Baumer TCR6 Operating Instructions Manual

Valid for FlexTop™ 2202 / 2211 / 2221
The FlexProgrammer configuration unit must not be connected to the FlexTop within the hazardous area.
Configuration procedure:
a. Disconnect mains from the 4...20 mA loop circuit b. Disconnect the product from the circuitry within the hazardous area c. Bring the product to the safe area d. Connect the FlexProgrammer and perform the configuration e. Reinstall the product in the hazardous area f. Connect the power supply to the circuit
Valid for FlexTop™ 2221 only
Configuration for the FlexTop™ 2221 can be made within the hazardous area by means of a handheld HART configurator, providing the precau­tions and guidelines described in the products manual are observed.
www.baumer.com
Page 1 / 16
2019-10-29 Design and specifications subject to change without notice
CombiTempTCR6 is a temperature sensor, based on RTD technolo­gy, which is designed and produced to meet the requirements in general industry where threaded connections are used.
CombiTempTCR6 comprises a series of basic elements which can be combined in various ways to a CombiTemp TCR6 temperature sensor. The product offers great flexibility in respect to modification, service and maintenance.
The sensor can be made to feature a RTD output signal or with a built in FlexToptemperature transmitter types 2202, 2211, 2221 with 4-20 mA output and the type 2231 with Profibus output (for documentation of FlexTops, please see relevant data sheet or operating instructions).
Description
Safety instructions
This instrument is built and tested according to the current EU-directives and packed in technically safe conditions. In order to maintain this condi­tion and to ensure safe operation, the user must follow the hints and warnings given in this instruction.
During the installation the valid national rules have to be observed. Ig­noring the warnings may lead to severe personal injury or substantial damage of property.
The product must be operated by trained staff. Correct and safe opera­tion of this equipment is dependent on proper transport, storage installa­tion and operation.
All electrical wirings must conform to local standards. In order to prevent stray electrical radiation, we recommend twisted and shielded input cables and also to keep power supply cables separated from the input cables. The connection must be made according to the connection dia­grams.
Before switching on the power supply take care that other equipment is not affected. Ensure that the power voltage and the conditions is the environment comply with the specification of the device.
Before switching of the power supply voltage, check the possible effects on other equipment and the processing system.
ATEX application - configuration
WARNING
For electrical installations and commissioning of the explosion protected devices, the data given in the conformity certificate as also the local regulations for installation of electrical apparatus within explosion pro­tected areas must be considered. The intrinsically safe versions can be mounted in the explosion hazarded area according to its specification and only connected to a certified intrinsically safe supply loop with the corresponding electrical values.
After mounting of the device - do check that the housing has a ground potential.
The product contains not replaceable parts, except from insert and/or FlexTop transmitter if selected. In case of malfunction the product must be sent to Baumer for repair.
Technical specifications
Sensor and connection material Stainless steel, AISI 316L
Housing
M16 3 … 9 mm
M16 5 … 9 - M20 8 … 13 -
Media temperature -50...400°C on sensor tube tip
Ambient temperature (cable) -50...160°C w. RTD output
-50...85°C w. transmitter
Environment
Pressure ≤100 bar
Humidity <98% RH, condensing
Protection class IP65
Vibrations GL, test 2 (sensor tube <200 mm)
English page 1...4 Deutsch Seite 5...8 Français page 9...12
