Bard WA3S1, WA4S1, WA5S1 Installation Instructions Manual

INSTALLATION
WALL MOUNTED PACKAGED AIR CONDITIONER
INSTRUCTIONS
Models:
WA3S1 WA4S1 WA5S1
THIS IS AN R-410A
REFRIGERANT SYSTEM
Bard Manufacturing Company, Inc. Bryan, Ohio 43506
NOTE
HIGH PRESSURE
Manual No.: 2100-451E Supersedes: 2100-451D File: Volume III, Tab 16 Date: 09-02-08
Manual 2100-451E Page 1 of 24
CONTENTS
Getting Other Information and Publications
For more information contact these publishers........ 3
Wall Mount General Information
Air Conditioner Wall Mount Model Nomenclature.... 4
Shipping Damage .................................................... 7
General ............................................................... 7
Duct Work ............................................................... 7
Filters ............................................................... 7
Condensate Drain.................................................... 7
Installation Instructions
Wall Mounting Information....................................... 8
Mounting the Unit .................................................... 8
Typical Installations ................................................. 8
Wiring – Main Power ....................................... 8 & 9
Wiring – Low Voltage Wiring ............................... 12
Start Up
General ............................................................. 14
Topping Off System Charge................................... 14
Safety Practices..................................................... 14
Important Installer Note ......................................... 15
Crankcase Heaters................................................ 15
High & Low Pressure Switch ................................. 15
Three Phase Scroll Compressor Start Up
Information............................................................. 15
Service Hints ......................................................... 16
Sequence of Operation.......................................... 16
Blower Time Delay Disable.................................... 16
Compressor Control Module.................................. 16
Adjustments........................................................... 17
Phase Monitor ....................................................... 17
Motor Start Device ................................................. 17
Pressure Service Ports.......................................... 17
Troubleshooting
Compressor Solenoid ............................................ 18
Fan Blade Setting Dimensions .............................. 18
Removal of Fan Shroud......................................... 18
R-410A Refrigerant Charge ................................... 19
Pressure Chart ...................................................... 22
GE ECM™Motors................................................... 21
GE ECM™Motors................................................... 22
Optional Accessories ............................................. 24
Figures
Figure 1 Unit Dimensions..................................... 5
Figure 2 Mounting Instructions............................. 9
Figure 3 Wall-Mounting Instructions .................. 10
Figure 4 Wall-Mounting Instructions .................. 10
Figure 5 Common Wall-Mounting Instructions ....11
Figure 6 Electric Heat Clearance ....................... 12
Figure 7 Low Voltage Wiring.............................. 13
Figure 8 Start-Up Label...................................... 15
Figure 9 Fan Blade Setting ................................ 18
Figure 10 Control Disassembly............................ 22
Figure 11 Winding Test ........................................ 22
Figure 12 Drip Loop ............................................. 22
Tables
Table 1 Electric Heat Table ................................. 4
Table 2 Dimensions of Basic Unit....................... 5
Table 3 Electrical Specifications ......................... 6
Table 4 Operating Voltage Range .................... 12
Table 5 Thermostat Wire Size .......................... 12
Table 6 Wall Thermostats................................. 12
Thermostatic Control - Dual Unit.......... 12
Table 7 Fan Blade Dimensions......................... 18
Table 8 Liquid Line Temperatures .................... 19
Table 9 Cooling Pressure ................................. 20
Table 10 Indoor Blower Performance ................. 23
Table 11 Maximum ESP of Operation
Electric Heat Only ................................ 23
Table 12 Optional Accessories ........................... 24
Manual 2100-451E Page 2 of 24
Getting Other Information and Publications
These publications can help you install the air conditioner or heat pump. You can usually find these at your local library or purchase them directly from the publisher. Be sure to consult current edition of each standard.
National Electrical Code ...................... ANSI/NFPA 70
Standard for the Installation...............ANSI/NFPA 90A
of Air Conditioning and Ventilating Systems
Standard for Warm Air ...................... ANSI/NFPA 90B
Heating and Air Conditioning Systems
Load Calculation for ....................... ACCA Manual J or
Residential Winter and Manual N Summer Air Conditioning
Low Pressure, Low Velocity..........ACCA Manual D or
Duct System Design for Winter Manual Q and Summer Air Conditioning
FOR MORE INFORMATION, CONTACT THESE PUBLISHERS:
ACCA Air Conditioning Contractors of America
1712 New Hampshire Ave. N.W. Washington, DC 20009 Telephone: (202) 483-9370 Fax: (202) 234-4721
ANSI American National Standards Institute
11 West Street, 13th Floor New York, NY 10036 Telephone: (212) 642-4900 Fax: (212) 302-1286
ASHRAE American Society of Heating Refrigerating,
and Air Conditioning Engineers, Inc.
