X - Barometric Fresh Air Damper (Standard)
B - Blank-off Plate
M - Motorized Fresh Air Damper
V - Commercial Ventilator - Motorized with Exhaust
E - Economizer (Internal) - Fully Modulating with Exhaust
R - Energy Recovery Ventilator - Motorized with Exhaust
(See Spec. Sheet S3398)
A - Manual Fresh Air Damper
H - Commercial Ventilator - Motorized with Exhaust
SHIPPING DAMAGE
Upon receipt of equipment, the carton should be
checked for external signs of shipping damage. If
damage is found, the receiving party must contact
the last carrier immediately, preferably in writing,
requesting inspection by the carrier’s agent.
X - Beige (Standard)
1 - White
4 - Buckeye Gray
5 - Desert Brown
8 - Dark Bronze
FILTER OPTIONS
X - One Inch Throwaway (Standard)
W - One Inch Washable
P - Two Inch Pleated
OUTLET OPTIONS
X - Front (Standard)
These instructions and any instructions packaged with
any separate equipment required to make up the entire
air conditioning system should be carefully read before
beginning the installation. Note particularly “Starting
Procedure” and any tags and/or labels attached to the
equipment.
CONTROL MODULES
(See Spec. Sheets
S3416 & S3417)
COIL OPTIONS
X - Standard
1 - Phenolic Coated Evaporator
2 - Phenolic Coated Condenser
3 - Phenolic Coated Evaporator
and Condenser
While these instructions are intended as a general
GENERAL
The equipment covered in this manual is to be installed
by trained, experienced service and installation
technicians.
The refrigerant system is completely assembled and
charged. All internal wiring is complete.
The unit is designed for use with or without duct work.
Flanges are provided for attaching the supply and return
ducts.
These instructions explain the recommended method
to install the air cooled self-contained unit and the
electrical wiring connections to the unit.
recommended guide, they do not supersede any
national and/or local codes in any way. Authorities
having jurisdiction should be consulted before the
installation is made. See Page 3 for information on
codes and standards.
Size of unit for a proposed installation should be
based on heat loss/gain calculation made according
to methods of Air Conditioning Contractors of
America (ACCA). The air duct should be installed
in accordance with the Standards of the National
Fire Protection Association for the Installation of Air
Conditioning and Ventilating Systems of Other Than
Residence Type, NFPA No. 90A, and Residence Type
Warm Air Heating and Air Conditioning Systems,
NFPA No. 90B. Where local regulations are at a
variance with instructions, installer should adhere to
local codes.
Manual 2100-527H
Page 4 of 29
Page 5
DUCT WORK
All duct work, supply and return, must be properly
sized for the design airow requirement of the
equipment. Air Conditioning Contractors of America
(ACCA) is an excellent guide to proper sizing. All duct
work or portions thereof not in the conditioned space
should be properly insulated in order to both conserve
energy and prevent condensation or moisture damage.
Design the duct work according to methods given by
the Air Conditioning Contractors of America (ACCA).
When duct runs through unheated spaces, it should be
insulated with a minimum of one inch of insulation.
Use insulation with a vapor barrier on the outside of the
insulation. Flexible joints should be used to connect the
duct work to the equipment in order to keep the noise
transmission to a minimum.
A 1/4 inch clearance to combustible material for the
rst three feet of duct attached to the outlet air frame is
required. See Wall Mounting Instructions and Figures
3A, 3B and 4 for further details.
Ducts through the walls must be insulated and all joints
taped or sealed to prevent air or moisture entering the
wall cavity.
Some installations may not require any return air duct. A
metallic return air grille is required with installations not
requiring a return air duct. The spacing between louvers
on the grille shall not be larger than 5/8 inch.
FILTERS
A 1-inch throwaway lter is standard with each unit.
The lter slides into position making it easy to service.
This lter can be serviced from the outside by removing
the lter access panel. A 1-inch washable lter and
2-inch pleated lter are also available as optional
accessories. The internal lter brackets are adjustable
to accommodate the 2-inch lter by bending two (2)
tabs down on each side of the lter support bracket.
FRESH AIR INTAKE
All units are built with fresh air inlet slots punched in
the service door.
If the unit is equipped with a fresh air damper assembly,
the assembly is shipped already attached to the unit.
The damper blade is locked in the closed position.
To allow the damper to operate, the maximum and
minimum blade position stops must be installed. See
Figure 1.
All capacity, efciency and cost of operation
information is based upon the fresh air blank-off plate
in place and is recommended for maximum energy
efciency.
The blank-off plate is available upon request from the
factory and is installed in place of the fresh air damper
shipped with each unit.
Any grille that meets with 5/8 inch louver criteria may be
used. It is recommended that Bard Return Air Grille Kit
RG2 through RG5 or RFG2 through RFG5 be installed
when no return duct is used. Contact distributor or
factory for ordering information. If using a return air
lter grille, lters must be of sufcient size to allow a
maximum velocity of 400 fpm.
NOTE: If no return air duct is used, applicable
installation codes may limit this cabinet to
installation only in a single story structure.
FIGURE 1
FRESH AIR DAMPER
CONDENSATE DRAIN
A plastic drain hose extends from the drain pan at
the top of the unit down to the unit base. There are
openings in the unit base for the drain hose to pass
through. In the event the drain hose is connected to a
drain system of some type, it must be an open or vented
type system to assure proper drainage.
Manual 2100-527H
Page 5 of 29
Page 6
INSTALLATION INSTRUCTIONS
WALL MOUNTING INFORMATION
1. Two holes for the supply and return air openings
must be cut through the wall as shown in Figure 3.
2. On wood frame walls, the wall construction must be
strong and rigid enough to carry the weight of the
unit without transmitting any unit vibration.
3. Concrete block walls must be thoroughly inspected
to insure that they are capable of carrying the
weight of the installed unit.
MOUNTING THE UNIT
1. These units are secured by wall mounting brackets
which secure the unit to the outside wall surface at
both sides. A bottom mounting bracket, attached
to skid for shipping, is provided for ease of
installation, but is not required.
2. The unit itself is suitable for 0 inch clearance,
but the supply air duct ange and the rst 3 feet
of supply air duct require a minimum of 1/4 inch
clearance to combustible material. However, it is
generally recommended that a 1-inch clearance is
used for ease of installation and maintaining the
required clearance to combustible material. See
Figure 3 for details on opening sizes.
3. Locate and mark lag bolt locations and bottom
mounting bracket location. See Figures 3A & 3B.
4. Mount bottom mounting bracket.
5. Hook top rain ashing, attached to front - right of
supply ange for shipping, under back bend of top.
6. Position unit in opening and secure with 5/16 lag bolts;
use 7/8 inch diameter at washers on the lag bolts.
7. Secure rain ashing to wall and caulk across entire
length of top. See Figures 3A & 3B.
WARNING
Failure to provide the 1/4 inch clearance
between the supply duct and a combustible
surface for the rst 3 feet of duct can result in
re causing damage, injury or death.
PLACEMENT
1. On side-by-side installations, maintain a minimum
of 20 inches clearance on right side to allow access
to control panel and heat strips, and to allow proper
airow to the outdoor coil. Additional clearance
may be required to meet local or national codes.
2. Care should be taken to ensure that the recirculation
and obstruction of condenser discharge air does
not occur. Recirculation of condenser discharge
air can be from either a single unit or multiple
units. Any object such as shrubbery, a building
or a large object can cause obstructions to the
condenser discharge air. Recirculation or reduced
airow caused by obstructions will result in reduced
capacity, possible unit pressure safety lockouts and
reduced unit service life.
Units with a blow through condenser, such as
the S**H 10 EER units, it is recommended that
a minimum distance of 15 feet between the front
of the unit and any barrier or 20 feet between the
fronts of two opposing (facing) units.
Units with a draw through condenser, such as the
W**H 10 EER units, it is recommended that a
minimum distance of 10 feet between the front of
the unit and any barrier or opposing (facing) unit.
8. For additional mounting rigidity, the return air
and supply air frames or collars can be drilled
and screwed or welded to the structural wall itself
(depending upon wall construction). Be sure to
observe required clearance if combustible wall.