Operating instructions: 11119033 08
Operating instructions for temperature sensor
TCR6
Industrial temperature sensor
www.baumer.com
Sensor element specifications (DIN/EN/IEC 60751)
Sensor element Pt100
Accuracy (sensor element) Class B ±(0,3 + 0,005×t)°C
- 1/3 B ±1/3 × (0,3 + 0,005×t)°C
- 1/6 B ±1/6 × (0,3 + 0,005×t)°C Class A ±(0,15 + 0,002×t)°C
Single element 1 × Pt100 Double element 2 × Pt100
Connection 2-wire or 4-wire
Sensor element Pt1000
Accuracy (sensor element) Class B ±1/3 × (0,3 + 0,005×t)°C
Connection 2-wire
Material Stainless steel, AISI 316L
Sensor tube diameter Ø6, Ø8 or Ø10 mm
Sensor tube and process connection
R 1/2 (½BSPT) G 1/2 A G 1/2 G 1/2 A, G 3/4 A G 3/4 A G 3/4 M18 × 1,5 G 1 A M20 × 1,5 ½-14 NPT
76
71
M20
Connection A A/F L
Without 18.5 Ø18 25...3.000
G 1/2 A, R 1/2 20.5 22.0 25...3.000
M18, M20 20.5 22.0 25...3.000
½-14 NPT 20,5 22.0 25...3.000
G 1/2 A nipple 40,0 27.0 25...3.000
G 3/4 A nipple 44,5 32.0 25...3.000
G 1 A nipple 47,5 36.0 25...3.000
G 1/2 union 51.0 27.0 25...3.000
G 3/4 union 51.0 32.0 25...3.000
Connection Norm
G 1/2 A
ISO 228/1
DIN 3852 form A
R 1/2 ISO 7/1
M18, M20 ISO 261
½-14 NPT
ANSI/ASME
B1.20.1
G 1/2 A, G 3/4 A, G 1 A nipple
ISO 228/1
G 1/2, G 3/4 union ISO 228/1
Sensor tip
Standard Fast response
Ø4 × 20 mm
DIN form B head
Response time (time constant)
0,5
Sensor
diameter
Sensor
tip
Insert Liquid
0,4 m/sec
Air
3 m/sec
Air
0 m/sec
Ø6 mm Fast <1,5 sec <21,4 sec <135,6 sec
Standard <6,1 sec <27,2 sec <137,8 sec
8 mm Fast <1,5 sec <33,6 sec <181,0 sec
Standard <7,6 sec <47,7 sec <200,9 sec
Standard Yes <13,6 sec <51,1 sec <253,1 sec
10 mm Fast <1,5 sec <46,8 sec <238,9 sec
Standard <11,1 sec <57,8 sec <270,6 sec
Standard Yes <28,1 sec <67,0 sec <271,1 sec
°C
100
80
60
40
20
1
2
3
1: Sensor without thermowell (Embedded sensor)
2: Sensor with thermowell, with thermal compound
3: Sensor with thermowell, without thermal compound
Note: When a thermowell is used, the time delay increases. The delay is the time duration for the sensor to reflect the correct temperature after a temperature change in the media.
0 1 2 3 4 5 6 7 8 9 10 Minutes
Page 2 / 16 Operating instructions: 11119033 08
English
Operating instructions for temperature sensor
TCR6
Industrial temperature sensor
www.baumer.com
The CombiTempTCR6 can be mounted in more different ways.
1. Sensor tube without connection
Baumer offers compression glands fitting Ø6 and Ø8 mm sensor diameter. This type of mounting is normally used for mounting a sensor direct into a non-pressurized application. If pressurized, ensure that the
connection is tightened correct, so no leakage occur.
A duct channel mounting flange for 8 mm sensor is also available (type: ZPX1-002)
All threaded connection can be mounted direct into the application without thermowell, however often a thermowell is required to enable the user to take out the sensor for e.g. calibration without opening the system.
2. Sensor with male threaded process connection G 1/2 A
This G 1/2 A connection can be mounted in a Baumer thermowell type ZPT4. The process connection available are R 1/2, G 1/2 A, G 3/4 A, M20×1,5 or with hygienic ISO 2852 clamp DN 38
3. Sensor with male threaded process connection G 3/4 A and G 1 A and sensors with G 1/2 or G 3/4 female thread
For these connections a special thermowell can be supplied.
Mount the gland/pocket into the application and install the sensor after the gland/pocket is fixed to the application. This will ensure that the cable is not twisted during mounting.
Baumer recommend to use a thermal compound filled into the thermowell ensure best possible heat transfer between the pocket and the Com­biTemp TCR6.
Baumer offers a 6 gram bag Thermal compound, type ZPX1-001.
Mounting
Electrical connection
Temperature transmitter Ceramic terminal block
Pt100
2-w 4-w 3-w 2-w
- +
4...20 mA
Pt100
2-w 3-w 4-w 2-w
White White Red Red
Warning
Note: Check the maximum temperature for the cable used.
