Bard WFERV-A-X, WFERV-A-4 Installation Instructions Manual

INSTALLATION INSTRUCTIONS
ENERGY RECOVERY VENTILATOR
WITH EXHAUST
MODELS:
WFERV-A-X
WFERV-A-4
Bard Manufacturing Company, Inc. Bryan, Ohio 43506
Since 1914...Moving ahead, just as planned.
Manual: 2100-495A Supersedes: 2100-495 File: Volume III, Tab 19 Date: 04-02-08
Manual 2100-495A Page 1 of 21
CONTENTS
Model Nomenclature Legend..................................... 3
Electrical Specifications............................................. 3
General Description ................................................... 3
General Information ................................................... 3
Unpacking .................................................................. 3
Performance and Application Data - WFERV............ 4
Basic Installation (Field Installation)................... 5 & 6
Basic Installation (Factory Installed Versions)......... 15
Figures
Figure 1 Intake Hood Assembly ............................ 6
Figure 2 Remove Vent Option Door...................... 7
Figure 2A Assembly of Exhaust Blower Enclosure ... 7
Figure 3 Filter & Exhaust Plate Location .............. 8
Control Wiring.......................................................... 15
Control Requirements.............................................. 15
Recommended Control Sequences......................... 15
Ventilation Airflow .................................................... 15
Energy Recovery Ventilator Maintenance ............... 16
Maintenance Procedures......................................... 16
Quarterly & Annual Maintenance............................. 17
Wiring Diagram ........................................................ 21
Tables
Table 1 Ventilation Air (CFM)................................ 16
Figure 4
Figure 5 Installation of WFERV........................... 10
Figure 6 WFERV Assembly..................................11
Figure 7 Wiring - 230 Volt ................................... 12
Figure 8 Installation of Fresh Air Intake
Figure 9 Operation of Unit with WFERV ............. 14
Figure 10 Thermostat Wiring ................................ 18
Figure 11 Terminal Block Location Diagram ......... 19
Figure 12 Hub Assembly with Ball Bearings ......... 20
Installation of Exhaust Blower Assembly ...
Hood Assembly ..................................... 13
BARD MANUFACTURING COMPANY , INC.
BRYAN, OHIO USA 43506
9
Manual 2100-495A Page 2 of 21
MODEL NOMENCLATURE LEGEND
WF = Wall Mount Gas Furnace
WF ERV – X
Energy Recovery Ventilator
ELECTRICAL SPECIFICATIONS
lortnoC
ledoMegatloVspmA
VREFW802/0321.2V42
egatloV
GENERAL DESCRIPTION
The Energy Recovery Ventilator was designed to provide energy efficient, cost effective ventilation to meet I.A.Q. (Indoor Air Quality) requirements while still maintaining good indoor comfort and humidity control for a variety of applications such as schools, classrooms, lounges, conference rooms, beauty salons and others. It provides a constant supply of fresh air for control of airborne pollutants including CO2, smoke, radon, formaldehyde, excess moisture, virus and bacteria.
The ventilator incorporates patented rotary heat exchanger technology to remove both heat and moisture.
It is designed as a single package, which can be easily factory or field installed for new installations or retrofit to Bard WF wall mounted units. The package consists of a unique rotary Energy Recovery Cassette that can be easily removed for cleaning or maintenance. The cassette has a 21-inch diameter heat transfer wheel for efficient heat transfer. The heat transfer wheel uses a permanently bonded dry desiccant coating for total heat recovery.
Ventilation is accomplished with two (2) blower/motor assemblies each consisting of a drive motor and dual blowers for maximum ventilation at low sound levels. On non-independent motor control models, the air is exhausted at the same rate that fresh air is brought into the structure, thus not impacting building pressure. On independent motor control models, the air can be exhausted at a different rate than the intake or fresh air. Never operate the fresh air at a lower speed than the exhaust air. Operating the fresh air at a higher speed than the exhaust air will help maintain a slight positive pressure in the building. The rotating energy wheel provides the heat transfer effectively during both summer and winter conditions. Provides required ventilation to meet the requirements of ASHRAE 62.1­2007 standard.
Color
-X = Beige
-4 = Buckeye Gray
NOTE: Never set intake blower at a lower speed than
the exhaust blower, as it will create a negative pressure in the room.
During operation below 5 degrees F outdoor temperature, freezing of moisture in the heat transfer wheel can occur. Consult the factory if this possibility exists.
GENERAL INFORMATION
The ventilator should only be installed by a trained heating and air conditioning technician. These instructions serve as a guide to the technician installing the ventilator package. They are not intended as a step­by-step procedure with which the mechanically-inclined owner can install the package.
The ventilator housing is shipped in one carton, which contains the following:
1. Energy Recovery Ventilator
2. Service Door
3. Rain Hood and Mist Eliminator
4. Installation Instructions
UNPACKING
Upon receipt of the equipment, be sure to compare the model number found on the shipping label with the accessory identification information on the ordering and shipping document to verify that the correct accessory has been shipped.