Clearances Required for Service Access
and Adequate Condenser Airow
MODELSLEFT SIDERIGHT SIDE
S26H, S31H
W26H, W31H
S38H, S43H, S49H, S61H
W38H, W43H, W49H, W61H
Manual 2100-527H
Page 6 of 29
15"20"
20"20"
Minimum Clearances Required to
Combustible Materials
MODELS
S26H, S31H
W26H, W31H
S38H, S43H, S49H, S61H
W38H, W43H, W49H, W61H
SUPPLY AIR
DUCT FIRST
THREE FEET
1/4"0
1/4"0
CABINET
Page 7
Panel
Filter Access
Vent Option
Door
Ventilation
Air
Front View
5.75
F
W
G
Condenser
Air Inlet
MIS-2763
Rain Hood
(Lockable)
Built In
4° Pitch
Entrance
Disconnect
Access Panel
Electrical
Entrance
Low Voltage
Panel
Access
Heater
Heat
Electric
C. Breaker/
High Voltage
Electrical
Drain
Side View
J
K
D
A
C H
2.13
I
Cond.
Air
Outlet
Mounting
(Built In)
Side Wall
Location
Brackets
Shipping
Entrances
Return Air Opening
Electrical
Supply Air Opening
Optional
Top Rain
Flashing
Bottom Installation
Bracket
Back View
S2
T
.44
N
Q
P
M
L
O
E
R
S1
S1
S1
S2
B
FIGURE 2
Dimensions of Basic Unit for Architectural and Installation Requirements (Nominal)
All dimensions are in inches. Dimensional drawings are not to scale.
SUPPLY RETURN
(H)
ABCBEFGIJKLMNOPQRS1 S2T
S**H & W**H
RIGHT UNIT
Manual 2100-527H
Page 7 of 29
Page 8
D
12"
12"
12"
12"
12"
CCA
28"
1"
3"
4"
Typ.
4
1
2
"
B
E
14"
1"
3
1
8
"
4"
Typ.
5"
4
1
2
"
7
8
"
RETURN AIR
SUPPLIED
Return Opening
16 7/84 9/164 1/21030
17 5/83 13/165 1/48 1/228 1/2
EDCBA
COMBUSTIBLE MATERIALS
RECOMMENDED 1" CLEARANCE FROM
REQUIRED DIMENSIONS TO MAINTAIN
THE SIDE MOUNTING FLANGES AND UNDER
1/4" CLEARANCE ON ALL
RAIN FLASHING
COMBUSTIBLE MATERIALS
DUCT
TOP FLASHING AT TIME OF INSTALLATION.
1/4" MIN. CLEARANCE FROM
REQUIRED DIMENSIONS TO MAINTAIN
OPENING
ENTIRE LENGTH OF TOP.
MATERIALS
NOTES:
OF CAULKING ALONG
PANEL
FOAM AIR SEAL
FOUR SIDES OF SUPPLY
AIR DUCT IS REQUIRED
FROM COMBUSTABLE
WALL STRUCTURE
TOP
MIS-311 C
Wall Opening and Hole Location ViewRight Side View
WALL
HEATER ACCESS
SEAL WITH BEAD
IT IS RECOMMENDED THAT A BEAD OF
SILICONE CAULKING BE PLACED BEHIND
SUPPLY AIR
Supply Opening
W*RUNIT SHOWN, W*L UNIT
CONTROLS AND HEATER ACCESS
IS ON OPPOSITE (LEFT) SIDE.
FIGURE 3A
MOUNTING INSTRUCTIONS
S26H1, S31H1, W26H1, W31H1
Manual 2100-527H
Page 8 of 29
Page 9
D
16"
16"
16"
16"
16"
1
7
8
"
6
1
2
"6
1
2
"
2
1
8
"
7
8
"
1"
3"
4"
Typ.
4"
Typ.
6
1
2
"
30"
E
16"
ACC
3
1
8
"
B
Wall Opening and Hole Location View
RETURN AIR
1
REQUIRED DIMENSIONS TO MAINTAIN
1/4" MIN. CLEARANCE FROM
COMBUSTIBLE MATERIALS
REQUIRED DIMENSIONS TO MAINTAIN
29
DUCT
COMBUSTIBLE MATERIALS
ABCDE
30 1/2
10 1/2
6 1/41 1/4 29 3/4
32125 1/2
2
NOTES:
WALL STRUCTURE
1
SUPPLY AIR
IT IS RECOMMENDED THAT A BEAD OF
OPENING
Right Side View
RAIN FLASHING
SILICONE CAULKING BE PLACED BEHIND
RECOMMENDED 1" CLEARANCE FROM
THE SIDE MOUNTING FLANGES AND UNDER
TOP FLASHING AT TIME OF INSTALLATION.
TOP.
PANEL
HEATER ACCESS
FOUR SIDES OF SUPPLY
AIR DUCT IS REQUIRED
FROM COMBUSTABLE
WALL
1/4" CLEARANCE ON ALL
MATERIALS
Supply Opening
FOAM AIR SEAL
SUPPLIED
SEAL WITH BEAD
OF CAULKING ALONG
ENTIRE LENGTH OF
TOP
1
Return Opening
MIS-416 E
Dimension is 21" on 95" tall units.
2
Dimension is 10" on T48H1 & T60H1.
2
Dimension is 6" on T48H1 & T60H1.
3
3
FIGURE 3B
MOUNTING INSTRUCTIONS
S38H1, S43H1, S49H1, W38H1, W43H1, W49H1
Manual 2100-527H
Page 9 of 29
Page 10
FIGURE 4
ELECTRIC HEAT CLEARANCE
SIDE SECTION VIEW OF SUPPLY AIR DUCT
FOR WALL MOUNTED UNIT SHOWING 1/4 INCH
CLEARANCE TO COMBUSTIBLE SURFACES.
WARNING
A minimum of 1/4 inch clearance must be maintained between
the supply air duct and combustible materials. This is required for
the rst 3 feet of ducting.
It is important to insure that the 1/4 inch minimum spacing is
maintained at all points.
Failure to do this could result in overheating the combustible
material and may result in a re causing damage, injury or death.
Manual 2100-527H
Page 10 of 29
Page 11
FIGURE 5
DUCT
OPENING
RETURN AIR
SUPPLY AIR
WOOD FRAME WALL INSTALLATION
OPENING
WALL BEFORE
MOUNT ON UNIT
OPENING
BEFORE INSTALLATION
BOTTOM MOUNTING
CONCRETE BLOCK WALL INSTALLATION
BRACKET. MOUNT ON
OPENING
WOOD OR STEEL SIDING
OPENING
INSTALLING UNIT.
RETURN AIR
WALL STRUCTURE
RETURN AIR
SUPPLY AIR
FACTORY SUPPLIED
RAIN FLASHING.
SUPPLY AIR
MIS-548 A
SIDE VIEW
I
A
C
K
E + 1.000
B
1.000
SUPPLY DUCT
OVER FRAME
INTERIOR FINISHED WALL
ALL AROUND DUCT
FRAMING MATERIAL
EXTERIOR FINISH WALL
OPENING
FOR ACTUAL DIMENSIONS.
2 x 4'S, 2 x 6'S &/OR
STRUCTURAL STEEL
ATTACH TO TOP
1.000" CLEARANCE
1.000" CLEARANCE
PLATE OF WALL
C
SEE UNIT DIMENSIONS, FIGURE 2,
OPENING
RETURN DUCT
2 x 6
ATTACH TO BOTTOM
OVER FRAME
PLATE OF WALL
L
THIS STRUCTURAL MEMBER
LOCATED TO MATCH STUD
SPACING FOR REST OF WALL.
A SECOND MEMBER MAY BE
REQUIRED FOR SOME WALLS.