Ambient temperature with built in transmitter: -40...85°C
Page 3 / 16 Operating instructions: 11119033 08
English
Operating instructions for temperature sensor
TCR6
Industrial temperature sensor
Ambient temperature with ceramic block: -40...160°C
Cable sensor insert
Single element, 4-wire Single element, 2-wire
Double element
M12 plug version
Transmitter:
Pin 1 = 4...20 mA + Pin 3 = 4...20 mA -
Ceramic block, 2-wire:
Pin 1/2 = 1st wire Pin 3/4 = 2nd wire
Ceramic block, 4-wire:
Pin 1 = 1st wire Pin 2 = 2nd wire Pin 3 = 3rd wire Pin 4 = 4th wire
Ceramic block, double element
Pin 1 = Element 1, 1st wire Pin 2 = Element 1, 2nd wire Pin 3 = Element 2, 1st wire Pin 4 = Element 2, 2nd wire
www.baumer.com
Page 4 / 16 Operating instructions: 11119033 08
English
Approval ATEX II 1G, Ex ia IIC T5/T6 Voltage supply range 8...28 V DC Internal inductivity Li ≤10 µH
Internal capacity Ci ≤10 nF Temperature class T1...T5: -40 <Tamb <85°C
T6: -40 <Tamb <50°C Barrier data Ui: ≤28 VDC
Ii: ≤0,1A Pi: ≤0,7 W
Approval ATEX II 1G, Ex ia IIC T5/T6 Voltage supply range 2211 6,5...30 V DC
2221 8 … 30 V DC Internal inductivity Li ≤15 µH
Internal capacity Ci ≤5 nF Temperature class T1...T5: -40 <Tamb <85°C
T6: -40 <Tamb <50°C Barrier data Ui: ≤28 VDC
Ii: ≤0,1A Pi: ≤0,7 W
Approval ATEX II 3G, Ex nA IIC T4/T5 Voltage supply range
2202, 2221: Ui: 8...30 V DC, 2211: Ui: 6,5...30 V DC, Ii: <100 mA
Temperature class T4: -20 <Tamb <70°C T5: -20 <Tamb <60°C
Ex-data for FlexTop TM 2211 and 2221
Hazardous area (ATEX)
Ex-data for FlexTop TM with nA approval
Ex-data for FlexTop TM 2202
Electrical connection ATEX ia
Approval ATEX II 1G, Ex ia IIC T5/T6 Internal inductivity Li ≤0 µH
Internal capacity Ci ≤0 nF Temperature class T1...T5: -40 <Tamb <75°C
T6: -40 <Tamb <60°C Barrier data Ui: ≤15 VDC
Ii: ≤50 mA Pi: ≤25 mW
Ex-data for Simple apparatus (no transmitter or display)
The CombiTempTCR6 can be supplied for hazardous area. Either as a Simple Apparatus with RDT output or with built in transmitter with 4 … 20 mA output.
A CombiTempTCR6 with built in transmitter will have two possible ATEX approvals, Ex ia (zone 0, 1 or 2) or Ex nA (zone 2).
II 1 G, EX ia IIC T4/T5, Gas II 3 G, Ex nA IIC T4/T5, Gas
The remaining Ex parameters depend on the type of transmitter and display selected for the product. See detailed data below.
The CombiTempTCR6 with Ex ia must be installed in accordance with prevailing guidelines for zone 0 and zone1 and a certified intrinsi­cally safe zener barrier with the listed maximum values must be used. Electrical connection for the temperature transmitter as per below dia­gram.
CombiTempTCR6 with Ex nA must be installed in accordance with prevailing guidelines for zone 2 without a barrier.
Pt100
2-w 4-w 3-w 2-w
- 4...20 mA +
Hazardous Safe
+
Barrier
Supply and output
Operating instructions for temperature sensor
TCR6
Industrial temperature sensor
Factory settings
FlexTop 2202
Range: 0...120°C
Connection: 2-wire
Damping: 0 s
Sensor break detection: 23 mA
FlexTop 2211 / 2221 / 2212 / 2222
Range: 0...100°C
Connection: 2-wire
Damping: 0 s
Sensor break detection: 23 mA
www.baumer.com
Der CombiTempTCR6 ist ein Temperatursensor auf Basis der RTD
-Technologie, der für die Anforderungen in allgemeinen Industriean­wendungen mit Gewindeanschlüssen entwickelt wurde.
Der CombiTemp TCR6 besteht aus einer Reihe von Grundelemen­ten, die auf verschiedene Weise zu einem CombiTemp TCR6 Tem­peratursensor zusammengestellt werden können. Das Produkt bietet
größte Flexibilität im Hinblick auf Modifizierbarkeit, Service und War­tung.
Der Sensor kann für ein RTD-Ausgangssignal konfiguriert werden oder mit einem integrierten FlexTop Temperaturmessumformer Typ 2202, 2211 oder 2221 mit 4-20-mA-Ausgang sowie Typ 2231 mit Pro­fibus-Ausgang ausgestattet werden. (Die Dokumentation für FlexTop Temperaturmessumformer finden Sie im entsprechenden Datenblatt bzw. der zugehörigen Bedienungsanleitung.)
