Bard WE252, WE301, WE371, WE421, WE482 Installation Instructions Manual

...
WALL MOUNTED PACKAGED
AIR CONDITIONER INSTALLATION INSTRUCTIONS
Models:
WE252 WE301 WE371 WE421 WE482 WE602 WE701
THESE MODELS ALL USE REFRIGERANT R-407C
and ARE FOR 50HZ OPERATION.
Bard Manufacturing Company Bryan, Ohio 43506
Since 1914...Moving ahead, just as planned.
MIS-383
Manual No.: 2100-385B Supersedes: 2100-385A File: Volume III, Tab 16 Date: 04-25-05
©
Copyright 2002
CONTENTS
Getting Other Information
...................................1
Wall Mount General Information
Model Nomenclature ............................................ 2
Shipping Damage ................................................ 5
General ................................................................ 5
Duct Work ............................................................ 5
Filters ................................................................... 6
Fresh Air Intake .................................................... 6
Condensate Drain ................................................ 6
Installation Instructions
Wall Mounting Information ................................... 7
Proper Unit Placement ......................................... 7
Mounting the Unit ................................................. 7
Wiring – Main Power .......................................... 12
Wiring – Low Voltage ......................................... 12
Start Up
Important Installer Note...................................... 14
High Pressure Switch ........................................ 14
Service Hints ...................................................... 14
Sequence of Operations .................................... 14
Compressor Control Module .............................. 14
Adjustments ....................................................... 15
Phase Monitor .................................................... 15
Pressure Service Ports ...................................... 15
Troubleshooting
Fan Blade Setting Dimensions .......................... 16
Removal of Fan Shroud ..................................... 16
Refrigerant Charge ............................................ 16
Cooling Pressures ............................................. 18
Optional Accessories ......................................... 19
R-407C Refrigerant
Service Procedures & Considerations ............... 20
Charging ............................................................ 20
Leaks ................................................................. 20
Figures
Figure 1 Unit Dimensions................................... 4
Figure 2 Fresh Air Damper Assembly ................ 6
Figure 3 Mounting Instructions........................... 8
Figure 4 Electric Heat Clearance ....................... 9
Figure 5 Wall-Mounting Instructions ................. 10
Figure 6 Wall-Mounting Instructions ................. 10
Figure 7 Common Wall-Mounting Instructions . 11
Figure 8 Low Voltage Wiring Diagram ............. 13
Figure 9 Fan Blade Setting .............................. 16
Tables
Table 1 Electric Heat Table ............................... 2
Table 2 Electrical Specifications ....................... 3
Table 3 Thermostat Wire Size ........................ 12
Table 4 Wall Thermostat and
Subbase Combinations...................... 12
Table 5 Fan Blade Setting Dimension ............ 16
Table 6 Suction Line Temperatures ................ 16
Table 7 Rated CFM and ESP ......................... 16
Table 8 Indoor Blower Performance ............... 17
Table 9 Maximum ESP of Operation –
Electric Heat Only .............................. 17
Table 10 Cooling Pressures ............................. 18
Table 11 Optional Accessories ......................... 19
Table 12 R-407C Temperature/Pressure Chart 20
GETTING OTHER INFORMATION AND PUBLICATIONS
These publications can help you install the air conditioner or heat pump. You can usually find these at your local library or purchase them directly from the publisher. Be sure to consult current edition of each standard.
National Electrical Code ........................ ANSI/NFPA 70
Standard for the Installation ................ ANSI/NFPA 90A
of Air Conditioning and Ventilating Systems
Standard for Warm Air ........................ ANSI/NFPA 90B
Heating and Air Conditioning Systems
Load Calculation for ............................. ACCA Manual J
Residential Winter and Summer Air Conditioning
Duct Design for Residential ................ ACCA Manual D
Winter and Summer Air Conditioning and Equipment Selection
FOR MORE INFORMATION, CONTACT THESE PUBLISHERS:
ACCA Air Conditioning Contractors of America
1712 New Hampshire Avenue NW Washington, DC 20009 Telephone: (202) 483-9370 Fax: (202) 234-4721
ANSI American National Standards Institute
11 West Street, 13th Floor New York, NY 10036 Telephone: (212) 642-4900 Fax: (212) 302-1286
ASHRAE American Society of Heating Refrigerating,
and Air Conditioning Engineers, Inc.
