Table 7Vent & Control Options ......................... 23
Manual 2100-538E
Page2 of 23
GETTING OTHER INFORMATION AND PUBLICATIONS
These publications can help you install the air
conditioner or heat pump. You can usually find these at
your local library or purchase them directly from the
publisher. Be sure to consult current edition of each
standard.
National Electrical Code ...................... ANSI/NFPA 70
Standard for the Installation .............. ANSI/NFPA 90A
of Air Conditioning and Ventilating Systems
Standard for Warm Air ...................... ANSI/NFPA 90B
Heating and Air Conditioning Systems
Load Calculation for ............................ACCA Manual J
Residential Winter and Summer Air Conditioning
Duct Design for Residential .............. ACCA Manual D
Winter and Summer Air Conditioning and Equipment
Selection
FOR MORE INFORMATION, CONTACT
THESE PUBLISHERS:
ACCAAir Conditioning Contractors of America
1712 New Hampshire Ave. N.W.
Washington, DC 20009
Telephone: (202) 483-9370
Fax: (202) 234-4721
ANSIAmerican National Standards Institute
11 West Street, 13th Floor
New York, NY 10036
Telephone: (212) 642-4900
Fax: (212) 302-1286
Batterymarch Park
P.O. Box 9101
Quincy, MA 02269-9901
Telephone: (800) 344-3555
Fax: (617) 984-7057
Manufactured under the following
U.S. Patent numbers:
5,485,878; 5,301,744
Manual 2100-538E
Page3 of 23
WALL MOUNT GENERAL INFORMATION
Environmental Control Unit (ECU) Wall-Mount Model Nomenclature
W3RV1–R10XXXXXX
MODEL
SERIES
Wall-Mount
SYSTEM DESIGN
Variable Capacity
(Digital Compressor) ECU
COMPRESSOR &
CONTROLS LOCATION
R - Right Side
L - Left Side
REVISIONS
SPECIAL
FEATURES
ELECTRICAL RATING
R - 230/208-60-1 & 220/200-50-1
S - 230/208-60-3 & 220/200-50-3
T - 460-60-3 & 400-50-3
KW
Electric
Heat @
Rated
Voltage
COLOR OPTIONS
X - Beige (Standard)
1-White
4 - Buckeye Gray
5 - Desert Brown
6 - Dark Bronze
A - Aluminum
S - Stainless Steel
COIL OPTIONS
X - Standard Copper Tube/Aluminum Fin
1 - Phenolic Coated Indoor Coil
2 - Phenolic Coated Outdoor Coil
3 - Phenolic Coated Indoor & Outdoor Coil
OTHER OPTIONS
X - None
NOMINAL TONS
3 - 3 Ton (37,000 on 60Hz; 33,700 on 50Hz)
5 - 5 Ton (54,000 on 60Hz; 49,200 on 50Hz)
6 - 6 Ton (68,000 on 60Hz; 61,900 on 50Hz)
NOTE: Vent options X and B are without exhaust capability. May require separate field supplied barometric relief in building.
SHIPPING DAMAGE
Upon receipt of equipment, the carton should be
checked for external signs of shipping damage. If
damage is found, the receiving party must contact the
last carrier immediately, preferably in writing,
requesting inspection by the carrier’s agent.
VENTILATION OPTIONS
X - Barometric Fresh Air Damper (Standard)
B - Blank-off Plate
These instructions and any instructions packaged with
any separate equipment required to make up the entire
air conditioning system should be carefully read before
beginning the installation. Note particularly “Starting
Procedure” and any tags and/or labels attached to the
equipment.
FILTER OPTIONS
X - One Inch Throwaway (Standard)
W - One Inch Washable
P - Two Inch Pleated
While these instructions are intended as a general
GENERAL
The equipment covered in this manual is to be installed
by trained, experienced service and installation
technicians.
The refrigerant system is completely assembled and
charged. All internal wiring is complete.
The unit is designed for use with or without duct work.
Flanges are provided for attaching the supply and return
ducts.
These instructions explain the recommended method to
install the air cooled self-contained unit and the
electrical wiring connections to the unit.
recommended guide, they do not supersede any national
and/or local codes in any way. Authorities having
jurisdiction should be consulted before the installation is
made. See Page 3 for information on codes and
standards.
Size of unit for a proposed installation should be based
on heat loss calculation made according to methods of
Air Conditioning Contractors of America (ACCA). The
air duct should be installed in accordance with the
Standards of the National Fire Protection Association
for the Installation of Air Conditioning and Ventilating
Systems of Other Than Residence Type, NFPA No.
90A, and Residence Type Warm Air Heating and Air
Conditioning Systems, NFPA No. 90B. Where local
regulations are at a variance with instructions, installer
should adhere to local codes.
OUTLET OPTIONS
X - Front (Standard)
Manual 2100-538E
Page4 of 23
DUCT WORK
All duct work, supply and return, must be properly sized
for the design airflow requirement of the equipment.
Air Conditioning Contractors of America (ACCA) is an
excellent guide to proper sizing. All duct work or
portions thereof not in the conditioned space should be
properly insulated in order to both conserve energy and
prevent condensation or moisture damage.