Beschreibung
Sicherheitshinweise
Dieses Gerät wurde gemäß den geltenden EU-Richtlinien gebaut und geprüft und in technisch sicherem Zustand verpackt. Um diesen Zu­stand zu erhalten und einen sicheren Betrieb zu gewährleisten, muss der Anwender die in dieser Anleitung gegebenen Anweisungen und Warnhinweise befolgen.
Bei der Installation sind die im jeweiligen Land geltenden Vorschriften zu beachten. Die Nichtbeachtung der Warnhinweise kann zu erhebli­chen Personen- und Sachschäden führen.
Das Produkt darf nur von geschultem Personal bedient werden. Sach­gemäßer Transport sowie eine sachgemäße Lagerung, Installation und Bedienung sind entscheidend für einen korrekten und sicheren Betrieb dieses Gerätes.
Die gesamte elektrische Verkabelung muss den örtlichen Standards entsprechen. Um elektrische Störstrahlung zu vermeiden, empfehlen wir, verdrillte und geschirmte Eingangskabel zu verwenden und die Stromversorgungskabel von den Eingangskabeln getrennt zu halten. Die Anschlüsse müssen gemäß den Schaltplänen ausgeführt werden.
Vor dem Einschalten der Spannungsversorgung ist darauf zu achten, dass keine anderen Geräte beeinflusst werden. Es ist sicherzustellen, dass die Versorgungsspannung und die Umgebungsbedingungen den Spezifikationen für dieses Gerät entsprechen.
Vor dem Abschalten der Versorgungsspannung sind mögliche Auswir­kungen auf andere Geräte und das gesamte System zu prüfen.
ATEX-Anwendungen – Konfiguration
Gültig für FlexTop 2202 / 2211 / 2221
Das FlexProgrammer Konfigurationsgerät darf in der gefährlichen Umgebung nicht an den FlexTop angeschlossen werden.
Konfiguration:
a Netz vom 4...20 mA-Regelkreis trennen.
b Das Produkt vom Schaltkreis im gefährlichen Bereich trennen.
c Produkt in den sicheren Bereich bringen.
d FlexProgrammer anschließen und die Konfiguration durchführen.
e Das Produkt wieder im gefährlichen Bereich installieren.
f Versorgungsspannung an den Schaltkreis anschließen.
Nur gültig für FlexTop 2221
Die Konfiguration für FlexTop 2221 kann im gefährlichen Bereich mithilfe eines HART-Handkonfigurators erfolgen, vorausgesetzt, dass die im Handbuch des Produkts beschriebenen Vorsichtsmaßnahmen und Richtlinien eingehalten werden.
WARNUNG
Bei der elektrischen Installation und Inbetriebnahme von explosions­geschützten Geräten sind die Daten im Konformitätszertifikat und die örtlichen Vorschriften für die Installation von elektrischen Geräten in explosionsgeschützten Bereichen zu beachten. Die eigensicheren Versionen sind im explosionsgefährdeten Bereich gemäß ihrer Spezifi­kation zu montieren und dürfen nur an eine zertifizierte eigensichere Spannungsversorgung mit entsprechenden elektrischen Werten ange­schlossen werden.
Nach der Montage des Gerätes ist unbedingt zu prüfen, ob das Ge­häuse mit einem Erdpotenzial verbunden ist.
Dieses Produkt enthält keine austauschbaren Teile, mit Ausnahme des Einsatzes bzw. des FlexTop Messumformers, falls eine solche Ausfüh­rung gewählt wurde. Bei Fehlfunktion ist das Produkt zur Reparatur an
Baumer einzusenden
Technische Daten
Material Sensor und Anschluss Edelstahl , AISI 316L
Gehäuse DIN Form B, Aluminium, grau
Elektrischer Anschluss Standard M20
Optional M16
M12-A
Kabeldurchmes. messing vernick. M16 3 … 9 mm im Kabelver- messing vernick.
schraubung (Geschirmt) M16 5 … 9 -
messing vernick. M20 8 … 13 -
Medientemperatur -50...400°C an der Sensorrohrspitze
Umgebungstemperatur -50...160°C mit RTD-Ausgang
-50...85°C mit Messumformer
Umgebung
Druck ≤100 bar Feuchtigkeit <98% rF, kondensierend
Schutzart IP65
Vibrationen GL, Test 2 (Sensorrohr < 200 mm)
Seite 5 / 16 Bedienungsanleitung: 11119033 08