MIS-549 B
ALL AROUND DUCT
WALL MOUNTING INSTRUCTIONS
SEE FIGURE 3 – MOUNTING INSTRUCTIONS
FIGURE 6
WALL MOUNTING INSTRUCTIONS
Manual 2100-527H
Page 11 of 29
Page 12
FIGURE 7
LOWERED
RAISED FLOOR
RAFTERS
SUPPLY AIR
CEILING SURFACE
WALL SLEEVE
RETURN AIR
CLOSET WALL
GRILLE
FLASHING
RETURN AIR
FLASHING
SUPPLY DUCT MAYBE LOCATED IN AN ATTIC
OR BELOW CEILING RAFTERS AS SHOWN
SUPPLY DUCT MAY BE LOCATED IN AN ATTIC
SURFACE
RAFTERS
FINISHED CEILING
SUPPLY AIR DUCT
WALL
OPENING W/ GRILLE
SUPPLY DUCT MAYBE LOCATED IN AN ATTIC
OR BELOW CEILING RAFTERS AS SHOWN
CEILING
RAIN
RETURN AIR
SLEEVE
WALL
SUPPLY AIR DUCT
RAFTERS
RAFTERS
RETURN AIR
OPENING W/ GRILLE
RAIN
FALSE WALL INSTALLATION
DUCTED SUPPLY
GRILLE
OUTSIDE
SPACE
FALSE WALL
RETURN AIR GRILLE
OUTSIDE
OR BELOW CEILING RAFTERS AS SHOWN
FINISHED CEILING SURFACE
RAIN
FLASHING
RAIN
FLASHING
RETURN AT UNITNO DUCT
WALL
SUPPLY AIR DUCT
CLOSET INSTALLATION
RETURN AIR
FINISHED
FINISHED CEILING SURFACE
MIS-550 B
FREE AIR FLOW
OUTSIDE
WALL
OUTSIDE
WALL
SUPPLY AIR DUCT
W/ GRILLE
COMMON WALL MOUNTING INSTALLATIONS
Manual 2100-527H
Page 12 of 29
Page 13
WIRING – MAIN POWER
Refer to the unit rating plate for wire sizing information
and maximum fuse or “HACR” type circuit breaker
size. Each outdoor unit is marked with a “Minimum
Circuit Ampacity”. This means that the eld wiring
used must be sized to carry that amount of current.
Depending on the installed KW of electric heat, there
may be two eld power circuits required. If this is the
case, the unit serial plate will so indicate. All models
are suitable only for connection with copper wire. Each
unit and/or wiring diagram will be marked “Use Copper
Conductors Only”. These instructions must be adhered
to. Refer to the National Electrical Code (NEC) for
complete current carrying capacity data on the various
insulation grades of wiring material. All wiring must
conform to NEC and all local codes.
The electrical data lists fuse and wire sizes (75°C
copper) for all models including the most commonly
used heater sizes. Also shown are the number of eld
power circuits required for the various models with
heaters.
The unit rating plate lists a “Maximum Time Delay
Relay Fuse” or “HACR” type circuit breaker that is to
be used with the equipment. The correct size must be
used for proper circuit protection and also to assure that
there will be no nuisance tripping due to the momentary
high starting current of the compressor motor.
WIRING – LOW VOLTAGE WIRING
230/208V, 1 phase and 3 phase equipment dual primary
voltage transformers. All equipment leaves the factory
wired on 240V tap. For 208V operation, reconnect
from 240V to 208V tap. The acceptable operating
voltage range for the 240 and 208V taps are:
power connection point in the unit and while
the unit is operating at full load (maximum
amperage operating condition).
For wiring size and connections, refer to Wiring
Manual 2100-516.
The disconnect access door on this unit may be locked
to prevent unauthorized access to the disconnect. To
convert for the locking capability, bend the tab located
in the bottom left-hand corner of the disconnect
opening under the disconnect access panel straight
out. This tab will now line up with the slot in the door.
When shut, a padlock may be placed through the hole
in the tab preventing entry.
See “Start Up” section for important information on
three phase scroll compressor start ups.
See Tables 7A & 7B for Electrical Specications.
Manual 2100-527H
Page 13 of 29
Page 14
FIGURE 8
COMPRESSOR CUTOFF THERMOSTAT WIRING
4 – 10KW 1 PH – 6 & 9KW 3 PH
FIGURE 9
COMPRESSOR CUTOFF THERMOSTAT WIRING
15 – 20KW 1 PH AND 3 PH
OPTIONAL OUTDOOR THERMOSTAT
APPLICATIONS
Since most equipment at the time of manufacture is not
designated for any specic destination of the country
and are installed in areas not approaching the lower
outdoor temperature range, outdoor thermostats are not
factory installed as standard equipment, but are offered
as an option. There are also different applications for
applying outdoor thermostats. The set point of either
type of outdoor thermostat application is variable with
geographic region and sizing of the heating equipment
to the individual structure. Utilization of the heating
Application Data, and the heat loss calculation of the
building are useful in determining the correct set points.
NOTE: The additional LAB (low ambient bypass) relay
is required to prevent heater operation during low
temperature cooling operation.
Manual 2100-527H
Page 14 of 29
OPTIONAL COMPRESSOR CUTOFF
THERMOSTAT (See Figures 8 & 9)
Heat pump compressor operation at outdoor
temperatures below 0°F are neither desirable nor
advantageous in term of efciency. An outdoor
thermostat can be applied to take the mechanical
heating (compressor) off line, and send the
(compressor) signal to energize electric heat in its place
(to make electric heat rst stage heating). This can also
be applied to bank the quantity of available electric
heat. For example: A heat pump operates with 10KW
second stage heat – once the outdoor thermostat has
switched then operates 15KW without the compressor
as rst stage heat.
Page 15
ELECTRIC HEAT HOLD-OFF
(See Figures 10 & 11)
In other applications, it is desirable to disable the
operation of the electric heat until outdoor temperatures
have reached a certain design point. This won't allow
the electric heat to come on as second stage heating
unless the outdoor temperature is below the set point
of the outdoor thermostat. This is done to maximize
FIGURE 10
ELECTRIC HEAT HOLD-OFF WIRING
4 – 10KW 1 PH — 6 & 9KW 3 PH
efciency by utilizing the heat pump to bring the
conditioned space temperature up, rather than cycling
on the electric heat due a second stage call for heat
from the thermostat on start-up coming off a night setback condition or someone increasing the thermostat
set point. (NOTE: Some programmable thermostats
do have a built-in time delay for pulling in second stage
heat when coming off set-back conditions.)
FIGURE 11
ELECTRIC HEAT HOLD-OFF WIRING
15 – 20KW 1 PH & 3 PH
Manual 2100-527H
Page 15 of 29
Page 16
START UP
THESE UNITS REQUIRE R-410A
REFRIGERANT AND POLYOL
ESTER OIL.
GENERAL:
1. Use separate service equipment to avoid cross
contamination of oil and refrigerants.
2. Use recovery equipment rated for R-410A
refrigerant.
3. Use manifold gauges rated for R-410A (800 psi/250
psi low).
4. R-410A is a binary blend of HFC-32 and HFC-125.
5. R-410A is nearly azeotropic - similar to R-22 and
R-12. Although nearly azeotropic, charge with
liquid refrigerant.
6. R-410A operates at 40-70% higher pressure than
R-22, and systems designed for R-22 cannot
withstand this higher pressure.
7. R-410A has an ozone depletion potential of zero,
but must be reclaimed due to its global warming
potential.
8. R-410A compressors use Polyol Ester oil.
9. Polyol Ester oil is hygroscopic; it will rapidly
absorb moisture and strongly hold this moisture in
the oil.
10. A liquid line dryer must be used - even a deep
vacuum will not separate moisture from the oil.
11. Limit atmospheric exposure to 15 minutes.
12. If compressor removal is necessary, always plug
compressor immediately after removal. Purge with
small amount of nitrogen when inserting plugs.
TOPPING OFF SYSTEM CHARGE
If a leak has occurred in the system, Bard
Manufacturing recommends reclaiming, evacuating
(see criteria above), and charging to the nameplate
charge. If done correctly, topping off the system charge
can be done without problems.
With R-410A, there are no signicant changes in the
refrigerant composition during multiple leaks and
recharges. R-410A refrigerant is close to being an
azeotropic blend (it behaves like a pure compound
or single component refrigerant). The remaining
refrigerant charge, in the system, may be used after
leaks have occurred and then “top-off” the charge by
utilizing the pressure charts on the inner control panel
cover as a guideline.
REMEMBER: When adding R-410A refrigerant, it
must come out of the charging cylinder/tank as a liquid
to avoid any fractionation, and to insure optimal system
performance. Refer to instructions for the cylinder that
is being utilized for proper method of liquid extraction.
WARNING
Failure to conform to these practices
could lead to damage, injury or death.
SAFETY PRACTICES:
1. Never mix R-410A with other refrigerants.
2. Use gloves and safety glasses, Polyol Ester oils can
be irritating to the skin, and liquid refrigerant will
freeze the skin.
3. Never use air and R-410A to leak check; the
mixture may become ammable.
