Bard S26H1-B, S31H1-B, S26H1-C, S31H1-A, S31H1-C Installation Instructions Manual

...
Page 1
INSTALLATION INSTRUCTIONS
WALL MOUNTED
PACKAGED HEAT PUMP
Models:
S26H1DA S26H1DB S26H1DC S31H1DA S31H1DB S31H1DC S38H1DA S38H1DB S38H1DC
S43H1DA S43H1DB S43H1DC S49H1DA S49H1DB S49H1DC S61H1DA S61H1DB S61H1DC
W26H1-A W26H1-B W26H1-C W31H1-A W31H1-B W31H1-A W38H1-A W38H1-B W38H1-C
W43H1-A W43H1-B W43H1-C W49H1-A W49H1-B W49H1-C W61H1-A W61H1-B W61H1-C
Refer to Supplemental Instruction 7960-593 (latest revision)
for dedicated dehumidification information.
Bard Manufacturing Company, Inc. Bryan, Ohio 43506
www.bardhvac.com
Manual: 2100-527H Supersedes: 2100-527G Date: 7-28-15
Page 1 of 29
Page 2
Contents
Getting Other Information and Publications 3
Wall Mount General Information
Wall Mount Model Nomenclature .............................. 4
Shipping Damage ..................................................... 4
General ................................................................. 4
Duct Work .................................................................5
Filters ................................................................. 5
Fresh Air Intake ......................................................... 5
Condensate Drain .................................................... 5
Installation Instructions
Wall Mounting Information ........................................6
Mounting the Unit ...................................................... 6
Placement ................................................................. 6
Clearances Required ................................................ 6
Minimum Clearances ................................................ 6
Wiring – Main Power ............................................... 13
Wiring – Low Voltage Wiring ................................... 13
Optional Outdoor T-Stat Applications ...................... 14
Figures
Figure 1 Fresh Air Damper Assembly ..................... 5
Figure 2 Unit Dimensions ....................................... 7
Figure 3A Mounting Instructions S/W26 & 31 ........... 8
Figure 3B Mounting Instructions S/W38, 43, 49 ....... 9
Figure 4 Electric Heat Clearance ......................... 10
Figure 5 Wall Mounting Instructions ..................... 11
Figure 6 Wall Mounting Instructions ..................... 11
Figure 7 Common Wall Mounting Installations ..... 12
Figure 8 Compressor Cutoff ................................. 14
Figure 9 Compressor Cutoff ................................. 14
Figure 10 Electric Heat Hold-Off Wiring .................15
Figure 11 Electric Heat Hold-Off Wiring .................15
Figure 12 Defrost Control Board ............................19
Figure 13 Fan Blade Setting ...................................22
Figure 14 Control Disassembly ..............................29
Figure 15 Winding Test ........................................... 29
Figure 16 Drip Loop ................................................29
Start Up
General ............................................................... 16
Topping Off System Charge .................................... 16
Safety Practices ...................................................... 16
Important Installer Note ........................................... 17
High & Low Pressure Switch ................................... 17
Three Phase Scroll Compressor ............................. 17
Phase Monitor ......................................................... 17
Condenser Fan Operation ...................................... 17
Service Hints ........................................................... 17
Sequence of Operation ........................................... 18
Pressure Service Ports ........................................... 18
Defrost Cycle .......................................................... 18
Troubleshooting
Solid State Heat Pump Control ............................... 20
Checking Temperature Sensor ............................... 21
Fan Blade Setting Dimensions ................................ 22
Removal of Fan Shroud .......................................... 22
R-410A Refrigerant Charge ....................................22
Troubleshooting GE ECM Motors ........................... 28
Troubleshooting GE ECM Motors ........................... 29
Tables
Table 1 Clearances Required ............................... 6
Table 2 Min. Clearances Required ........................ 6
Table 3 Troubleshooting......................................20
Table 4 Fan Blade Dimension ............................. 22
Table 5A Cooling Pressure .................................... 23
Table 5B Heating Pressure ................................... 23
Table 6A Cooling Pressure .................................... 24
Table 6B Heating Pressure ................................... 24
Table 7A Electrical Specications S**H ................. 25
Table 7B Electrical Specications W**H ................ 26
Table 8 Indoor Blower Performance ................... 27
Tables 9A Indoor Blower Performance S**H ........... 27
Tables 9B Indoor Blower Performance W**H .......... 27
Manual 2100-527H Page 2 of 29
Page 3
GETTING OTHER INFORMATION AND PUBLICATIONS
These publications can help you install the air
conditioner or heat pump. You can usually nd these
at your local library or purchase them directly from the publisher. Be sure to consult current edition of each standard.
National Electrical Code ....................... ANSI/NFPA 70
Standard for the Installation ............... ANSI/NFPA 90A
of Air Conditioning and Ventilating Systems
Standard for Warm Air ....................... ANSI/NFPA 90B
Heating and Air Conditioning Systems
Load Calculation for ......................... ACCA Manual J
Residential Winter and Summer Air Conditioning
Duct Design for Residential ............... ACCA Manual D
Winter and Summer Air Conditioning and Equipment Selection
FOR MORE INFORMATION, CONTACT THESE PUBLISHERS:
ACCA Air Conditioning Contractors of America 1712 New Hampshire Ave. N.W. Washington, DC 20009 Telephone: (202) 483-9370 Fax: (202) 234-4721
ANSI American National Standards Institute 11 West Street, 13th Floor New York, NY 10036 Telephone: (212) 642-4900 Fax: (212) 302-1286
ASHRAE American Society of Heating, Refrigeration and Air Conditioning Engineers, Inc. 1791 Tullie Circle, N.E.
