These publications can help you install the air
conditioner or heat pump. You can usually find these at
your local library or purchase them directly from the
publisher. Be sure to consult current edition of each
standard.
National Electrical Code ...................... ANSI/NFPA 70
Standard for the Installation of .......... ANSI/NFPA 90A
Air Conditioning and
Ventilating Systems
Standard for Warm Air Heating ........ ANSI/NFPA 90B
and Air Conditioning Systems
Load Calculation for ............................ACCA Manual J
Residential Winter and
Summer Air Conditioning
Duct Design for ................................. ACCA Manual D
Residential Winter and
Summer Air Conditioning
and Equipment Selection
For more information, contact these
publishers:
ACCAAir Conditioning Contractors of America
1712 New Hampshire Avenue NW
Washington, DC 20009
Telephone: (202) 483-9370
Fax: (202) 234-4721
ANSIAmerican National Standards Institute
11 West Street, 13th Floor
New York, NY 10036
Telephone: (212) 642-4900
Fax: (212) 302-1286
ASHRAE American Society of Heating, Refrigerating
and Air Conditioning Engineers, Inc.
1791 Tullie Circle, NE
Atlanta, GA 30329-2305
Telephone: (404) 636-8400
Fax: (404) 321-5478
NFPANational Fire Protection Association
Batterymarch Park
P.O. Box 9101
Quincy, MA 02269-9901
Telephone: (800) 344-355
Fax: (617) 984-7057
Manufactured under the following U.S. patent numbers:
5,485,878; and 5,301,744
Manual2100-234I
Page3 of 17
WALL MOUNT GENERAL INFORMATION
AIR CONDITIONER WALL MOUNT MODEL NOMENCLATURE
MODEL NUMBER
CAPACITY
12 - 1 Ton
REVISIONS
VOLTS & PHASE
A - 230/208/60/1
K - 115/60/1
WA 12 1 – A 00 X X X X X J
COLOR OPTIONS
KW
00 - No KW
02 - 2.2 KW
03 - 3.6 KW
05 - 5.0 KW
VENTILATION OPTIONS
X - Barometric Fresh Air
Damper (Standard)
B - Blank-off Plate
E - Economizer (Internal) - Fully
Modulating with Exhaust
TABLE 1
ELECTRIC HEAT TABLE
X - Beige
4 - Buckeye Gray
FILTER OPTIONS
X - One Inch Throwaway
(Standard)
P - Two Inch Pleated
CONTROL MODULES
E - Low Ambient Control
J - Telecommunication
COIL OPTIONS
X - Standard Coils
OUTLET OPTIONS
X - Front
sledoMA-121AWK-121AWG-121AW
WKA1UTBA1UTBA1UTBA1UTBA1UTB
203.81589,70.01566,81.9003,7
300.51067,210.31507,90.51067,218.31008,01
508.02045,711.81572,31
1dedulcnisttawrewolbhtiW
Manual 2100-234I
Page4 of 17
V042V802V021V042V022
FIGURE 1
UNIT DIMENSIONS
FACTORY BUILT AT 5 INCHES
Manual2100-234I
Page5 of 17
TABLE 2
ELECTRICAL HEAT SPECIFICATIONS
TIUCRICELGNIS
3
stloVdetaR
dna
sledoM
00A-121AW
30A
50A
00K-121AW
20K
00G-121AW
20G
30G
Maximum size of the time delay fuse or HACR type circuit breaker for protection of field wiring conductors.
Based on 75° C copper wire. All wiring must conform to NEC and all local codes.
These “Minimum Circuit Ampacity” values are to be used for sizing the field power conductors. Refer to the
National Electrical Code (latest revision), article 310 for power conductor sizing.
CAUTION: When more than one field power conductor circuit is run through one conduit, the conductors
must be derated. Pay special attention to note 8 of table 310 regarding Ampacity Adjustment Factors when
more than 3 conductors are in a raceway.
esahP
1-802/032
1-511
1-05-022
dleiF.oN
rewoP
stiucriC
1
1
1
1
1
1
1
1
muminiM
tiucriC
yticapmA
8
02
72
71
52
7
31
02
1
2
mumixaM
esuFlanretxE
tiucriCro
rekaerB
51
02
03
52
03
51
51
02
rewoPdleiF
eziSeriW
41
21
01
01
01
41
41
21
2
dnuorG
eziSeriW
41
21
01
01
01
41
41
21
SHIPPING DAMAGE
Upon receipt of equipment, the carton should be checked
for external signs of shipping damage. If damage is
found, the receiving party must contact the last carrier
immediately, preferably in writing, requesting inspection
by the carrier’s agent.
GENERAL
The equipment covered in this manual is to be installed
by trained, experienced service and installation
technicians.
The refrigerant system is completely assembled and
charged. All internal wiring is complete.
The unit is designed for use with or without duct work.
Flanges are provided for attaching the supply and return
air ducts.
These instructions explain the recommended method to
install the air cooled self-contained unit and the electrical
wiring connections to the unit.
These instructions and any instructions packaged with
any separate equipment required to make up the entire air
conditioning system should be carefully read before
beginning the installation. Note particularly “Starting
Procedure” and any tags and/or labels attached to the
equipment.
While these instructions are intended as a general
recommended guide, they do not supersede any national
and/or local codes in any way. Authorities having
jurisdiction should be consulted before the installation is
made. See Page 3 for information on codes and
standards.
Size of unit for a proposed installation should be based
on heat loss calculation made according to methods of
Air Conditioning Contractors of America (ACCA). The
air duct should be installed in accordance with the
Standards of the National Fire Protection Association for
the Installation of Air Conditioning and Ventilating
Systems of Other Than Residence Type, NFPA No. 90A,
and Residence Type Warm Air Heating and Air
Conditioning Systems, NFPA No. 90B. Where local
regulations are at a variance with instructions, installer
should adhere to local codes.
Manual 2100-234I
Page6 of 17
Loading...
+ 11 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.