Baxi EcoBlue Heat Quick Start Manual

Page 1
United Kingdom
en
Installation and Service Manual
Gas Fired Wall Mounted Powered Flue Condensing Boiler
E
12 - 15 - 18 - 21 - 24
These instructions include the Benchmark Commissioning Checklist
and should be left with the user for safe keeping.
They must be read in conjunction with the Flue Installation Guide.
Page 2
1 Introduction
Model Range
Baxi EcoBlue 12 Heat
G.C.No 41 470 02
Baxi EcoBlue 15 Heat
o
G.C.N
41 470 03
Baxi EcoBlue 18 Heat
o
41 470 04
G.C.N
Baxi EcoBlue 21 Heat
o
G.C.N
41 470 05
Baxi EcoBlue 24 Heat
G.C.No 41 470 06
Building Regulations and the Benchmark Commissioning Checklist
Building Regulations (England & Wales) require notification of the
installation of a heating appliance to the relevant Local Authority
Building Control Department. This can be achieved via a
Competent Persons Self Certification Scheme as an option to
notifying the Local Authority directly.
The Health & Safety Executive operates the ‘Gas Safe Register’, a self-
certification scheme for gas heating appliances.
This company is a member of the Benchmark initiative and fully
supports the aims of the programme. Its aim is to improve the
standards of installation and commissioning of central heating systems
in the UK and to encourage the regular servicing of all central heating
systems to ensure safety and efficiency.
Building Regulations require that installations should comply with
manufacturer's instructions. It is therefore important that the
commissioning checklist is completed by the installer. The relevant
section of Building Regulations only relates to dwellings. Therefore the
checklist only applies if the appliance is being installed in a dwelling or
some related structure.
The flowchart opposite gives guidance for installers on the process
necessary to ensure compliance with Building Regulations.
The Benchmark Scheme
0086
Benchmark places responsibilities on both manufacturers and installers.
The purpose is to ensure that customers are provided with the correct
equipment for their needs, that it is installed, commissioned and
serviced in accordance with the manufacturer’s instructions by
competent persons and that it meets the requirements of the
appropriate Building Regulations. The Benchmark Checklist can be
used to demonstrate compliance with Building Regulations and should
be provided to the customer for future reference.
ISO 9001
FM 00866
© Baxi Heating UK Ltd 2014 All rights reserved. No part of this publication may be reproduced or transmitted in any form or by any means, or stored in any retrieval system of any nature (including in any database), in each case whether electronic, mechanical, recording or otherwise, without the prior written permission of the copyright owner, except for permitted fair dealing under Copyrights, Designs and Patents Act 1988.
Applications for the copyright owner’s permission to reproduce or make other use of any part of this publication should be made, giving details of the proposed use, to the following address:
Installers are required to carry out installation, commissioning and
servicing work in accordance with the Benchmark Code of Practice
which is available from the Heating and Hotwater Industry Council who
manage and promote the Scheme. Visit www.centralheating.co.uk for
more information.
The Company Secretary, Baxi Heating UK Limited, Brooks House, Coventry Road, Warwick. CV34 4LL
Full acknowledgement of author and source must be given.
WARNING: Any person who does any unauthorised act in relation to a copyright work may be liable to criminal prosecution and civil claims for damages.
You have just purchased one of our appliances and we thank you for the trust you have placed in our products. Please note that the product will provide good service for a longer period of time if it is regularly checked and maintained. Our customer support network is at your disposal at all times.
2 EcoBlue Heat 7212435 - 02 (08/14)
Page 3
Installer Notification Guidelines
Choose Building
Regulations Notification
Route
Installer Notification Guidelines
1
Competent Person's
Self Certification Scheme
Install and Commission this appliance to manufacturer's
instructions
Complete the
Benchmark Checklist
If you notify via the ‘Gas Safe
Register’, the register will issue
the Building Regulations
certificate on members’ behalf
Building Control
Contact your relevant Local
Authority Building Control
(LABC) who will arrange
an inspection or contact a government approved
inspector
Install and Commission this appliance to manufacturer's
instructions
Scheme Members only
Call ‘Gas Safe Register’ on:
0800 408 5577
or log onto:
www.gassaferegister.co.uk
within 10 days
You must ensure that the
certificate number issued by
the ‘Gas Safe Register’ is written
onto the Benchmark Checklist
‘Gas Safe Register’ will issue a
Building Regulations Compliance
Certificate to the property owner
and inform the relevant LABC
Complete the
Benchmark Checklist
LABC will record the data
and will issue a
certificate of compliance
7212435 - 02 (08/14) EcoBlue Heat 3
Page 4
Contents
Contents
1 Introduction
1.1 General
1.2 Additional Documentation
1.3 Symbols Used
1.4 Abbreviations
1.5 Extent of Liabilities
1.5.1 Manufacturer’s Liability
1.5.2 Installer’s Liability
1.6 Homologations
1.6.1 Certifications
1.6.2 Directives
1.6.3 Standards
2 Safety
2.1 General Safety Instructions
2.2 Recommendations
2.3 Specific Safety Instructions
2.3.1 Handling
3 Technical Specifications
3.1 Technical Data
3.2 Dimensions and Connections
3.3 Electrical Diagram
4 Description of the Product
4.1 General Description
4.2 Operating Principle
4.3 Main Components
4.4 Control Panel Description
4.4.1 User Interaction Controller
4.5 Standard Delivery
4.6 Accessories & Options
4.6.1 Optional Extras
7
7 8 8 8 9
9 10 10 10 10
11
12
12 12 13 13
14
14 15 16
17
17 18 19 20 20 21 21 21
5 Before Installation
5.1 Installation Regulations
5.2 Installation Requirements
5.2.1 Gas Supply
5.2.2 Electrical Supply
5.2.3 Hard Water Areas
5.2.4 Bypass
5.2.5 System Control
5.2.6 Treatment of Water Circulating Systems
5.2.7 System Details - General
5.2.8 Low Head Installation / Open
5.2.9 Sealed Systems Details
5.3 Choice of the Location
5.3.1 Location of the Appliance
5.3.2 Data Plate
5.3.3 Bath & Shower Rooms
5.3.4 Ventilation
5.3.5 Condensate Drain
5.3.6 Clearances - Access in Service
5.3.7 Flue / Chimney Location
5.3.8 Horizontal Flue / Chimney Systems
22
22 22 22 23 23 23 23 23 24 24 25 26 26 26 26 26 27 29 30 32
4 EcoBlue Heat 7212435 - 02 (08/14)
Page 5
Contents
5.3.9 Flue/Chimney Trim
5.3.10 Terminal Guard
5.3.11 Flue/Chimney Deflector
5.3.12 Flue/Chimney Accessories
5.4 Unpacking & Initial Preparation
5.4.1 Unpacking
5.4.2 Initial Preparation
5.4.3 Making the Water Connection
5.4.4 Filling the Condensate Trap
5.4.5 Connecting the Condensate Drain
5.4.6 Connecting the Gas Supply
6 Installation
6.1 Air Supply / Flue Gas Connections
6.1.1 Connecting the Top Flue
6.2 Electrical Connections
6.2.1 Electrical Connections of the Appliance
6.2.2 Connecting External Devices
6.3 Filling the System
6.4 Completing the Installation
6.4.1 Completion
7 Commissioning
7.1 General
7.2 Checklist before Commissioning
7.2.1 Preliminary Electrical Checks
7.2.2 Checks
7.3 Commissioning Procedure
7.4 Gas Settings
7.4.1 ‘Chimney Sweep’ Mode
7.4.2 ‘Chimney Sweep’ Mode - Combustion Check
7.5 Configuring the System
7.5.1 Check the Operational (Working) Gas Inlet Pressure & Gas Rate
7.6 Final Instructions
33 33 33 33 34 34 34 35 35 35 35
36
36 36 38 38 38 39 39 39
40
40 40 40 40 40 41 41 42 43 43 44
8 Operation
8.1 General
8.2 Start-Up
8.3 Shutdown
8.4 Use of the Control Panel
8.5 Frost Protection
9 Settings
9.1 Parameters
45
45 45 45 46 46
47
47
7212435 - 02 (08/14) EcoBlue Heat 5
Page 6
Contents
10 Maintenance
10.1 General
10.2 Standard Inspection & Maintenance Operation
10.3 Specific Maintenance Operation
10.3.1 Spark Ignition Electrode
10.3.2 Automatic Air Vent
10.3.3 Condensate Trap
10.3.4 Removal of Ducts
10.3.5 Pressure Switch (21 & 24 only)
10.3.6 Flow Temperature Sensor
10.3.7 Overheat Sensor
10.3.8 Return Temperature Sensor
10.3.9 Parameter Unit
10.3.10 Gas Valve
10.3.11 Control & Fan Assembly
10.3.12 User Interaction Controller
10.3.13 Setting the Gas Valve (CO
11 Troubleshooting
11.1 Error Codes - Auto Reset
11.2 Lockout Condition
12 Decommissioning Procedure
12.1 Decommissioning Procedure
Check)
2
48
48 49 50 50 50 50 51 51 52 52 52 52 53 54 54 55
56
56 57
58
58
13 Spare Parts
13.1 General
13.2 Spare Parts List
14 Notes
Benchmark Commissioning Checklist
59
59 59
60
62
6 EcoBlue Heat
7212435 - 02 (08/14)
Page 7
1 Introduction
1.1 General
Introduction 1
WARNING
Installation, repair and maintenance must only be carried out only by a competent person. This document is intended for use by competent persons,
All Gas Safe registered engineers carry an ID card with their licence number and a photograph. You can check your engineer is registered by telephoning 0800 408 5500 or online at www.gassaferegister.co.uk
This appliance must be installed in accordance with the manufacturer’s instructions and the regulations in force. If the appliance is sold or transferred, or if the owner moves leaving the appliance behind you should ensure that the manual is kept with the appliance for consultation by the new owner and their installer. Read the instructions fully before installing or using the appliance.
In GB, this must be carried out by a competent person as stated in the Gas Safety (Installation & Use) Regulations (as may be amended from time to time). Definition of competence: A person who works for a Gas Safe registered company and holding current certificates in the relevant ACS modules, is deemed competent.
In IE, this must be carried out by a competent person as stated in I.S. 813 “Domestic Gas Installations”.
The addition of anything that may interfere with the normal operation of the appliance without express written permission from the manufacturer or his agent could invalidate the appliance warranty. In GB this could also infringe the Gas Safety (Installation and Use) Regulations.
The appliance is designed as a boiler for use in residential domestic environments on a governed meter supply only. The selection of this boiler is entirely at the owner’s risk. If the appliance is used for purposes other than or in excess of these specifications, the manufacturer will not accept any liability for resulting loss, damage or injury.
The manufacturer will not accept any liability whatsoever for loss, damage or injury arising as a result of failure to observe the instructions for use, maintenance and installation of the appliance.
WARNING
Check the information on the data plate is compatible with local supply conditions.
7212435 - 02 (08/14) EcoBlue Heat 7
Page 8
1 Introduction
1.2 Additional Documentation
1.3 Symbols Used
These Installation & Service Instructions must be read in conjunction with the Flue Accessories & Fitting Guide supplied in the Literature Pack.
Various timers, external controls, flue accessories, etc. are available as optional extras. Full details are contained in the relevant sales literature.
In these instructions, various levels are employed to draw the user's attention to particular information. In so doing, we wish to safeguard the user's safety, prevent hazards and guarantee correct operation of the appliance. Each level is accompanied by a warning triangle
DANGER
1.4 Abbreviations
Risk of a dangerous situation causing serious physical injury.
WARNING
Risk of a dangerous situation causing slight physical injury.
CAUTION
Risk of material damage.
Signals important information .
Signals a referral to other instructions or other pages in the instructions.
8 EcoBlue Heat
DHW: Domestic hot water
CH: Central heating
GB: Great Britain
IE: Ireland
BS: British standard
HHIC: Heating and Hotwater Industry Council
CSM: Chimney Sweep Mode
PCB: Printed Circuit Board
PU: Parameter Unit
7212435 - 02 (08/14)
Page 9
1.5 Extent of Liabilities
Introduction 1
1.5.1 Manufacturer's Liability
Our products are manufactured in compliance with the requirements of the various european applicable Directives. They are therefore delivered with marking and all relevant documentation. In the interest of customers, we are continuously endeavouring to make improvements in product quality. All the specifications stated in this document are therefore subject to change without notice.
The manufacturer will not accept any liability for loss, damage or injury arising as a result of:-
Failure to abide by the instructions on using the appliance. Failure to regularly maintain the appliance, or faulty or inadequate maintenance of the appliance. Failure to abide by the instructions on installing the appliance.
This company declares that no substances harmful to health are contained in the appliance or used during appliance manufacture.
The appliance is suitable only for installation in GB and IE and should be installed in accordance with the rules in force, and only used in a suitably ventilated location.
In GB, the installation must be carried out by a Gas Safe Registered Installer. It must be carried out in accordance with the current and relevant requirements of legislation and guidance including the:-
• Gas Safety (Installation & Use) Regulations.
• The appropriate Building Regulations either The Building Regulations, The Building Regulations (Scotland), Building Regulations (Northern Ireland).
