone who works at the company has a commitment to quality because, as shareholders, we know that satisfied customers mean continued success.
We hope you get a satisfactory service from Baxi. If not, please let us know.
3
Baxi is a BS-EN ISO 9001 Accredited Company
CONTENTS
Introduction Technical Data System Details
(and By-pass Requirements)
Site Requirement
Installation
Commissioning the Appliance Fitting the Outer Case Overheat Cut-Off Device Annual Servicing
Changing Components
Fault Finding Short Parts List
PAGE 5
PAGE 6 - 7
PAGE 8 - 11
Water Circulating Systems System Controls Pipework Fully Pumped, Open Vented Systems Low Head Installation Sealed Systems Gravity Systems Hydraulic Charts
PAGE 12 - 14
Location Clearances Flue Position Flue Dimensions Ventilation of Compartments Gas Supply Electrical Supply
PAGE 15 - 25
Initial Preparation Flue Preparation Fitting the Wall Mounting Plate Fitting the Flue Duct Terminal Guard Fitting a Terminal Guard Fitting the Boiler Water Connections Pipe Routes Fully Pumped System Sealed System Gravity Hot Water System Gas Connection Electrical Supply
PAGE 26 - 27
PAGE 28
PAGE 29
PAGE 30 - 32
Dismantling the Boiler Cleaning the Burner/Injectors Cleaning the Combustion Box
PAGE 33 - 40
Eco Interrupter Leads Piezo Igniter Solenoid Operator Thermocouple Spark Electrode & Lead Pilot Injector Pilot Bracket & Gasket Overheat Thermostat Main Thermostat Pump Overrun Timer Removal of Combustion Chamber Door Burner and Injectors Gas Valve Insulation Panels
PAGE 41
PAGE 42
4
INTRODUCTION
Description
The Baxi Solo 2 RS is a wall mounted gas
fired room sealed natural draught central heating boiler with range rated outputs as
shown in the table below.
Each appliance is preset at its MAXIMUM
heat input rating and is designed for use on NATURAL GAS only. They are suitable for gravity domestic hot water with pumped
central heating, fully pumped open vented central heating and domestic hot water and sealed systems.
The standard flue assembly supplied is suitable
for wall thicknesses between 100mm (4in) and 356mm (14in). An optional flue extension kit is available for walls of 356mm (14in) and 610mm (24in) thickness.
The appliance data badge is fitted to the combustion chamber door above the gas valve.
Installation
The installation must be carried out by a CORGI Registered Installer and be in accordance with the relevant requirements of GAS SAFETY (Installation and Use) REGULATIONS, the BUILDING REGULATIONS (Scotland) (Consolidation), the
LOCAL BUILDING REGULATIONS, the current I.E.E. WIRING REGULATIONS and the bye laws of the
LOCAL WATER UNDERTAKING. (Where no specific instruction is given reference should be made to the relevant BRITISH STANDARD CODES OF PRACTICE.)
Important Information
This product contains Refractory Ceramic Fibres (R.C.F.) which are man-made vitreous silicate fibres. Excessive exposure to these materials may cause temporary irritation to eyes, skin and respiratory tract. Care must be taken when handling these articles to ensure the release of dust or fibres is kept to a minimum. To ensure that the release of fibres from these articles is kept to a minimum, during installation and servicing it is recommended that a H.E.P.A. filtered vacuum is used to remove any dust, soot or other debris accumulated in and around the appliance. This should be performed before and after working on the installation. It is recommended that any replaced item(s) are not broken up but sealed within heavy duty polythene bags and clearly labelled “R.C.F. waste”. This is not classified as “hazardous waste” and may be disposed of at a tipping site licensed for the disposal of industrial waste. Protective clothing is not required when handling these articles but it is recommended that gloves are worn and the normal hygiene rules of not smoking, eating or drinking in the work area are followed and always wash hands before eating or drinking.
HEAT OUTPUT
Model Min Max
30 6.15kW (21,000 Btu/h) 8.79kW (30,000 Btu/h) 40 9.09kW (31,000 Btu/h) 11.72kW (40,000 Btu/h) 50 12.02kW (41,000 Btu/h) 14.65kW (50,000 Btu/h) 60 14.95kW (51,000 Btu/h) 17.58kW (60,000 Btu/h)
5
B.S. Codes of Practice
STANDARD SCOPE
BS 6891 Gas Installation. BS 5546 Installation of hot water supplies
for domestic purposes. BS 5449 Part 1 Forced circulation hot water systems. BS 6798 Installation of gas fired hot water
boilers. BS 5440 Part 1 Flues. BS 5440 Part 2 Air Supply.