Atlanta, GA 30329-2305 Telephone: (404) 636-8400 Fax: (404) 321-5478
NFPA National Fire Protection Association Batterymarch Park P.O. Box 9101 Quincy, MA 02269-9901 Telephone: (800) 344-3555 Fax: (617) 984-7057
Manual 2100-527H Page 3 of 29
Page 4
WALL MOUNT GENERAL INFORMATION
HEAT PUMP WALL MOUNT MODEL NOMENCLATURE
S 38 H 1 – A 10 X X X X X A
MODEL NUMBER
S - Blow Through
W - Draw Through
CAPACITY |
26 - 2 Ton 31 - 2½ Ton 38 - 3 Ton 43 - 3½ Ton 49 - 4 Ton 61 - 5 Ton
NOTE: Vent options X, B and M are without exhaust capability. May require separate eld supplied barometric relief in building.
S**H Ventilation Option only. W**H Ventilation Option only.
H - Heat Pump
VENTILATION OPTIONS
X - Barometric Fresh Air Damper (Standard) B - Blank-off Plate M - Motorized Fresh Air Damper V - Commercial Ventilator - Motorized with Exhaust E - Economizer (Internal) - Fully Modulating with Exhaust R - Energy Recovery Ventilator - Motorized with Exhaust (See Spec. Sheet S3398) A - Manual Fresh Air Damper H - Commercial Ventilator - Motorized with Exhaust
SHIPPING DAMAGE
Upon receipt of equipment, the carton should be checked for external signs of shipping damage. If damage is found, the receiving party must contact the last carrier immediately, preferably in writing, requesting inspection by the carrier’s agent.
REVISIONS
VOLTS & PHASE
A - 230/208/60/1 B - 230/208/60/3 C - 460/60/3
KW 0Z - 0KW 04 - 4KW 05 - 5KW 06 - 6KW 08 - 8KW 09 - 9KW 10 -10KW 15 -15KW 20 -20KW
COLOR OPTIONS
X - Beige (Standard) 1 - White 4 - Buckeye Gray 5 - Desert Brown 8 - Dark Bronze
FILTER OPTIONS
X - One Inch Throwaway (Standard) W - One Inch Washable P - Two Inch Pleated
OUTLET OPTIONS
X - Front (Standard)
These instructions and any instructions packaged with any separate equipment required to make up the entire air conditioning system should be carefully read before beginning the installation. Note particularly “Starting Procedure” and any tags and/or labels attached to the equipment.
CONTROL MODULES
(See Spec. Sheets S3416 & S3417)
COIL OPTIONS
X - Standard 1 - Phenolic Coated Evaporator 2 - Phenolic Coated Condenser 3 - Phenolic Coated Evaporator and Condenser
While these instructions are intended as a general
GENERAL
The equipment covered in this manual is to be installed by trained, experienced service and installation technicians.
The refrigerant system is completely assembled and charged. All internal wiring is complete.
The unit is designed for use with or without duct work. Flanges are provided for attaching the supply and return ducts.
These instructions explain the recommended method to install the air cooled self-contained unit and the electrical wiring connections to the unit.
recommended guide, they do not supersede any national and/or local codes in any way. Authorities having jurisdiction should be consulted before the installation is made. See Page 3 for information on codes and standards.
Size of unit for a proposed installation should be based on heat loss/gain calculation made according to methods of Air Conditioning Contractors of America (ACCA). The air duct should be installed in accordance with the Standards of the National Fire Protection Association for the Installation of Air Conditioning and Ventilating Systems of Other Than Residence Type, NFPA No. 90A, and Residence Type Warm Air Heating and Air Conditioning Systems, NFPA No. 90B. Where local regulations are at a variance with instructions, installer should adhere to local codes.
Manual 2100-527H Page 4 of 29
Page 5
DUCT WORK
All duct work, supply and return, must be properly
sized for the design airow requirement of the
equipment. Air Conditioning Contractors of America (ACCA) is an excellent guide to proper sizing. All duct work or portions thereof not in the conditioned space should be properly insulated in order to both conserve energy and prevent condensation or moisture damage.
Design the duct work according to methods given by the Air Conditioning Contractors of America (ACCA). When duct runs through unheated spaces, it should be insulated with a minimum of one inch of insulation. Use insulation with a vapor barrier on the outside of the insulation. Flexible joints should be used to connect the duct work to the equipment in order to keep the noise transmission to a minimum.
A 1/4 inch clearance to combustible material for the
rst three feet of duct attached to the outlet air frame is
required. See Wall Mounting Instructions and Figures 3A, 3B and 4 for further details.
Ducts through the walls must be insulated and all joints taped or sealed to prevent air or moisture entering the wall cavity.
Some installations may not require any return air duct. A metallic return air grille is required with installations not requiring a return air duct. The spacing between louvers on the grille shall not be larger than 5/8 inch.
FILTERS
A 1-inch throwaway lter is standard with each unit. The lter slides into position making it easy to service. This lter can be serviced from the outside by removing the lter access panel. A 1-inch washable lter and 2-inch pleated lter are also available as optional accessories. The internal lter brackets are adjustable to accommodate the 2-inch lter by bending two (2) tabs down on each side of the lter support bracket.
FRESH AIR INTAKE
All units are built with fresh air inlet slots punched in the service door.
If the unit is equipped with a fresh air damper assembly, the assembly is shipped already attached to the unit. The damper blade is locked in the closed position. To allow the damper to operate, the maximum and minimum blade position stops must be installed. See Figure 1.
All capacity, efciency and cost of operation
information is based upon the fresh air blank-off plate in place and is recommended for maximum energy
efciency.
The blank-off plate is available upon request from the factory and is installed in place of the fresh air damper shipped with each unit.
Any grille that meets with 5/8 inch louver criteria may be used. It is recommended that Bard Return Air Grille Kit RG2 through RG5 or RFG2 through RFG5 be installed when no return duct is used. Contact distributor or factory for ordering information. If using a return air
lter grille, lters must be of sufcient size to allow a
maximum velocity of 400 fpm.
