Bard WL3S, WL5S, WA5S, WA3S User Manual

THE WALL-MOUNT™ STEP CAPACITY AIR CONDITIONERS
Integrated Part Load Value (IPLV) Efficiency Up To 15.2 BTU/WATT
WA3S – WA5S Right Side Control Panel
GREEN REFRIGERANT
WL3S – WL5S Left Side Control Panel 3 to 5 Ton (35,400 to 56,500 Btuh) 60Hz
The Bard WA/L "S" Series is the world's most energy efficient wall mounted air conditioner featuring a multi-step capacity compressor with environmentally friendly non-ozone depleting refrigerant.
The Bard Wall-Mount Air Conditioner is a self contained energy efficient system, which is designed to offer maximum indoor comfort at a minimal cost without using valuable indoor floor space or outside ground space. This unit is the ideal product for versatile applications such as: new construction, modular offices, school modernization, telecommunication structures, portable structures or correctional facilities. Factory or field installed accessories are available to meet specific job requirements.
Engineered Features
Multi-Capacity Two-Stage:
Simple thermostatic control seamlessly stages the compressor and indoor airflow rate between high and low capacity operations without cycling the compressor. This helps to maximize comfort, humidity control, energy efficiency and overall reduction in compressor cycling for improved system life.
Multi-Step Capacity Compressor:
Copeland step-capacity scroll compressors are designed for increased efficiency, quieter operation and improved reliability for longer life.
R-410A Refrigerant:
Designed with R-410A (HFC) non­ozone depleting refrigerant in compliance with the Montreal protocol and 2010 EPA requirements.
ECM Indoor Blower Motor:
Features a variable speed motor providing super-high efficiency, low sound levels and soft-start capabilities. adjusting to provide the proper airflow rate for the staged capacity, and for higher static pressure in ducted installations without user adjustment or wiring changes.
The motor is self-
Aluminum Finned Copper Coils:
Grooved tubing and enhanced louvered fin for maximum heat transfer and energy efficiency.
Twin Blowers:
Move air quietly. All models feature variable speed blower motors providing automatic airflow adjustment for high static or free blow (non-ducted) operation at a very low sound level. Motor overload protection is standard on all models.
Foil Faced Insulation:
Standard on all units.
Start Kit:
A PTCR compressor start assist (Positive Temperature Coefficient Resistor) is standard on all -A single­phase models to increase system reliability. This helps to insure compressor starts at adverse conditions by increasing the compressor starting torque.
Compressor Control Module:
Built-in off-delay timer adjustable from 30 seconds to 5 minutes. 2­minute on-delay if power interrupt. 120-second bypass for low pressure control, and both soft and manual lockouts for high and low pressure controls. Alarm output for alarm relay.
Liquid Line Filter Drier:
Standard on all units. Protects system against moisture.
High & Low Pressure Switches are Auto-Reset:
Standard on all units. Built-in lock­out circuit resets from the room thermostat. Provides commercial quality protection to the compressor.
Crankcase Heaters:
Factory installed crankcase heaters are standard on all models. This helps to insure ease of start at low temperatures and improves compressor life.
Phase Rotation Monitor:
Standard on all 3 phase scroll compressors. Protects against reverse rotation if power supply is not properly connected.
Galvanized 20 Gauge Zinc Coated Steel Cabinet:
Cleaned, rinsed, sealed and dried before the polyurethane primer is applied. The cabinet is handsomely finished with a baked on textured enamel, which allows it to withstand 1000 hours of salt spray tests per ASTM B117-03.
Galvanized 16 Gauge Zinc Coated Unit Base:
The unit base is treated with the same paint coatings as the cabinet above, insuring years of service without visible corrosion.
Drain Pan:
The evaporator drain pan is constructed of stainless steel material for maximum corrosion resistance.
Electrical Components:
Are easily accessible for routine inspection and maintenance through a right side, service panel opening. Features a lockable, hinged access cover to the circuit breaker or toggle disconnect switch.
R-410A
Electric Heat Strips:
Features line break automatic limit and dual backup safety controls. Heater packages can be factory or field installed for all models.
Filter Service Door:
Separate service door provides easy access for filter change.
Two-Inch, Pleated Disposable Air Filters:
Are standard equipment.
Condenser Fan and Motor Shroud Assembly:
Slides out for easy access.
Circuit Breakers/Rotary Disconnect:
Standard on all versions of single (230/ 208 volt) and three phase (230/208 volt) equipment. Rotary disconnects are standard on all versions of three phase (460 volt) equipment.
Slope Top:
Standard feature for water run-off.
Full Length Mounting Brackets:
Built into cabinet for improved appearance and easy installation. NOTE: Bottom mounting bracket included to assist in installation.
Top Rain Flashing:
Standard feature on all models.
Complies with efficiency requirements of ANSI/ASHRAE/IESNA 90.1-2010.
Certified to ANSI/ARI Standard 390-2003 for SPVU (Single Package Vertical Units).