1791 Tullie Circle, N.E. Atlanta, GA 30329-2305 Telephone: (404) 636-8400 Fax: (404) 321-5478
NFPA National Fire Protection Association
Batterymarch Park P.O. Box 9101 Quincy, MA 02269-9901 Telephone: (800) 344-3555 Fax: (617) 984-7057
Manual 2100-451E Page 3 of 24
WALL MOUNT GENERAL INFORMATION
AIR CONDITIONER WALL MOUNT MODEL NOMENCLATURE
WA 4S 1 – B 09 B P X X X X
MODEL NUMBER
CAPACITY
3S – 3 Ton 4S – 4 Ton 5S – 5 Ton
VOLTS & PHASE
A – 230/208-1 B – 230/208/60-3 C – 460/60-3
KW
0Z – No KW
05 – 5 KW 06 – 6 KW 08 – 8 KW 09 – 9 KW 10 – 10 KW 15 – 15 KW 20 – 20 KW
REVISION
w/Circuit Breaker or Pull Disconnect
VENTILATION OPTIONS
B – Blank-off Plate(Standard) V – Commercial Room Ventilator -
Motorized with Exhaust (3-Position)
E – Economizer (Internal) - Fully
Modulating with Exhaust
R – Energy Recovery Ventilator -
with Exhaust
CONTROL MODULES
COIL OPTIONS
X – Standard
OUTLET OPTIONS
X – Front (Standard)
COLOR OPTIONS
X – Beige
(Standard) 4 – Buckeye Gray 5 – Desert Brown 8 – Dark Bronze
FILTER OPTIONS
P – Two Inch Pleated
NOTE: For 0KW and circuit breakers (230/208 V) or pull disconnects (460 V) applications, insert 0Z in the KW field of model number.
TABLE 1
ELECTRIC HEAT TABLE
lanimoN
WK
wKspmAhP-1spmAhP-3hutBwKspmAhP-1spmAhP-3hutBwKspmAhP-3hutBwKspmAhP-3hutB
0.50.58.02560,7157.30.81997,21
0.60.64.41874,0205.45.21953,510.62.7874,0225.59.6048,81
0.80.83.33403,7200.68.82874,02
0.90.97.12717,0357.67.81830,320.98.01717,0382.84.01062,82
0.010.017.14031,4305.71.63895,52
0.510.515.261.63591,1552.111.452.13693,830.510.81591,158.313.71990,74
0.020.023.38062,8600.511.27591,15
)1(V042tA)1(V802tA)2(V084tA)2(V064tA
.ylnostinuV802/032nielbaliavaerasretaehcirtceleesehT)1(
.ylnostinuV084nielbaliavaerasretaehcirtceleesehT)2(
See Table 3 for Heater Availability by Model
Manual 2100-451E Page 4 of 24
88.11S4AW
00.61
00.01
88.32
73.388.24
86.2349.6296.4334.23
00.03
66.13
TABLE 2
FIGURE 1
UNIT DIMENSIONS
EFGI JKLMNOPQSTABCB
ylppuSnruteR
88.988.9288.5188.9288.3401.91
thgieH
578.48
H
htpeD
DIMENSIONS OF BASIC UNIT FOR ARCHITECTURAL AND INSTALLATION REQUIREMENTS (NOMINAL)
D
578.4966.1486.2449.6396.4434.2488.3300.12
htdiW
W
tinU
570.24234.22
1S3AW
1S5AW
All dimensions in inches. Dimensional Drawings are not to scale.