• The Water Fittings Regulations or Water Byelaws in Scotland.
• The Current I.E.E. Wiring Regulations.
Where no specific instructions are given, reference should be made to the relevant British Standard Code of Practice.
In IE, the installation must be carried out by a competent Person and installed in accordance with the current edition of I.S. 813 ‘Domestic Gas Installations’, the current Building Regulations and reference should be made to the current ETCI rules for electrical installation.
Prior to commissioning all systems must be thoroughly flushed and treated after installation with inhibitor (see section 5.2.6). Failure to do so will invalidate the appliance warranty.
Incorrect installation could invalidate the warranty and may lead to prosecution.
7212435 - 02 (08/14) EcoBlue Heat 9
Page 10
1 Introduction
1.5.2 Installer's Responsibility
The installer is responsible for the installation and initial start up of the appliance. The installer must adhere to the following:
Read and follow the instructions given in the manuals provided with the appliance. Carry out installation in compliance with the prevailing legislation and standards. Ensure the system is flushed and inhibitor added. Install the flue/chimney system correctly ensuring it is operational and complies with prevailing legislation and standards, regardless of location of the boiler’s installation. Only the installer should perform the initial start up and carry out any checks necessary. Explain the installation to the user. Complete the Benchmark Commissioning Checklist - this is a condition of the warranty ! Warn the user of the obligation to check the appliance and maintain it in good working order. Give all the instruction manuals to the user.
1.6 Homologations
1.6.1 Certifications
EC - Declaration of Conformity
Baxi Heating Uk Limited being the manufacturer / distributor within the European Economic Area of the following
Baxi EcoBlue Heat declare that the above is in conformity with the provisions of the Council Directive
2009/142 EC 92/42 EEC 2004/108 EC 2006/95 EC and has been subject to the following conformity procedures laid down in
Annex 2 - Article 3 of 2009/142 EC under the supervision of the British Standards Institution, a Notified Body authorized by the United Kingdom Competent Authority, and carrying the Notified Body Number 0086.
1.6.2 Directives
The boiler meets the requirements of Statutory Instrument “ The Boiler (Efficiency) Regulations 1993 N meet the requirements of Directive 92/42/EEC on the energy efficiency requirements for new hot water boilers fired with liquid or gaseous fuels:-
o
3083” and is deemed to
10 EcoBlue Heat
Type test for purpose of Regulation 5 certified by: Notified Body 0063.
Product/Production certified by: Notified Body 0086.
For GB/IE only.
7212435 - 02 (08/14)
Page 11
Introduction 1
1.6.3 Standards
Codes of Practice - refer to the most recent version
In GB the following Codes of Practice apply: Standard Scope BS 6891 Gas Installation. BS 5546 Installation of hot water supplies for domestic
purposes. BS EN 12828 Heating systems in buildings. BS EN 12831 Heating systems in buildings - Calculation of
load. BS EN 14336 Installation & commissioning of water based
heating systems. BS 6798 Installation of gas fired hot water boilers. BS 5440 Part 1 Flues. BS 5440 Part 2 Ventilation. BS 7074 Expansion vessels and ancillary equipment for
sealed water systems. BS 7593 Treatment of water in domestic hot water
central heating systems.
In IE the following Codes of Practice apply: Standard Scope I.S. 813 Domestic Gas Installations. The following standards give valuable additional information; BS 5546 Installation of hot water supplies for domestic
purposes. BS EN 12828 Heating systems in buildings. BS EN 12831 Heating systems in buildings - Calculation of
load. BS EN 14336 Installation & commissioning of water based
heating systems. BS 7074 Expansion vessels and ancillary equipment for
sealed water systems. BS 7593 Treatment of water in domestic hot water
central heating systems.
7212435 - 02 (08/14) EcoBlue Heat 11
Page 12
2 Safety
2 Safety
2.1 General Safety Instructions
2.2 Recommendations
DANGER
If you smell gas:
1. Turn off the gas supply at the meter
2. Open windows and doors in the hazardous area
3. Do not operate light switches
4. Do not operate any electrical equipment
5. Do not use a telephone in the hazardous area
6. Extinguish any naked flame and do not smoke
7. Warn any other occupants and vacate the premises
8. Telephone the National Gas Emergency Service on:- 0800 111 999
WARNING
Installation, repair and maintenance must be carried out by a Gas Safe Registered Engineer (in accordance with prevailing local and national regulations).
When working on the boiler, always disconnect the boiler from the mains and close the main gas inlet valve.
After maintenance or repair work, check the installation to ensure that there are no leaks.
CAUTION
The boiler should be protected from frost.
Only remove the casing for maintenance and repair operations. Replace the casing after maintenance and repair operations.
12 EcoBlue Heat
7212435 - 02 (08/14)
Page 13
2.3 Specific Safety Instructions
Safety 2
2.3.1 Handling
General
• The following advice should be adhered to, from when first handling the boiler to the final stages of installation, and also during maintenance.
• Most injuries as a result of inappropriate handling and lifting are to the back, but all other parts of the body are vulnerable, particularly shoulders, arms and hands. Health & Safety is the responsibility of EVERYONE.
• Before lifting the boiler, the circumstances of the installation must be assessed, please use appropriate manual handling techniques and equipment.
• Do not handle or lift unless you feel physically able.
• Wear appropriate Personal Protection Equipment e.g. protective gloves, safety footwear etc.
Preparation
• Co-ordinate movements - know where, and when, you are both going.
• Minimise the number of times needed to move the boiler ­ plan ahead.
• Always ensure when handling or lifting the route is clear and unobstructed. If possible avoid steps, wet or slippery surfaces, unlit areas etc. and take special care on ladders/into lofts.
Technique
• When handling or lifting always use safe techniques - keep your back straight, bend your knees. Don’t twist - move your feet, avoid bending forwards and sideways and keep the load as close to your body as possible.
• Where possible transport the boiler using a sack truck or other suitable trolley.
• Always grip the boiler firmly, and before lifting feel where the weight is concentrated to establish the centre of gravity, repositioning yourself as necessary. See the ‘Installation’ section of these instructions for recommended lift points.
Remember
• The circumstances of each installation are different. Always assess the risks associated with handling and lifting according to the individual conditions.
• If at any time when installing the boiler you feel that you may have injured yourself STOP !! DO NOT ‘work through’ the pain - you may cause further injury.
IF IN ANY DOUBT DO NOT HANDLE OR LIFT THE BOILER ­OBTAIN ADVICE OR ASSISTANCE BEFORE PROCEEDING !
7212435 - 02 (08/14) EcoBlue Heat 13
Page 14
3 Technical Specification
3 Technical Specifications
3.1 Technical Data
Appliance Type C13 C33 C
Appliance Category CAT I
2H
Heat Input (Gross) Max Min
12 model kW 14.88 8.59
15 model kW 18.32 8.59
18 model kW 21.75 8.59
21 model kW 24.04 8.59
24 model kW 28.62 8.59
Heat Output
(Non Condensing 70° C Mean Water Temp) Max Min
12 model kW 13 7.5
15 model kW 16 7.5
18 model kW 19 7.5
21 model kW 21 7.5
24 model kW 25 7.5
Max Gas Rate (Natural Gas - G20) (After 10 Mins)
m3/hr
12 model 1.42
15 model 1.75
18 model 2.07
21 model 2.29
24 model 2.73
Dynamic (nominal) Inlet Pressure
(Natural Gas - G20)
mbar 20
with a CV of 37.78 MJ/m
3
53
Horizontal Flue Terminal Diameter 100mm Dimensions Projection 125mm
Connections
Gas Supply - 22mm Central Heating Flow (compression fitting) - 22mm Central Heating Return (compression fitting) - 22mm Condensate Drain - for 21.5mm plastic waste pipe
Outercase Dimensions
Nox Class 5
Electrical Supply 230V~ 50Hz
(Appliance must be connected to an earthed supply)
Power Consumption Max Rate
12 model W 17 15 model W 20 18 model W 23 21 model W 25 24 model W 33
External Fuse Rating 3A
Overall Height Inc Flue Elbow - 790mm Casing Height - 625mm Casing Width - 370mm Casing Depth - 270mm
Clearances
Both Sides 5mm Min Above Casing (Top Flue) 19 0mm Min Above Casing (Rear Flue) 35mm Min Below Casing (in Cupboard) 35mm Min
Internal Fuse Rating (Terminal Strip)
Fuse 1.6T
Electrical Protection IPX4D
Water Content
litres 1.7
Static Head
max 25 metres Below Casing 120 mm Min Front (For Servicing) 800mm Min
Low Head 0.4m min
Front (In Operation) 5mm Min
See Section 5.3.6 for full details !
Weights
Packaged Boiler Carton 21.5 kg Installation Lift Weight 19.5 kg
System Detail
fully pumped open vented & sealed systems
Pressure Switch
12/15/18 Model - Not Fitted
CO/CO2Ratio Up to a maximum
21/24 Model - Fitted
of 0.004
Flow Temperature (adjustable)
30° C to 80° C (± 5° C)
Recommended System
NOTE: All data in this section are nominal
values and subject to normal production tolerances.
Temperature Drop
Condensing 20°C 36°F
SEDBUK 2009 Declaration
12 model - 89.2% 21 model - 89.2% 15 model - 89.2% 24 model - 89.1% 18 model - 89.2%
SEDBUK 2005 Declaration
12 model - 90.2% 21 model - 90.1% 15 model - 90.2% 24 model - 90% 18 model - 90.1%
This value is used in the UK Government’s Standard
Assessment Procedure (SAP) for energy rating of
dwellings. The test data from which it has been
calculated has been certified by 0063.
14 EcoBlue Heat
300
250
200
150
100
Pressure drop (mbar)
50
0
0.00.20.40.60.81.01.21.41.61.8
Pressure drop vs Flow
3
Flow (m
hr)
7212435 - 02 (08/14)
Page 15
3.2 Dimensions and Connections
Technical Specifications 3
At Least
1.5°
DIMENSIONS
E
G
A 625mm
For clearances see Section 5.3.6
B 270mm
C 370mm
D 116mm Ø Min.
A
E 165mm
F 155mm
G 110mm
B
360° Orientation
H 550mm
NOTE: There must be no part of the air duct (white tube) visible outside the property after
D
C
installation. The flue seal should fit neatly and effect a good seal.
Tube Ø 100mm
IMPORTANT: The 1.5° fall provided by the elbow is to allow condensate to run back to the boiler, for disposal through the condensate discharge pipe. When using extensions the fall along the flue system must be increased to 3°. Where extensions are used ensure the clearance above the top of the flue elbow (X) is as shown in the table below:-
F
Y
6m max
Flue length (Y)
up to 1m
1m - 2m
2m - 3m
3m - 4m
X
4m - 5m
5m - 6m
Clearance (X)
30mm
84mm
134mm
186mm
238mm
290mm
At Least 3°
7212435 - 02 (08/14) EcoBlue Heat 15
Page 16
3 Technical Specifications
3.3 Electrical Diagram
br
b
g/y
Safety Thermostat
User Interaction
Gas Valve
Controller
3.1 Technical Data (cont)
g/y
Electrode
r
L
Electrical Test Point
Mains
g/y
br
b
N
Pressure Switch (where fitted)
Not used
Return Sensor
b
Flow Sensor
r
Parameter
Unit
Loop Connector (where no pressure switch fitted)
16 EcoBlue Heat
Key To Wiring Colours
b - Blue
r - Red
br - Brown
g/y - Green/Yellow
All other wires are black
7212435 - 02 (08/14)
Page 17
4 Description of the Product
4.1 General Description
Description of the Product 4
1. The Baxi EcoBlue Heat Range are gas fired wall mounted powered flue condensing boilers.
2. The maximum output of the boiler is :-
12 model - 13 kW 15 model - 16 kW 18 model - 19 kW 21 model - 21 kW 24 model - 25 kW
Information Label
Slide Forward
Fig. 1
Data Label
3. The boiler modulates automatically to the system load up to the set output. It is designed for use on Natural Gas (G20) only.
4. The two illuminated User Interaction Controller push buttons provide information about the operating condition of the boiler.
5. The boiler is suitable for fully pumped open vented central heating and domestic hot water systems and sealed systems.
6. An information label giving details of the model, serial number and Gas Council number is situated on the front left underside of the outercase and is accessed by pulling forward gently (Fig. 1).
7. The boiler data label is positioned on the inside lower right­hand side of the boiler and can be seen when the outercase panel is removed (Fig. 1).
8. The boiler is intended to be installed in residential/domestic environments on a governed meter supply only.
9. The boiler must be installed with one of the purpose designed flues such as one of the standard telescopic flue kits detailed in the Flue Accessories & Fitting Guide.
All systems must be thoroughly cleansed, flushed and treated with inhibitor (see Section 5.2.6).
These Installation & Servicing Instructions MUST be read in conjunction with the Flue Accessories & Fitting Guide supplied in the Literature Pack.
7212435 - 02 (08/14) EcoBlue Heat 17
Page 18
3 Technical Specifications
4.2 Operating Principle
Mains On.