4. Do not inhale R-410A – the vapor attacks the
nervous system, creating dizziness, loss of coordination and slurred speech. Cardiac irregularities, unconsciousness and ultimate death
can result from breathing this concentration.
5. Do not burn R-410A. This decomposition produces hazardous vapors. Evacuate the area if
exposed.
6. Use only cylinders rated DOT4BA/4BW 400.
7. Never ll cylinders over 80% of total capacity.
8. Store cylinders in a cool area, out of direct
sunlight.
9. Never heat cylinders above 125°F.
10. Never trap liquid R-410A in manifold sets, gauge
lines or cylinders. R-410A expands signicantly
at warmer temperatures. Once a cylinder or line is
full of liquid, any further rise in temperature will
cause it to burst.
Manual 2100-527H
Page 16 of 29
Page 17
START UP (Continued)
IMPORTANT INSTALLER NOTE
For improved start up performance wash the indoor coil
with a dish washing detergent.
HIGH & LOW PRESSURE SWITCH
All S**H and W**H wall mounted air conditioner series
models are supplied with a remote reset for the high and
low pressure switch. If tripped, this pressure switch may
be reset by turning the thermostat off then back on again.
THREE PHASE SCROLL COMPRESSOR
START UP INFORMATION
Scroll compressors, like several other types of
compressors, will only compress in one rotational
direction. Direction of rotation is not an issue with
single phase compressors since they will always start
and run in the proper direction.
However, three phase compressors will rotate in
either direction depending upon phasing of the power.
Since there is a 50-50 chance of connecting power
in such a way as to cause rotation in the reverse
direction, verication of proper rotation must be made.
Verication of proper rotation direction is made by
observing that suction pressure drops and discharge
pressure rises when the compressor is energized.
Reverse rotation also results in an elevated sound level
over that with correct rotation, as well as substantially
reduced current draw compared to tabulated values.
Verication of proper rotation must be made at the
time the equipment is put into service. If improper
rotation is corrected at this time, there will be no
negative impact on the durability of the compressor.
However, reverse operation for over one hour may have
a negative impact on the bearing due to oil pump out.
NOTE: If compressor is allowed to run in reverse
rotation for several minutes, the compressor’s
internal protector will trip.
PHASE MONITOR
All units with three phase scroll compressors are
equipped with a 3-phase line monitor to prevent
compressor damage due to phase reversal.
The phase monitor in this unit is equipped with two
LEDs. If the Y signal is present at the phase monitor
and phases are correct the green LED will light.
If phases are reversed, the red fault LED will be lit and
compressor operation is inhibited.
If a fault condition occurs, reverse two of the supply
leads to the unit. Do not reverse any of the unit
factory wires as damage may occur.
CONDENSER FAN OPERATION
Applies to S38, S43, S49, S61 & W38, W43, W49, W61
models only. The condenser fan motor on 230/208
volt, one and three phase, 60 HZ units is a two-speed
motor that comes factory wired on high speed for peak
performance. If ambient conditions permit, it can be
reconnected to low speed (red wire) for lower sound
level. See wiring diagram.
50 HZ models must have fan wired on low speed.
These models are factory wired on low speed.
SERVICE HINTS
1. Caution owner/operator to maintain clean air
lters at all times. Also, not to needlessly close off
supply and return air registers. This reduces airow
through the system, which shortens equipment
service life as well as increasing operating costs.
2. Check all power fuses or circuit breakers to be sure
they are the correct rating.
3. Periodic cleaning of the outdoor coil to permit full
and unrestricted airow circulation is essential.
All three phase ZP compressors are wired identically
internally. As a result, once the correct phasing
is determined for a specic system or installation,
connecting properly phased power leads to the same
Fusite terminal should maintain proper rotation
direction.
The direction of rotation of the compressor may be
changed by reversing any two line connections to the
unit.
Manual 2100-527H
Page 17 of 29
Page 18
SEQUENCE OF OPERATION
COOLING – Circuit R-Y makes at thermostat pulling in
compressor contactor, starting the compressor and outdoor
motor. The G (indoor motor) circuit is automatically
completed on any call for cooling operation or can be
energized by manual fan switch on subbase for constant air
circulation.
HEATING – A 24V solenoid coil on reversing valve
controls heating cycle operation. Two thermostat options,
one allowing “Auto” changeover from cycle to cycle and
the other constantly energizing solenoid coil during heating
season, and thus eliminating pressure equalization noise
except during defrost, are to be used. On “Auto” option
a circuit is completed from R-B and R-Y on each heating
“on” cycle, energizing reversing valve solenoid and pulling
in compressor contactor starting compressor and outdoor
motor. R-G also make starting indoor blower motor. Heat
pump heating cycle now in operation. The second option
has no “Auto” changeover position, but instead energizes
the reversing valve solenoid constantly whenever the
system switch on subbase is placed in “Heat” position,
the “B” terminal being constantly energized from R. A
Thermostat demand for heat completes R-Y circuit, pulling
in compressor contactor starting compressor and outdoor
motor. R-G also make starting indoor blower motor.
PRESSURE SERVICE PORTS
High and low pressure service ports are installed on all units
so that the system operating pressures can be observed.
Pressure tables can be found later in the manual covering all
models. It is imperative to match the correct pressure table to
the unit by model number. See Tables 5A & 5B.
If some abnormal or temporary condition such as a high
wind causes the heat pump to have a prolonged defrost
cycle, the heat pump control will restore the system to
heating operation automatically after 8 minutes.
The heat pump defrost control board has an option of 30, 60
or 90-minute setting. By default, this unit is shipped from
the factory with the defrost time on the 60 minute pin. If
circumstances require a change to another time, remove
the wire from the 60-minute terminal and reconnect to the
desired terminal. Refer to Figure 12.
There is a cycle speed up jumper on the control. This can be
used for testing purposes to reduce the time between defrost
cycle operation without waiting for time to elapse.
Use a small screwdriver or other metallic object, or another
¼ inch QC, to short between the SPEEDUP terminals to
accelerate the HPC timer and initiate defrost.
Be careful not to touch any other terminals with the instrument
used to short the SPEEDUP terminals. It may take up to
10 seconds with the SPEEDUP terminals shorted for the
speedup to be completed and the defrost cycle to start.
As soon as the defrost cycle kicks in remove the shorting
instrument from the SPEEDUP terminals. Otherwise the
timing will remain accelerated and run through the 1-minute
minimum defrost length sequence in a matter of seconds and
will automatically terminate the defrost sequence.
There is an initiate defrost jumper (sen jump) on the control
that can be used at any outdoor ambient during the heating
cycle to simulate a 0° coil temperature.
This can be used to check defrost operation of the unit
without waiting for the outdoor ambient to fall into the
defrost region.
DEFROST CYCLE
The defrost cycle is controlled by temperature and time on
the solid state heat pump control.
When the outdoor temperature is in the lower 40°F
temperature range or colder, the outdoor coil temperature is
32°F or below. This coil temperature is sensed by the coil
temperature sensor mounted near the bottom of the outdoor
coil. Once coil temperature reaches 30°F or below, the
coil temperature sensor sends a signal to the control logic
of the heat pump control and the defrost timer will start
accumulating run time.
After 30, 60 or 90 minutes of heat pump operation at 30°F
or below, the heat pump control will place the system in the
defrost mode.
During the defrost mode, the refrigerant cycle switches back
to the cooling cycle, the outdoor motor stops, electric heaters
are energized, and hot gas passing through the outdoor coil
melts any accumulated frost. When the temperature rises to
approximately 57°F, the coil temperature sensor will send a
signal to the heat pump control which will return the system
to heating operations automatically.
Manual 2100-527H
Page 18 of 29
By placing a jumper across the SEN JMP terminals (a
¼ inch QC terminal works best) the defrost sensor mounted
on the outdoor coil is shunted out & will activate the timing
circuit. This permits the defrost cycle to be checked out in
warmer weather conditions without the outdoor temperature
having to fall into the defrost region.
In order to terminate the defrost test the SEN JMP jumper
must be removed. If left in place too long, the compressor
could stop due to the high pressure control opening because
of high pressure condition created by operating in the
cooling mode with outdoor fan off. Pressure will rise fairly
fast as there is likely no actual frost on the outdoor coil in
this articial test condition.