Intertek ETL Listed to Standard for Safety Heating and Cooling Equipment ANSI/UL
1995/CSA 22.2 No. 236-05, Fourth Edition.
Commercial Product - Not intended for Residential application.
Form No. S3378-1112 Supersedes S3378-712 Page 1 of 12
Capacity and Efficiency Ratings
c
1
SLEDOM
noitarepOegatSdn2,HUTByticapaCgnilooC
noitarepOegatSdn2REE 21
)lioCteW(MFCdetaR
noitarepOegatSts1,HUTByticapaCgnilooC
noitarepOegatSts1REE 2
)lioCteW(MFCdetaR
3S3AW 2S3LW
004,53
1.11 0011
000,42
7.11
008
3S4AW 2S4LW
000,64
2.11 0051
000,43
6.11 0011
3S5AW 2S5LW
005,65
1.01 0071
000,04
8.01 0031
VLPI 3 1.512.513.41
1 Certified in accordance with ANSI/ARI Standard 390-2003 for single package vertical units. 2 EER = Energy Efficiency Ratio - BTU/WATT efficiency. 3 Integrated Part Load Value - BTU/WATT efficiency and certified in accordance with ANSI/ARI Standard 390-2003.
All capacity, efficiency and cost of operation information is based on operation with fresh air cover plate. Cover plate is recommended for use to obtain maximum energy efficiency where ventilation air is not required.
Indoor Blower Performance - CFM (0.00" through 0.80" H2O) 1
ylnOrewolBgnilooCegatSts1gnilooCegatSdn2
3S3AW 2S3LW
3S4AW 2S4LW
3S5AW 2S5LW
008008001100110041
5280011005100110051
0580031007100110051
cirtcelEWK01-5
taeH
1 These systems contain Variable Speed ECM Motor, which maintains airflow across static range at
dry and wet coil conditions.
irtcelEWK02-51
taeH
Specifications 3 Ton through 5 Ton
SLEDOM
yticapaCgnilooC004,53004,53004,53000,64000,64000,64005,65005,65005,65 yticapaCgnitaeH elbaTtaeHcirtcelEeeS
zH06--gnitaRlacirtcelE
egnaRegatloVgnitarepO352-791352-791605-414352-791352-791605-414352-791352-791605-414
AtiucriC--rosserpmoC
egatloV 802/032 802/032 064 802/032 802/032 064 802/032 802/032 064
spmAdaoLdetaR 6.41/3.21 9.7/7.6 6.3 1.91/1.61 21/1.01 8.4 6.62/9.12 9.81/5.51 8.7
tnerruCnoitceleStiucriChcnarB 7.61 6.11 7.5 2.12 0.41 5.6 1.72 9.81 0.9
spmArotoRkcoL3837834011.381435101125
epyTrosserpmoCllorcSllorcSllorcSllorcSllorcSllorcSllorcSllorcSllorcS
resnednoC&rotoMnaF
DPS-MPR-PH--rotoMnaF2-528-3/12-528-3/12-528-3/12-528-3/12-528-3/12-528-3/12-528-3/12-528-3/12-528-3/1
spmA--rotoMnaF5.25.23.15.25.23.15.25.23.1
MFC/AID--naF0072-"420072-"420072-"420082-"420082-"420082-"420082-"420082-"420082-"42
.pavE&rotoMrewolB
DPS-MPR-PH--rotoMrewolBelbairaV-2/1elbairaV-2/1elbairaV-2/1elbairaV-4/3elbairaV-4/3elbairaV-4/3elbairaV-4/3elbairaV-4/3elbairaV-4/3
spmA--rotoMrewolB3.53.53.58.68.68.68.68.68.6
gnilooCMFC
)lioCteW(retliF/w
.DTS)sehcni(seziSretliF2x03x022x03x022x03x022x03x022x03x022x03x022x03x022x03x022x03x02
.SBL--thgieWgnippihS
A-3S3AW A-2S3LW
1-802/032 3-802/032 3-064 1-802/032 3-802/032 3-064 1-802/032 3-802/032 3-064
001100110011005100510051007100710071
035 035 035 035 035 035 035 035 035
B-3S3AW B-2S3LW
C-3S3AW C-2S3LW
A-3S4AW A-2S4LW
B-3S4AW B-2S4LW
C-3S4AW C-2S4LW
A-3S5AW A-2S5LW
B-3S5AW B-2S5LW
C-3S5AW C-2S5LW
Form No. S3378-1112 Supersedes S3378-712 Page 2 of 12
Ventilation System Packages
Bard Wall-Mounts are designed to provide optional ventilation packages to meet all of your ventilation and indoor air quality requirements. All units are equipped with a blank off plate as the standard ventilation package. All ventilation packages can be built-in at the factory, or field­installed at a later date.
BLANK OFF PLATE - BOP STANDARD
A blank off plate is installed on the inside of the service door. It covers the air inlet openings which restricts any outside air from entering the unit. The blank off plate should be utilized in applications where outside air is not
required to be mixed with the conditioned air.