1791 Tullie Circle, N.E. Atlanta, GA 30329-2305 Telephone: (404) 636-8400 Fax: (404) 321-5478
NFPA National Fire Protection Association
Batterymarch Park P.O. Box 9101 Quincy, MA 02269-9901 Telephone: (800) 344-3555 Fax: (617) 984-7057
Manufactured under the following U.S. patent numbers:
5,485,878; 5,301,744; 5,002,116;
4,924,934; 4,875,520; 4,825,936
Manual 2100-385B Page 1
WALL MOUNT GENERAL INFORMATION
AIR CONDITIONER WALL MOUNT MODEL NOMENCLATURE
WE 42 1 — F 07 X X X X X J
MODEL NUMBER
CAPACITY
25 - 2 TON 30 - 2-1/2 TON 37 - 3 TON 42 - 3-1/2 TON 48 - 4 TON 60 - 5 TON 70 - 6 TON
REVISIONS
VOLTS & PHASE
D - 240/220-50-1 F - 415/380-50-3
VENTILATION OPTIONS
X - BAROMETRIC FRESH AIR DAMPER B - BLANK-OFF PLATE M - MOTORIZED FRESH AIR DAMPER V - COMMERCIAL VENTILATOR
MOTORIZED WITH EXHAUST
E - ECONOMIZER (INTERNAL) - FULLY
MODULATING WITH EXHAUST
R - ENERGY RECOVERY VENTILATOR -
MOTORIZED WITH EXHAUST
KW
COLOR OPTIONS
X-
BEIGE (STANDARD) 1 - WHITE 2 - MESA TAN 4 - BUCKEYE GRAY 5 - DESERT BROWN
FILTER OPTIONS
X - ONE INCH THROWAWAY W - ONE INCH WASHABLE P - TWO INCH PLEATED
OUTLET OPTIONS
X - FRONT (STANDARD)
COIL OPTIONS
X - STANDARD 1 - PHENOLIC COATED EVAPORATOR 2 - PHENOLIC COATED CONDENSER 3 - PHENOLIC COATED EVAPORATOR
AND CONDENSER
CONTROL MODULES
TABLE 1
ELECTRIC HEAT TABLE
D-103EW
sledoMD-252EWF-252EW
WK
1-V042 STTAW
1-V022 STTAW
3-V514 STTAW
3-V083 STTAW
D-173EW
1-V042 STTAW
1-V022 STTAW
0.5110502244844157311050224
0.7 0476656504760665
0.811081276
0.0149991148
0.21 871118049
0.41 0543108211
F-103EW F-173EW
3-V514 STTAW
3-V083 STTAW
3-V514 STTAW
F-124EW F-284EW F-206EW F-107EW
3-V083 STTAW
Manual 2100-385B Page 2
TABLE 2
ELECTRICAL SPECIFICATIONS
1
3
gnitarepO
stloVdetaR
ledoM
Z0D-252EW 50D 80D
Z0F-252EW 50F
Z0D-103EW 50D 01D
Z0F-103EW 70F 21F
Z0D-173EW 50D 01D
Z0F-173EW 70F 21F
Z0F-124EW 70F 41F
Z0F-284EW 70F 41F
Z0F-206EW 70F 41F
Z0F-107EW 70F 41F
1
Maximum size of the time delay fuse or HACR type circuit breaker for protection of field wiring conductors.
2
Based on 75°C copper wire. All wiring must conform to NEC and all local codes.
3
These “Minimum Circuit Ampacity” values are to be used for sizing the field power conductors. Refer to the National Electric Code (latest revision), Article 310 for power conductor sizing.
Caution: When more than one field power conductor circuit is run through one conduit, the conductors must be derated. Pay special attention to Note 8 of Table 310 regarding Ampacity Adjustment Factors when more than three (3) conductors are in a raceway.
IMPORTANT: While this electrical data is presented as a guide, it is important to electrically connect properly sized
fuses and conductor wires in accordance with all existing local codes.