NOTE: If no return air duct is used, applicable
installation codes may limit this cabinet to installation only in a single story structure.
FIGURE 1
FRESH AIR DAMPER
CONDENSATE DRAIN
A plastic drain hose extends from the drain pan at the top of the unit down to the unit base. There are openings in the unit base for the drain hose to pass through. In the event the drain hose is connected to a drain system of some type, it must be an open or vented type system to assure proper drainage.
Manual 2100-527H Page 5 of 29
Page 6
INSTALLATION INSTRUCTIONS
WALL MOUNTING INFORMATION
1. Two holes for the supply and return air openings must be cut through the wall as shown in Figure 3.
2. On wood frame walls, the wall construction must be strong and rigid enough to carry the weight of the unit without transmitting any unit vibration.
3. Concrete block walls must be thoroughly inspected to insure that they are capable of carrying the weight of the installed unit.
MOUNTING THE UNIT
1. These units are secured by wall mounting brackets which secure the unit to the outside wall surface at both sides. A bottom mounting bracket, attached to skid for shipping, is provided for ease of installation, but is not required.
2. The unit itself is suitable for 0 inch clearance,
but the supply air duct ange and the rst 3 feet
of supply air duct require a minimum of 1/4 inch clearance to combustible material. However, it is generally recommended that a 1-inch clearance is used for ease of installation and maintaining the required clearance to combustible material. See Figure 3 for details on opening sizes.
3. Locate and mark lag bolt locations and bottom mounting bracket location. See Figures 3A & 3B.
4. Mount bottom mounting bracket.
5. Hook top rain ashing, attached to front - right of supply ange for shipping, under back bend of top.
6. Position unit in opening and secure with 5/16 lag bolts;
use 7/8 inch diameter at washers on the lag bolts.
7. Secure rain ashing to wall and caulk across entire
length of top. See Figures 3A & 3B.
WARNING
Failure to provide the 1/4 inch clearance
between the supply duct and a combustible surface for the rst 3 feet of duct can result in re causing damage, injury or death.
PLACEMENT
1. On side-by-side installations, maintain a minimum of 20 inches clearance on right side to allow access to control panel and heat strips, and to allow proper
airow to the outdoor coil. Additional clearance
may be required to meet local or national codes.
2. Care should be taken to ensure that the recirculation and obstruction of condenser discharge air does not occur. Recirculation of condenser discharge air can be from either a single unit or multiple units. Any object such as shrubbery, a building or a large object can cause obstructions to the condenser discharge air. Recirculation or reduced
airow caused by obstructions will result in reduced
capacity, possible unit pressure safety lockouts and reduced unit service life.
Units with a blow through condenser, such as
the S**H 10 EER units, it is recommended that a minimum distance of 15 feet between the front of the unit and any barrier or 20 feet between the fronts of two opposing (facing) units.
Units with a draw through condenser, such as the
W**H 10 EER units, it is recommended that a minimum distance of 10 feet between the front of the unit and any barrier or opposing (facing) unit.
8. For additional mounting rigidity, the return air and supply air frames or collars can be drilled and screwed or welded to the structural wall itself (depending upon wall construction). Be sure to observe required clearance if combustible wall.
Clearances Required for Service Access
and Adequate Condenser Airow
MODELS LEFT SIDE RIGHT SIDE
S26H, S31H W26H, W31H
S38H, S43H, S49H, S61H W38H, W43H, W49H, W61H
Manual 2100-527H Page 6 of 29
15" 20"
20" 20"
Minimum Clearances Required to Combustible Materials
MODELS
S26H, S31H W26H, W31H
S38H, S43H, S49H, S61H W38H, W43H, W49H, W61H
SUPPLY AIR DUCT FIRST
THREE FEET
1/4" 0
1/4" 0
CABINET
Page 7
Panel
Filter Access
Vent Option Door
Ventilation Air
Front View
5.75
F
W
G
Condenser
Air Inlet
MIS-2763
Rain Hood
(Lockable)
Built In
4° Pitch
Entrance
Disconnect
Access Panel
Electrical
Entrance
Low Voltage
Panel
Access
Heater
Heat
Electric
C. Breaker/
High Voltage
Electrical
Drain
Side View
J
K
D
A
C H
2.13
I
Cond.
Air
Outlet
Mounting
(Built In)
Side Wall
Location
Brackets
Shipping
Entrances
Return Air Opening
Electrical
Supply Air Opening
Optional
Top Rain
Flashing
Bottom Installation Bracket
Back View
S2
T
.44
N
Q
P
M
L
O
E
R
S1
S1
S1
S2
B
FIGURE 2
Dimensions of Basic Unit for Architectural and Installation Requirements (Nominal)
WIDTH
DEPTH
MODEL
S26H1 S31H1 W26H1 W31H1
S38H1 S43H1 S49H1 W38H1 W43H1 W49H1
S61H1 W61H1
(W)
38.200 17.125 70.563 7.88 27.88 13.88 27.88 40.00 10.88 25.75 17.93 26.75 28.75 29.25 27.00 2.63 39.13 22.75 9.14 4.19 12.00 12.00 5.00
42.075 22.432 84.875 9.88 29.88 15.88 29.88 43.88 13.56 31.66 30.00 32.68 26.94 34.69 32.43 3.37 43.00 23.88 10.00 1.44 16.00 16.00 1.88
42.075 22.432 94.875 9.88 29.88 15.88 29.88 43.88 13.56 41.66 30.00 42.68 36.94 44.69 42.43 3.37 43.00 33.88 10.00 1.44 16.00 21.00 1.88
HEIGHT
(D)
All dimensions are in inches. Dimensional drawings are not to scale.
SUPPLY RETURN
(H)
A B C B E F G I J K L M N O P Q R S1 S2 T
S**H & W**H RIGHT UNIT
Manual 2100-527H Page 7 of 29
Page 8
D
12"
12"
12"
12"
12"
C CA
28"
1"
3"
4"
Typ.