Manual 2100-451E
Page 5 of 24
eriW
2 dnuorG
eziSeriW
rewoP
2 dleiF
01010101
010101
01
6
01010101
010101
601
01
6
601
01010101
010101
01
6
601
888
esuFlanretxE
.rkrB.tkCro
03060603
1 mumixaM
545454
yticapmA
tiucriC
3 muminiM
A.tkC B.tkC C.tkC A.tkC B.tkC C.tkC A.tkC B.tkC C.tkC A.tkC B.tkC C.tkC
TABLE 3
ELECTRICAL SPECIFICATIONS
eriW
2 dnuorG
eziSeriW
rewoP
tiucriCelgniS tiucriCelpitluM
2 dleiF
esuFlanretxE
.rkrB.tkCro
1 mumixaM
62252562
535353
010101
886
88663
060709
54
54
2
511
010101
01
01
03
030406
888
03060603
545454
62252562
737373
01
41
41
21
01
010101
41
41
21
8
6
01
88643
51
51
02
03
060709
54
54
886
2
021
010101
01
01
040404
01
212101
01
212101
020252
01
03
8
6
06
888
03060603
050505
62252562
444444
010101
886
88663
0505060709
2
021
010101
888
040404
01
6
06
010101
010101
525252
01
01
03
yticapmA
tiucriC
3 muminiM
dleiF.oN
stiucriC
rewoP
esahPdna
detaR
stloV
ledoM
Manual 2100-451E Page 6 of 24
135315
111
Z0A-1S3AW
50A-
311
16
327263
78
2ro1
2ro1
3ro1
111
1-802/032
Z0B-1S3AW
80A-
01A-
60B-
02A-
51A-
5.31
21
91
55
1
3-802/032
90B-
51B-
111
3-064
Z0C-1S3AW
60C-
82
1
90C-
51C-
8383353698
111
Z0A-1S4AW
50A-
511
829283
2ro1
2ro1
3ro1
111
1-802/032
80A-
01A-
3-802/032
Z0B-1S4AW
02A-
60B-
51A-
90B-
65
1
51B-
51
61
111
3-064
Z0C-1S4AW
60C-
12
03
44
44
1
111
Z0A-1S5AW
90C-
51C-
50A-
353698
2ro1
1-802/032
80A-
01A-
511
43
43
83
2ro1
3ro1
111
3-802/032
Z0B-1S5AW
02A-
60B-
51A-
90B-
65
1
51B-
71
71
111
3-064
Z0C-1S5AW
60C-
12
03
1
CAUTION: When more than one filed power conductor circuit is run through one conduit, the conductors must be derated.
90C-
51C-
Maximum size of the time delay fuse or HACR type circuit breaker for protection of field wiring conductors.
Based on 75°C copper wire. All wiring must conform to the National Electric Code (NEC) and all local codes.
These “Minimum Circuit Ampacity” values are to be used for sizing the field power conductors. Refer to the National Electric Code (latest version), Article 310 for power
conductor sizing.
Pay special attention to Note * of Table 310 regarding Ampacity Adjustment Factors when more than 3 conductors are in a raceway.
123
SHIPPING DAMAGE
Upon receipt of equipment, the carton should be checked for external signs of shipping damage. If damage is found, the receiving party must contact the last carrier immediately, preferably in writing, requesting inspection by the carrier’s agent.
GENERAL
The equipment covered in this manual is to be installed by trained, experienced service and installation technicians.
The refrigerant system is completely assembled and charged. All internal wiring is complete.
The unit is designed for use with or without duct work. Flanges are provided for attaching the supply and return ducts.
These instructions explain the recommended method to install the air cooled self-contained unit and the electrical wiring connections to the unit.
These instructions and any instructions packaged with any separate equipment required to make up the entire air conditioning system should be carefully read before beginning the installation. Note particularly “Starting Procedure” and any tags and/or labels attached to the equipment.
Refer to Table 9 for maximum static pressure available for duct design.
Design the duct work according to methods given by the Air Conditioning Contractors of America (ACCA). When duct runs through unheated spaces, it should be insulated with a minimum of 1-inch of insulation. Use insulation with a vapor barrier on the outside of the insulation. Flexible joints should be used to connect the duct work to the equipment in order to keep the noise transmission to a minimum.
A 1/4 inch clearance to combustible material for the first three feet of duct attached to the outlet air frame is required. See Wall Mounting Instructions and Figures 3 and 4 for further details.
Ducts through the walls must be insulated and all joints taped or sealed to prevent air or moisture entering the wall cavity.
CAUTION
Some installations may not require any return air duct. A return air grille is required with installations not requiring a return air duct. The spacing between louvers on the grille shall not be larger than 5/8 inches.
While these instructions are intended as a general recommended guide, they do not supersede any national and/or local codes in any way. Authorities having jurisdiction should be consulted before the installation is made. See Page 3 for information on codes and standards.
Size of unit for a proposed installation should be based on heat loss calculation made according to methods of Air Conditioning Contractors of America (ACCA). The air duct should be installed in accordance with the Standards of the National Fire Protection Association for the Installation of Air Conditioning and Ventilating Systems of Other Than Residence Type, NFPA No. 90A, and Residence Type Warm Air Heating and Air Conditioning Systems, NFPA No. 90B. Where local regulations are at a variance with instructions, installer should adhere to local codes.
