Barksdale XT, XTi User Manual

Index: B / 923-1884
Transmitters for bypass level indicators
Features / Description
The measuring principle and construction of this series are identical to those of the XM series, however the XT series is equipped with a 2-wire transmitter module (instead of simple terminals in the KLS terminal box). This transmitter module (transducer) converts the resistance into a 4...20 mA output signal. For e.g. interface measurement the output signal can also be inverted (20...4 mA). A version with linearisation of the tank content graph is available as an option.  Two versions are available: XT - Standard version XTi - EEx i for intrinsically safe applications Transmitter XT with type MU3L, circuit monitoring with selective fault recognition and selective output control (Namur NE43) 3.5 mA or 23 mA, reversed polarity protection. Transmitter XTi with type MUEX, intrinsically safe transmitter module with ATEX approval EEx ia IIC T1...T6, reversed polarity protection and fault recognition with selective output control (Namur NE 43) 3.5 mA or 23 mA.
Technical Data
Power supply:
XT: Xti:
Output:4…20 mA, reversed polarity protected Load:max. 700 Ohm at 24 V Delay:0.33 sec Accuracy:max. ±0.2% f. s. Temperature range:
XT:
 8…35 VDC, max. 10% residual ripple 8…24 VDC, max. 10% residual ripple
-40 °C... +85 °C
-50 °C…+150 °C for high-temperature version
Level
Dimensions (mm / inch)
Circuit diagram
Type XT/XTi TransmittersType XT/XTi
Type XT/XTi TransmittersType XT/XTi
XTi:
NoteThe configuration of the selective output
Order Code
Order number example for XT:
XT-HT-R12-LM2500
Order number example for XTi :
XTi-R12-LM2500
T1…T4: -40 °C…+85 °C T5 and T6: -40 °C…+60 °C
control for fault recognition is ≤3.5 mA unless expressly specified otherwise in the order.
Measuring length LM in mm
Screen R12
HT high-temperature version (option)
Type: XT = KLS (incl. Transducer)
Measuring length LM in mm
Screen R12
Type: XTi = KLS (incl. Transducer)
Barksdale
Subject to technical changes.