4
1
2
"
B
E
14"
1"
3
1
8
"
4"
Typ.
5"
4
1
2
"
7
8
"
RETURN AIR
SUPPLIED
Return Opening
16 7/84 9/164 1/21030
17 5/83 13/165 1/48 1/228 1/2
EDCBA
COMBUSTIBLE MATERIALS
RECOMMENDED 1" CLEARANCE FROM
REQUIRED DIMENSIONS TO MAINTAIN
THE SIDE MOUNTING FLANGES AND UNDER
1/4" CLEARANCE ON ALL
RAIN FLASHING
COMBUSTIBLE MATERIALS
DUCT
TOP FLASHING AT TIME OF INSTALLATION.
1/4" MIN. CLEARANCE FROM
REQUIRED DIMENSIONS TO MAINTAIN
OPENING
ENTIRE LENGTH OF TOP.
MATERIALS
NOTES:
OF CAULKING ALONG
PANEL
FOAM AIR SEAL
FOUR SIDES OF SUPPLY
AIR DUCT IS REQUIRED
FROM COMBUSTABLE
WALL STRUCTURE
TOP
MIS-311 C
Wall Opening and Hole Location View Right Side View
WALL
HEATER ACCESS
SEAL WITH BEAD
IT IS RECOMMENDED THAT A BEAD OF
SILICONE CAULKING BE PLACED BEHIND
SUPPLY AIR
Supply Opening
W*R UNIT SHOWN, W*L UNIT
CONTROLS AND HEATER ACCESS
IS ON OPPOSITE (LEFT) SIDE.
FIGURE 3A
MOUNTING INSTRUCTIONS
S26H1, S31H1, W26H1, W31H1
Manual 2100-527H Page 8 of 29
Page 9
D
16"
16"
16"
16"
16"
1
7
8
"
6
1
2
" 6
1
2
"
2
1
8
"
7
8
"
1"
3"
4"
Typ.
4"
Typ.
6
1
2
"
30"
E
16"
A CC
3
1
8
"
B
Wall Opening and Hole Location View
RETURN AIR
1
REQUIRED DIMENSIONS TO MAINTAIN
1/4" MIN. CLEARANCE FROM
COMBUSTIBLE MATERIALS
REQUIRED DIMENSIONS TO MAINTAIN
29
DUCT
COMBUSTIBLE MATERIALS
A B C DE
30 1/2
10 1/2
6 1/4 1 1/4 29 3/4
32 12 5 1/2
2
NOTES:
WALL STRUCTURE
1
SUPPLY AIR
IT IS RECOMMENDED THAT A BEAD OF
OPENING
Right Side View
RAIN FLASHING
SILICONE CAULKING BE PLACED BEHIND
RECOMMENDED 1" CLEARANCE FROM
THE SIDE MOUNTING FLANGES AND UNDER
TOP FLASHING AT TIME OF INSTALLATION.
TOP.
PANEL
HEATER ACCESS
FOUR SIDES OF SUPPLY
AIR DUCT IS REQUIRED
FROM COMBUSTABLE
WALL
1/4" CLEARANCE ON ALL
MATERIALS
Supply Opening
FOAM AIR SEAL
SUPPLIED
SEAL WITH BEAD
OF CAULKING ALONG
ENTIRE LENGTH OF
TOP
1
Return Opening
MIS-416 E
Dimension is 21" on 95" tall units.
2
Dimension is 10" on T48H1 & T60H1.
2
Dimension is 6" on T48H1 & T60H1.
3
3
FIGURE 3B
MOUNTING INSTRUCTIONS
S38H1, S43H1, S49H1, W38H1, W43H1, W49H1
Manual 2100-527H Page 9 of 29
Page 10
FIGURE 4
ELECTRIC HEAT CLEARANCE
SIDE SECTION VIEW OF SUPPLY AIR DUCT FOR WALL MOUNTED UNIT SHOWING 1/4 INCH CLEARANCE TO COMBUSTIBLE SURFACES.
WARNING
A minimum of 1/4 inch clearance must be maintained between the supply air duct and combustible materials. This is required for
the rst 3 feet of ducting.
It is important to insure that the 1/4 inch minimum spacing is maintained at all points.
Failure to do this could result in overheating the combustible
material and may result in a re causing damage, injury or death.
Manual 2100-527H Page 10 of 29
Page 11
FIGURE 5
DUCT
OPENING
RETURN AIR
SUPPLY AIR
WOOD FRAME WALL INSTALLATION
OPENING
WALL BEFORE
MOUNT ON UNIT
OPENING
BEFORE INSTALLATION
BOTTOM MOUNTING
CONCRETE BLOCK WALL INSTALLATION
BRACKET. MOUNT ON
OPENING
WOOD OR STEEL SIDING
OPENING
INSTALLING UNIT.
RETURN AIR
WALL STRUCTURE
RETURN AIR
SUPPLY AIR
FACTORY SUPPLIED
RAIN FLASHING.
SUPPLY AIR
MIS-548 A
SIDE VIEW
I
A
C
K
E + 1.000
B
1.000
SUPPLY DUCT
OVER FRAME
INTERIOR FINISHED WALL
ALL AROUND DUCT
FRAMING MATERIAL
EXTERIOR FINISH WALL
OPENING
FOR ACTUAL DIMENSIONS.
2 x 4'S, 2 x 6'S &/OR
STRUCTURAL STEEL
ATTACH TO TOP
1.000" CLEARANCE
1.000" CLEARANCE
PLATE OF WALL
C
SEE UNIT DIMENSIONS, FIGURE 2,
OPENING
RETURN DUCT
2 x 6
ATTACH TO BOTTOM
OVER FRAME
PLATE OF WALL
L
THIS STRUCTURAL MEMBER LOCATED TO MATCH STUD SPACING FOR REST OF WALL. A SECOND MEMBER MAY BE REQUIRED FOR SOME WALLS.