(CH or DHW demand)
1. Switched Live On: When the boiler switched live turns on the boiler, a 20 second check cycle takes place. If the flow temperature is less than the boiler set-point temperature the ignition cycle will start. Pre-purge, Ignition and Burner on.
Self test cycle for 20s
(output setting displayed)
NO
temperature less
than set point ?
10 second pre-purge
5 second ignition
Flame detected ?
Burner on
Modulate output
Flow
YES
YES
NO
5th ignition attempt ?
YES
Ignition Lockout
2. Fan Pre-Purge: The boiler has a 10 second pre-purge (Fan On, Spark Generator and Gas Valve off) before the start of the ignition sequence.
3. Ignition: The boiler has a 5 second ignition period (Fan, Spark Generator and Gas Valve on) and burner on occurs when a flame is detected. If a flame is not detected within the 5 second ignition period then 4 more ignition attempts are made. If a flame is not detected after the 5 ignition attempts the boiler goes to an ignition lock-out and an error code is displayed.
4. Burner on: After a successful ignition, Burner on occurs (Fan and Gas Valve on, Spark Generator off). The boiler flow temperature is controlled by varying the fan speed (and thereby the gas rate) to achieve the optimum boiler operation. If the boiler flow temperature exceeds the boiler set-point, the burner will turn off (Fan and Gas Valve off).
5. Overtemperature: If a boiler overtemperature event occurs (triggering the safety thermostat) the burner shuts down (Fan off and Gas Valve off). A locking signal is generated and an error code is displayed.
6. Lockout: If a lock-out error is displayed (Fan, Spark Generator and Gas Valve off) the boiler can only be reset by manually pressing the reset button. If 5 lock-outs are reset within a 1 hour period then boiler becomes inoperable. It is necessary to switch off the power supply to the boiler, and when reinstated the reset button pressed again to operate the appliance.
Flow temp or
rate of rise too
high ?
Burner Off
NO
Over Temp
Fault ?
YES
Lockout
18 EcoBlue Heat
Any lock-out errors that occur regularly will require further investigation and rectification.
Technical Enquiries: 0844 871 1555.
NO
YES
Mains Off
(Demand satisfied)
7212435 - 02 (08/14)
Page 19
4.3 Main Components
4
Description of the Product 4
1. Heat Exchanger
2. Combustion Control Unit
3. Condensate Trap
8
4. Exhaust Tube
5. Inlet Silencer
6. User Interaction Controller
10
7. Gas Cock
8. Air Pressure Switch (21 & 24 model only)
9. System Drain Cock
10. Air Vent
1
5
2
9
6
3
7
7212435 - 02 (08/14) EcoBlue Heat 19
Page 20
4 Description of the Product
4.4 Control Panel Description
4.4.1 USER INTERACTION CONTROLLER
(Control Panel) (Fig. 2)
Key to symbols
Heating Water Temperature
Sweep Key and Status Signals
Reset button and On/Off Signal
1. The User Interaction Controller has 2 illuminating push buttons which provide information about the operating condition of the boiler.
Fig. 2
2. The RESET button lights up green when the boiler has a demand for CH or DHW.
3. The button can flash in a range of colours and at different frequencies.
4. The User Interaction Controller also has one rotary knob. The rotary knob can be used to set the maximum flow
temperature of the heating water.
Maximum temperature is 80°C
5. The temperature on this rotary knob must be set to a higher
temperature than the cylinder thermostat to achieve the required hot water demand.
20 EcoBlue Heat
7212435 - 02 (08/14)
Page 21
4.5 Standard Delivery
4.6 Accessories & Options
Description of the Product 4
1. The pack contains:
Boiler Wall Fixing Bracket Copper Tail (Gas Connection) and Fibre Washer Power Lead Literature pack
• Installation & Servicing Manual (including ‘benchmark’)
• User Guide
• Flue Accessories & Fitting Guide
• Service Contract Leaflet
• Registration Card
• Envelope
• Fernox Leaflet
• Wall Template
4.6.1 Optional Extras
1. Various items are available as optional extras.
Flue Accessories (elbows, extensions, clamps etc.) (refer to the Flue Accessories & Fitting Guide supplied in the literature pack.) Remote relief valve kit 1M Condensate Drain Pipe ‘Trace Heating’ Element 2M Condensate Drain Pipe ‘Trace Heating’ Element 3M Condensate Drain Pipe ‘Trace Heating’ Element 5M Condensate Drain Pipe ‘Trace Heating’ Element
7212435 - 02 (08/14) EcoBlue Heat
21
Page 22
5 Before Installation
5 Before Installation
5.1 Installation Regulations
WARNING
Installation, repair and maintenance must only be carried out by a competent person. This document is intended for use by competent persons.
Installation must be carried out in accordance with the prevailing regulations, the codes of practice and the recommendations in these instructions.
Installation must also respect the following points:
This instruction manual and any other applicable documentation. Building Regulations. British Standards. 92/42/EEC Efficiency Directive. 2009/142/EC Gas Appliance Directive. 2006/95/EC Low Voltage Directive. 2004/108/EC Electromagnetic Compatibility Directive. Gas safety regulations. Water supply regulations.
5.2 Installation Requirements
5.2.1 Gas Supply
1. The gas installation should be in accordance with the relevant
standards. In GB this is BS 6891 (NG). In IE this is the current edition of I.S. 813 “Domestic Gas Installations”.
2. The connection to the appliance is a 22mm copper tail
located at the rear of the gas service cock.
3. Ensure that the pipework from the meter to the appliance is of
adequate size and the demands of any other gas appliances in the property are taken into consideration.
4. The gas service cock incorporates a pressure test point.
22 EcoBlue Heat
7212435 - 02 (08/14)
Page 23
Description of the Product 4
5.2.2 Electrical Supply
1. External wiring must be correctly earthed, polarised and in accordance with relevant regulations/rules. In GB this is the current I.E.E. Wiring Regulations. In IE reference should be made to the current edition of ETCI rules.
2. The mains supply is 230V ~ 50Hz fused at 3A.
The method of connection to the electricity supply must facilitate complete electrical isolation of the appliance. Connection may be via a fused double-pole isolator with a contact separation of at least 3mm in all poles and servicing the boiler and system controls only. Isolation of the boiler can be checked at the electrical test point.
5.2.3 Hard Water Areas
1. If the area of the installation is recognised as a HARD WATER AREA then this must be taken into account when filling the system.
5.2.4 Bypass
1. An automatic bypass must be fitted on the system for protection of the boiler and pump.
5.2.5 System Control
1. The system must be fitted with thermostats and TRVs to comply with Part L of the Building Regulations.
5.2.6 Treatment of Water Circulating Systems
1. All recirculatory water systems will be subject to corrosion unless they are flushed and an appropriate water treatment is applied. To prevent this, follow the guidelines given in BS 7593 “Treatment of Water in Domestic Hot Water Central Heating Systems” and the treatment manufacturers instructions.
2. Treatment must involve the use of a proprietary cleanser, such as Sentinel X300 or X400, or Fernox F3 and an inhibitor such as Sentinel X100 or Fernox MB-1.
3. Full instructions are supplied with the cleansing products, for further information contact Sentinel (0800 389 4670) or Fernox (0870 870 0362).
Failure to flush and add inhibitor to the system will invalidate the appliance warranty.
4. It is important to check the inhibitor concentration after installation, system modification and at every service in accordance with the inhibitor manufacturer’s instructions. (Test kits are available from inhibitor stockists.)
5. Complete the label supplied with the inhibitor and attach to the inside of the boiler case. Detail of system treatment should be added for future reference.
6. For information or advice regarding any of the above contact Technical Enquiries 0844 871 1555.
7212435 - 02 (08/14) EcoBlue Heat 23
Page 24
5 Before Installation
5.2.7 System Details - General
Flow
Return
Fig. 3
400mm
Min Head
Flow
Fig. 4
22mm Open Vent
400mm
Min Head
Pump
Flow
If Conditions Require,
This System Possible
Copper
0.4m
Copper
1m
22mm Open Vent
15mm
Cold
Feed
Pump
500mm
45°
150mm
Max
Return
1000mm
Min
Boiler
Typical Low Head Installation
500mm
45°
15mm
Cold
Feed
150mm
Max
Return
1000mm
Min
Fig. 5
Copper
0.6m
Boiler
Boiler
Water Circulating Systems
1. The appliance is suitable for use with open vent fully pumped systems and sealed systems . The following conditions should be observed on all systems:
• The static head must not exceed 25m of water.
• The boiler must not be used with a direct cylinder.
• Drain cocks should be fitted to all system low points.
• All gas and water pipes and electrical wiring must be installed in a way which would not restrict the servicing of the boiler.
• Position isolating valves as close to circulating pump as possible.
Pipework
1. The sizes of flow and return pipes from the boiler should be determined by normal methods, according to the requirements of the system. The connections on the boiler are 22mm.
2. A 20 °C (36°F) drop in temperature across the system is recommended for condensing boilers. Existing radiators may be oversized and so allow this, but where radiator sizing is marginal it may be advisable to retain a system temperature drop of 11°C (20°F).
3. In systems using non-metallic pipework it is necessary to use copper pipe for the boiler Flow and Return. The copper must extend at least 1 metre from the boiler and include any branches (Fig. 3).
5.2.8 Low Head Installation / Open
1. Using a close coupled arrangement the minimum head is as shown in the diagrams (Figs. 4, 5 & 6) subject to the following conditions:
a) The pump being adjusted to give a 20°C drop across
the boiler.
b) Ideally the pump should be fitted on the flow but providing that the cold feed and open vent pipe are positioned correctly (e.g. the system is not prone to pumping over, air entrainment etc.) the pump may be fitted on the primary return pipe.
c) The pump must be fitted in accordance with the pump manufacturer's instructions.
d) The open vent pipe must be taken up from a tee in a horizontal section of the flow pipe.
Flow
Fig. 6
Alternative Low Head Installation
24 EcoBlue Heat
22mm
Feed & Vent
Pipe
Separator
Pump
Air
Return
200mm
Min
400mm
Min Head
Boiler
Venting
1. A method of venting the system during filling and commissioning is provided by an automatic air vent fitted inside the boiler. The air vent is supplied in the open position.
7212435 - 02 (08/14)
Page 25
Before Installation 5
3 Litre Top Up Bottle (if required)
Radiator Circuit
Max Boiler Flow
Temp = 82° C
Fig. 7
Method of determining minimum valve of
Static
Head
( m)
<5
Air
Vent
Filling
Point
Pump
Expansion Vessel
expansion vessel volume for sealed
systems using Baxi Boilers
Vessel
Charge
Pressure
(Bar)
0.5
Pressure
System Drains at Low Point
Initial
System
(Bar)
0.5
1.0
1.5
2.0
Pressure
Gauge
Multiply Total
Water Content
Of System By
(Litres)
0.067
0.112
0.207
0.441
Safety
Valve
Boiler
5.2.9 Sealed Systems Details
1. SAFETY VALVE - A safety valve complying with the requirements of BS 6750 Part 1 must be fitted close to the boiler on the flow pipe by means of a horizontal or vertically upward connection with no intervening valve or restrictions and should be positioned to facilitate testing. The valve should be pre-set and non-adjustable to operate at a pressure of 3 bar (45 Ibf/in2). It must be arranged to discharge any water or steam through a pipe to a safe outlet position.
2. PRESSURE GAUGE - A pressure gauge of minimum range 0-4 bar (0-60 Ibf/in2) with a fill pressure indicator must be fitted to the system, preferably at the same point as the expansion vessel in an easily visible position.
3. EXPANSION VESSEL - An expansion vessel complying with the requirements of BS 4814 must be fitted to the system by means of a connection close to the inlet side of the circulating pump in accordance with the manufacturers instructions, the connecting pipe being unrestricted and not less than 15mm (1/2 in) nominal size. The volume of the vessel should be suitable for the system water content and the nitrogen or air charge pressure should not be less than the system static head (See Table. 1a).
Further details of sealed system design can be obtained from BS 5449 and the British Gas publication entitled 'Specifications for Domestic Wet Central Heating Systems'.
<10
<15
Example :-
Table. 1a
Then :-
Where a vessel of the calculated size is not obtainable
then the next available larger size should be used.
Return
CH
1.0
1.5
System Volume = 75 litres Vessel Charge Pressure = 1.0 bar Initial System Pressure = 1.5 bar 75 x 0.152 = 11.4 litres Expansion Vessel Volume
Stop Valve
Temporary Hose
1.0
1.5
2.0
1.5
2.0
NOTE
Double Check Valve
Stop Valve
0.087
0.152
0.330
0.125
0.265
Mains Cold Supply
4. FILLING POINT - A filling point connection on the central heating return pipework must be provided to facilitate initial filling and pressurising and also any subsequent water loss replacement / refilling. The sealed primary circuits may be filled or replenished by means of a temporary connection between the primary circuit and a supply pipe provided a ‘Listed’ double check valve or some other no less effective backflow prevention device is permanently connected at the inlet to the circuit and the temporary connection is removed after use. The filling method adopted must be in accordance with all relevant water supply regulations and use approved equipment. Your attention is drawn to, for GB: Guidance G24.2 and recommendation R24.2 of the Water Regulations Guide. for IE: the current edition of I.S. 813 “Domestic Gas Installations”.