DUCT WORK
All duct work, supply and return, must be properly sized for the design air flow requirement of the equipment. Air Conditioning Contractors of America (ACCA) is an excellent guide to proper sizing. All duct work or portions thereof not in the conditioned space should be properly insulated in order to both conserve energy and prevent condensation or moisture damage.
Any grille that meets the 5/8 inch louver criteria, may be used. It is recommended that Bard Return Air Grille Kit RG-5 or RFG-5 be installed when no return duct is used. Contact distributor or factory for ordering information. If using a return air filter grille, filters must be of sufficient size to allow a maximum velocity of 400 fpm.
NOTE: If no return air duct is used, applicable
installation codes may limit this cabinet to installation only in a single story structure.
FILTERS
A 2-inch pleated filter is supplied with each unit. The filter slides into position making it easy to service. This filter can be serviced from the outside by removing the service door. The internal filter brackets are adjustable to accommodate the 1-inch filter by bending up the tabs to allow spacing for the 1-inch filters.
CONDENSATE DRAIN
A plastic drain hose extends from the drain pan at the top of the unit down to the unit base. There are openings in the unit base for the drain hose to pass through. In the event the drain hose is connected to a drain system of some type, it must be an open or vented type system to assure proper drainage.
Manual 2100-451E
Page 7 of 24
INSTALLATION INSTRUCTIONS
WALL MOUNTING INFORMATION
1. Two holes, for the supply and return air openings, must be cut through the wall as shown in Figure 3.
2. On wood-frame walls, the wall construction must be strong and rigid enough to carry the weight of the unit without transmitting any unit vibration. See Figures 4 and 5.
WARNING
Fire hazard can result if 1/4 inch clearance to combustible materials for supply air duct is not maintained. See Figure 3.
3. Concrete block walls must be thoroughly inspected to insure that they are capable of carrying the weight of the installing unit. See Figure 4.
MOUNTING THE UNIT
1. These units are secured by wall mounting brackets which secure the unit to the outside wall surface at both sides. A bottom mounting bracket is provided for ease of installation.
2. The unit itself is suitable for “0” inch clearance, but the supply air duct flange and the first 3 feet of supply air duct require a minimum of 1/4 inch clearance to combustible material. If a combustible wall, use a minimum of 30-1/2" x 10-1/2" dimensions for sizing. However, it is generally recommended that a 1-inch clearance is used for ease of installation and maintaining the required clearance to combustible material. The supply air opening would then be 32" x 12". See Figures 2, 3 and 6 for details.
WARNING
Failure to provide the 1/4 inch clearance between the supply duct and a combustible surface for the first 3 feet of duct can result in fire.
3. Locate and mark lag bolt locations and bottom mounting bracket location. See Figure 4.
4. Mount bottom mounting bracket.
5. Hook top rain flashing under back bend of top. Top rain flashing is shipped secured to the right side of the back.
6. Position unit in opening and secure with 5/16 lag bolts; use 7/8 inch diameter flat washers on the lag bolts.
7. Secure rain flashing to wall and caulk across entire length of top. See Figure 2.
8. For additional mounting rigidity, the return air and supply air frames or collars can be drilled and screwed or welded to the structural wall itself (depending upon wall construction). Be sure to observe required clearance if combustible wall.
9. On side-by-side installations, maintain a minimum of 20 inches clearance on right side to allow access to heat strips and control panel and to allow proper airflow to the outdoor coil. Additional clearance may be required to meet local or national codes.
TYPICAL INSTALLATIONS
See Figure 5 for common ways to install the wall mount unit.
WIRING — MAIN POWER
Refer to the unit rating plate for wire sizing information and maximum fuse or “HACR” type circuit breaker size. Each outdoor unit is marked with a “Minimum Circuit Ampacity”. This means that the field wiring used must be sized to carry that amount of current. Depending on the installed KW of electric heat, there may be two field power circuits required. If this is the case, the unit serial plate will so indicate. All models are suitable only for connection with copper wire. Each unit and/or wiring diagram will be marked “Use Copper Conductors Only”. These instructions must be adhered to. Refer to the National Electrical Code (NEC) for complete current carrying capacity data on the various insulation grades of wiring material. All wiring must conform to NEC and all local codes.
The electrical data lists fuse and wire sizes (75ºC copper) for all models, including the most commonly used heater sizes. Also shown are the number of field power circuits required for the various models with heaters.
Manual 2100-451E Page 8 of 24
Loading...
+ 16 hidden pages