MIS-549 B
ALL AROUND DUCT
WALL MOUNTING INSTRUCTIONS
SEE FIGURE 3 – MOUNTING INSTRUCTIONS
FIGURE 6
WALL MOUNTING INSTRUCTIONS
Manual 2100-527H Page 11 of 29
Page 12
FIGURE 7
LOWERED
RAISED FLOOR
RAFTERS
SUPPLY AIR
CEILING SURFACE
WALL SLEEVE
RETURN AIR
CLOSET WALL
GRILLE
FLASHING
RETURN AIR
FLASHING
SUPPLY DUCT MAYBE LOCATED IN AN ATTIC
OR BELOW CEILING RAFTERS AS SHOWN
SUPPLY DUCT MAY BE LOCATED IN AN ATTIC
SURFACE
RAFTERS
FINISHED CEILING
SUPPLY AIR DUCT
WALL
OPENING W/ GRILLE
SUPPLY DUCT MAYBE LOCATED IN AN ATTIC
OR BELOW CEILING RAFTERS AS SHOWN
CEILING
RAIN
RETURN AIR
SLEEVE
WALL
SUPPLY AIR DUCT
RAFTERS
RAFTERS
RETURN AIR OPENING W/ GRILLE
RAIN
FALSE WALL INSTALLATION
DUCTED SUPPLY
GRILLE
OUTSIDE
SPACE
FALSE WALL
RETURN AIR GRILLE
OUTSIDE
OR BELOW CEILING RAFTERS AS SHOWN
FINISHED CEILING SURFACE
RAIN
FLASHING
RAIN
FLASHING
RETURN AT UNITNO DUCT
WALL
SUPPLY AIR DUCT
CLOSET INSTALLATION
RETURN AIR
FINISHED
FINISHED CEILING SURFACE
MIS-550 B
FREE AIR FLOW
OUTSIDE
WALL
OUTSIDE
WALL
SUPPLY AIR DUCT W/ GRILLE
COMMON WALL MOUNTING INSTALLATIONS
Manual 2100-527H Page 12 of 29
Page 13
WIRING – MAIN POWER
Refer to the unit rating plate for wire sizing information and maximum fuse or “HACR” type circuit breaker size. Each outdoor unit is marked with a “Minimum
Circuit Ampacity”. This means that the eld wiring
used must be sized to carry that amount of current. Depending on the installed KW of electric heat, there
may be two eld power circuits required. If this is the
case, the unit serial plate will so indicate. All models are suitable only for connection with copper wire. Each unit and/or wiring diagram will be marked “Use Copper Conductors Only”. These instructions must be adhered to. Refer to the National Electrical Code (NEC) for complete current carrying capacity data on the various insulation grades of wiring material. All wiring must conform to NEC and all local codes.
The electrical data lists fuse and wire sizes (75°C copper) for all models including the most commonly
used heater sizes. Also shown are the number of eld
power circuits required for the various models with heaters.
The unit rating plate lists a “Maximum Time Delay Relay Fuse” or “HACR” type circuit breaker that is to be used with the equipment. The correct size must be used for proper circuit protection and also to assure that there will be no nuisance tripping due to the momentary high starting current of the compressor motor.
WIRING – LOW VOLTAGE WIRING
230/208V, 1 phase and 3 phase equipment dual primary voltage transformers. All equipment leaves the factory wired on 240V tap. For 208V operation, reconnect from 240V to 208V tap. The acceptable operating voltage range for the 240 and 208V taps are:
TAP RANGE
240 253 – 216 208 220 – 187
NOTE: Thevoltageshouldbemeasuredattheeld
power connection point in the unit and while the unit is operating at full load (maximum amperage operating condition).
For wiring size and connections, refer to Wiring Manual 2100-516.
The disconnect access door on this unit may be locked to prevent unauthorized access to the disconnect. To convert for the locking capability, bend the tab located in the bottom left-hand corner of the disconnect opening under the disconnect access panel straight out. This tab will now line up with the slot in the door. When shut, a padlock may be placed through the hole in the tab preventing entry.
See “Start Up” section for important information on three phase scroll compressor start ups.
See Tables 7A & 7B for Electrical Specications.
Manual 2100-527H Page 13 of 29
Page 14
FIGURE 8
COMPRESSOR CUTOFF THERMOSTAT WIRING
4 – 10KW 1 PH – 6 & 9KW 3 PH
FIGURE 9
COMPRESSOR CUTOFF THERMOSTAT WIRING
15 – 20KW 1 PH AND 3 PH
OPTIONAL OUTDOOR THERMOSTAT APPLICATIONS
Since most equipment at the time of manufacture is not
designated for any specic destination of the country
and are installed in areas not approaching the lower outdoor temperature range, outdoor thermostats are not factory installed as standard equipment, but are offered as an option. There are also different applications for applying outdoor thermostats. The set point of either type of outdoor thermostat application is variable with geographic region and sizing of the heating equipment to the individual structure. Utilization of the heating Application Data, and the heat loss calculation of the building are useful in determining the correct set points.
NOTE: The additional LAB (low ambient bypass) relay is required to prevent heater operation during low temperature cooling operation.
Manual 2100-527H Page 14 of 29
OPTIONAL COMPRESSOR CUTOFF THERMOSTAT (See Figures 8 & 9)
Heat pump compressor operation at outdoor temperatures below 0°F are neither desirable nor
advantageous in term of efciency. An outdoor
thermostat can be applied to take the mechanical heating (compressor) off line, and send the (compressor) signal to energize electric heat in its place
(to make electric heat rst stage heating). This can also
be applied to bank the quantity of available electric heat. For example: A heat pump operates with 10KW second stage heat – once the outdoor thermostat has switched then operates 15KW without the compressor
as rst stage heat.
