Bard WE121 Installation Instructions Manual

INSTALLATION INSTRUCTIONS
WALL MOUNTED
PACKAGE AIR CONDITIONERS
Model:
WE121
THIS MODEL USES REFRIGERANT R-407C
and IS FOR 50HZ OPERATION.
Bard Manufacturing Company , Inc. Bryan, Ohio 43506
Since 1914...Moving ahead, just as planned.
Manual : 2100-384B Supersedes: 2100-384A File: Volume III Tab 16 Date: 09-17-10
Manual 2100-384B Page 1 of 19
CONTENTS
Getting Other Informations and Publications ......... 3
Wall Mount General Information
Air Conditioner Wall Mount Model Nomenclature..... 4
Shipping Damage ..................................................... 6
General.....................................................................6
Duct Work ................................................................. 6
Filters........................................................................ 6
Fresh Air Intake ........................................................ 7
Condensate Drain..................................................... 7
Installation Instructions
Wall Mounting Information........................................ 8
Proper Unit Placement ............................................. 8
Mounting the Unit ..................................................... 8
Wiring – Main Power .............................................. 13
Wiring – Low Voltage Wiring .................................. 13
Figures
Figure 1 Unit Dimensions...................................... 5
Figure 2 Blower Damper Assembly....................... 7
Figure 3 Mounting Instructions Using CSRG-1..... 9
Figure 4 Mounting Instructions............................ 10
Figure 5 Wall Mounting Instructions ....................11
Figure 6 Wall Mounting Instructions ....................11
Figure 7 Common Wall Mounting
Instructions ........................................... 12
Figure 8 Fan Blade Setting Dimensions ............. 16
Start Up
Important Installer Note .......................................... 14
Service Hints .......................................................... 14
High Pressure Switch ............................................. 14
Sequence of Operation........................................... 14
Compressor Control Module................................... 14
Adjustments............................................................15
Pressure Service Ports...........................................15
Troubleshooting
Fan Blade Setting Dimension ................................. 16
Refrigerant Charge ................................................. 16
Pressure Table........................................................ 17
Optional Field Installed Accessories ....................... 17
R-407C Refrigerant
Service Procedure & Considerations...................... 18
Charging ................................................................. 18
Leaks ...................................................................... 18
Tables
Table 1 Electric Heat Table .................................. 4
Table 2 Electrical Specifications .......................... 4
Table 3 Fan Blade Dimensions.......................... 16
Table 4 Suction Line Temperatures ................... 16
Table 5 Indoor Blower Performance .................. 16
Table 6 Recommended Airflow Range .............. 16
Table 7 Maximum ESP of Operation
Electric Heat Only ................................. 16
Table 8 Pressure Table - Cooling ...................... 17
Table 9 Optional Accessories ............................ 17
Table 10 Temperature / Pressure Chart............... 19
Manual 2100-384B Page 2 of 19
GETTING OTHER INFORMATION AND PUBLICATIONS
These publications can help you install the air conditioner or heat pump. You can usually find these at your local library or purchase them directly from the publisher. Be sure to consult current edition of each standard.
National Electrical Code ...................... ANSI/NFPA 70
Standard for the Installation of .......... ANSI/NFPA 90A
Air Conditioning and Ventilating Systems
Standard for Warm Air Heating ........ ANSI/NFPA 90B
and Air Conditioning Systems
Load Calculation for............................ ACCA Manual J
Residential Winter and Summer Air Conditioning
Duct Design for ................................. ACCA Manual D
Residential Winter and Summer Air Conditioning and Equipment Selection
FOR MORE INFORMATION, CONTACT THESE PUBLISHERS:
ACCA Air Conditioning Contractors of America
1712 New Hampshire Avenue NW Washington, DC 20009 Telephone: (202) 483-9370 Fax: (202) 234-4721
ANSI American National Standards Institute
11 West Street, 13th Floor New York, NY 10036 Telephone: (212) 642-4900 Fax: (212) 302-1286
ASHRAE American Society of Heating, Refrigerating
and Air Conditioning Engineers, Inc.