There is also a 5-minute compressor time delay function built
into the HPC. This is to protect the compressor from short
cycling conditions. The board’s LED will have a fast blink
rate when in the compressor time delay. In some instances,
it is helpful to the service technician to override or speed up
this timing period, and shorting out the SPEEDUP terminals
for a few seconds can do this.
ACCUMULATED DEFROST TIME TIMER
(FACTORY SETTING 60 MIN.)
ON
Low Pressure Switch Bypass Operation - The control has a
selectable (SW1) low pressure switch bypass set up to ignore
the low pressure switch input during the rst (30, 60, 120 or
180 seconds) of “Y” operation.
After this period expires, the control will then monitor the low
pressure switch input normally to make sure that the switch is
closed during “Y” operation.
High Pressure Switch Operation - The control has a built-in
lockout system that allows the unit to have the high pressure
FIGURE 12
DEFROST CONTROL BOARD
switch trip up to two times in one hour and only encounter
a “soft” lockout. A “soft” lockout shuts the compressor off
and waits for the pressure switch to reset, which at that point
then allows the compressor to be restarted as long as the
5-minute short cycle timer has run out. If the high pressure
switch trips a third time within one hour, the unit is in “hard”
lockout indicating something is certainly wrong and it will
not restart itself.
Manual 2100-527H
Page 19 of 29
Page 20
TROUBLESHOOTING
SOLID STATE HEAT PUMP CONTROL
TROUBLESHOOTING PROCEDURE
1. NOTE: A thorough understanding of the defrost
cycle sequence is essential. Review that section
NOTE: If there was no power to 24 volt transformer,
the compressor and outdoor fan motor will not start for 5 minutes. This is because of the compressor short cycle protection.
earlier in this manual prior to troubleshooting the
control. Turn on AC power supply to unit.
2. Turn thermostat blower switch to “fan on” – the
indoor blower should start. (If it doesn’t,
troubleshoot indoor unit and correct problem.)
3. Turn thermostat blower to “auto” position. Indoor
blower should stop. NOTE:Many models have a
1-minute blower time delay on “off” command;
wait for this to time-out.
4. Set system switch to “heat” or “cool”. Adjust
thermostat to call for heat or cool. The indoor
blower, compressor and outdoor fan should start.
BLINK FUNCTION
Slow Normal function (1.0 sec on/1.0 sec off)
Fast ASCD (Compressor Delay) timer active
(0.1 sec on/0.1 sec off)
1 Low pressure switch failure
2 High pressure switch failure/“Soft” Lockout
3 Defrost mode active
4 High pressure switch failure/“Hard” Lockout
TABLE 3
TROUBLESHOOTING
SymptonDescription, Check & Possible CauseWhat & How to Check/Repair
Compressor will
not start (heating or
cooling)
Fan outdoor
motor does not run
(cooling or heating
except during
defrost)
Reversing valve
does not energize
(heating only)
Unit will not go into
defrost (heating
only)
Unit will not come
out of defrost
(heating only)
1. Check for LED illumination.
Is there an LED illuminated on the board
(ashing)?
2. Check for error codes.
Is the LED ashing a code?
3. Check for power at board.
Is there 24 volts AC between R and C?
4. Check codes.
What code is blinking?
5. Compressor delay active.
Wait for 5 minute delay or jump board's
"speed up pins".
6. Low pressure fault.Check wiring circuit and unit pressures.
7. High pressure fault.Check wiring circuit and unit pressures.
8. Check for Compressor input signal.
Is there 24 volts AC between Y and C?
9. No power to board.
10. Check for Compressor output signal.
Is there 24 volts AC between CC and C?
11. No "Y" compressor input signal.
12. No "CC" compressor output signal.Check compressor contactor for proper operation and nally check compressor.
13. Faulty board.Replace defrost board.
Heat pump control defective
Motor defectiveCheck for open or shorted motor winding. Replace motor.
Motor capacitor defectiveCheck capacitor rating. Check for open or shorted capacitor. Replace capacitor.
Heat pump control defective
Reversing valve solenoid coil defective
Temperature sensor or heat pump control
defective
Temperature sensor or heat pump control
defective
Yes = go to Step #2; No = go to Step #3
Yes = go to Step #4; No = go to Step #8
Yes = go to Step #13; No = go to Step #9
Code "1", got to Step #6; Code "2", go to Step #7; Fast Blink, go to Step #5
Check for proper operation; if still needed, go back to Step #1
Yes = go to Step #10; No = go to Step #11
The unit either does not have unit voltage, the transformer is bad or the unit wiring
is incorrect.
Yes = go to Step #12; No = go to Step #13
Check thermostat wiring, incorrect phase of unit (see section on Phase Monitor)
and nally unit wiring.
Check across fan relay on heat pump control. (Com-NC)
Replace heat pump control.
Check for 24 V between RV-C and B-C.
1. Check circuit control wiring.
2. Replace heat pump control.
Check for open or shorted coil.
Replace solenoid coil.
Disconnect temperature sensor from board and jumper across "SPEEDUP"
terminals and "SEN JMP" terminals. This should cause the unit to go through a
defrost cycle within one minute.
1. If unit goes through defrost cycle, replace temperature sensor.
2. If unit does not go through defrost cycle, replace heat pump control.
Jumper across "SPEEDUP" terminal. This should cause the unit to come out of
defrost within one minute.
1. If unit goes through defrost cycle, replace temperature sensor.
2. If unit does not go through defrost cycle, replace heat pump control.
LED BLINK CODES
Manual 2100-527H
Page 20 of 29
Page 21
CHECKING TEMPERATURE SENSOR
OUTSIDE UNIT CIRCUIT
1. Disconnect temperature sensor from board and
from outdoor coil.
2. Use an ohmmeter and measure the resistance of the
sensor. Also use ohmmeter to check for short or
open.
TEMPERATURE F VS. RESISTANCE R OF TEMPERATURE SENSOR
FRFRFRFR
-25.019687113.05698553.01937489.07507
-24.019009914.05528452.01886790.07334
-23.018358515.05364053.01837591.07165
-22.017731816.05205154.01798992.07000
-21.017128917.05051455.01743493.06840
-20.016548718.04902856.01698494.06683
-19.015990419.04759057.01654795.06531
-18.015452920.04620058.01612296.06383
-17.014935521.04485559.01571097.06239
-16.014437422.04355460.01531098.06098
-15.013957623.04229561.01492199.05961
-14.013495624.04107762.014544100.05827
-13.013050625.03989863.014177101.05697
-12.012621926.03875764.013820102.05570
-11.012208927.03765265.013474103.05446
-10.011810828.03658366.013137104.05326
-9.011427229.03554867.012810105.05208
-8.011057530.03454568.012492106.05094
-7.010701031.03357469.012183107.04982
-6.010357432.03263470.011883108.04873
-5.010026033.03172371.011591109.04767
-4.09706434.03084072.011307110.04663
-3.09398135.02998673.011031111 . 04562
-2.09100836.02915774.010762112.04464
-1.08813937.02835575.010501113.04367
0.08537138.02757776.010247114.04274
1.08269939.02682377.010000115.04182
2.08012140.02609278.09760116.04093
3.07763241.02538379.09526117.04006
4.07523042.02469680.09299118.03921
5.07291043.02403081.09077119.03838
6.07067044.02338482.08862120.03757
7.06850745.02275883.08653121.03678
8.06641846.02215084.08449122.03601
9.06439947.02156185.08250123.03526
10.06244948.02098986.08057124.03452
11.06056549.02043587.07869
12.05874550.01989688.07686
3. Check resistance reading to chart of resistance. Use
sensor ambient temperature. (Tolerance of part is
± 10%.)
4. If sensor resistance reads very low, then sensor is
shorted and will not allow proper operation of the
heat pump control.
5. If sensor is out of tolerance, shorted, open or reads
very low ohms then it should be replaced.
Manual 2100-527H
Page 21 of 29
Page 22
TROUBLESHOOTING
"A"
S**H AIRFLOW
W**H AIRFLOW
MIS-2725 A
FAN BLADE SETTING DIMENSIONS
Shown in Figure 13 is the correct fan blade setting for
proper air delivery across the outdoor coil. Refer to
Table 4 for unit specic dimension.
Any service work requiring removal or adjustment
in the fan and/or motor area will require that the
dimensions below be checked and blade adjusted in or
out on the motor shaft accordingly.