Page 15
ELECTRIC HEAT HOLD-OFF (See Figures 10 & 11)
In other applications, it is desirable to disable the operation of the electric heat until outdoor temperatures have reached a certain design point. This won't allow the electric heat to come on as second stage heating unless the outdoor temperature is below the set point of the outdoor thermostat. This is done to maximize
FIGURE 10
ELECTRIC HEAT HOLD-OFF WIRING
4 – 10KW 1 PH — 6 & 9KW 3 PH
efciency by utilizing the heat pump to bring the
conditioned space temperature up, rather than cycling on the electric heat due a second stage call for heat from the thermostat on start-up coming off a night set­back condition or someone increasing the thermostat set point. (NOTE: Some programmable thermostats do have a built-in time delay for pulling in second stage heat when coming off set-back conditions.)
FIGURE 11
ELECTRIC HEAT HOLD-OFF WIRING
15 – 20KW 1 PH & 3 PH
Manual 2100-527H Page 15 of 29
Page 16
START UP
THESE UNITS REQUIRE R-410A REFRIGERANT AND POLYOL ESTER OIL.
GENERAL:
1. Use separate service equipment to avoid cross contamination of oil and refrigerants.
2. Use recovery equipment rated for R-410A refrigerant.
3. Use manifold gauges rated for R-410A (800 psi/250 psi low).
4. R-410A is a binary blend of HFC-32 and HFC-125.
5. R-410A is nearly azeotropic - similar to R-22 and R-12. Although nearly azeotropic, charge with liquid refrigerant.
6. R-410A operates at 40-70% higher pressure than R-22, and systems designed for R-22 cannot withstand this higher pressure.
7. R-410A has an ozone depletion potential of zero, but must be reclaimed due to its global warming potential.
8. R-410A compressors use Polyol Ester oil.
9. Polyol Ester oil is hygroscopic; it will rapidly absorb moisture and strongly hold this moisture in the oil.
10. A liquid line dryer must be used - even a deep vacuum will not separate moisture from the oil.
11. Limit atmospheric exposure to 15 minutes.
12. If compressor removal is necessary, always plug compressor immediately after removal. Purge with small amount of nitrogen when inserting plugs.
TOPPING OFF SYSTEM CHARGE
If a leak has occurred in the system, Bard Manufacturing recommends reclaiming, evacuating (see criteria above), and charging to the nameplate charge. If done correctly, topping off the system charge can be done without problems.
With R-410A, there are no signicant changes in the
refrigerant composition during multiple leaks and recharges. R-410A refrigerant is close to being an azeotropic blend (it behaves like a pure compound or single component refrigerant). The remaining refrigerant charge, in the system, may be used after leaks have occurred and then “top-off” the charge by utilizing the pressure charts on the inner control panel cover as a guideline.
REMEMBER: When adding R-410A refrigerant, it must come out of the charging cylinder/tank as a liquid to avoid any fractionation, and to insure optimal system performance. Refer to instructions for the cylinder that is being utilized for proper method of liquid extraction.
WARNING
Failure to conform to these practices could lead to damage, injury or death.
SAFETY PRACTICES:
1. Never mix R-410A with other refrigerants.
2. Use gloves and safety glasses, Polyol Ester oils can be irritating to the skin, and liquid refrigerant will freeze the skin.
3. Never use air and R-410A to leak check; the
mixture may become ammable.
4. Do not inhale R-410A – the vapor attacks the nervous system, creating dizziness, loss of coordination and slurred speech. Cardiac irregularities, unconsciousness and ultimate death can result from breathing this concentration.
5. Do not burn R-410A. This decomposition produces hazardous vapors. Evacuate the area if exposed.
6. Use only cylinders rated DOT4BA/4BW 400.
7. Never ll cylinders over 80% of total capacity.
8. Store cylinders in a cool area, out of direct sunlight.
9. Never heat cylinders above 125°F.
10. Never trap liquid R-410A in manifold sets, gauge
lines or cylinders. R-410A expands signicantly
at warmer temperatures. Once a cylinder or line is full of liquid, any further rise in temperature will cause it to burst.
Manual 2100-527H Page 16 of 29
Page 17
START UP (Continued)
IMPORTANT INSTALLER NOTE
For improved start up performance wash the indoor coil with a dish washing detergent.
HIGH & LOW PRESSURE SWITCH
All S**H and W**H wall mounted air conditioner series models are supplied with a remote reset for the high and low pressure switch. If tripped, this pressure switch may be reset by turning the thermostat off then back on again.
THREE PHASE SCROLL COMPRESSOR START UP INFORMATION
Scroll compressors, like several other types of compressors, will only compress in one rotational direction. Direction of rotation is not an issue with single phase compressors since they will always start and run in the proper direction.
However, three phase compressors will rotate in either direction depending upon phasing of the power. Since there is a 50-50 chance of connecting power in such a way as to cause rotation in the reverse
direction, verication of proper rotation must be made. Verication of proper rotation direction is made by
observing that suction pressure drops and discharge pressure rises when the compressor is energized. Reverse rotation also results in an elevated sound level over that with correct rotation, as well as substantially reduced current draw compared to tabulated values.
Verication of proper rotation must be made at the time the equipment is put into service. If improper rotation is corrected at this time, there will be no negative impact on the durability of the compressor. However, reverse operation for over one hour may have a negative impact on the bearing due to oil pump out.
NOTE: If compressor is allowed to run in reverse
rotation for several minutes, the compressor’s internal protector will trip.
PHASE MONITOR
All units with three phase scroll compressors are equipped with a 3-phase line monitor to prevent compressor damage due to phase reversal.
The phase monitor in this unit is equipped with two LEDs. If the Y signal is present at the phase monitor and phases are correct the green LED will light.