Inspect the carton housing of each ventilator as it is received, and before signing the freight bill, verify that all items have been received and that there is no visible damage. Note any shortages or damage on all copies of the freight bill. The receiving party must contact the last carrier immediately, preferably in writing, requesting inspection by the carrier’s agent. Concealed damage not discovered until after loading must be reported to the carrier within 15 days of its receipt.
Manual 2100-495A Page 3 of 21
tneibmA
.D.O
/BD
BWF
5015707
56 08
57
001
07 56 06
08 57 07
59
56 06
08 57 07
09
56 06
08 57 07
58
56 06
57 07
08
56 06
07
57
56
APPLICATION DATA — WFERV
SUMMER COOLING PERFORMANCE
(INDOOR DESIGN CONDITIONS 75°DB/63°WB)
MFC054ETARNOITALITNEV
)kcalB(deepShgiH
YCNEICIFFE%27
TLVSLVLLVTRHSRHLRHTLVSLVLLVTRHSRHLRHTLVSLVLLVTRHSRHLRH
00471
00821
00821
00821
00821
00701
00662
00701
00571
00701
00701
00701
00701
00701
00701
0068
00862
0068
00771
0068
0069
0068
0068
0068
0068
004
00862
6
00771
0046
0069
0046
0046
0046
0046
0046 0034
00172
0034
00971
0034
0079
0034
0034
0034
0034
0012
0081 0089 0052 0012
00001 0062
51 0012 0012 0012
0 0
0029
0
0029
0
00191
00951
00621
0086
0077
0 0 0
00281 0019
21 0001 0 0
00402 00311 0023 0 0
00822 00631 0045 0 0
009 0077 004 0
00001 0062
077 0077 0077
00391 007 0096 0026 0026
00381 00721 0096 0064 0064
00591
013 00921 0096 0013 0013
00031 0007 0081 0051
0027
0
0091
0
0
0029
0
0029 0077
00411
0077
0094
0
0 0
0077
0
0077
00131
0026
0056
0026
007
0026
0
0026
0
0026
00741
0064
0018
0064
0032
0064 0064 0064
0 0013 0013 0013 0013
0051 0051 0051 0051
8 0 0
00461 0089 0083 0 0
00511 0055 0003 0
0027 0091
00211
00211
0
00211
0211
0049
00432
0049
00451
0049
0049
0049
0049
0049
0049
0057
00432
0057
00551
0057
0048
0057
0057
0057
0057 00532
0065
00651
0065
004
0065 0065
0065
0065
0065
0083
00832
0083
00851
0083
0068
0083
0083
0083
0083
0091
00851
0091
0078
0091
0032 0091
0088 0042
4
0091
0 0
00211
00251
0033
0029
00521
0064
00821
00111
0004
0028
0
0028
0
00171
00041
00211
0006
0096
0
0096
0
0096
0 00951
00171
0008
00211
009
0016 0055
0
0055
0
00271
00971
00411
00001
0016
0082
0014
0
0014
0
00471
00002
00511
00021
0
0084
036
0
0082
0
0082
00931
00511
0086
0036
00
0071 0041
0 0088
0046
0042
0571
MFC073ETARNOITALITNEV
)eulB(deepSmuideM
YCNEICIFFE%37
0019
00421
0092
0028
0
0028
0
0028 0096
00201
00
96
0 0
0034 0
0096
0
0096
0
0096
00611
0055
0075
0055
006
0055
0
0055
0
0055
00131
0014
0037
0014
0002
0014
0
0014
0
0014
00641
0082
0078
0082
0053
0082
0
0082
0
0082
00101
0041
0094
0041
003
0041
0
0041
0046 0571
0019
0019
0019
0019
0067
00981
0067
00421
0067
0067
0067
0067
0067
0067
0016
00091 00521 0086 0016 0016
0
0191
00721 0096 0064 0064
00291 00721 0096 0003 0003
00821 0007 0081 0051
0017 0091
921 0016 0016 0016 0016
0064 0064 0064 0064 0064
0003 0003 0003 0003 0003
0051 0051 0051 0051
0 0
0033 0 0
00311 0084 0 0 0
00 0046 007 0 0
00541 0018 0032 0 0
00261 0079 0093 0 0
00311 0055 003 0
0017 0091
ETARNOITALITNEV 082 MFC
0029 0076 0076
00041 0029 0065 0065 0065
00041 0029 0005 0054 0054
00141 0049 0015 0043 0043
00241 0049 0015 0022 0022
0059 002
5
0031 0011
0025 0041
)deR(deepSwoL
YCNEICIFFE%47
0076 0076 0076
0065 0065 0065 0065 0065
0054 0054 0054 0054 0054
0043 0043 0043 0043 0043
0022 0022 0022 0022 0022
0011 0011 0011 0011
0 0
0052 0 0
0048 0063 0 0 0
0059 0074 005 0 0
00701 0006 0071 0 0
00021 0027 0092 0 0
0048 0014 002 0
0025 0041
WINTER HEATING PERFORMANCE
(INDOOR DESIGN CONDITIONS 70° F DB)
ETARNOITALITNEV
tneibmA
.D.O
MFC054
.FFE%67
MFC073
.FFE%87
MFC082
.FFE%08
F°BDLVWRHWLVWRHWLVWRHW
56009402730043056200420291 06004606840094028300930213 55009700060046099400450234 05004905170097061600960255 540081107980099027700580086 040014101701008110029003010428 5300371051310053103501002110698 03009810634100751052210073106901 52002120116100771008310045102321 02006320497100791073510017108631 51009520869100712039610088104051
NOTE: Sensible performance only is shown for winter application
Manual 2100-495A Page 4 of 21
LEGEND:
VLT = Ventilation Load – Total VLS = Ventilation Load – Sensible VLL = Ventilation Load – Latent HRT = Heat Recover – Total HRS = Heat Recovery – Sensible HRL = Heat Recovery – Latent WVL = Winter Ventilation Load WHR = Winter Heat Recovery
BASIC INSTALLATION (Field Installation)
1. Unpack the ventilator assembly, which includes the integral ventilator with attached electrical harness and miscellaneous hardware.