5. MAKE UP SYSTEM - A method of replacing water lost from the system should be provided either by means of a make up vessel of not more than 3 litres (5 pints) capacity, mounted above the highest point of the system, or by re-pressurisation of the system.
6. VENTING - A method of venting the system during filling and commissioning is provided by an automatic air vent fitted inside the boiler. The air vent is supplied in the open position.
7. HOT WATER STORAGE - The hot water storage vessel must be of the indirect coil type. All components used in the system must be suitable for operation at 110°C (230°F) and at the pressure allowed by the safety valve.
Fig. 8
7212435 - 02 (08/14) EcoBlue Heat 25
Page 26
5 Before Installation
5.3 Choice of the Location
Zone 2
Window Recess
Zone 1
Zone 2
Zone 0
0.6 m
Window Recess
Zone 2
Fig. A
In GB Only
5.3.1 Location of the Appliance
Due to the high efficiency of the boiler a plume of water vapour will be discharged from the flue. This should be taken into account when siting the flue terminal.
1. The boiler may be fitted to any suitable wall with the flue passing through an outside wall or roof and discharging to atmosphere in a position permitting satisfactory removal of combustion products and providing an adequate air supply. The boiler should be fitted within the building unless otherwise protected by a suitable enclosure i.e. garage or outhouse. (The boiler may be fitted inside a cupboard).
2. If the boiler is sited in an unheated enclosure then it is recommended to incorporate an appropriate device for frost protection in the system controls.
3. If the boiler is fitted in a room containing a bath or shower it MUST NOT BE fitted in zone 0 or 1, ONLY within the shaded area (Figs. A & B shows zone dimensions for a bathtub. For other examples refer to the Current I.E.E. Wiring Regulations) reference must be made to the relevant requirements. In GB this is the current I.E.E. Wiring Regulations and Building Regulations. In IE reference should be made to the current edition of I.S. 813 “Domestic Gas Installations” and the current ETCI rules.
4. If the boiler is to be fitted into a building of timber frame construction then reference must be made to the current edition of Institute of Gas Engineers Publication IGE/UP/7 (Gas Installations in Timber Framed Housing).
5.3.2 Data Plate
Zone 1
Zone 0
Fig. B
Window Recess Zone 2
Zone 2
0.6 m
Outside Zones
In GB Only
2.25 m
Ceiling
1. The boiler data label gives details of the model, serial number and Gas Council number and is situated on the lower right hand inside face of the outercase. It is visible when the outercase front panel is removed (Fig. 5).
5.3.3 Bath & Shower Rooms
1. If the boiler is fitted in a room containing a bath or shower it can be fitted in zone 2, (Figs. A & B shows zone dimensions for a bathtub. For other examples refer to the Current I.E.E. Wiring Regulations) reference must be made to the relevant requirements. In GB this is the current I.E.E. Wiring Regulations and Building Regulations. In IE reference should be made to the current edition of I.S. 813 “Domestic Gas Installations” and the current ETCI rules.
5.3.4 Ventilation
1. Where the appliance is installed in a cupboard or compartment, no air vents are required.
2. BS 5440: Part 2 refers to room sealed appliances installed in compartments. The appliance will run sufficiently cool without ventilation.
26 EcoBlue Heat
7212435 - 02 (08/14)
Page 27
Before Installation 5
Examples are shown of the following methods of termination:­i) to an internal soil & vent pipe ii) via an internal discharge branch (e.g. sink waste) downstream of the trap iii) to a drain or gully iv) to a purpose made soakaway v) pumped into an internal discharge branch (e.g. sink waste) downstream of the trap vi) pumped into an external soil & vent pipe vii) to a drain or gully with extended external run & trace heating
It is strongly recommended to discharge internally into the household drainage system. If connecting to a rain water drain, that drain MUST discharge into a foul drain.
21.5mm
32mm
i) Termination to an internal soil
and vent pipe
Insulation
5.3.5 Condensate Drain
FAILURE TO INSTALL THE CONDENSATE DISCHARGE PIPEWORK CORRECTLY WILL AFFECT THE RELIABLE OPERATION OF THE BOILER.
CAREFUL CONSIDERATION MUST BE GIVEN TO THE POSSIBILITY OF THE PIPEWORK BEING SUBJECT TO FREEZING CONDITIONS AND APPROPRIATE MEASURES TAKEN TO PREVENT BLOCKAGE. CORRECT INSTALLATION IN ACCORDANCE WITH THIS SECTION WILL CONSIDERABLY MINIMISE THE LIKELIHOOD OF BLOCKAGE AND SUBSEQUENT BOILER LOCK-OUT.
A CONDENSATE DISCHARGE PUMP AND PIPE ‘TRACE HEATING’ ARE AVAILABLE AS ACCESSORIES - see paragraphs 5.3.5.12 to 5.3.5.15 for further details.
The condensate discharge pipe MUST NOT RISE at any point along its length. There MUST be a fall of AT LEAST 2.5° (50mm per metre) along the entire run EXCEPT when employing a suitable condensate pump in basement and cellar or similar applications.
50mm per metre of pipe run
2.5° Minimum fall
450mm min*
*450mm is applicable to properties up to 3 storeys. For multi-storey building installations consult BS 6798.
Boiler
Sink
50mm per metre
of pipe run
2.5° Minimum fall
ii) External termination via internal discharge branch e.g sink waste - downstream*
The boiler condensate trap incorporates a water seal of 75mm, therefore it is unnecessary to install an additional air break and trap in the discharge pipework.
1. The condensate outlet will accept 21.5mm (
3
/4in) plastic
overflow pipe. It is strongly recommended that this
discharges internally into the household drainage system.
Where this is not possible, discharge into an outside drain is permissible providing every possible precaution is taken to prevent freezing.
2. Ensure the discharge of condensate complies with any national or local regulations in force. BS 6798 & Part H1 of the
Building Regulations give further detailed guidance.
3. The discharge pipe should be run in a proprietary drain pipe material e.g. PVC, PVC-U, ABS, PVC-C or PP.
4. Metal pipework is NOT suitable for use in condensate discharge systems.
5. The pipe should be a minimum of 21.5mm diameter and must be supported using suitably spaced clips of the correct design to prevent sagging.
6. It is advisable that the full length of condensate pipe is
Pipe must terminate above water level but below surrounding surface. Cut end at 45°
*It is NOT RECOMMENDED to connect upstream of the sink or other waste water receptacle !
7212435 - 02 (08/14) EcoBlue Heat 27
run internally and preferably be less than 3 metres.
7. Internal runs greater than 3 metres or runs in cold areas should use 32mm waste pipe.
8. External runs MUST be a MINIMUM of 32mm and fully insulated with material suitable for external use.
Page 28
5 Before Installation
Boiler
2.5° Minimum fall
Pipe must terminate above water level but below surrounding surface. Cut end at 45°
iv) Termination to a purpose made soakaway
Further specific requirements for
Boiler
soakaway design are referred to in BS 6798.
50mm per metre
of pipe run
2.5° Minimum fall
iii) Termination to a drain or gully
50mm per metre of pipe run
9. If the boiler is fitted in an unheated location the entire condensate discharge pipe should be treated as an external run and sized and insulated accordingly.
10. In all cases discharge pipe must be installed to aid disposal of the condensate. To reduce the risk of condensate being trapped, as few bends and fittings as possible should be used and any burrs on cut pipe removed.
11. When discharging condensate into a soil stack or waste pipe the effects of existing plumbing must be considered. If soil pipes or waste pipes are subjected to internal pressure fluctuations when WC's are flushed or sinks emptied then back­pressure may force water out of the boiler trap and cause appliance lockout.
12. A boiler discharge pump is available, ‘MULTIFIT’ part no. 720648301. This pump will dispose of both condensate & high temperature water from the relief valve. It has a maximum head of 5 metres. Follow the instructions supplied with the pump.
500mm min
13. Condensate Drain Pipe ‘Trace Heating’ Elements are available in various lengths. ‘MULTIFIT’ part nos.:-
Holes in the soak-away must face away from the building
v) pumped into an internal discharge branch (e.g. sink waste) downstream of the trap
Sink
5m
vi) pumped into an external soil & vent pipe
Unheated Location (e.g. Garage)
5m
50mm per metre of pipe run
2.5° Minimum fall
Basement or
Boiler
50mm per metre of pipe run
Boiler
similar (heated)
Condensate Pump
2.5° Minimum fall
Basement or similar (heated)
Pipe must terminate above water level but below surrounding surface. Cut end at 45°
1 metre 720644401 2 metre 720664101 3 metre 720664201 5 metre 720664401*
*Where the drain is between 3 & 5 metres a 5 metre kit can be used and “doubled back” upon itself.
14. It is possible to fit the element externally on the condensate drain or internally as detailed in the instructions provided.
15. The fitting of a ‘Trace Heating’ Element is NOT a substitute for correct installation of the condensate drain. ALL requirements in this section must still be adhered to.
vii) to a drain or gully with extended external run & trace heating
The ‘Trace Heating’ element must be installed in
Boiler
50mm per metre of pipe run
2.5° Minimum fall
accordance with the instructions supplied. External runs & those in unheated locations still require insulation.
Pipe must terminate above water level but below surrounding surface. Cut end at 45°
28 EcoBlue Heat
Condensate Pump
7212435 - 02 (08/14)
Page 29
Before Installation 5
5.3.6 Clearances - Access in Service
1. A flat vertical area is required for the installation of the boiler.
2. These dimensions include the necessary clearances around the boiler for case removal, spanner access and air movement (Figs. 9 & 10). Additional clearances may be required for the passage of pipes around local obstructions such as joists running parallel to the front face of the boiler.
*These are MINIMUM recommended dimensions. Greater clearance will aid installation and maintenance.
At least
1.5°
Fig. 9
270mm
800mm Min
For Servicing
Purposes
5mm Min
In Operation
5mm Min
370mm
5mm Min
190 mm
625mm
35mm Min*
in Cupboard
120mm Min*
35mm Min when in
cupboard 300mm deep
120mm Min when over
surface 600mm deep
7212435 - 02 (08/14) EcoBlue Heat 29
Page 30
5 Before Installation
5.3.7 Flue/Chimney Location
1. The following guidelines indicate the general requirements for siting balanced flue terminals. For GB recommendations are given in BS 5440 Pt 1. For IE recommendations are given in the current edition of I.S. 813 “Domestic Gas Installations”.
Under car ports we recommend the use of the plume displacement kit. The terminal position must ensure the safe and nuisance - free dispersal of combustion products.
R
N
M
I
I
F
L
Likely flue positions requiring a flue terminal guard
J,K
T
U
D
C
E
I
A
S
I
B
F
A
G
A
H
H
J,K
I
Fig. 11
Terminal Position with Minimum Distance (Fig. 11) (mm)
1
Directly below an opening, air brick, opening windows, etc. 300
A
1
B
Above an opening, air brick, opening window etc. 300
1
C
Horizontally to an opening, air brick, opening window etc. 300
2
D
Below gutters, soil pipes or drain pipes. 25 (75)
2
E
Below eaves. 25 (200)
2
F
Below balconies or car port roof. 25 (200)
2
G
From a vertical drain pipe or soil pipe. 25 (150)
2
H
From an internal or external corner. 25 (300) I Above ground, roof or balcony level. 300 J From a surface or boundary line facing a terminal. 600 K From a terminal facing a terminal (Horizontal flue). 1200
From a terminal facing a terminal (Vertical flue). 600
L From an opening in carport (e.g. door, window)
into the dwelling. 1200 M Vertically from a terminal on the same wall. 1500 N Horizontally from a terminal on the same wall. 300 R From adjacent wall to flue (vertical only). 300 S From an adjacent opening window (vertical only). 1000 T Adjacent to windows or openings on pitched and flat roofs 600 U Below windows or openings on pitched roofs 2000
1
In addition, the terminal should be no nearer than 150 mm to an opening in the building fabric formed for the purpose of accommodating a built-in element such as a window frame.
2
Only ONE 25mm clearance is allowed per installation. If one of the dimensions D, E, F, G or H is 25mm then the remainder MUST be as shown in brackets, in accordance with B.S.5440-1.
30 EcoBlue Heat
7212435 - 02 (08/14)
Page 31
Flue Deflector
Terminal Assembly
Top View Rear Flue
300 min
Before Installation 5
Due to the nature of the boiler a plume of water vapour will be discharged from the flue. This should be taken into account when siting the flue terminal.
2. If the terminal discharges onto a pathway or passageway, check that combustion products will not cause a nuisance and that the terminal will not obstruct the passageway.
3. If a terminal is less than 2 metres above a balcony, above ground or above a flat roof to which people have access, then a
*
suitable terminal guard must be provided.
*4. The distance from a fanned draught appliance terminal installed parallel to a boundary may not be less than 300mm in accordance with the diagram opposite (Fig. 12).
Reduction to the boundary is possible down to 25mm but flue deflector part no. 5111068 or the appropriate Plume Displacement Kit must be used. The nuisance factor must still be taken into account when these options are being considered.