If phases are reversed, the red fault LED will be lit and compressor operation is inhibited.
If a fault condition occurs, reverse two of the supply leads to the unit. Do not reverse any of the unit
factory wires as damage may occur.
CONDENSER FAN OPERATION
Applies to S38, S43, S49, S61 & W38, W43, W49, W61 models only. The condenser fan motor on 230/208
volt, one and three phase, 60 HZ units is a two-speed motor that comes factory wired on high speed for peak performance. If ambient conditions permit, it can be reconnected to low speed (red wire) for lower sound level. See wiring diagram.
50 HZ models must have fan wired on low speed. These models are factory wired on low speed.
SERVICE HINTS
1. Caution owner/operator to maintain clean air
lters at all times. Also, not to needlessly close off supply and return air registers. This reduces airow
through the system, which shortens equipment service life as well as increasing operating costs.
2. Check all power fuses or circuit breakers to be sure they are the correct rating.
3. Periodic cleaning of the outdoor coil to permit full
and unrestricted airow circulation is essential.
All three phase ZP compressors are wired identically internally. As a result, once the correct phasing
is determined for a specic system or installation,
connecting properly phased power leads to the same Fusite terminal should maintain proper rotation direction.
The direction of rotation of the compressor may be changed by reversing any two line connections to the unit.
Manual 2100-527H Page 17 of 29
Page 18
SEQUENCE OF OPERATION
COOLING – Circuit R-Y makes at thermostat pulling in
compressor contactor, starting the compressor and outdoor motor. The G (indoor motor) circuit is automatically completed on any call for cooling operation or can be energized by manual fan switch on subbase for constant air circulation.
HEATING – A 24V solenoid coil on reversing valve controls heating cycle operation. Two thermostat options, one allowing “Auto” changeover from cycle to cycle and the other constantly energizing solenoid coil during heating season, and thus eliminating pressure equalization noise except during defrost, are to be used. On “Auto” option a circuit is completed from R-B and R-Y on each heating “on” cycle, energizing reversing valve solenoid and pulling in compressor contactor starting compressor and outdoor motor. R-G also make starting indoor blower motor. Heat pump heating cycle now in operation. The second option has no “Auto” changeover position, but instead energizes the reversing valve solenoid constantly whenever the system switch on subbase is placed in “Heat” position, the “B” terminal being constantly energized from R. A Thermostat demand for heat completes R-Y circuit, pulling in compressor contactor starting compressor and outdoor motor. R-G also make starting indoor blower motor.
PRESSURE SERVICE PORTS
High and low pressure service ports are installed on all units so that the system operating pressures can be observed. Pressure tables can be found later in the manual covering all models. It is imperative to match the correct pressure table to the unit by model number. See Tables 5A & 5B.
If some abnormal or temporary condition such as a high wind causes the heat pump to have a prolonged defrost cycle, the heat pump control will restore the system to heating operation automatically after 8 minutes.
The heat pump defrost control board has an option of 30, 60 or 90-minute setting. By default, this unit is shipped from the factory with the defrost time on the 60 minute pin. If circumstances require a change to another time, remove the wire from the 60-minute terminal and reconnect to the desired terminal. Refer to Figure 12.
There is a cycle speed up jumper on the control. This can be used for testing purposes to reduce the time between defrost cycle operation without waiting for time to elapse.
Use a small screwdriver or other metallic object, or another ¼ inch QC, to short between the SPEEDUP terminals to accelerate the HPC timer and initiate defrost.
Be careful not to touch any other terminals with the instrument used to short the SPEEDUP terminals. It may take up to 10 seconds with the SPEEDUP terminals shorted for the speedup to be completed and the defrost cycle to start.
As soon as the defrost cycle kicks in remove the shorting instrument from the SPEEDUP terminals. Otherwise the
timing will remain accelerated and run through the 1-minute minimum defrost length sequence in a matter of seconds and will automatically terminate the defrost sequence.
There is an initiate defrost jumper (sen jump) on the control that can be used at any outdoor ambient during the heating cycle to simulate a 0° coil temperature.
This can be used to check defrost operation of the unit without waiting for the outdoor ambient to fall into the defrost region.
DEFROST CYCLE
The defrost cycle is controlled by temperature and time on the solid state heat pump control.
When the outdoor temperature is in the lower 40°F temperature range or colder, the outdoor coil temperature is 32°F or below. This coil temperature is sensed by the coil temperature sensor mounted near the bottom of the outdoor coil. Once coil temperature reaches 30°F or below, the coil temperature sensor sends a signal to the control logic of the heat pump control and the defrost timer will start accumulating run time.
After 30, 60 or 90 minutes of heat pump operation at 30°F or below, the heat pump control will place the system in the defrost mode.
During the defrost mode, the refrigerant cycle switches back to the cooling cycle, the outdoor motor stops, electric heaters are energized, and hot gas passing through the outdoor coil melts any accumulated frost. When the temperature rises to approximately 57°F, the coil temperature sensor will send a signal to the heat pump control which will return the system to heating operations automatically.
Manual 2100-527H Page 18 of 29
By placing a jumper across the SEN JMP terminals (a ¼ inch QC terminal works best) the defrost sensor mounted on the outdoor coil is shunted out & will activate the timing circuit. This permits the defrost cycle to be checked out in warmer weather conditions without the outdoor temperature having to fall into the defrost region.
In order to terminate the defrost test the SEN JMP jumper must be removed. If left in place too long, the compressor could stop due to the high pressure control opening because of high pressure condition created by operating in the cooling mode with outdoor fan off. Pressure will rise fairly fast as there is likely no actual frost on the outdoor coil in
this articial test condition.
There is also a 5-minute compressor time delay function built into the HPC. This is to protect the compressor from short cycling conditions. The board’s LED will have a fast blink rate when in the compressor time delay. In some instances, it is helpful to the service technician to override or speed up this timing period, and shorting out the SPEEDUP terminals for a few seconds can do this.