WARNING
Open breaker switch before installing this accessory to prevent injury or death due to electrical shock or contact with moving parts. Turn thermostat to OFF.
htiWesUroF
ledoM
VREFW521-050FW
2. Remove intake hood assembly from back of ventilator. (See Figure 1.)
3. Remove the existing exterior vent option door on the unit. (See Figure 2.)
4. Remove and save existing unit air filter. Remove and discard the rear exhaust cover plate. (See Figure 3.)
5. Install exhaust blower assembly in rear exhaust opening and secure with four (4) screws. Position 4 pin connector so it is accessible. (See Figure 4.) Assemble exhaust blower enclosure as shown in Figure 2A. Fasten exhaust blower enclosure to bottom of unit as shown in Figure 4.
6. Install ventilator into the unit. (See Figure 5.)
IMPORTANT NOTE: Position front lip of ventilator
over front grille and on top of condenser partition. (See Figure 5.) This is important to insure proper
stinUgniwolloFlacirtcelE
1-802/032 esahp3ro
drainage of any water entering damper assembly.
7. Remove cassette and plug in exhaust blower. Replace cassette. (See Figure 6.)
8. Open control panel to gain access to unit low voltage terminal block. (Insure all power is OFF prior to opening the control panel.)
9. Remove female plug of low voltage wiring harness from the heat recovery assembly and snap into filter rack. Route electrical harness leads through the bushing into the low voltage box. (See Figure 5.)
10. Connect leads C (black), W (blue), and G (orange) with fork terminal to corresponding points on terminal strip. (See Figure 7 for 230V units.)
NOTE: These 24 volt control wires control the
starting and stopping of the Energy Recovery Ventilator and can be independently controlled by an energy management control or timer. See separate section on Control Wiring for suggested control schemes.
11. Remove female plug of high voltage wiring harness from the heat recover assembly and snap into filter rack. Wire to terminal block. (See Figure 7 for 230V units.)
12. Plug male plug from female at filter rack. (See Figure 5.)
13. Close control panel cover.
14. Replace filter and one (1) screw in condenser grille. (See Figure 3)
15. Ventilator checkout A. Resupply power to unit. B. Energize the evaporator blower by
switching thermostat to the manual fan position with Heat/Cool in OFF position.
C. Ventilator heat transfer wheels should
rotate slowly (49 RPM). Intake and exhaust blowers should run. (See Figure 9.)
D. De-energize the evaporator blower.
Energy Recovery wheels, and fresh air and exhaust air blowers should stop.
E. This completes ventilator checkout.
7/8"
Manual 2100-495A Page 5 of 21
16. Disconnect the wires connected in Step 10 if other control options are to be used.
17. Replace the lower service access panel with the new panel provided. Attach air intake hood with screws provided. (See Figure 9.) Be sure to insert the top flange of the air intake hood into and through the slot in the service door and between the door and insulation to prevent bowing of the door.
INTAKE HOOD ASSEMBLY
18. Close front door.
19. Apply Certification label, included with Installation Instructions, next to unit Serial Plate.
20. Assemble exhaust blower enclosure as shown in Figure 2A and install on unit as shown in Figure 4 (with screws provided).
21. Ventilator is now ready for operation.
FIGURE 1
Manual 2100-495A Page 6 of 21
FRONT DOOR
VENT OPTION DOOR
FIGURE 2
REMOVE VENT OPTION DOOR
EXHAUST COVER PLATES
FIGURE 2A
ASSEMBLY OF EXHAUST BLOWER ENCLOSURE
PART NUMBERS
COLOR A B C
BEIGE 134-248-X 134-244-X 134-243-X
GRAY 134-248-4 134-244-4 134-243-4
A
B
MIS-2350
B
C
A
MIS-2461
Manual 2100-495A Page 7 of 21
Loading...
+ 14 hidden pages