FIGURE 13
FAN BLADE SETTING
TABLE 4
FAN BLADE DIMENSION
ModelDimension A
W26H1
W31H1
W38H1
W43H1
W49H1
W61H1
S26H1
S31H1
S38H1
S43H1
S49H1
S61H1
1.00"
1.25"
1.75"
REMOVAL OF FAN SHROUD
1. Disconnect all power to the unit.
2. Remove the screws holding both grilles, one on
each side of unit, and remove grilles.
3. Remove screws holding fan shroud to condenser
and bottom. Nine (9) screws.
4. Unwire condenser fan motor.
5. Slide complete motor, fan blade, and shroud
assembly out the left side of the unit.
6. Service motor/fan as needed.
7. Reverse steps to reinstall.
R-410A
REFRIGERANT CHARGE
This unit was charged at the factory with the quantity of
refrigerant listed on the serial plate. AHRI capacity and
efciency ratings were determined by testing with this
refrigerant charge quantity.
The following pressure tables show nominal pressures
for the units. Since many installation specic situations
can affect the pressure readings, this information should
only be used by certied technicians as a guide for
evaluating proper system performance. They shall not
be used to adjust charge. If charge is in doubt, reclaim,
evacuate and recharge the unit to the serial plate charge.
Manual 2100-527H
Page 22 of 29
Page 23
Model
S26H1
S31H1
S38H1
S43H1
S49H1
S61H1
Return Air
Temperature
75 deg. DB
62 deg. WB
80 deg. DB
67 deg. WB
85 deg. DB
72 deg. WB
75 deg. DB
62 deg. WB
80 deg. DB
67 deg. WB
85 deg. DB
72 deg. WB
75 deg. DB
62 deg. WB
80 deg. DB
67 deg. WB
85 deg. DB
72 deg. WB
75 deg. DB
62 deg. WB
80 deg. DB
67 deg. WB
85 deg. DB
72 deg. WB
75 deg. DB
62 deg. WB
80 deg. DB
67 deg. WB
85 deg. DB
72 deg. WB
75 deg. DB
62 deg. WB
80 deg. DB
67 deg. WB
85 deg. DB
72 deg. WB
TABLE 5A
COOLING PRESSURE TABLE
Pressure7580859095100105110115120
Low SIde
High Side
Low SIde
High Side
Low SIde
High Side
Low SIde
High Side
Low SIde
High Side
Low SIde
High Side
Low SIde
High Side
Low SIde
High Side
Low SIde
High Side
Low SIde
High Side
Low SIde
High Side
Low SIde
High Side
Low SIde
High Side
Low SIde
High Side
Low SIde
High Side
Low SIde
High Side
Low SIde
High Side
Low SIde
High Side
129
298
133
306
143
317
122
312
130
320
135
331
125
314
134
322
139
333
128
329
137
337
142
349
131
338
140
347
145
359
122
336
131
345
136
357
130
320
134
328
144
339
124
329
133
337
138
349
127
332
136
340
141
352
130
343
139
352
144
364
131
355
140
364
145
377
123
353
132
362
137
375
131
342
135
351
145
363
126
347
135
356
140
368
129
351
138
360
143
373
132
361
141
370
146
383
132
372
141
382
146
395
125
371
134
381
139
394
132
366
136
375
145
388
129
368
136
377
143
390
131
371
140
381
145
394
134
381
143
391
148
405
133
392
142
402
147
416
126
392
135
402
140
416
133
390
137
397
147
414
131
390
137
405
145
414
133
394
141
400
147
418
137
404
144
413
151
428
134
413
142
421
148
439
128
416
137
427
142
442
Air Temperature Entering Outdoor Coil °F
134
414
143
425
148
440
133
413
142
424
147
439
135
417
144
428
149
443
138
429
148
440
153
455
136
437
145
448
150
464
130
442
139
453
144
469
135
440
144
451
149
467
135
439
144
450
149
466
137
442
146
453
151
469
140
457
150
469
155
485
137
461
147
473
152
490
132
470
141
482
146
499
137
466
146
478
151
495
137
466
146
478
151
495
138
468
148
480
153
497
143
488
153
501
158
519
139
488
149
501
154
519
133
500
142
513
147
531
138
493
148
506
153
524
138
494
147
507
152
525
140
496
150
509
155
527
145
522
155
535
160
554
142
517
152
530
157
549
136
532
145
546
150
565
140
522
150
535
155
554
139
525
149
538
154
557
141
526
151
539
156
558
148
558
158
572
164
592
145
547
155
561
160
581
137
567
147
582
152
602
Low side pressure ± 4 PSIG High side pressure ± 10 PSIG
Tables are based upon rated CFM (airow) across the evaporator coil. If there is any doubt as to correct operating charge being in the system, the charge
should be removed, system evacuated and recharged to serial plate charge weight.
NOTE: Pressure table based on high speed condenser fan operation. If condensing pressures appear elevated check condenser fan wiring. See
“Condenser Fan Operation”.
HEATING PRESSURES – (ALL TEMPERATURES °F)
Model
S26H170 Deg.
S31H170 Deg.
S38H170 Deg.
S43H170 Deg.
S49H170 Deg.
S61H170 Deg.
Return Air
Temperature
Pressure05101520253035404550556065
Low Side
High Side373044330550307573116331771325783358534693352
Low Side
High Side382814429150300573106432171332793438635494366
Low Side
High Side37270432764928255289622966930476313833229133399343
Low Side
High Side492735027553278572826228767294743038231291323
Low Side
High Side32310373114131553320643287333782348893619537799394
Low Side
High Side44283462924730249313523245733563347713608037391387
TABLE 5B
101
360
102
379
100
335
109
117
410
119
404
116
367
123
363
104
433
117
416
126
430
127
418
125
380
136
379
105
456
133
431
391
110
391
107
355
111
348
102
413
103
401
Manual 2100-527H
Page 23 of 29
134
452
136
432
134
393
150
396
104
481
149
447
Page 24
Model
W26H1
W31H1
W38H1
W43H1
W49H1
W61H1
Return Air
Temperature
75 deg. DB
62 deg. WB
80 deg. DB
67 deg. WB
85 deg. DB
72 deg. WB
75 deg. DB
62 deg. WB
80 deg. DB
67 deg. WB
85 deg. DB
72 deg. WB
75 deg. DB
62 deg. WB
80 deg. DB
67 deg. WB
85 deg. DB
72 deg. WB
75 deg. DB
62 deg. WB
80 deg. DB
67 deg. WB
85 deg. DB
72 deg. WB
75 deg. DB
62 deg. WB
80 deg. DB
67 deg. WB
85 deg. DB
72 deg. WB
75 deg. DB
62 deg. WB
80 deg. DB
67 deg. WB
85 deg. DB
72 deg. WB
TABLE 6A
COOLING PRESSURE TABLE
Pressure7580859095100105110115120
Low SIde
High Side
Low SIde
High Side
Low SIde
High Side
Low SIde
High Side
Low SIde
High Side
Low SIde
High Side
Low SIde
High Side
Low SIde
High Side
Low SIde
High Side
Low SIde
High Side
Low SIde
High Side
Low SIde
High Side
Low SIde
High Side
Low SIde
High Side
Low SIde
High Side
Low SIde
High Side
Low SIde
High Side
Low SIde
High Side
131
309
140
317
145
328
123
311
132
319
137
330
126
313
135
321
140
332
131
325
140
333
145
345
128
315
137
323
142
334
123
336
132
345
137
357
132
326
141
334
146
346
125
330
134
338
139
350
127
330
136
338
141
350
131
343
140
352
145
364
129
337
138
346
143
358
123
353
132
362
137
375
133
345
142
354
147
366
128
350
137
359
142
372
129
348
138
357
143
369
132
363
141
372
146
385
130
361
139
370
144
383
124
371
133
381
138
394
135
366
144
375
149
388
130
371
139
381
144
394
131
370
140
379
145
392
134
384
143
394
148
408
131
385
140
395
145
409
125
392
134
402
139
416
136
390
145
400
150
414
133
395
140
405
147
419
133
394
140
397
147
418
135
408
143
418
149
433
132
411
141
430
146
437
127
415
137
437
141
441
Air Temperature Entering Outdoor Coil °F
137
415
146
426
151
441
135
419
144
430
149
445
135
420
144
431
149
446
137
432
147
443
152
459
134
439
143
450
148
466
128
441
137
452
142
468
138
444
148
455
153
471
137
446
146
457
151
473
137
449
146
461
151
477
139
458
149
470
154
486
136
467
145
479
150
496
130
469
139
481
144
498
139
474
149
486
154
503
138
474
148
486
153
503
139
482
149
494
154
511
142
487
152
499
157
516
137
496
147
509
152
527
133
499
142
512
147
530
141
506
151
519
156
537
140
504
150
517
155
535
141
516
151
529
156
548
145
516
155
529
160
548
140
527
150
541
155
560
136
532
145
546
150
565
142
541
152
555
157
574
142
535
152
549
157
568
144
553
154
567
159
587
148
547
158
561
164
581
143
560
153
574
158
594
138
567
148
582
153
602
Low side pressure ± 4 PSIG High side pressure ± 10 PSIG
Tables are based upon rated CFM (airow) across the evaporator coil. If there is any doubt as to correct operating charge being in the system, the charge
should be removed, system evacuated and recharged to serial plate charge weight.