Fig. 12
Plume Displacement Kit
Air Inlet
Property Boundary Line
If fitting a Plume Displacement Flue Kit, the air inlet must be a minimum of 150mm from any opening windows or doors (Fig. 13).
Opening Window or Door
150mm
Fig. 13
7212435 - 02 (08/14) EcoBlue Heat 31
MIN.
Page 32
5 Before Installation
5.3.8 Horizontal Flue/Chimney Systems
1. The standard telescopic flue is suitable only for horizontal termination applications. It allows for lengths between 315mm
(ii)
(i)
and 500mm from elbow to terminal without the need for cutting (Fig. 14). Extensions of 250mm, 500mm & 1m are available.
2. All fittings should be fully engaged. The approximate engagement is 40mm. Apply the lubricant supplied to the seal on each fitting to aid assembly.
3. Maximum permissible Horizontal Concentric equivalent flue lengths are:-
(60/100) (80/125) 6 metres 12 metres
4. Any additional “in line” bends in the flue system must be taken into consideration. Their equivalent lengths are:-
135° bend 0.5 metres 93° bend 1.0 metres
5. The elbow supplied with the standard horizontal telescopic flue kit is not included in any equivalent length calculations.
Fig. 14
315mm 500mm
Horizontal Flues
Flue Trims
Flue length is measured from point (i) to (ii) as shown below.
Read this section in conjunction with the Flue Accessories & Fitting Guide supplied with the boiler. That document includes details of vertical flue/chimney systems and Plume Displacement Kits.
This bend is equivalent to 1 metre
A
C
(ii)
B
(i)
This bend is equivalent to 1 metre
Total equivalent length =
32 EcoBlue Heat
A+B+C+2 x 90° Bends
NOTE: Horizontal flue extensions should
always be installed with a fall of at least 3° from the terminal to allow condensate to run back to the boiler.
7212435 - 02 (08/14)
Page 33
Fig. 15
Terminal
Guard
Before Installation 5
5.3.9 Flue/Chimney Trim
1. The flexible flue trims supplied can be fitted on the outer and inner faces of the wall of installation (Fig. 14).
5.3.10 Terminal Guard
1. When codes of practice dictate the use of terminal guards (Fig. 15) ‘Multifit’ accessory part no. 720627901 can be used (NOTE: This is not compatible with Flue Deflector referred too below).
2. There must be a clearance of at least 50mm between any part of the terminal and the guard.
3. When ordering a terminal guard, quote the appliance name and model number.
4. The flue terminal guard should be positioned centrally over the terminal and fixed as illustrated.
Flue Deflector
Fig. 16
5.3.11 Flue/Chimney Deflector
1. Push the flue deflector over the terminal end, it may point upwards as shown, or up to 45° either way from vertical. Secure the deflector to the terminal with screws provided (Fig. 16).
5.3.12 Flue/Chimney Accessories
For full details of Flue Accessories (elbows, extensions, clamps etc.) refer to the Flue Accessories & Fitting Guide supplied in the literature pack.
WARNING
SUPPORT - All flue systems MUST be securely supported, a MINIMUM of once every metre and at each change of direction. It is recommended that every straight piece is supported irrespective of length. Additional supports are available as accessories. VOIDS - Consideration must be given to flue systems in voids and the provision of adequate access for subsequent periodic visual inspection.
7212435 - 02 (08/14) EcoBlue Heat 33
Page 34
5 Before Installation
5.4 Unpacking & Initial Preparation
Fig. 18
Part No. 7212282-01
116mm Dia Minimum Aperture For Flue Tube
Heating
Heating
Position of Elbow Rear Flue
Return
Flow
(22mm)
56mm
Part No. 7212282-01
60mm
Securing Points
110mm Dia Minimum Aperture For Flue Tube
Securing Points
5 mm Minimum Side Clearance
Profile of Outercase
95mm
(22mm)
Vertical Flue Centre Line
WALL FIXING BRACKET
IMPORTANT: For ease of installation it is recommended that the horizontal tongues and slots are visible whilst mounting the appliance. Familiarise yourself with the method of fixing and retaining before commencing.
IMPORTANT
The minimum clearances must be
maintained for regular operation
and servicing.
Condensate
Drain Connection
25mm Min Cupboard Clearance
120mm Minimum Clearance
Wall Bracket
155mm
For Side Flue Exit
Fig. 19
Safety
Bracket
Fig. 21
Sealing
Caps
200mm Minimum Clearance
35mm Minimum
Boiler Mounting Bracket
Clearance for
Horizontal Securing Tongue
Rear Flue
Locate the slots in the boiler hanging bracket over the horizontal securing tongues
5 mm Minimum Side Clearance
Gas Inlet
(22mm)
Fig. 20
5.4.1 Unpacking
1. Follow the procedure on the carton to unpack the boiler. See Section 2.3.1 Handling before lifting the boiler.
5.4.2 Initial Preparation
1. After considering the site requirements, position the fixing template on the wall ensuring it is level both horizontally and vertically (Fig. 20).
2. Mark the position of the four most suitable fixing slots for the wall bracket, the lower securing point and the position of the centre of the flue hole whether rear, top or side flue.
3. If required, mark the position of the gas and water pipes, and the electrical supply. Remove the template.
4. Cut the hole for the required flue position (rear, top or side) using a minimum diameter of 116mm.
5. Drill the wall as previously marked to accept suitable wall plugs. Secure the wall bracket using appropriate fixing screws.
6. Using a spirit level ensure that the bracket is level before finally tightening the screws (Fig. 21).
Electrical Socket
47mm
Mains Input
142mm
7. For top flue installation, the flue can be fitted after the boiler has been fitted to the wall bracket (see Section 6.1).
If the boiler is being fitted in a cupboard or other place where clearance underneath will be at the minimum 35mm (see Section 5.3.6) all soldering and pipework should be completed prior to installation. Also the lower panel retaining cords can be dispensed with - See Section 10.2 for removal of the lower panel - the cords can then be disconnected.
8. Lift the boiler using the lower polystyrene packing and locate the slots in the wall bracket over the horizontal tongues on the wall bracket. As the boiler is pushed back the wall bracket spring latch will positively engage over the wall bracket (Figs. AA, BB & CC).
Fig.22
34 EcoBlue Heat
Lower Securing
Point Screw
Fig. AA
Snap off rear polystyrene and lift using lower polystyrene (can be discarded if space is limited)
9. Locate the slots in the safety bracket over the two vertical tongues on the wall bracket and secure with the two screws (Fig CC). Adjust the jack screw to ensure the boiler is fully vertical and then insert the lower securing screw.
Fig. CC
7212435 - 02 (08/14)
Safety Bracket
Screw
Horizontal Tongue
Fig. BB
Spring Latch
Page 35
Before Installation 5
5.4.3 Making the Water Connections (Fig. 22)
1. There are two water connections at the top of the boiler. The left connection is the return pipe (indicated with blue label) and the flow the right hand one (indicated with red label). Remove the sealing caps from the boiler connections.
2. It is essential that the flow and return pipes are connected to the boiler correctly. The boiler connections will accept 22mm compression fittings.
3. For a top flue installation make sure the water connections do not clash with the flue position.
When soldering of joints is to be performed under the boiler the condensate trap must be removed to prevent damage.
5.4.4 Filling the Condensate Trap
1. The condensate trap must be filled with water before the boiler is commissioned.
90° rubber hose
Sealing Cap - to
be discarded
Fig. 23
Condensate Trap
2. If access to the condensate trap is impeded remove the facia panel with the User Interaction Controller.
3. Disengage the condensate trap retaining clip and carefully pull out the trap. Remove and discard the sealing cap.
4. Fill the condensate trap with tap water to a depth of approximately 75mm.
5. Carefully relocate the condensate trap in the boiler ensuring all seals are located properly and reattach the retaining clip.
6. If necessary remove the boiler front panel to inspect that the seals are located properly and refit the facia panel with the User Interaction Controller.
5.4.5 Connecting the Condensate Drain (Fig. 23)
1. Using the 90° rubber hose supplied, connect the condensate drain pipework to the boiler condensate trap outlet pipe.
Ensure the discharge of condensate complies with any national or local regulations in force (see British Gas “Guidance Notes for the Installation of Domestic Gas Condensing Boilers” & HHIC recommendations) and Section 5.3.5.
Elbow & Nut
2. The hose will accept 21.5mm (3/4in) plastic overflow pipe which should generally discharge internally into the household
Sealing Washer
Gas Cock
drainage system. If this is not possible, discharge into an outside drain is acceptable.
5.4.6 Connecting the Gas Supply (Fig. 23a)
1. The elbow and nut assembly supplied must be used to connect to the gas supply. The flared end of the elbow is 22mm O.D.
Fig. 23a
7212435 - 02 (08/14) EcoBlue Heat 35
2. Engage the nut onto the gas cock, ensuring that the sealing washer is in place. Tighten the nut.
Page 36
6 Installation
6 Installation
6.1 Air Supply / Flue Gas Connections
315mm 500mm
Terminal Assembly
Connection Assembly
Fig. 24
6.1.1 Connecting the Top Flue
HORIZONTAL TELESCOPIC FLUE
1. There are two telescopic sections, the Terminal Assembly and the Connection Assembly, a roll of sealing tape and two self tapping screws. A 93° elbow is also supplied.
2. The two sections can be adjusted to provide a length between 315mm and 500mm (Fig. 24) when measured from the flue elbow (there is 40mm engagement into the elbow).
Wall Thickness
(X)
Fig. 25
‘TOP’ Label
(X)
Wall
Thickness
3. Locate the flue elbow on the adaptor at the top of the boiler. Set the elbow to the required orientation (Fig. 25).
The flue elbow is angled at 93 degrees to ensure a fall back to the boiler.
4. Measure the distance from the outside wall face to the elbow. This dimension will be known as ‘X’ (Fig. 25).
5. If the distance from the flue elbow to the outside face of the wall (‘X’ in Fig. 25) is less than 250mm the Connection Assembly can be discarded and the Terminal Assembly fitted directly into the elbow.
6. In instances where the dimension ‘X’ (Fig. 25) is between 250mm and 315mm it will be necessary to shorten the Terminal Assembly by careful cutting to accommodate walls of these thicknesses.
7. To dimension ‘X’ add 40mm. This dimension to be known as ‘Y’.
8. Adjust the two telescopic sections to dimension ‘Y’ and seal the joint with the tape provided (Fig. 26). Ensure that the labels marked ‘TOP’ on the Terminal and Connection Assemblies are uppermost.
Dimension ‘Y’
Sealing Tape
9. Using the clearance holes in the Connection Assembly secure it to the Terminal Assembly using the screws supplied (Fig. 27).
‘Peak’ to be
uppermost
Fig. 26
36 EcoBlue Heat 7212435 - 02 (08/14)
‘TOP’ Label
Securing Screw
Fig. 27
Page 37
Spring Latch
Horizontal Tongue
Fig. AA Fig. BB
Safety Bracket
Screw
Installation 6
10. Lift the boiler and locate the slots in the wall bracket over the horizontal tongues on the wall bracket. As the boiler is pushed back the wall bracket spring latch will positively engage over the wall mounted bracket (Figs. AA, BB & CC).
11. Locate the slots in the safety bracket over the two vertical tongues on the wall bracket and secure with the two screws (Fig CC).
12. Insert the flue through the hole in the wall. Fit the elbow to the boiler adaptor, ensuring that it is pushed fully in (Fig. 29).
13. Draw the flue back through the wall and engage it in the elbow. It may be necessary to lubricate to ease assembly of the elbow and flue (Fig. 30).
Boiler Elbow
Apply the lubricant supplied for ease of assembly (do not use any other type).
Ensure Elbow is
fully engaged into
Boiler Adaptor
Apply the lubricant supplied for ease of assembly (do not use any other type).
Ensure Flue is fully
engaged into Elbow
Fig. CC
Adaptor
Fig. 29
14. Ensure that the terminal is positioned with the slots to the bottom (Fig. 31). Secure the flue to the elbow with the screws supplied (Fig. 30).
It is essential that the flue terminal is fitted as shown to
ensure correct boiler operation and prevent water
entering the flue. There must be no part of the air duct
(white tube) visible outside the property after
installation.
15. Make good between the wall and air duct outside the building, appropriate to the wall construction and fire rating.
16. If necessary fit a terminal guard (see Section 5.3.11).
If not already done so, make the water connections, fill the condensate trap, connect the condensate drain and connect the gas supply as described in Sections 5.4.3, 5.4.4, 5.4.5 &
5.4.6 respectively.
Fig. 30
Slots at bottom
7212435 - 02 (08/14) EcoBlue Heat 37
Fig. 31
Page 38
6 Installation
6.2 Electrical Connections
321
6.2.1 Electrical Connections of the Appliance
1. See Section 5.2.2. for details of the electrical supply. 1.3 metres of 3 core cable and a multipin male plug connected to a female socket at the left rear are supplied with the boiler. The cable live must be connected to the boiler switched live control.
N
2. If necessary the cable can be replaced by one of greater length providing it is of equivalent specification (Fig. 32).