WARNING
The addition of anything that may interfere with the normal operation of the appliance (e.g. FLUE DAMPERS,ECONOMISERS etc) without the express written permission of BAXI could invalidate the appliance warranty and infringe the GAS SAFETY (Installation and Use) REGULATIONS.
“Benchmark” Log Book
As part of the industry-wide Benchmark initiative all Baxi boilers now include an Installation, Commissioning and Service Record Log Book. Please read the Log Book carefully and complete all sections relevant to the appliance and installation. These include sections on the type of controls employed, flushing the system, burner operating pressure etc. The details of the Log Book will be required in the event of any warranty work. Also, there is a section to be completed at each subsequent regular service visit.
TECHNICAL DATA
30 RS
40 RS
Heat Input Max Min
kW 11.00 7.69
Btu/h 37,500 26,250
Heat Output Max Min
kW 8.79 6.15
Btu/h 30,000 21,000
Burner Pressure Max Min
mbar 15.4
+
0.5 8.0 +0.5
in wg 6.2 +0.2 3.2 +0.2
Gas Connection RC1/2(1/2in BSPT)
Electrical Supply 230V~50Hz
fused 3A
Controls on/off boiler thermostat with pilot/thermocouple cut out/overheat thermostat on fully pumped applications only
Heat Exchanger cast iron monobloc
Lifting Weight 37.3 kg (82.1 lbs)
Water Content 2.1 litres (0.46 gals)
Static Head Max Min
metres 30 1
feet 100 3.25
Low Head Min 0.15m (6in)
System Design gravity hot water fully
pumped open vented and sealed systems
Connections 2 x 22mm and a kit for
gravity
Gas Rate (after 10 mins) 1.05m
3
/h (37.0ft3/h)
Outercase Height 600mm Dimensions
Width 420mm
Depth 287mm
Flue Terminal Height 208mm Dimensions
Width 293mm
Depth 173mm
Heat Input Max Min
kW 14.65 11.36
Btu/h 50,000 38,750
Heat Output Max Min
kW 11.72 9.09
Btu/h 40,000 31,000
Burner Pressure Max Min
mbar 16.3
+
0.5 10.3 +0.5
in wg 6.5 +0.2 4.1 +0.2
Gas Connection RC
1
/2(1/2in BSPT)
Electrical Supply 230V~50Hz
fused 3A
Controls on/off boiler thermostat with pilot/thermocouple cut out/overheat thermostat on fully pumped applications only
Heat Exchanger cast iron monobloc
Lifting Weight 37.3 kg (82.1 lbs)
Water Content 2.1 litres (0.46 gals)
Static Head Max Min
metres 30 1
feet 100 3.25
Low Head Min 0.15m (6in)
System Design gravity hot water fully
pumped open vented and sealed systems
Connections 2 x 22mm and a kit for
gravity
Gas Rate (after 10 mins) 1.40m
3
/h (49.3ft3/h)
Outercase Height 600mm Dimensions
Width 420mm
Depth 287mm
Flue Terminal Height 208mm Dimensions
Width 293mm
Depth 173mm
50
50
5
5
300
80
for
ravity
for
servicing
5
inside
cupboard
Clearances
50
50
5
5
300
80
for
ravity
for
servicing
5
inside
cupboard
Clearances
NOTE: On gravity applications a clearance of 80mm (31/8in) is required from the top panel
NOTE: On gravity applications a clearance of 80mm (3
1
/8in) is required from the top
panel
6
50 RS
60 RS
Heat Input Max Min
kW 18.32 15.02
Btu/h 62,500 51,250
Heat Output Max Min
kW 14.65 12.02
Btu/h 50,000 41,000
Burner Pressure Max Min
mbar 16.3
+
0.5 11.2 +0.5
in wg 6.5 +0.2 4.5 +0.2
Gas Connection RC1/2(1/2in BSPT)
Electrical Supply 230V~50Hz
fused 3A
Controls on/off boiler thermostat with pilot/thermocouple cut out/overheat thermostat on fully pumped applications only
Heat Exchanger cast iron monobloc
Lifting Weight 37.3 kg (82.1 lbs)
Water Content 2.1 litres (0.46 gals)
Static Head Max Min
metres 30 1
feet 100 3.25
Low Head Min 0.15m (6in)
System Design gravity hot water fully
pumped open vented and sealed systems
Connections 2 x 22mm and a kit for
gravity
Gas Rate (after 10 mins) 1.75m
3
/h (61.6ft3/h)
Outercase Height 600mm Dimensions
Width 420mm
Depth 287mm
Flue Terminal Height 208mm Dimensions
Width 293mm
Depth 173mm
Heat Input Max Min
kW 21.98 18.68
Btu/h 75,000 63,750
Heat Output Max Min
kW 17.58 14.95
Btu/h 60,000 51,000
Burner Pressure Max Min
mbar 16.0
+
0.5 12.0 +0.5
in wg 6.4
+
0.2 4.8 +0.2
Gas Connection RC
1
/2(1/2in BSPT)
Electrical Supply 230V~50Hz