NOTE: Pressure table based on high speed condenser fan operation. If condensing pressures appear elevated check condenser fan wiring. See
“Condenser Fan Operation”.
HEATING PRESSURES – (ALL TEMPERATURES °F)
Model
W26H170 Deg.
W31H170 Deg.
W38H170 Deg.
W43H170 Deg.
W49H170 Deg.
W61H170 Deg.
Manual 2100-527H
Page 24 of 29
Return Air
Temperature
Pressure05101520253035404550556065
Low Side
High Side42279462855029256299623086831775327833389135099362
Low Side
High Side39274442834929355303613146832575336823489036198373
Low Side
High Side25251342604326952278602876829675306823159032596335
Low Side
High Side34265402704627553278602816728774294813048931797331
Low Side
High Side48283492935130354313583236333469345773568636896380
Low Side
High Side34270362783928643296493065531762328703418035490369
These “Minimum Circuit Ampacity” values are to be used for sizing the eld power conductors. Refer to the National Electrical Code (latest version),
Article 310 for power conductor sizing.
Caution: When more than one eld power circuit is run through one conduit, the conductors must be derated. Pay special attention to note 8 of Table 310
regarding Ampacity Adjustment Factors when more than three (3) conductors are in a raceway.
Maximum size of the time delay fuse or HACR type circuit breaker for protection of eld wiring conductors.
Based on 75°C copper wire. All wiring must conform to the National Electrical Code and all local codes.
Maximum KW that can operate with the heat pump on is 10KW.
Maximum KW that can operate with the heat pump on is 5KW.
Maximum KW that can operate with the heat pump on is 4KW.
IMPORTANT: While this electrical data is presented as a guide, it is important to electrically connect properly sized fuses & conductor wires in accordance with the
National Electrical Code & all local codes.
These “Minimum Circuit Ampacity” values are to be used for sizing the eld power conductors. Refer to the National Electrical Code (latest version), Article
310 for power conductor sizing.
Caution: When more than one eld power circuit is run through one conduit, the conductors must be derated. Pay special attention to note 8 of Table 310
regarding Ampacity Adjustment Factors when more than three (3) conductors are in a raceway.
Maximum size of the time delay fuse or HACR type circuit breaker for protection of eld wiring conductors.
Based on 75°C copper wire. All wiring must conform to the National Electrical Code and all local codes.
Maximum KW that can operate with the heat pump on is 10KW.
Maximum KW that can operate with the heat pump on is 5KW.
Maximum KW that can operate with the heat pump on is 4KW.
IMPORTANT: While this electrical data is presented as a guide, it is important to electrically connect properly sized fuses & conductor wires in accordance with the
National Electrical Code & all local codes.
Rated Volts, HZ
and Phase
230/208-60-1
230/208-60-3
460-60-3
230/208-60-1
230/208-60-3
460-60-3
230/208-60-1
230/208-60-3
460-60-3
230/208-60-1
230/208-60-3
460-60-3
230/208-60-1
230/208-60-3
460-60-3
230/208-60-1
230/208-60-3
460-60-3
Field
Power
Circuits
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1 or 2
1 or 2
1 or 2
1
1
1
1
1
1
1
1
1
1
1 or 2
1 or 2
1 or 2
1 or 2
1
1
1
1
1
1
1
1
1
1
1 or 2
1 or 2
1 or 2
1 or 2
1
1
1
1
1
1
1
1
1
1 or 2
1 or 2
1 or 2
1 or 3
1
1
1
1
1
1
Minimum
Ampacity
Manual 2100-527H
Page 26 of 29
Maximum Circuit
Exterior Fuse or
Circuit Breaker
45
45
45
60
45
60
50
30
50
45
50
60
50
60
50
30
50
45
50
60
50
60
60
30
60
60
60
60
60
6030
Field Power Wire
Size
8
8
8
6
8
6
8
10
8
8
8
6
8
6
8
10
8
8
8
6
8
6
8
10
8
6
8
6
6
610
Ground WIre Size
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
1010
C
Page 27
TABLES 8
INDOOR BLOWER PERFORMANCE CFM
AT 230 OR 460 VOLTS
S26H1, S31H1
ESP in Inches
Water Column
High Speed
Dry/Wet Coil
W26H1, W31H1
Low Speed
Dry/Wet Coil
.01050/1000950/900
.1900/850540/800
.2750/700700/650
Above data is with 1" standard disposable or 1" washable lter
For optional 2" pleated lter - reduce ESP by 0.08 in.
Reconnect to next lower speed for free blow (non-ducted) installation.
NOTE: These units are equipped with a variable speed (ECM) indoor motor that automatically adjusts itself to maintain approximately
the same rate of indoor airow in both heating & cooling, dry & wet coil conditions and at both 230/208 or 460 volts.
Maximum ESP (inches WC) shown is with 2" thick disposable lter.
Blower only CFM is the total air being circulated during continuous fan mode.
NOTE: These units are equipped with a variable speed (ECM) indoor motor that automatically adjusts itself to maintain approximately
the same rate of indoor airow in both heating & cooling, dry & wet coil conditions and at both 230/208 or 460 volts.
Maximum ESP (inches WC) shown is with 2" thick disposable lter.
Blower only CFM is the total air being circulated during continuous fan mode.
CFM output on Cooling or Electric Heat.
Manual 2100-527H
Page 27 of 29
Page 28
TROUBLESHOOTING GE ECM
™
MOTORS
CAUTION:
Disconnect power from unit before removing or replacing
connectors, or servicing motor. To avoid electric shock from
the motor’s capacitors, disconnect power and wait at least 5
minutes before opening motor.
Symptom Cause/Procedure
Motor rocks slightly • This is normal start-up for ECM
when starting
Motor won’t start • Check blower turns by hand
• No movement
• Check low voltage (24 Vac R to C) at motor
• Check low voltage connections
(G, Y, W, R, C) at motor
• Check for unseated pins in connectors on
motor harness
• Test with a temporary jumper between R - G
• Check motor for tight shaft
• Perform motor/control replacement check
• Perform Moisture Check
• Motor rocks, • Check for loose or compliant motor mount
but won’t start
• Perform motor/control replacement check
Motor oscillates up • It is normal for motor to oscillate with no
load & down while being on shaft
tested off of blower
Motor starts, but
runs erratically
• Varies up and down • Check line voltage for variation or “sag”
or intermittent • Check low voltage connections
(G, Y, W, R, C) at motor, unseated pins in
motor harness connectors
• Check “Bk” for erratic CFM command (in
variable-speed applications)
• Check out system controls, Thermostat
• Perform Moisture Check
• “Hunts” or “puffs” at • Does removing panel or lter reduce
high CFM (speed) “pufng”?
- Reduce restriction
- Reduce max airow
• Stays at low CFM • Check low voltage (Thermostat) wires and
despite system call connections
for cool or heat CFM • Verify fan is not in delay mode; wait until
delay complete
• “R” missing/not connected at motor
• Perform motor/control replacement check
• Stays at high CFM • “R” missing/not connected at motor
• Is fan in delay mode? - wait until delay time
complete
• Perform motor/control replacement check
• Blower won’t shut off •
Check for Triac switched thermostat or solid state relay
Excessive noise• Determine if it’s air noise, cabinet, duct or motor noise; interview customer, if necessary
• Air noise • High static creating high blower speed?
- Is airow set properly?