1791 Tullie Circle, NE Atlanta, GA 30329-2305 Telephone: (404) 636-8400 Fax: (404) 321-5478
NFPA National Fire Protection Association
Batterymarch Park P.O. Box 9101 Quincy, MA 02269-9901 Telephone: (800) 344-355 Fax: (617) 984-7057
Manual 2100-384B Page 3 of 19
WALL MOUNT GENERAL INFORMATION
AIR CONDITIONER WALL MOUNT MODEL NOMENCLATURE
WE 12 1 – G 00 X X X X X J
MODEL NUMBER
CAPACITY
12 - 1 Ton
REVISIONS
VOLTS & PHASE
G - 220/200/50/1
VENTILATION OPTIONS
X - Barometric Fresh Air Damper (Standard) B - Blank-off Plate E - Economizer (Internal) - Fully Modulating w/Exhaust
KW
00 - No KW 02 - 2 KW 03 - 3 KW
TABLE 1
ELECTRIC HEAT TABLE
ledoMG-121EW
V022V002
WKA1UTBA
CONTROL MODULES
E - Low Ambient Control J - Telecommunication
COIL OPTIONS
X - Standard Coils
OUTLET OPTIONS
X - Front
COLOR OPTIONS
X - Beige 4 - Buckeye Gray
FILTER OPTIONS
X - One Inch Throwaway (Standard) P - Two Inch Pleated
1
UTB
201.9038,62.8051,6
307.31052,016.21041,9
TABLE 2
ELECTRICAL HEAT SPECIFICATIONS
dleiF.oN
stloVdetaR
sledoM
esahPdna
00G-121EW 20G-
1/05/002/022
30G-
1 Maximum size of the time delay fuse or HACR type circuit breaker for protection of field wiring conductors. 2 Based on 75°C copper wire. All wiring must conform to NEC and all local codes.
These “Minimum Circuit Ampacity” values are to be used for sizing the field power conductors. Refer to the National Electrical Code (latest revision), article 310 for power conductor sizing.
CAUTION: When more than one field power conductor circuit is run through one conduit, the conductors must be derated.
Pay special attention to note 8 of table 310 regarding Ampacity Adjustment Factors when more than 3 conductors are in a raceway.
rewoP
stiucriC
1 1 1
muminiM
tiucriC
yticapmA
7
31 02
1
2
2
mumixaM
esuFlanretxE
tiucriCro
rekaerB
51 51 02
rewoPdleiF
eziSeriW
41 41 21
dnuorG
eziSeriW
41 41 21
Manual 2100-384B Page 4 of 19
FIGURE 1
UNIT DIMENSIONS
FACTORY BUILT AT 5 INCHES
WE121
Manual 2100-384B Page 5 of 19
SHIPPING DAMAGE
Upon receipt of equipment, the carton should be checked for external signs of shipping damage. If damage is found, the receiving party must contact the last carrier immediately, preferably in writing, requesting inspection by the carrier’s agent.
GENERAL
The equipment covered in this manual is to be installed by trained, experienced service and installation technicians.
The refrigerant system is completely assembled and charged. All internal wiring is complete.
The unit is designed for use with or without duct work. Flanges are provided for attaching the supply and return air ducts.
These instructions explain the recommended method to install the air cooled self-contained unit and the electrical wiring connections to the unit.
These instructions and any instructions packaged with any separate equipment required to make up the entire air conditioning system should be carefully read before beginning the installation. Note particularly “Starting Procedure” and any tags and/or labels attached to the equipment.
While these instructions are intended as a general recommended guide, they do not supersede any national and/or local codes in any way. Authorities having jurisdiction should be consulted before the installation is made. See Page 3 for information on codes and standards.
Size of unit for a proposed installation should be based on heat loss calculation made according to methods of Air Conditioning Contractors of America (ACCA). The air duct should be installed in accordance with the Standards of the National Fire Protection Association for the Installation of Air Conditioning and Ventilating Systems of Other Than Residence Type, NFPA no. 90A, and Residence Type Warm Air Heating and Air Conditioning Systems, NFPA No. 90B. Where local regulations are at a variance with instructions, installer should adhere to local codes.
DUCT WORK
All duct work, supply and return must be properly sized for the design air flow requirement of the equipment. Air Conditioning Contractors of America (ACCA) is an excellent guide to proper sizing. All duct work or portions thereof not in the conditioned space should be properly insulated in order to both conserve energy and prevent condensation or moisture damage.
Refer to Table 7 for maximum static pressure available for duct design.
Design the duct work according to methods given by the Air Conditioning Contractors of America (ACCA). When duct runs through unheated spaces, it should be insulated with a minimum of one inch of insulation. Use insulation with a vapor barrier on the outside of the insulation. Flexible joints should be used to connect the duct work to the equipment in order to keep the noise transmission to a minimum.
Ducts through the walls must be insulated and all joints taped or sealed to prevent air or moisture entering the wall cavity.
Some installations may not require any return air duct. It is recommended that on this type of installation that a filter grille be located in the wall. Filters must be of sufficient size to allow a maximum velocity of 400 FPM.
NOTE: If no return air duct is used, applicable
installation codes may limit this cabinet to installation only in a single story structure.
FILTERS
A 1-inch throwaway filter is supplied with each unit. The filter slides into position making it easy to service. This filter can be serviced from the outside by removing the service door. A 2-inch pleated filter is also available as an optional accessory. The internal filter brackets are adjustable to accommodate the 2-inch filter by bending the metal tabs holding the 1-inch filter down. There are two tabs on each side of the filter.
Manual 2100-384B Page 6 of 19
Loading...
+ 13 hidden pages