These publications can help you install the air
conditioner or heat pump. You can usually find these at
your local library or purchase them directly from the
publisher. Be sure to consult current edition of each
standard.
National Electrical Code ...................... ANSI/NFPA 70
Standard for the Installation of .......... ANSI/NFPA 90A
Air Conditioning and Ventilating Systems
Standard for Warm Air Heating ........ ANSI/NFPA 90B
Duct Design for ................................. ACCA Manual D
Residential Winter and Summer Air Conditioning
and Equipment Selection
FOR MORE INFORMATION, CONTACT
THESE PUBLISHERS:
ACCAAir Conditioning Contractors of America
1712 New Hampshire Avenue NW
Washington, DC 20009
Telephone: (202) 483-9370
Fax: (202) 234-4721
ANSIAmerican National Standards Institute
11 West Street, 13th Floor
New York, NY 10036
Telephone: (212) 642-4900
Fax: (212) 302-1286
ASHRAE American Society of Heating, Refrigerating
and Air Conditioning Engineers, Inc.
1791 Tullie Circle, NE
Atlanta, GA 30329-2305
Telephone: (404) 636-8400
Fax: (404) 321-5478
NFPANational Fire Protection Association
Batterymarch Park
P.O. Box 9101
Quincy, MA 02269-9901
Telephone: (800) 344-355
Fax: (617) 984-7057
Manual 2100-384B
Page3 of 19
WALL MOUNT GENERAL INFORMATION
AIR CONDITIONER WALL MOUNT MODEL NOMENCLATURE
WE 12 1 – G 00 X X X X X J
MODEL NUMBER
CAPACITY
12 - 1 Ton
REVISIONS
VOLTS & PHASE
G - 220/200/50/1
VENTILATION OPTIONS
X - Barometric Fresh Air Damper (Standard)
B - Blank-off Plate
E - Economizer (Internal) - Fully Modulating w/Exhaust
KW
00 - No KW
02 - 2 KW
03 - 3 KW
TABLE 1
ELECTRIC HEAT TABLE
ledoMG-121EW
V022V002
WKA1UTBA
CONTROL MODULES
E - Low Ambient Control
J - Telecommunication
COIL OPTIONS
X - Standard Coils
OUTLET OPTIONS
X - Front
COLOR OPTIONS
X - Beige
4 - Buckeye Gray
FILTER OPTIONS
X - One Inch Throwaway (Standard)
P - Two Inch Pleated
1
UTB
201.9038,62.8051,6
307.31052,016.21041,9
TABLE 2
ELECTRICAL HEAT SPECIFICATIONS
dleiF.oN
stloVdetaR
sledoM
esahPdna
00G-121EW
20G-
1/05/002/022
30G-
1 Maximum size of the time delay fuse or HACR type circuit breaker for protection of field wiring conductors.
2 Based on 75°C copper wire. All wiring must conform to NEC and all local codes.
These “Minimum Circuit Ampacity” values are to be used for sizing the field power conductors. Refer to the National Electrical
Code (latest revision), article 310 for power conductor sizing.
CAUTION:When more than one field power conductor circuit is run through one conduit, the conductors must be derated.
Pay special attention to note 8 of table 310 regarding Ampacity Adjustment Factors when more than 3 conductors
are in a raceway.
rewoP
stiucriC
1
1
1
muminiM
tiucriC
yticapmA
7
31
02
1
2
2
mumixaM
esuFlanretxE
tiucriCro
rekaerB
51
51
02
rewoPdleiF
eziSeriW
41
41
21
dnuorG
eziSeriW
41
41
21
Manual 2100-384B
Page4 of 19
FIGURE 1
UNIT DIMENSIONS
FACTORY BUILT AT 5 INCHES
WE121
Manual 2100-384B
Page5 of 19
SHIPPING DAMAGE
Upon receipt of equipment, the carton should be
checked for external signs of shipping damage. If
damage is found, the receiving party must contact the
last carrier immediately, preferably in writing,
requesting inspection by the carrier’s agent.
GENERAL
The equipment covered in this manual is to be installed
by trained, experienced service and installation
technicians.
The refrigerant system is completely assembled and
charged. All internal wiring is complete.
The unit is designed for use with or without duct work.
Flanges are provided for attaching the supply and return
air ducts.
These instructions explain the recommended method to
install the air cooled self-contained unit and the
electrical wiring connections to the unit.
These instructions and any instructions packaged with
any separate equipment required to make up the entire
air conditioning system should be carefully read before
beginning the installation. Note particularly “Starting
Procedure” and any tags and/or labels attached to the
equipment.
While these instructions are intended as a general
recommended guide, they do not supersede any national
and/or local codes in any way. Authorities having
jurisdiction should be consulted before the installation is
made. See Page 3 for information on codes and
standards.
Size of unit for a proposed installation should be based
on heat loss calculation made according to methods of
Air Conditioning Contractors of America (ACCA). The
air duct should be installed in accordance with the
Standards of the National Fire Protection Association
for the Installation of Air Conditioning and Ventilating
Systems of Other Than Residence Type, NFPA no. 90A,
and Residence Type Warm Air Heating and Air
Conditioning Systems, NFPA No. 90B. Where local
regulations are at a variance with instructions, installer
should adhere to local codes.
DUCT WORK
All duct work, supply and return must be properly sized
for the design air flow requirement of the equipment.
Air Conditioning Contractors of America (ACCA) is an
excellent guide to proper sizing. All duct work or
portions thereof not in the conditioned space should be
properly insulated in order to both conserve energy and
prevent condensation or moisture damage.
Refer to Table 7 for maximum static pressure available
for duct design.
Design the duct work according to methods given by the
Air Conditioning Contractors of America (ACCA).
When duct runs through unheated spaces, it should be
insulated with a minimum of one inch of insulation.
Use insulation with a vapor barrier on the outside of the
insulation. Flexible joints should be used to connect the
duct work to the equipment in order to keep the noise
transmission to a minimum.
Ducts through the walls must be insulated and all joints
taped or sealed to prevent air or moisture entering the
wall cavity.
Some installations may not require any return air duct.
It is recommended that on this type of installation that a
filter grille be located in the wall. Filters must be of
sufficient size to allow a maximum velocity of 400
FPM.
NOTE: If no return air duct is used, applicable
installation codes may limit this cabinet to
installation only in a single story structure.
FILTERS
A 1-inch throwaway filter is supplied with each unit.
The filter slides into position making it easy to service.
This filter can be serviced from the outside by removing
the service door. A 2-inch pleated filter is also available
as an optional accessory. The internal filter brackets are
adjustable to accommodate the 2-inch filter by bending
the metal tabs holding the 1-inch filter down. There are
two tabs on each side of the filter.
Manual 2100-384B
Page6 of 19
Loading...
+ 13 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.