- Does removing lter cause blower to slow
down? Check lter
- Use low-pressure drop lter
- Check/correct duct restrictions
• Check power at motor
• Make sure blower wheel is tight on shaft
Current leakage from controls into G, Y or W?
SymptomCause/Procedure
• Noisy blower or cabinet • Check for loose blower housing, panels, etc.
• High static creating high blower speed?
- Check for air whistling through seams in
ducts, cabinets or panels
- Check for cabinet/duct deformation
• “Hunts” or “puffs” at • Does removing panel or lter reduce
high CFM (speed)
- Reduce restriction
- Reduce max. airow
Evidence of Moisture
• Motor failure or • Replace motor and
malfunction has occurred
and moisture is present
• Evidence of moisture
present inside air mover
“pufng”?
• Perform Moisture Check
Perform Moisture Check
Do Don’t
• Check out motor, controls, • Automatically assume the motor is bad.
wiring and connections
thoroughly before replacing
motor
• Orient connectors down so • Locate connectors above 7 and 4 o’clock
water can’t get in positions
- Install “drip loops”
• Use authorized motor and • Replace one motor or control model # with
model #’s for replacement another (unless an authorized replacement)
• Keep static pressure to a • Use high pressure drop lters some have
minimum: H20 drop!
- Recommend high • Use restricted returns
efciency, low static lters
- Recommend keeping lters
clean.
- Design ductwork for min.
static, max. comfort
- Look for and recommend
ductwork improvement,
where necessary
• Size the equipment wisely • Oversize system, then compensate with low
airow
• Check orientation before • Plug in power connector backwards
inserting motor connectors • Force plugs
½"
Moisture Check
• Connectors are oriented “down” (or as recommended by equipment
manufacturer)
• Arrange harness with “drip loop” under motor
• Is condensate drain plugged?
• Check for low airow (too much latent capacity)
• Check for undercharged condition
• Check and plug leaks in return ducts, cabinet
Comfort Check
• Check proper airow settings
• Low static pressure for lowest noise
• Set low continuous-fan CFM
• Use humidistat and 2-speed cooling units
• Use zoning controls designed for ECM that regulate CFM
• Thermostat in bad location?
Manual 2100-527H
Page 28 of 29
Page 29
TROUBLESHOOTING GE ECM
™
MOTORS CONT’D.
Replacing ECM Control Module
To replace the control module for the GE variable-speed indoor blower motor
you need to take the following steps:
1. You MUST have the correct replacement module. The controls are
factory programmed for specic operating modes. Even though they look
alike, different modules may have completely different functionality.
USING THE WRONG CONTROL MODULE VOIDS ALL PRODUCT
WARRANTIES AND MAY PRODUCE UNEXPECTED RESULTS.
2. Begin by removing AC power from the furnace or air handler being serviced. DO NOT WORK ON THE MOTOR WITH AC POWER
APPLIED. To avoid electric shock from the motor’s capacitors, disconnect
power and wait at least 5 minutes before opening motor.
3. It is usually not necessary to remove the motor from the blower
assembly. However, it is recommended that the whole blower assembly,
with the motor, be removed from the furnace/air handler. (Follow the
manufacturer’s procedures). Unplug the two cable connectors to the motor.
There are latches on each connector. DO NOT PULL ON THE WIRES.
The plugs remove easily when properly released.
4. Locate the two standard
housing (at the back end of the control opposite the shaft end). Refer to Figure 14. Remove these two bolts from the motor and control assembly
while holding the motor in a way that will prevent the motor or control
from falling when the bolts are removed. If an ECM2.0 control is being
replaced (recognized by an aluminum casting rather that a deep-drawn
black steel can housing the electronics), remove only the hex-head bolts.
DO NOT REMOVE THE TORX-HEAD SCREWS.
5. The control module is now free of mechanical attachment to the
motor endshield but is still connected by a plug and three wires inside
the control. Carefully rotate the control to gain access to the plug at
the control end of the wires. With thumb and forenger, reach the latch
holding the plug to the control and release it by squeezing the latch tab
and the opposite side of the connector plug and gently pulling the plug
out of the connector socket in the control. DO NOT PULL ON THE
WIRES. GRIP THE PLUG ONLY.
6. The control module is now completely detached from the motor.
Verify with a standard ohmmeter that the resistance from each motor
lead (in the motor plug just removed) to the motor shell is >100K ohms.
Refer to Figure 15. (Measure to unpainted motor end plate.) If any motor
lead fails this test, do not proceed to install the control module. THE MOTOR IS DEFECTIVE AND MUST BE REPLACED. Installing
the new control module will cause it to fail also.
7. Verify that the replacement control is correct for your application.
Refer to the manufacturer's authorized replacement list. USING THE
WRONG CONTROL WILL RESULT IN IMPROPER OR NO
BLOWER OPERATION. Orient the control module so that the 3-wire
motor plug can be inserted into the socket in the control. Carefully insert
the plug and press it into the socket until it latches. A SLIGHT CLICK WILL BE HEARD WHEN PROPERLY INSERTED.
the replacement control per one of the three following paragraphs, 8a, 8b or 8c.
8a. IF REPLACING AN ECM 2.0 CONTROL (control in cast
aluminum can with air vents on the back of the can) WITH AN ECM
2.3 CONTROL (control containing black potting for water protection in
black deep-drawn steel case with no vents in the bottom of the can), locate
the two through-bolts and plastic tab that are packed with the replacement
control. Insert the plastic tab into the slot at the perimeter of the open end
of the can so that the pin is located on the inside of the perimeter of the
can. Rotate the can so that the tab inserts into the tab locater hole in the
endshield of the motor. Using the two through-bolts provided with the
replacement control, reattach the can to the motor.
THE TWO THROUGH-BOLTS PROVIDED WITH THE
REPLACEMENT ECM 2.3 CONTROL ARE SHORTER THAN
THE BOLTS ORIGINALLY REMOVED FROM THE ECM 2.0
CONTROL AND MUST BE USED IF SECURE ATTACHMENT OF
THE CONTROL TO THE MOTOR IS TO BE ACHIEVED.
DO NOT OVERTIGHTEN THE BOLTS.
¼" hex head bolts at the rear of the control
Finish installing
8b. IF REPLACING AN ECM 2.3 CONTROL WITH AN ECM 2.3 CONTROL, the plastic tab and shorter through-bolts are not needed. The
control can be oriented in two positions 180° apart. MAKE SURE THE
ORIENTATION YOU SELECT FOR REPLACING THE CONTROL
ASSURES THE CONTROL'S CABLE CONNECTORS WILL
BE LOCATED DOWNWARD IN THE APPLICATION SO THAT
WATER CANNOT RUN DOWN THE CABLES AND INTO THE
CONTROL. Simply orient the new control to the motor's endshield, insert
bolts, and tighten. DO NOT OVERTIGHTEN THE BOLTS.
8c. IF REPLACING AN ECM 2.0 CONTROL WITH AN ECM 2.0
CONTROL (It is recommended that ECM 2.3 controls be used for all
replacements), the new control must be attached to the motor using through
bolts identical to those removed with the original control. DO NOT
OVERTIGHTEN THE BOLTS.
9. Reinstall the blower/motor assembly into the HVAC equipment.
Follow the manufacturer's suggested procedures.
10. Plug the 16-pin control plug into the motor. The plug is keyed.
Make sure the connector is properly seated and latched.
11. Plug the 5-pin power connector into the motor. Even though the
plug is keyed, OBSERVE THE PROPER ORIENTATION. DO NOT FORCE THE CONNECTOR. It plugs in very easily when properly
oriented. REVERSING THIS PLUG WILL CAUSE IMMEDIATE
FAILURE OF THE CONTROL MODULE.
Final installation check. Make sure the motor is installed as follows:
12.
a. Unit is as far INTO the blower housing as possible.
b. Belly bands are not on the control module or covering vent holes.
c. Motor connectors should be oriented between the 4 o’clock and 8
o’clock positions when the blower is positioned in its nal
location and orientation.
d. Add a drip loop to the cables so that water cannot enter the motor
by draining down the cables. Refer to Figure 16.
The installation is now complete. Reapply the AC power to the HVAC
equipment and verify that the new motor control module is working
properly. Follow the manufacturer's procedures for disposition of the old
control module.
Figure 14
Figure 15
Figure 16
Manual 2100-527H
Page 29 of 29
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.