esahPdna
1-022/042452-891
3-083/514654-243
1-022/042452-891
3-083/514654-243
1-022/042452-891
3-083/514654-243
3-083/514654-243
3-083/514654-243
3-083/514654-243
3-083/514654-243
egatloV
egnaR
rebmuN
rewoPdleiF
stiucriC
1 1 1
1 1
1 1 1
1 1 1
1 1 1
1 1 1
1 1 1
1 1 1
1 1 1
1 1 1
muminiM tiucriC
yticapmA
51
72
34
7
01 22
92 55
9
51 32
42 92 55
11
61 52
11
61 03
31 61 03
51 61 03
91 91 23
mumixaM
lanretxE
esuF
tiucriCro
rekaerB
02 03 54
51 51
53 53 06
51 51 52
53 53 06
51 02 52
51 02 03
02 02 03
02 02 03
52 52 53
2
rewoPdleiF
eziSeriW
21 01
8
41 41
8 8 6
41 41 01
8 8 6
41 21 01
41 21 01
21 21 01
21 21 01
01 01 01
2
dnuorG
eziSeriW
21 01 01
41 41
01 01 01
41 41 01
01 01 01
41 21 01
41 21 01
21 21 01
21 21 01
01 01 01
Manual 2100-385B Page 3
MIS-1665
BACK VIEW
FIGURE 1
UNIT DIMENSIONS (IN INCHES)
EFGI JKLMNOPQRSTUABCB
ylppuSnruteR
thgieH
)H(
htpeD
)D(
htdiW
)W(
ledoM
2.83572.71365.0788.788.7288.3188.720.045.8157.5239.7157.6257.8252.920.7257.291.9357.2241.991.40.210.50.21
103EW
252EW3.33521.71365.0788.788.9188.1188.910.535.8157.5265.0257.6260.8252.920.7236.231.4360.2255.0191.40.210.50.21
173EW
124EW
570.24234.22578.4888.988.9288.5188.9288.3401.9166.130.0386.2349.6296.4334.2373.388.2488.320.0144.10.6188.10.61
284EW
206EW
SIDE VIEW
FRONT VIEW
107EW570.2434.22578.4988.988.9288.5188.9288.3401.9166.140.0386.240.7357.445.2473.388.2488.330.010.20.6188.10.12
Manual 2100-385B Page 4
SHIPPING DAMAGE
DUCT WORK
Upon receipt of equipment, the carton should be checked for external signs of shipping damage. If damage is found, the receiving party must contact the last carrier immediately, preferably in writing, requesting inspection by the carrier’s agent.
GENERAL
The equipment covered in this manual is to be installed by trained, experienced service and installation technicians.
The refrigerant system is completely assembled and charged. All internal wiring is complete.
The unit is designed for use with or without duct work. Flanges are provided for attaching the supply and return ducts.
These instructions explain the recommended method to install the air cooled self-contained unit and the electrical wiring connections to the unit.
These instructions and any instructions packaged with any separate equipment required to make up the entire air conditioning system should be carefully read before beginning the installation. Note particularly “Starting Procedure” and any tags and/or labels attached to the equipment.
While these instructions are intended as a general recommended guide, they do not supersede any national and/or local codes in any way. Authorities having jurisdiction should be consulted before the installation is made. See Page 1 for information on codes and standards.
Size of unit for a proposed installation should be based on heat loss calculation made according to methods of Air Conditioning Contractors of America (ACCA). The air duct should be installed in accordance with the Standards of the National Fire Protection Association for the Installation of Air Conditioning and Ventilating Systems of Other Than Residence Type, NFPA No. 90A, and Residence Type Warm Air Heating and Air Conditioning Systems, NFPA No. 90B. Where local regulations are at a variance with instructions, installer should adhere to local codes.
All duct work, supply and return, must be properly sized for the design air flow requirement of the equipment. Air Conditioning Contractors of America (ACCA) is an excellent guide to proper sizing. All duct work or portions thereof not in the conditioned space should be properly insulated in order to both conserve energy and prevent condensation or moisture damage.
Refer to Table 9 for maximum static pressure available for duct design.
Design the duct work according to methods given by the Air Conditioning Contractors of America (ACCA). When duct runs through unheated spaces, it should be insulated with a minimum of one inch of insulation. Use insulation with a vapor barrier on the outside of the insulation. Flexible joints should be used to connect the duct work to the equipment in order to keep the noise transmission to a minimum.
A 1/4 inch clearance to combustible material for the first 3 feet of duct attached to the outlet air frame is required. See Wall Mounting Instructions and Figures 3 and 4 for further details.
Ducts through the walls must be insulated and all joints taped or sealed to prevent air or moisture entering the wall cavity.
Some installations may not require any return air duct. A metallic return air grille is required with installations not requiring a return air duct. The spacing between louvers on the grille shall not be larger than 5/8 inches.
Any grille that meets the 5/8 inch louver criteria may be used. It is recommended that Bard Return Air Grille Kit RG-2 thru RG-5 or RFG-2 thru RFG-5 be installed when no return duct is used. Contact distributor or factory for ordering information. If using a return air filter grille, filters must be of sufficient size to allow a maximum velocity of 400 fpm.
NOTE: If no return air duct is used, applicable
installation codes may limit this cabinet to installation only in a single story structure.
Manual 2100-385B Page 5
Loading...
+ 16 hidden pages