fused 3A
Controls on/off boiler thermostat with pilot/thermocouple cut out/overheat thermostat on fully pumped applications only
Heat Exchanger cast iron monobloc
Lifting Weight 37.3 kg (82.1 lbs)
Water Content 2.1 litres (0.46 gals)
Static Head Max Min
metres 30 1
feet 100 3.25
Low Head Min 0.15m (6in)
System Design gravity hot water fully
pumped open vented and sealed systems
Connections 2 x 22mm and a kit for
gravity
Gas Rate (after 10 mins) 2.09m
3
/h (74.0ft3/h)
Outercase Height 600mm Dimensions
Width 420mm
Depth 287mm
Flue Terminal Height 208mm Dimensions
Width 293mm
Depth 173mm
50
50
5
5
300
80
for
ravity
for
servicing
5
inside
cupboard
Clearances
50
50
5
5
300
80
for
ravity
for
servicing
5
inside
cupboard
Clearances
NOTE: On gravity applications a clearance of 80mm (31/8in) is required from the top panel
NOTE: On gravity applications a clearance of 80mm (3
1
/8in) is required from the top
panel
7
This system is unlikely to require a By-pass unless all radiators are thermostatically controlled
Water Circulating Systems
The appliance is suitable for use with fully pumped open vented systems (small bore and micro-bore), gravity domestic hot water with pumped central heating systems and sealed systems. The following conditions should be observed on all systems:
The static head must not exceed 30m (100ft) of
water.
The boiler must only be used with an indirect
cylinder.
Drain points should be fitted to the lowest points in
the system.
All electrical wiring, gas and water pipes must be installed in a way which would not restrict the servicing of the boiler.
Position isolating valves as close to circulating pump
as practicable.
For fuel economy and best boiler performance, the
system should be designed so that gravity circulation
does not take place in the heating system when the
pump is not running.
Treatment of Water Circulating Systems
For optimum performance after installation, this boiler and its
associated central heating system must be flushed in
accordance with the guidelines given in BS7593:1992
Treatment of water in domestic hot water central heating
systems”.
This must involve the use of a proprietry cleanser, such as
BetzDearborns Sentinel X300 or X400, or Fernoxs Superfloc. Full
instructions are supplied with the products but for immediate information please contact BetzDearborn on 0151 420 9563, or Fernox on 01799 550811. For long term protection against corrosion and scale, after flushing it is recommended that an inhibitor such as BetzDearborns Sentinel X100, or Fernoxs MB-1 or Copal is dosed in accordance with the guidelines given in BS7593:1992.
Failure to flush and add inhibitor to the system may invalidate the appliance warranty.
BYPASS REQUIREMENTS
The boiler is fitted with a pump overrun device which allows the removal of residual heat from the boiler. NOTE: The pump overrun will operate for approximately 3 minutes. The system design must therefore always provide an open circuit for water to circulate
between the boiler flow and return.
If a system has an open circuit a bypass is not required.
A system using a 3 port diverter valve does not normally require a bypass and therefore this system is recommended. The exception to this is where all radiators in the system are fitted with thermostatic valves, in which case a bypass would be required. However, if one radiator in such a system was fitted with 2 lockshield valves a bypass would not be required.
A system controlled by non-electrical valves e.g. mechanical thermostatic control valves both on the radiators and the hot water circuit and systems using twin zone valves (e.g. Honeywell 'S' Plan) will require a bypass.
The bypass circuit can be:­A) A minimum of 9 metres of 22mm pipe (measured between the boiler flow and return connections). It should be fitted with a lockshield valve opened at least 1 full turn to give a minimum flow rate of 8 litres/min (1.8 gal/min).