6.2.2 Connecting External Devices
Fig. 32
Key to colours
b - Blue br - Brown w - White o - Orange gr - Grey g/y - Green/Yellow
230V 50Hz
L NE
g/y
Room
Stat
1. System Controls - This boiler operates on a switched live only. If there is a permanent live in the existing supply it can be connected to spare terminals 2 or 3 of the plug supplied.
2. To comply with Part L1 of the Building Regulations the heating system into which the boiler is installed should include the following:
a) Zone Controls b) Timing Controls c) Boiler Control Interlocks (Room & Cylinder Thermostats)
3. Such a system needs to be fully pumped and must provide independent temperature and time control to both the heating and hot water circuits.
4. An automatic bypass must be fitted on the system for
3 Core Cable Connection
protection of the boiler and pump.
5. Connection diagrams for Y and S plan systems are shown.
230V
b
w
Cylinder
Stat
1
C 2
Y Plan
Diverter
Valve
gr
o
50Hz
L NE
gr
Motor
b
S Plan
br
Valve
g/y
Room
Stat
b
Cylinder
Stat
Boiler
L NE
gr
Motor
br
o
S Plan
g/y
Valve
o
Boiler
L NE
Timer
L
N
CH on HW on HW off
Pump
LNE
Y Plan, Room Thermostat System, CH Interlocked By Room Thermostat
At least the Radiator(s) near the Room Thermostat not TRV’d Pump run from Switched Live
Timer
L
N
CH on
HW on
Pump
LNE
S Plan, Room Thermostat System, CH Interlocked By Room Thermostat
At least the Radiator(s) near the Room Thermostat not TRV’d Pump run from Switched Live
38 EcoBlue Heat 7212435 - 02 (08/14)
Page 39
6.3 Filling the System
6.4 Completing the Installation
Installation 6
See Section 5.2.6. for details of treating the system, Section 5.2.7. for open vent system details, Section 5.2.9. for sealed system details and Section 5.4.4. for filling the condensate trap.
6.4.1 Completion
1. Before turning on the electrical and gas supply to commission the boiler, check that all the installation requirements for the chosen heating system and flue options have been satisfied.
2. Ensure that the system is vented to expel any excess air.
7212435 - 02 (08/14) EcoBlue Heat 39
Page 40
7 Commissioning
7 Commissioning
7.1 General
7.2 Checklist before Commissioning
1. Reference should be made to BS:EN 12828 & 14336 when commissioning the boiler.
2. At the time of commissioning, complete all relevant sections of the Benchmark Checklist at the rear of this publications.
3. Turn the gas supply on and purge according to in GB BS 6891 and in IE I.S. 813 “Domestic Gas Installations”.
The combustion for this appliance has been checked, adjusted and preset at the factory for operation on the gas type specified on the appliance data plate.
7.2.1 Preliminary Electrical Checks
7.3 Commissioning Procedure
1. Prior to commissioning preliminary electrical system checks should be carried out.
2. These should be performed using a suitable meter, and include checks for Earth Continuity, Resistance to Earth, Short Circuit and Polarity.
7.2.2 Checks
Check that the boiler has been installed in accordance with these instructions. Check the integrity of the flue system and the flue seals. Check the integrity of the boiler combustion circuit and the relevant seals. Check the integrity of all gas and water joints.
CAUTION
On first firing the boiler, an odour may be present for a short period.
1. Open the main gas supply.
2. Open the gas cock on the boiler.
3. Set the controls (thermostats, control system) so that they request heat to turn the boiler on.
4. The boiler incorporates an automatic air vent. As supplied this is in the open position to allow venting of the system.
40 EcoBlue Heat 7212435 - 02 (08/14)
Page 41
7.4 Gas Settings
Commissioning 7
Flue Sampling
Point
Plug
Analyser Probe
After refitting the sampling point plug ensure there is no leakage of products !
7.4.1 ‘Chimney Sweep’ Mode (CSM)
1. The current operating condition of the boiler is shown by the button on the User Interaction Controller. The
button can flash in a range of colours and at different frequencies.
2. Follow the flow chart on the next page to comply with the
requirement to check combustion on commissioning.
3. Setting the boiler to maximum and minimum heat outputs is
achieved as follows;
• Press the button for 3 seconds.
• CSM is activated and will go to the min rate.
• Pressing again will make it adjust to max rate.
• To exit press the RESET for 3 seconds.
Fig. 33
7212435 - 02 (08/14) EcoBlue Heat 41
Page 42
7 Commissioning
7.4.2 ‘Chimney Sweep’ Mode - Combustion Check
Verify Flue Integrity
Indication that products of combustion & inlet air are mixing - further investigation is required. Check all flue components are correctly assembled, fixed & supported. Check the flue & terminal are unobstructed.
Is O
2  20.6% and
CO
2 < 0.2% ?
No
TURN APPLIANCE OFF !
Call 0844 871 1555 for advice. The appliance MUST NOT be commissioned until all problems are identified and resolved.
Set Boiler to Maximum Rate
Allow the combustion to stabilise. Do not insert probe to avoid ‘flooding’ the analyser.
Perform Flue Integrity Combustion Check
Insert the analyser probe into the air inlet test point, allowing the reading to stabilise.
No
Is O
2  20.6% and
CO
2 < 0.2% ?
Yes
Verify Integrity of Seals
Check all burner seals, internal flue seals, door & case seals. Replace any seals that appear unsound.
Is CO < 350ppm and CO/CO < 0.004 ?
2 ratio
1. Follow the flow chart opposite.
Check CO & Combustion Ratio at Maximum Rate
Whilst the boiler is still
Yes
operating at maximum insert the analyser probe into the flue gas test point, allowing the reading to stabilise.
No
Is CO < 350ppm and CO/CO < 0.004 ?
Yes
2 ratio
Set Boiler to Minimum Rate
Allow the combustion to
Yes
stabilise. Do not insert probe to avoid ‘flooding’ the analyser.
Check CO & Combustion Ratio at Minimum Rate
Whilst the boiler is operating at minimum insert the analyser probe into the flue gas test point, allowing the reading to stabilise.
No
TURN APPLIANCE OFF !
Call 0844 871 1555 for advice.
No
The appliance MUST NOT be commissioned until all problems are identified and resolved. If commissioning cannot be fully completed the appliance must be disconnected from the gas supply in accordance with the GSIUR. Note: Check & record the CO & combustion ratio at both maximum & minimum rates before calling 0844 871 1555.
42 EcoBlue Heat 7212435 - 02 (08/14)
Is CO < 350ppm and CO/CO
2 ratio
< 0.004 ?
Yes
BOILER OPERATING
SATISFACTORILY. NO
FURTHER ACTION
REQUIRED
Ensure test points are capped, the boiler case front panel is correctly fitted & secured and all other commissioning procedures completed. Complete the ‘Benchmark’ Checklist, recording the CO & combustion ratio readings as required.
Page 43
7.5 Configuring the System
Commissioning 7
7.5.1 Check the Operational (Working) Gas Inlet Pressure
1. Ensure that all controls are calling for heat and maximum load
is applied to the system.
2. With the boiler operating in the maximum rate condition check
that the operational (working) gas pressure at the inlet gas pressure test point is in accordance with B.S. 6798 & B.S. 6891. This must be AT LEAST 17mb ! (Fig. 34)
3. Ensure that this inlet pressure can be obtained with all other
gas appliances in the property working.
Measure the Gas Rate
4. With any other appliances & pilot lights turned OFF the gas
rate can be measured. It should be as shown in Section 3.1 Technical Data.
5. For IE, it is necessary to complete a “Declaration of
Conformity” to indicate compliance with I.S. 813. An example of this is given in I.S. 813 “Domestic Gas Installations”. This is in addition to the Benchmark Commissioning Checklist.
Check gas pressure here
17-21 mbar
Gas Valve
Gas Cock
18-22 mbar
19-23 mbar
Gas Meter
Fig. 34
Working Gas Pressures
If the pressure drops are greater than shown above a problem with the pipework or connections is indicated.
7212435 - 02 (08/14) EcoBlue Heat 43
Page 44
7 Commissioning
7.6 Final Instructions
1. Carefully read and complete all sections of the Benchmark Commissioning Checklist at the rear of this publication that are relevant to the boiler and installation. These details will be required in the event of any warranty work.
2. The publication must be handed to the user for safe keeping and each subsequent regular service visit recorded.
3. Hand over the User’s Operating, Installation and Servicing Instructions, giving advice on the necessity of regular servicing.
4. For IE, it is necessary to complete a “Declaration of Conformity” to indicate compliance with I.S. 813. An example of this is given in I.S. 813 “Domestic Gas Installations”. This is in addition to the Benchmark Commissioning Checklist.
5. Instruct the user in the operation of the boiler controls. Hand over the User’s Operating, Installation and Servicing Instructions, giving advice on the necessity of regular servicing.
6. Demonstrate to the user the action required if a gas leak occurs or is suspected. Show them how to turn off the gas supply at the meter control, and advise them not to operate electric light or power switched, and to ventilate the property.
7. Show the user the location of the system control isolation switch, and demonstrate its operation.
8. Advise the user that they may observe a plume of vapour from the flue terminal, and that it is part of the normal operation of the boiler.
9. Complete the label supplied with the inhibitor and stick to the inside of the boiler case. Detail of system treatment must be recorded in the Benchmark Commissioning Checklist.
44 EcoBlue Heat 7212435 - 02 (08/14)
Page 45
8 Operation
8.1 General
Operation 8
1. It is the responsibility of the installer to instruct the user in the
day to day operation of the boiler and controls and to hand over the completed Benchmark Checklist at the back of this manual.
2. Set the central heating and hot water temperatures to the
requirements of the user. Instruct the user in the operation of the boiler and system.
3. The temperature on the boiler rotary knob must be set to a
higher temperature than the cylinder thermostat to achieve the required hot water demand.
4. Instruct the user in the operation of the boiler and system
controls.
5. Demonstrate to the user the action required if a gas leak
occurs or is suspected. Show them how to turn off the gas supply at the meter control, and advise them not to operate electric light or power switched, and to ventilate the property.
8.2 Start-up
8.3 Shutdown
6. Show the user the location of the system control isolation
switch, and demonstrate its operation.
7. Advise the user that they may observe a plume of vapour from
the flue terminal, and that it is part of the normal operation of the boiler.
8. When installed on a sealed system the method of
repressurising the primary system should be demonstrated.
1. Switch on the boiler at the fused spur unit and ensure that the
time control is in the on position and any other controls (i.e. room thermostat) are calling for heat.
2. The boiler will begin it start sequence.
3. The orange LED will flash at EVERY heating demand. The
number of flashes will correspond with the output of the boiler e.g. 4 orange flashes = 21kW. This is normal and does not indicate a fault condition.
1. If the CH system is shut down for remedial work requiring
either the electrical power to be switched off or the gas supply to be turned off then any frost protection present will be inactive.
2. Switching off the boiler’s power supply or turning off the gas
supply will disable any frost protection that has been incorporated into the control system.
7212435 - 02 (08/14) EcoBlue Heat 45
Page 46
8 Operation
8.4 Use of the Control Panel
8.5 Frost Protection
See Section 4.4 Control Panel Description
1. To prevent radiators and pipework from freezing in areas where there is a risk of frost (e.g. a garage or storage room), a frost thermostat should be connected to the control system.
The following arrangement is recommended:­ Utilise a room frost thermostat in conjunction with a pipe thermostat. The pipe thermostat should be located on the primary return close to the boiler.
46 EcoBlue Heat 7212435 - 02 (08/14)
Page 47
9 Settings
9.1 Parameters
Settings 9
The operating parameters for this boiler are factory set.
7212435 - 02 (08/14) EcoBlue Heat 47
Page 48
10 Maintenance
10 Maintenance
10.1 General
WARNING
When changing components ensure that both the gas and electrical supplies to the boiler are isolated before any work is started. When the component has been changed recommission the boiler as described in Section 7. The Case Front Panel MUST seal effectively against the boiler side panels.
1. For reasons of safety and economy, it is recommended that the boiler is serviced annually. Servicing must be performed by a competent person in accordance with B.S. 7967-4.
2. After servicing, complete the relevant Service Interval Record section of the Benchmark Commissioning Checklist at the rear of this publication.
During routine servicing, and after any maintenance or change of part of the combustion circuit, the following must be checked:-
• The integrity of the complete flue system and the flue seals by checking air inlet sample to eliminate the possibility of recirculation. O2 20.6% & CO2< 0.2%
• The integrity of the boiler combustion circuit and relevant seals.
• The operational gas inlet pressure and the gas rate as described in Section 7.5.1.
• The combustion performance as described in ‘Check the Combustion Performance’ below.
Flue Sampling
Point
Plug
Analyser Probe
Fig. 35
After refitting the sampling point plug ensure there is no leakage of products !
3. Competence to carry out Checking Combustion
Performance B.S. 6798 ‘Specification for Installation & Maintenance of Gas Fired Boilers not exceeding 70kWh’ advises that:-
• The person carrying out a combustion measurement should have been assessed as competent in the use of a flue gas analyser and the interpretation of the results.