Refer to Maximum ESP of operation Electric Heat
Table 5.
Design the duct work according to methods given by the
Air Conditioning Contractors of America (ACCA).
When duct runs through unheated spaces, it should be
insulated with a minimum of one inch of insulation. Use
insulation with a vapor barrier on the outside of the
insulation. Flexible joints should be used to connect the
duct work to the equipment in order to keep the noise
transmission to a minimum.
For model series W3R/LV, W5R/LV and W6R/LV a 1/4
inch clearance to combustible material for the first three
feet of duct attached to the outlet air frame is required.
See Wall Mounting Instructions and Figures 3A, 3B and
4 for further details.
Ducts through the walls must be insulated and all joints
taped or sealed to prevent air or moisture entering the
wall cavity.
Some installations may not require any return air duct. A
metallic return air grille is required with installations not
requiring a return air duct. The spacing between louvers
on the grille shall not be larger than 5/8 inch.
Any grille that meets with 5/8 inch louver criteria may be
used. It is recommended that Bard Return Air Grille Kit
RG2 through RG5 or RFG2 through RFG5 be installed
when no return duct is used. Contact distributor or
factory for ordering information. If using a return air
filter grille, filters must be of sufficient size to allow a
maximum velocity of 400 fpm.
NOTE: If no return air duct is used, applicable
installation codes may limit this cabinet to
installation only in a single story structure.
FILTERS
A 1-inch throwaway filter is standard with each unit.
The filter slides into position making it easy to service.
This filter can be serviced from the outside by removing
the filter access panel. A 1-inch washable filter and 2inch pleated filter are also available as optional
accessories. The internal filter brackets are adjustable
to accommodate the 2-inch filter by bending two (2)
tabs down on each side of the filter support bracket.
FRESH AIR INTAKE
All units are built with fresh air inlet slots punched in
the service door.
If the unit is equipped with a fresh air damper assembly,
the assembly is shipped already attached to the unit.
The damper blade is locked in the closed position. To
allow the damper to operate, the maximum and
minimum blade position stops must be installed. See
Figure 1.
All capacity, efficiency and cost of operation
information is based upon the fresh air blank-off plate in
place and is recommended for maximum energy
efficiency.
The blank-off plate is available upon request from the
factory and is installed in place of the fresh air damper
shipped with each unit.
CONDENSATE DRAIN
A plastic drain hose extends from the drain pan at the
top of the unit down to the unit base. There are
openings in the unit base for the drain hose to pass
through. In the event the drain hose is connected to a
drain system of some type, it must be an open or vented
type system to assure proper drainage.
FIGURE 1
FRESH AIR DAMPER
Manual 2100-538E
Page5 of 23
C
a
M
E
W
W
W
W
T
INSTALLATION INSTRUCTIONS
WALL MOUNTING INFORMATION
1. Two holes for the supply and return air openings
must be cut through the wall as shown in Figures 3A
& 3B.
2. On wood frame walls, the wall construction must be
strong and rigid enough to carry the weight of the
unit without transmitting any unit vibration.
3. Concrete block walls must be thoroughly inspected
to insure that they are capable of carrying the weight
of the installed unit.
MOUNTING THE UNIT
1. These units are secured by wall mounting brackets
which secure the unit to the outside wall surface at
both sides. A bottom mounting bracket, attached to
skid for shipping, is provided for ease of installation,
but is not required.
2. The supply air duct flange and the first 3 feet of
supply air duct require a minimum of 1/4 inch
clearance to combustible material for model series
W3R/LV, W5R/LV and W6R/LV
generally recommended that a 1-inch clearance is
used for ease of installation and maintaining the
required clearance to combustible material. See
Figures 3A & 3B for details on opening sizes.
3. Locate and mark lag bolt locations and bottom
mounting bracket location. See Figures 3A & 3B.
. However, it is
WARNING
Failure to provide the 1/4 inch clearance
between the supply duct and a combustible
surface for the first 3 feet of duct can result in
fire causing damage, injury or death.
6. Position unit in opening and secure with 5/16 lag
bolts; use 7/8 inch diameter flat washers on the lag
bolts.
7. Secure rain flashing to wall and caulk across entire
length of top. See Figures 3A & 3B.
8. For additional mounting rigidity, the return air and
supply air frames or collars can be drilled and
screwed or welded to the structural wall itself
(depending upon wall construction). Be sure to
observe required clearance if combustible wall.
9. On side-by-side installations, maintain a minimum
of 20 inches clearance on right side to allow access
to control panel and heat strips, and to allow proper
airflow to the outdoor coil. Additional clearance
may be required to meet local or national codes.
4. Mount bottom mounting bracket.
5. Hook top rain flashing, attached to front - right of
supply flange for shipping, under back bend of top.
sseccAecivreSrofderiuqeRsecnarael
wolfriAresnednoCetauqedAdn
SLEDO
1VR3
1VL3
1VR6W,1VR5
1VL6W,1VL5
NOTE: For side by side installation of two (2) W*RV models there
must be 20" between units. This can be reduced to 15" by using
a W*LV model (left side compressor and controls) for the left unit
and W*R (right side compressor and controls) for right unit.