MOTORIZED FRESH AIR DAMPER - MFAD OPTIONAL
The motorized fresh air damper is internally mounted behind the service door and allows outside ventilation air, up to 25% of the total airflow rating of the unit, to be introduced through the air inlet openings and to be mixed with the conditioned air. The two position damper can be fully open or closed. The damper blade is powered open by a 24VAC motor with spring return on power loss. The damper can be controlled by indoor blower operation or can be field connected to be managed based on building occupancy.
Motorized Fresh Air Damper
COMMERCIAL ROOM VENTILATOR
NOTE: This vent system is intake only without built-in exhaust capability. Building will likely require separate field
installed barometric relief or mechanical exhaust elsewhere within the conditioned space. Other building systems will govern actual amount of intake air.
COMMERCIAL ROOM VENTILATOR - CRVMP OPTIONAL
The built-in commercial room ventilator is internally mounted behind the service door and allows outside ventilation air, up to 50% of the total airflow rating of the unit, to be introduced through the air inlet openings. It includes a built-in exhaust air damper with integral bug screen. Automatic control is integrated to maintain desired ventilation air at the various supply airflows.
The commercial room ventilator (CRV) is a simple and innovative approach to improving the indoor air quality by providing fresh air intake and exhaust capability through the CRV. The damper can be easily adjusted to control the amount of fresh air supplied into the building. The CRV can be controlled by indoor blower operation or field controlled based on room occupancy. The CRV is power open - spring return on power loss. Complies with ANSI/ASHRAE Standard 62.1 “Ventilation for Acceptable Indoor Air Quality.”
Economizer
ENERGY RECOVERY VENTILATOR
ECONOMIZER - ECONWM-Series OPTIONAL
The built-in economizer system is internally mounted behind the service door and allows outdoor air to be introduced through the air inlet openings. The amount of outdoor air varies in response to the system controls and settings defined by the end user. It includes a built-in exhaust air damper. The economizer is designed to provide “free cooling” when outside air conditions are cool and dry enough to satisfy cooling requirements without running the compressor. This in turn provides lower operating costs, while extending the life of the compressor.
ECONWMT Equipment Building versions have extended air intake hood to deliver up to 100% of cooling rated airflow.
16" for ECONWMT-E2 or T2, and E3 or T318" for ECONWMT-E5 or T5
ECONWMS Classroom versions have 3" air intake hood to deliver up to 75% of cooling rated airflow.
Standard Features:
Fully modulating
Honeywell Direct Drive Hi-Torque Actuator
No linkage required
Simple single blade design
Positive shut-off with non-stick gaskets
Electronic DB and/or Enthalpy sensors depending upon version
Honeywell JADE electronic economizer module with precision settings and diagnostics
DB or Enthalpy economizer versions available
WALL-MOUNT ENERGY RECOVERY VENTILATOR - ERVF OPTIONAL
The wall-mount energy recovery ventilator (ERV) is a highly innovative approach to meeting indoor air quality ventilation requirements as established by ANSI/ASHRAE Standard 62.1. The ERV allows from 200 to 450 CFM (depending upon model) of fresh air and exhaust through the unit while maintaining superior indoor comfort and humidity levels. In most cases this can be accomplished without increasing equipment sizing or operating costs. Heat transfer efficiency is up to 67% during summer and 75% during winter conditions.
The ERV consists of a unique “rotary energy recovery cassette” that provides effective sensible and latent heat transfer capabilities during summer and winter conditions. Various control schemes are addressed including limiting ventilation during building occupancy only.
The ERV is designed to be internally mounted behind the service door in the WA/LS model wall-mount units. It can be built-in at the factory or field installed as an option. ERVF-*5 can be independently adjusted for intake and exhaust rates.
Manufactured under U.S. Patent Nos. 5,485,878; 5,301,744.
Form No. S3378-1112 Supersedes S3378-712 Page 3 of 12
800
700
600
CRVMP-5
WA3S/WL3S Ventilation Airflow
500
400
300
Ventilation Airflow (CFM)
200
100
0
0 2.5 5 7.5 10 12.5 15 17.5 20 22.5 25 27.5 30
Vent Position
CRVMP-5
1000
900
800
700
600
500
400
Ventilation Airflow (CFM)
300
WA4S/WL4S Ventilation Airflow
Stage #2 Operation
Blower Only & Stage #1 Operation
Stage #2 Operation
Stage #1 Operation
Blower Only
Ventilation Airflow (CFM)
Form No. S3378-1112 Supersedes S3378-712 Page 4 of 12
200
100
0
0 2.5 5 7.5 10 12.5 15 17.5 20 22.5 25 27.5 30
Vent Position
CRVMP-5
1000
900
800
700
600
500
400
300
200
100
0
0 2.5 5 7.5 10 12.5 15 17.5 20 22.5 25 27.5 30
WA5S/WL5S Ventilation Airflow
Vent Position
Stage #2 Operation
Stage #1 Operation
Blower Only