• The flue gas analyser used should be one meeting the requirements of BS7927 or BS-EN50379-3 and be calibrated in accordance with the analyser manufacturers’ requirements.
• Competence can be demonstrated by satisfactory completion of the CPA1 ACS assessment, which covers the use of electronic portable combustion gas analysers in accordance with BS 7967, Parts 1 to 4.
4. Check the Combustion Performance (CO/CO2ratio)
Set the boiler to operate at maximum rate as described
in Section 7.4.
5. Remove the plug from the flue sampling point (Fig. 35), insert
the analyser probe and obtain the CO/CO2ratio. This must be less than 0.004. If the combustion reading (CO/CO2 ratio) is greater than this, and the integrity of the complete flue system and combustion circuit seals has been verified, and the inlet gas pressure and gas rate are satisfactory either:-
• Perform the ‘Standard Inspection and Maintenance’ (Section
10.2) & re-check.
• Perform ‘Setting the Gas Valve’ (Section 10.3.13) & re-check.
• Replace and set the gas valve (Sections 10.3.10 & 13) & re-check.
48 EcoBlue Heat 7212435 - 02 (08/14)
Page 49
10.2 Standard Inspection and Maintenance Operation
WARNING
Ensure that the boiler is cool.
Ensure that both the gas and electrical supplies to the boiler are isolated. Electrical isolation can be checked at the electrical test point.
CAUTION
During inspection and maintenance operations, always replace all gaskets on the parts removed.
Fig. 36
Use only original spare parts that are intended for use with this type of boiler.
When performing any inspection or maintenance personal protective equipment must be used where appropriate.
Maintenance 10
Fig. 37
1. Unscrew the two screws located on the lower front panel (Fig. 36).
2. Slide the lower front panel forward and hinge down or remove (Fig. 37).
3. Unscrew the two securing screws on the front panel. Remove the front panel (Fig. 38).
4. Visually check for debris/damage and clean or replace if necessary the following:
a) Check the water pressure (sealed systems) b) Check the flue pipes and air supply pipes for leaks c) Check and clean (if necessary) the condensate trap d) Check the ignition electrode (replace if necessary) e) Check the combustion
f) Complete the relevant Service Interval Record section of the Benchmark Commissioning Checklist at the rear of this publication and then hand it back to the user
Electrical Test Point
Fig. 38
7212435 - 02 (08/14) EcoBlue Heat 49
Page 50
10 Maintenance
10.3 Specific Maintenance Operation
Earth Wire
Ignition Electrode Plug
Spark Ignition Electrode
Earth Wire
Gasket
WARNING
When changing components ensure that both the gas and electrical supplies to the boiler are isolated before any work is started. When the component has been changed recommission the boiler as described in Section 7. Always examine any seals or gaskets, replacing where necessary. The Case Front Panel MUST seal effectively against the air box side panels.
1. See section 10.2 for removal of lower front panel and front panel.
10.3.1 Spark Ignition Electrode (Fig. 39)
1. Disengage the fan protective cover securing tab and lower the cover.
Ta b
Fan Protective Cover
Automatic Air Vent
Clip
Fig. 40
Press the tap to hinge down the Fan Protective Cover
2. Disconnect the ignition electrode plug from the PCB and the earth wire from the electrode.
3. Undo the two securing screws securing and remove the electrode and gasket.
Fig. 39
4. Fit the new electrode and if necessary replace the gasket. Connect the electrode lead to the PCB and earth wire to the new electrode.
10.3.2 Automatic Air Vent (Fig. 40)
1. Remove the clip securing the automatic air vent.
2. Manoeuvre the air vent out of the adaptor in the heat exchanger.
3. Fit the new air vent and if necessary replace the ‘O’ ring . Refit the securing clip.
10.3.3 Condensate Trap (Fig. 41)
1. Disengage the condensate trap retaining clip and disconnect the condensate drain. Carefully pull out the trap.
2. Thoroughly clean the trap and if necessary replace the seal.
3. Fill the condensate trap with tap water to a depth of
Fig. 41
Push the Condensate Trap Clip either side to release the trap
Condensate Trap
50 EcoBlue Heat 7212435 - 02 (08/14)
approximately 75mm.
4. Carefully relocate the condensate trap in the boiler ensuring all seals are located properly and reattach the retaining clip.
Page 51
Maintenance 10
Removal of the fan air duct and flue outlet duct is
necessary to enable the changing of the pressure
switch, flow temperature sensor, return temperature
sensor, overheat sensor and gas valve.
Flue Clip
Fan Air Duct
Fig. 42
10.3.4 Removal of Ducts (Fig. 42)
1. Remove the air duct by pulling the bottom of the duct forward to disengage it from the gas valve and then sliding the top of the duct left away from the fan.
2. Disengage the clip at the top of the flue duct, pull the duct forwards and then manoeuvre it out of the heat exchanger sump connection.
10.3.5 Pressure Switch (21 & 24 only) (Fig. 43)
1. Disconnect the pressure switch wiring from the overheat sensor wiring harness.
2. Depress the retaining latch to release the pressure switch pull to the right and remove it from the top flue duct tube.
3. Fit the new pressure switch, ensuring the ‘O’ ring is in place on the lower spigot and reconnect to the wiring harness from the overheat sensor.
Flue Outlet Duct
Top Flue Duct Tube
Fig. 43
Pressure Switch Retaining Latch
Slide Pressure Switch away from Top Flue Duct Tube
Disconnect from Overheat
Sensor Harness
7212435 - 02 (08/14) EcoBlue Heat 51
Page 52
10 Maintenance
Flow Temperature Sensor
Overheat Sensor
Fig. 44
Fan Protective Cover removed for clarity
10.3.6 Flow Temperature Sensor (Fig. 44)
The sensor is fitted in a ‘dry’ pocket.
1. Disconnect the wiring from the flow temperature sensor.
2. Unscrew the sensor from the top of the heat exchanger.
3. Fit the new sensor and reconnect the wiring.
10.3.7 Overheat Sensor (Fig. 44)
The sensor is fitted in a ‘dry’ pocket. For ease of access remove the Flow Temperature Sensor (10.3.6)
1. Disconnect the wiring from the overheat sensor.
2. Unscrew the sensor from the top of the heat exchanger.
3. Fit the new sensor and reconnect the wiring.
10.3.8 Return Temperature Sensor (Fig. 45)
The sensor is fitted in a ‘dry’ pocket.
Push the retaining latch backwards to release the Parameter Unit
Slide the Parameter Unit upwards
Return Temperature Sensor
Fig. 45
1. Disconnect the wiring from the return temperature sensor.
2. Unscrew the sensor from the top of the heat exchanger.
3. Fit the new sensor and reconnect the wiring.
10.3.9 Parameter Unit (Fig. 46)
1. Push the retaining latch to release the parameter unit and slide it upwards to remove.
2. Disconnect the wiring from the parameter unit.
3. Fit the new parameter unit and reconnect the wiring.
Fan Protective Cover removed for clarity
Parameter Unit
52 EcoBlue Heat 7212435 - 02 (08/14)
Fig. 46
Page 53
Combustion Control Unit
Fig. 47
Maintenance 10
10.3.10 Gas Valve (Figs. 47, 48 & 49)
After replacing the valve the CO2must be checked and
adjusted as detailed in Section 10.3.13 Setting the Gas
Valve. Only change the valve if a suitable calibrated
combustion analyser is available, operated by a
competent person - see section 10.1.3.
A T25 Torx screwdriver will be required.
1. Ensure that the gas supply to the boiler is isolated.
Remove the ducts as described in Section 10.3.4
2. Disconnect the cable from the bottom of the PCB, disengage the fan protective cover securing tab and lower the cover.
3. Taking care not to touch the PCB components, disconnect the electrode lead, earth lead, mains power cable and the main sensor harness from the board. Re-engage the fan protective cover.
Fan Gas Supply Pipe
Electrical
Plug
Fig. 49
View from behind Combustion Control Unit
Gas Valve Securing Screws
Fan not shown for clarity
Fig. 48
Gas Valve Securing Screws
Gas Inlet Pipe
4. Disconnect the plug from the gas valve and undo the nut on the gas inlet pipe at the base of the valve.
5. Remove the combustion control unit from the boiler by releasing the over-centre catches that secure it to the heat exchanger (Fig. 47).
6. Remove the T25 screws securing the gas valve to the fan assembly.
7. Lift the gas valve from its seat and pull it gently downwards to release it from the fan assembly.
8. Remove the 2 O-Rings from the gas feed pipe and replace with new ones supplied in the kit. Take care not to damage the O-Rings when refitting. Apply a small quantity of the silicone grease provided to aid reassembly of the gas valve (Fig. 49).
9. Push the new gas valve onto the gas feed pipe taking care not to damage the O-Ring seals and push home securely. Secure the valve using the 2 T25 screws and shakeproof washers.
10. Reassemble all components in reverse order. When a seal kit is provided replace the existing seals with the new ones. Inspect all other seals before reassembly and replace if necessary. Check all the joints are tight and wires are securely connected.
Check gas tightness & CO2!
If the boiler will not light, prior to final setting, use a
suitable hexagon key to wind out the Throttle
Adjustment Screw until it is flush with the valve body,
then turn the screw 4 full turns clockwise. If the boiler
will not light, or the correct CO2 cannot be achieved
contact the ‘heateam’ technical helpline.
See Section 10.3.13 for CO2check.
7212435 - 02 (08/14) EcoBlue Heat 53
Page 54
10 Maintenance
Burner Manifold
Control & Fan Assembly
Fig. 50
10.3.11 Control & Fan Assembly (Figs. 50, 51 & 52)
1. Ensure that the gas supply to the boiler is isolated.
Remove the ducts as described in Section 10.3.4
An ESD wrist strap should be used when replacing these components.
A T25 screwdriver will be required.
2. Disconnect the cable from the bottom of the PCB, disengage the fan protective cover securing tab and lower the cover.
3. Taking care not to touch the PCB components, disconnect the electrode lead, earth lead, mains power cable and the main sensor harness from the board. Re-engage the fan protective cover.
4. Disconnect the plug from the gas valve and undo the nut on the gas inlet pipe at the base of the valve.
5. Remove the combustion control unit from the boiler by releasing the over-centre catches that secure it to the heat exchanger.
Gas Valve Securing Screws
Fig. 52
View from behind Combustion Control Unit
Fig. 51
Fan Gas Supply Pipe
Gas Valve Securing Screws
Fan not shown for clarity
6. Remove the screws securing the gas valve. Remove the gas valve by lifting it from its seat and pulling it downwards.
7. Using the special tool provided, remove the 4 T20 Torx screws securing the burner manifold and set the manifold aside.
8. Fit the burner manifold to the new fan and PCB assembly using the new seals and screws provided in the kit. Do not overcompress the manifold gasket or use any grease. Check visually that the gasket is correctly in place.
9. Replace the gas valve ensuring new O ring seals are greased prior to replacing the pipe.
10. Reassemble all components in reverse order. When a seal kit is provided replace the existing seals with the new ones. Inspect all other seals before reassembly and replace if necessary. Check all the joints are tight and wires are securely connected.
10.3.12 User Interaction Controller (Fig. 53)
1. Disconnect the user interaction controller cable from the PCB and undo the cable gland locknut.
2. Note the setting and carefully prise off the rotary temperature selection knob.
3. Ease apart the retaining clips on the lower panel and
Fig. 53
Lower Panel
withdraw the user interaction controller and cable.
4. Reassemble in reverse order, setting the rotary knob as previously noted.
Rotary Knob
54 EcoBlue Heat 7212435 - 02 (08/14)
User Interaction Controller
Page 55
Chimney Sweep Button
Flue Sampling
Point
Plug
Throttle
Adjustment Screw
Fig. 54
Fig. 55
Maintenance 10
10.3.13 Setting the Gas Valve (CO2Check)
The CO2must be only be checked and adjusted to set the valve if a suitable calibrated combustion analyser is available, operated by a competent person - see Section 10.1.3.
If a new gas valve has been fitted it is recommended that to assist the boiler to light prior to final setting, use a suitable hexagon key to wind out the Throttle Adjustment Screw (Fig. 54) until it is flush with the valve body, then turn the screw 4 full turns clockwise. If the boiler will not light, or the correct CO2cannot be achieved contact the ‘heateam’ technical helpline.
1. The maximum rate CO2setting can only be reached via the minimum rate. Press the Chimney Sweep (Fig. 55) button for approximately 3 seconds. The status signal for the Chimney Sweep button is orange and flashes green briefly to show that the minimum rate is selected.
2. Press the Chimney Sweep button again once. The orange status light for the Chimney Sweep button goes off briefly once and maximum rate is selected.
When the boiler first lights wait a short time before inserting the analyser probe to avoid saturation.
Analyser Probe
Offset
Adjustment Screw
(cap fitted)
Reduce CO at min. rate
Increase CO at min. rate
2
3. Remove the plug from the flue sampling point (Fig. 56) and
Fig. 56
insert the probe of the flue gas analyser.