B) A radiator fitted with lockshield valves. The radiator output should be a minimum of 800 watts (2,700 Btu/h). Typically a convector type radiator with an area of 3750 cm2(4ft2) is adequate.
C) By including an automatic bypass valve in the system (see diagram).
D) Any circuit that provides the same operating conditions as option A or option B.
Radiator Circuit
Examples of Open Circuits
By-pass Loops
SYSTEM DETAILS
(and By-pass Requirements)
Air Vent
8
A By-pass is required with this system
Typical Systems Arrangement
B
F
R
B
C
C
A
A
Flow from boiler
Boiler
Pump
Valve
A = D. H. W. Zone valve B = C. H. Zone valve C = Automatic Bypass valve
Bypass length = A + B + C
Bypass Incorporating Automatic Valve
Bypass Length
Pump
Boiler
Optional Bypass
Fully Pumped System
Air Vent
Twin Zone Valve System
Radiator Circuit
Air Vent
3 Port Diverter Valve System
Radiator Circuit
Radiator Circuit
Typical Low Head Installation
Alternative Layout
Alternative Low Head Installation
9
System Controls
For optimum operating conditions, the heating system into which the boiler is installed should include a control system.
Such a system will comprise of timer control and a separate room or cylinder thermostat as appropriate.
The boiler should be controlled so that it operates on demand only.
Operation of the system under control of the boiler thermostat only, does not produce the best results.
Pipework
The sizes of flow and return pipes from the boiler should be determined by normal methods, according to the requirements of the system.
It is recommended that the system is designed for an 11 °C (20°F) drop in temperature across the system.
In systems using non-metallic pipework it is necessary to use copper pipe for the boiler Flow and Return. The copper must extend at least 1 metre from the boiler and include any branches. The copper pipe must not be insulated.
Fully Pumped, Open Vented Systems
Low Head Installation
Using a close couple arrangement the minimum head is as shown in the diagram, subject to the following conditions:
1) The correct heat input.
2) The pump being adjusted to give an 11oC drop across the boiler.
3) The pump must be fitted on the flow.
4) The pump must be fitted in accordance with the
pump manufacturer's instructions.
5) The open vent pipe must be taken up from a tee
in a horizontal section of the flow pipe.
Alternative Low Head Installation for all Solo 2 RS
If less height is available then a combined vent and feed pipe may be connected. This must be a minimum of 22mm diameter. It is recommended that an air separator is fitted when using a combined feed and vent pipe.
Boiler
Flow
Return
Copper
0.5m
Copper
1m
Copper
0.5m
Copper Pipe In Non-Metallic System
Boiler
Automatic Air Vent
500mm
45
1000mm
Min
150mm
Max
Return
o
15mm Cold Feed
22mm Open Vent
400mm Min Head
Pump
Flow
500mm
45
1000mm
Min
o
15mm Cold Feed
22mm Open Vent
400mm
Min Head
150mm
Max
Boiler
200mm
Min
Boiler
22mm Feed & Vent Pipe
Air
Separator
Pump
Return
Return
Flow
Pump
Flow
Initial System Pressure (Bar)
Vessel Charge Pressure (Bar)
Multiply Total Water Content Of System By (Litres
0.067
0.112
0.207
0.441
0.087
0.152
0.330
0.125
0.265
0.5
1.0
1.5
2.0
1.0
1.5
2.0
1.5
2.0
0.5
1.0
1.5
Example :-
Then :-
System Volume = 75 litres Vessel Charge Pressure = 1.0 bar Initial System Pressure = 1.5 bar 75 x 0.152 = 11.4 litres Expansion Vessel Volume
Method of determining minimum
value of expansion vessel volume for
sealed systems using Baxi Boilers
NOTE
Where a vessel of the calculated size is not
then the next available larger size should
Sealed Systems
SAFETY VALVE
A safety valve complying with the requirements of BS 6750 Part 1 must be fitted close to the boiler on the flow pipe by means of a horizontal or vertically upward connection with no intervening valve or restrictions and should be positioned to facilitate testing. The valve should be pre-set and non-adjustable to operate at a pressure of 3 bar (45 Ibf/in2). It must be arranged to discharge any water or steam through a pipe to a safe
outlet position.
PRESSURE GAUGE
A pressure gauge of minimum range 0-4 bar (0-
60 Ibf/in2) with a fill pressure indicator must be
fitted to the system, preferably at the same point as the expansion vessel in an easily visible position.