4. Check the CO2is 9.3% ±0.1%. If the CO2is incorrect alter the Throttle Adjustment Screw (Fig. 57). Turn the screw anticlockwise to increase the CO2or clockwise to decrease (2.5mm hexagon key).
Do not turn either adjustment screw more than 1/8 of a turn at a time. Allow the analyser reading to settle
Throttle
Adjustment Screw
(cover removed)
before any further adjustment.
5. Press the Chimney Sweep button twice to select the minimum rate. The orange status light for the Chimney Sweep button flashes green briefly and minimum rate is selected.
6. Check the CO2is 8.9% ±0.1%. If the CO2is incorrect alter the Offset Adjustment Screw (Fig. 57). Turn the screw clockwise
Reduce CO at max. rate
2
to increase the CO2or anticlockwise to decrease (4mm hexagon key).
Re-check both the maximum and minimum values if
2
Gas Valve
Increase CO at max. rate
2
any adjustment has been made. THERE MUST ALWAYS BE A DIFFERENCE OF 0.4% BETWEEN MAXIMUM & MINIMUM CO2READINGS !
Fig. 57
7. Check the Combustion Performance (CO/CO2ratio). This must be less than 0.004.
8. Briefly press the RESET button to return the boiler to normal operating status and remove the analyser probe.
Refit the sampling point plug & ensure there is no leakage of products !
7212435 - 02 (08/14) EcoBlue Heat 55
Page 56
11 Troubleshooting
11 Troubleshooting
11.1 Error Codes
Operation status and error codes are displayed on the “chimney sweep” button (3) on the control panel. In normal operation this button is illuminated and goes off for a time once periodically.
When normal operation is interrupted for some reason this button will turn off and flash on a number of times periodically. The colour and number of flashes displayed is dependent on the boiler status or fault condition.
The orange LEDs will flash at EVERY heating demand. The number of flashes will correspond with the output of the boiler as shown in the table. e.g. 4 orange flashes = 21kW. This is normal and does not indicate a fault condition.
“Error” or auto reset conditions (Green flashes on “chimney sweep”)
The following table describes the conditions that may result in a blocking signal being displayed.
Status signal 1 flash green
2 flashes green
3 flashes green
4 flashes green
5 flashes green
6 flashes green
The boiler will try to re-start several times, and normal operation will resume once the blocking condition has been eliminated.
Should the conditions persist the boiler may go into lock-out (see following section)
Description Remedial actions by service
engineer
Temperature protection
Shutdown input
Flame loss
Communication fault
Parameter fault
Miscellaneous
• Maximum flow temperature
exceeded,
•Flow temperature rise rate too
high,
• Excessive difference between flow and return temperature
•BL terminals on User Interaction Controller are open circuit
•No flame detected during operation
•Bad connection or wiring fault
Internal communication fault
• Parameter error or faulty PU
• Configuration error or PCB fault
• Internal fault in combustion control unit
•Check system circulation & pump operation
•Check demands for boiler operation (switched live operation)
•Check temperature setting
•Check temperature sensors in boiler
• If condensate pump is wired to these terminals check operation of condensate pump
•Check wiring to BL terminals (link present or connections to external device correct)
•Check gas supply is turned on and gas is available if on a pre-payment meter
•Check flue condition
•Check wiring/connections between boiler and User Interaction Controller and within the box
• If necessary replace control/fan assy
•Replace PU and recommission
•Replace control/fan assy
•Replace combustion control unit
56 EcoBlue Heat 7212435 - 02 (08/14)
Page 57
Troubleshooting 11
Lock-out conditions (Red flashes on “chimney sweep”)
The following table describes the conditions that may result in a lock-out condition and red flashing signal being displayed.
To reset a lock-out condition press and hold the reset button until the fault indication flashes rapidly and goes out.
NOTE: a lock-out condition can be re-set up to 5 times within one hour using the reset button. Any repeating fault should be fully investigated and appropriate remedial actions taken by a Gas Safe registered service engineer.
Status signal 1 flash red
2 flashes red
3 flashes red
4 flashes red
5 flashes red
6 flashes red
Description Possible causes
Sensor error
•Bad connection to flow or return temperature sensor
•Fault with flow or return temperature sensor(s)
•Low or no flow through boiler
• Reverse flow through boiler
High temperature protection
• Over-temperature thermostat on heat exchanger activated
•No water flow through heat exchanger
• Over-temperature thermostat fault or bad connection (open circuit).
•PCB over-temperature condition
•Flue fault resulting in recirculation or activation of air pressure switch (if fitted)
Ignition fault
•No ignition
•No flame detected following ignition
•False flame signal detected
• Repeated loss of flame detected
Fan fault
•Fan calibration error
•Fan failure
Parameter fault
•Bad connection to PU
• Parameter error or faulty PU
Miscellaneous
•Bad connection or wiring fault internal or external to the boiler
• Parameter error
• Communication error
Remedial actions by service engineer
•Check connections to temperature sensors/PCB and condition of wiring loom
•Check resistance
of
temperature sensors
•Check pump operation and system circulation
•Check connections to and operation of O/T thermostat and air pressure switch (if fitted) and PCB and condition of wiring loom
•Check system pressure or that system is not air-locked
•Check pump operation and system circulation
•Check flue condition
•Check earthing of the appliance
•Check ignition electrode condition and clean/replace if necessary
•Check gas valve operation
•Check flue condition
•Check correct
combustion/gas
valve settings
•Check condensate drain for blockage
• If fan operates, check flue installation and condition.
•Replace control/fan assy
PCB and condition of wiring loom
•Replace PU and recommission
•Check all wiring connections
correctly made
are
• Using a service tool or Recom software check all parameter settings
• If necessary replace PU and/or control/fan assy
7212435 - 02 (08/14) EcoBlue Heat 57
Page 58
12 Decommissioning
12 Decommissioning
12.1 Decommissioning Procedure
1. Disconnect the gas & electric supplies and isolate them.
2. Drain the primary circuit and disconnect the filling device.
3 . Dismantle the chimney system and remove the boiler from the wall mounting frame.
58 EcoBlue Heat 7212435 - 02 (08/14)
Page 59
13 Spare Parts
Spare Parts 13
13.1 General
A
B
1. If, following the annual inspection or maintenance any part of the boiler is found to need replacing, use Baxi Spare Parts only.
13.2 Spare Parts List
D
C
E
Key Description Manufacturer’s No. Part No.
A Parameter Unit 7216298
B Sensor Kit 7216301
C Automatic Air Vent 7216300
D Ignition/Sensing Electrode 7216299
E Pressure Switch 7212522
F Combustion Control Unit 7216292
G User Interaction Controller 7600498
H Gas Valve 7618108
I Control & Fan Assembly 7618106
F
G
H
I
7212435 - 02 (08/14) EcoBlue Heat 59
Page 60
Notes 14
60 EcoBlue Heat 7212435 - 02 (08/14)
Page 61
Notes 14
7212435 - 02 (08/14) EcoBlue Heat 61
Page 62
*All installations in England and Wales must be to Local Authority Building Control (LABC) either directly or through a
Competent Persons Scheme. A Building Regulations Compliance
will then be issued to the customer.
www.centralheating.co.uk
© Heating and Hotwater Industry Council (HHIC)
This Commissioning Checklist is to be completed in full by the competent person who commissioned the boiler as a means of demonstrating compliance with the appropriate Building Regulations and then handed to the customer
to keep for future reference.
Failure to install and commission according to the manufacturer’s instructions and complete this Benchmark Commissioning Checklist will invalidate the warranty. This does not affect the customer’s statutory rights.
GAS BOILER SYSTEM COMMISSIONING CHECKLIST
Customer name: Telephone number:
Address:
Boiler make and model:
Boiler serial number:
Commissioned by (PRINT NAME): Gas Safe register number:
Company name: Telephone number:
Company address:
Commissioning date:
CONTROLS (tick the appropriate boxes)
Time and temperature control to heating
Room thermostat and programmer/timer Programmable room thermostat
Load/weather compensation Optimum start control
Time and temperature control to hot water Cylinder thermostat and programmer/timer Combination Boiler
Heating zone valves Fitted Not required
Hot water zone valves Fitted Not required
Thermostatic radiator valves Fitted Not required
Automatic bypass to system Fitted Not required
Boiler interlock Provided
ALL SYSTEMS
’s instructions Yes
What system cleaner was used?
What inhibitor was used? Quantity litres
Yes No
CENTRAL HEATING MODE measure and record:
Gas rate m³/hr OR ft³/hr
Burner operating pressure (if applicable) mbar OR Gas inlet pressure mbar
°C
Central heating return temperature °C
COMBINATION BOILERS ONLY
Is the installation in a hard water area (above 200ppm)? Yes No
Yes No
DOMESTIC HOT WATER MODE Measure and Record:
Gas rate m³/hr OR ft³/hr
Burner operating pressure (at maximum rate) mbar OR Gas inlet pressure at maximum rate mbar
Cold water inlet temperature °C
Hot water has been checked at all outlets Yes Temperature °C
I/min
CONDENSING BOILERS ONLY
The condensate drain has been installed in accordance with the manufacturer’s instructions and/or BS5546/BS6798 Yes
ALL INSTALLATIONS
Record the following:
At max. rate: CO ppm AND CO/CO
²
Ratio
At min. rate: (where possible) CO ppm AND CO/CO
²
Ratio
The heating and hot water system complies with
the appropriate Building Regulations Yes
The boiler and associated products have been installed and commissioned in accordance with the manufacturer’s instructions Yes
The operation of the boiler and system controls have been demonstrated to and understood by the customer Yes
The manufacturer’s literature, including Benchmark Checklist and
Service Record, has been explained and left with the customer Yes
Commissioning Engineer’s Signature
Customer’s Signature
www.centralheating.co.uk
62
Page 63
www.centralheating.co.uk
It is recommended that your heating system is serviced regularly and that the appropriate Service Interval Record is completed.
Service Provider
Before completing the appropriate Service Record below, please ensure you have carried out the service as described in the manufacturer’s instructions.
SERVICE RECORD
SERVICE 01
Date:
Engineer name:
Company name:
Telephone No:
Gas safe register No:
Record:
At max. rate: CO ppm AND CO² %
At min. rate:
(Where Possible) CO ppm AND CO
²
%
Comments:
Signature
SERVICE 02
Date:
Engineer name:
Company name:
Telephone No:
Gas safe register No:
Record:
At max. rate: CO ppm AND CO² %
At min. rate:
(Where Possible) CO ppm AND CO
²
%
Comments:
Signature
SERVICE 03
Date:
Engineer name:
Company name:
Telephone No:
Gas safe register No:
Record:
At max. rate: CO ppm AND CO² %
At min. rate:
(Where Possible) CO ppm AND CO
²
%
Comments:
Signature
SERVICE 04
Date:
Engineer name:
Company name:
Telephone No:
Gas safe register No:
Record:
At max. rate: CO ppm AND CO² %
At min. rate:
(Where Possible) CO ppm AND CO
²
%
Comments:
Signature
SERVICE 05
Date:
Engineer name:
Company name:
Telephone No:
Gas safe register No:
Record:
At max. rate: CO ppm AND CO² %
At min. rate:
(Where Possible) CO ppm AND CO
²
%
Comments:
Signature
SERVICE 06
Date:
Engineer name:
Company name:
Telephone No:
Gas safe register No:
Record:
At max. rate: CO ppm AND CO² %
At min. rate:
(Where Possible) CO ppm AND CO
²
%
Comments:
Signature
SERVICE 07
Date:
Engineer name:
Company name:
Telephone No:
Gas safe register No:
Record:
At max. rate: CO ppm AND CO² %
At min. rate:
(Where Possible) CO ppm AND CO
²
%
Comments:
Signature
SERVICE 08
Date:
Engineer name:
Company name:
Telephone No:
Gas safe register No:
Record:
At max. rate: CO ppm AND CO² %
At min. rate:
(Where Possible) CO ppm AND CO
²
%
Comments:
Signature
SERVICE 09
Date:
Engineer name:
Company name:
Telephone No:
Gas safe register No:
Record:
At max. rate: CO ppm AND CO² %
At min. rate:
(Where Possible) CO ppm AND CO
²
%
Comments:
Signature
SERVICE 10
Date:
Engineer name:
Company name:
Telephone No:
Gas safe register No:
Record:
At max. rate: CO ppm AND CO² %
At min. rate:
(Where Possible) CO ppm AND CO
²
%
Comments:
Signature
*All installations in England and Wales must be
to Local Authority Building Control (LABC) either directly or through a
Competent Persons Scheme. A Building Regulations Compliance
will then be issued to the customer.
© Heating and Hotwater Industry Council (HHIC)
63
Page 64
All descriptions and illustrations provided in this leaflet have been
carefully prepared but we reserve the right to make changes and
improvements in our products which may affect the accuracy of the
information contained in this leaflet. All goods are sold subject to our
standard Conditions of Sale which are available on request.
BAXI
A Trading Division of Baxi Heating UK Ltd (3879156)
Brooks House, Coventry Road, Warwick. CV34 4LL After Sales Service 0844 871 1525 Technical Enquiries 0844 871 1555 Website www.baxi.co.uk e&oe
7212435 - 02 (08/14)
Loading...