EXPANSION VESSEL
An expansion vessel complying with the
requirements of BS 4814 must be fitted to the
system by means of a connection close to the inlet
side of the circulating pump in accordance with the
manufacturers instructions, the connecting pipe being unrestricted and not less than 15mm (1/2in) nominal size. The volume of the vessel should be suitable for the system water content and the nitrogen or air charge pressure should not be less than the system static head.
Further details of sealed system design can be obtained from BS 5449: Part 1 and the British Gas publication entitled 'Specifications for Domestic Wet Central Heating Systems'.
FILLING POINT
A filling point and an approved stop valve to BS 1010 must be fitted at low level and the method used for filling the system should be approved by the local water undertaking. For further details see BS 6798.
MAKE UP SYSTEM
A method of replacing water lost from the system should be provided either by means of a make up vessel of not more than 3 litres (5 pints) capacity, mounted above the highest point of the system, or by pre-pressurisation of the system.
VENTING
A method of venting the system during filling and commissioning must be provided by fitting automatic air vents or by venting manually.
HOT WATER STORAGE
The hot water storage vessel must be of the indirect coil type. All components used in the system must be suitable for operation at 110OC (230OF) and at the pressure allowed by the safety valve.
Boiler
Safety Valve
System Drains at Low Point
Expansion Vessel
Pump
Pressure Gauge
Filling Point
Air Vent
3 Litre Top Up Bottle (If Required)
Radiator Circuit
Max Boiler Flow Temp = 82OC
10
n
e
Gravity Systems
When the boiler is to be installed to an existing or new gravity domestic hot water and pumped central heating
system, the following considerations should be given
to the design of the gravity domestic hot water flow
and return pipes.
The minimum circulating head should not be less
than 1m (3ft) with a maximum horizontal run of
3m (10ft) when using 28mm pipes. Smaller pipe
sizes and longer horizontal runs are acceptable with suitably increased circulating heads.
The system must be designed to prevent
reverse circulation.
Pipes should be laid to maximum fall avoiding
points of possible air lock.
If the domestic hot water temperature is controlled by a cylinder thermostat and zone valve, it is recommended that a bypass is installed in the gravity circuit. One method is to install a bathroom radiator, fitted with two lock shield valves. Mechanical valves which allow the boiler to operate when the valve is closed should not be used.
Note: If the above conditions cannot be met, then pumped primaries must be used.
See page 25 for wiring of boiler when installed with gravity hot water.
Hydraulic Charts
Boiler
Bathroom Radiator used as Gravity Circuit Bypass when a Zone Valve is used
m
11
Hydraulic Resistance Chart
For Gravity Systems - with injector wash
60 RS
(20)50
(16)40
(12)30
(8)20
(4)10
50 RS
40 RS
30 RS
Pressure Drop mbar (in wg)
0
4.5 9.0 13.5 18.0 22.5 (1) (2) (3) (4) (5)
Water Flow litres/min (gal/mi
(12)30
(8)20
(4)10
Pressure Drop
mbar (in wg)
Hydraulic Resistance Chart (For Fully Pumped Systems)
60 RS
50 RS
40 RS
30 RS
0
4.5 9.0 13.5 18.0 22.5 (1) (2) (3) (4) (5)
Water Flow litres/min (gal/
SITE REQUIREMENTS
Location
The appliance may be fitted to any suitable wall with the flue passing through an outside wall and discharging to atmosphere in a position permitting satisfactory removal of combustion products and providing an adequate air supply. The appliance should be fitted within the building unless other-wise protected by a suitable enclosure ie. garage or outhouse. The appliance may be fitted inside a cupboard provided that ventilation requirements and combustible material standards are adhered to.
If the appliance is fitted in a room containing a bath or shower reference must be made to the Current I.E.E. Wiring Regulations and Building Regulations. If the appliance is to be fitted into a building of timber frame construction then reference must be made to the current edition of Institute of British Gas Engineers Publication IGE/UP/7 (Gas Installations in Timber Framed Housing).
Recommendations for flues are given in BS 5440 Pt1.
Clearances
A flat vertical area is required for the installation of the
boiler measuring as shown. A space above
the boiler should also be left clear as
indicated by the dotted lines.
These dimensions include the necessary clearances around the appliance for case removal, spanner access and air movement. Additional clearances may
be required for the passage of pipes
around local obstructions such as joists
running parallel to the front face of the
appliance.
If fitted inside a cupboard the clearance of 300mm shown is only necessary when the cupboard door is open. A clearance of 5mm (3/16in) is required from the front of the casing when the door is closed.
NOTE: On gravity applications a clearance of 80mm (31/8 in) is required from the top panel.
Flue Position
The following guide lines indicate the general requirements for siting balanced flue terminals.
If the terminal is fitted within 1 metre (39in) of a plastic gutter, within 500mm (191/2in) of a painted eave or a painted gutter, an aluminium shield of at least 1 metre (39in) long should be fitted to the underside of the gutter or painted surface. An air space of 5mm (3/16in) should be left between shield and gutter.
If the terminal discharges onto a pathway or passageway, check that combustion products will not cause a nuisance and that the terminal will not obstruct the passageway.
If the outer surface of an outside wall is of combustible material, it should be protected by fitting a non­combustible plate so that it extends not less than 50mm (2in) around the terminal.
Aluminium Shield
600
420
50
50
5
5
300
12
Terminal Position with Minimum Distance (mm)
A Directly below an openable window or other
opening, e.g. an air brick. 300 B Below gutters, soil pipes or drain pipes. 300 C Below eaves. 300 D Below balconies or car port roof 600 E From vertical drain pipes and soil pipes. 75 F From internal or external corners. 600 G Above ground, roof or balcony level. 300 H From a surface facing a terminal. 600 I From a terminal facing a terminal. 600 J Vertically from a terminal on the same wall. 1500 K Horizontally from a terminal on the same wall. 300 L For an opening in a car port (e.g. door, window)
into a dwelling. 1200
WARNING
If a terminal is less than 2 metres (783/4in) above a balcony, above ground or above a flat roof to which
people have access then a suitable
terminal guard must be provided.
Flue Dimensions
Recommendations for flues are given in BS 5440:1.
The standard flue terminal supplied with the appliance is suitable for use with wall thickness between 100mm (4in) and 356mm (14in).
A flue terminal extension kit is available as an optional extra for wall thickness between 356mm (14in) and 610mm (24in) from the manufacturer. Quote appliance Model Nowhen ordering.
293
208
173
13
H,I
K
J
G
D
L
Likely positions requiring a flue terminal guard
D
E
B,C
G
A
F
A
G
D
F
Ventilation of Compartments
Where the appliance is installed in a cupboard or compartment, air vents are required (for cooling
purposes) in the cupboard or compartment at high and low level which may communicate with a room or direct to outside air.
Detailed recommendations for air supply are given in BS 5440: Part 2.
An existing cupboard or compartment may be used,
provided that it is modified for the purpose. Recommendations for air supplies and details of essential cupboard compartment design are given in BS 5440: Part 2.
NOTE: Both air vents must communicate with the same room or both be on the same wall to outside
air.
MINIMUM AIR VENT FREE AREA
Gas Supply
The gas installation should be in accordance with
BS 6891.
The connection on the appliance is RC1/
2
(1/2in BSPT internal) located at the bottom right hand side of the appliance.
Ensure that the pipework from the meter to the
appliance is of adequate size. Do not use pipes
of a smaller diameter than the appliance gas
connection.
Electrical Supply
External wiring must be correcty earthed, polarized and in accordance with CURRENT I.E.E. WIRING REGULATIONS.
The mains supply is 230V ~ 50Hz fused at 3A. NOTE: The method of connection to the electricity supply must facilitate complete electrical isolation of the appliance, preferably by the use of a fused three pin plug and unswitched shuttered socket outlet, both complying with the requirements of BS 1363. Alternatively, connection may be made via a fused double-pole isolator with a contact separation of a least 3mm in all poles and serving the appliance and system controls only.
Model
Position of Air from Air direct Air Vent Room from Outside
30
HIGH AND 99.0cm2FREE AREA 49.5cm2FREE AREA LOW LEVEL (15.35in2) (7.68in2)
40
HIGH AND 131.9cm2FREE AREA 66.0cm2FREE AREA LOW LEVEL (20.44in2) (10.22in2)
50
HIGH AND 164.9cm2FREE AREA 82.5cm2FREE AREA LOW LEVEL (25.56in2) (12.78in2)
60
HIGH AND 197.9cm2FREE AREA 99.0cm2FREE AREA LOW LEVEL (30.67in2) (15.34in2)
14
Loading...
+ 30 hidden pages