Page 19
120*
SW1SW
2 TIME (SEC)
OFF OFF
ON ON
OFF
ON
OFF
ON
30 60
180
MIS-2668 A
OFF
LOW PRESSURE BYPASS TIMER SWITCH *(FACTORY SETTING 120 SECONDS)
ACCUMULATED DEFROST TIME TIMER (FACTORY SETTING 60 MIN.)
ON
Low Pressure Switch Bypass Operation - The control has a selectable (SW1) low pressure switch bypass set up to ignore
the low pressure switch input during the rst (30, 60, 120 or
180 seconds) of “Y” operation.
After this period expires, the control will then monitor the low pressure switch input normally to make sure that the switch is closed during “Y” operation.
High Pressure Switch Operation - The control has a built-in lockout system that allows the unit to have the high pressure
FIGURE 12
DEFROST CONTROL BOARD
switch trip up to two times in one hour and only encounter a “soft” lockout. A “soft” lockout shuts the compressor off and waits for the pressure switch to reset, which at that point then allows the compressor to be restarted as long as the 5-minute short cycle timer has run out. If the high pressure switch trips a third time within one hour, the unit is in “hard” lockout indicating something is certainly wrong and it will not restart itself.
Manual 2100-527H Page 19 of 29
Page 20
TROUBLESHOOTING
SOLID STATE HEAT PUMP CONTROL TROUBLESHOOTING PROCEDURE
1. NOTE: A thorough understanding of the defrost cycle sequence is essential. Review that section
NOTE: If there was no power to 24 volt transformer, the compressor and outdoor fan motor will not start for 5 minutes. This is because of the compressor short cycle protection.
earlier in this manual prior to troubleshooting the control. Turn on AC power supply to unit.
2. Turn thermostat blower switch to “fan on” – the indoor blower should start. (If it doesn’t, troubleshoot indoor unit and correct problem.)
3. Turn thermostat blower to “auto” position. Indoor blower should stop. NOTE: Many models have a
1-minute blower time delay on “off” command; wait for this to time-out.
4. Set system switch to “heat” or “cool”. Adjust thermostat to call for heat or cool. The indoor blower, compressor and outdoor fan should start.
BLINK FUNCTION
Slow Normal function (1.0 sec on/1.0 sec off) Fast ASCD (Compressor Delay) timer active (0.1 sec on/0.1 sec off) 1 Low pressure switch failure 2 High pressure switch failure/“Soft” Lockout 3 Defrost mode active 4 High pressure switch failure/“Hard” Lockout
TABLE 3
TROUBLESHOOTING
Sympton Description, Check & Possible Cause What & How to Check/Repair
Compressor will not start (heating or cooling)
Fan outdoor motor does not run (cooling or heating except during defrost)
Reversing valve does not energize (heating only)
Unit will not go into defrost (heating only)
Unit will not come out of defrost (heating only)
1. Check for LED illumination.
Is there an LED illuminated on the board
(ashing)?
2. Check for error codes.
Is the LED ashing a code?
3. Check for power at board.
Is there 24 volts AC between R and C?
4. Check codes.
What code is blinking?
5. Compressor delay active.
Wait for 5 minute delay or jump board's
"speed up pins".
6. Low pressure fault. Check wiring circuit and unit pressures.
7. High pressure fault. Check wiring circuit and unit pressures.
8. Check for Compressor input signal.
Is there 24 volts AC between Y and C?
9. No power to board.
10. Check for Compressor output signal.
Is there 24 volts AC between CC and C?
11. No "Y" compressor input signal.
12. No "CC" compressor output signal. Check compressor contactor for proper operation and nally check compressor.
13. Faulty board. Replace defrost board.
Heat pump control defective
Motor defective Check for open or shorted motor winding. Replace motor.
Motor capacitor defective Check capacitor rating. Check for open or shorted capacitor. Replace capacitor.
Heat pump control defective
Reversing valve solenoid coil defective
Temperature sensor or heat pump control defective
Temperature sensor or heat pump control defective
Yes = go to Step #2; No = go to Step #3
Yes = go to Step #4; No = go to Step #8
Yes = go to Step #13; No = go to Step #9
Code "1", got to Step #6; Code "2", go to Step #7; Fast Blink, go to Step #5
Check for proper operation; if still needed, go back to Step #1
Yes = go to Step #10; No = go to Step #11
The unit either does not have unit voltage, the transformer is bad or the unit wiring is incorrect.
Yes = go to Step #12; No = go to Step #13
Check thermostat wiring, incorrect phase of unit (see section on Phase Monitor)
and nally unit wiring.
Check across fan relay on heat pump control. (Com-NC) Replace heat pump control.
Check for 24 V between RV-C and B-C.
1. Check circuit control wiring.
2. Replace heat pump control.
Check for open or shorted coil. Replace solenoid coil.
Disconnect temperature sensor from board and jumper across "SPEEDUP"
terminals and "SEN JMP" terminals. This should cause the unit to go through a defrost cycle within one minute.
1. If unit goes through defrost cycle, replace temperature sensor.
2. If unit does not go through defrost cycle, replace heat pump control.
Jumper across "SPEEDUP" terminal. This should cause the unit to come out of defrost within one minute.
1. If unit goes through defrost cycle, replace temperature sensor.
2. If unit does not go through defrost cycle, replace heat pump control.
LED BLINK CODES
Manual 2100-527H Page 20 of 29
Page 21
CHECKING TEMPERATURE SENSOR OUTSIDE UNIT CIRCUIT
1. Disconnect temperature sensor from board and from outdoor coil.
2. Use an ohmmeter and measure the resistance of the sensor. Also use ohmmeter to check for short or open.
TEMPERATURE F VS. RESISTANCE R OF TEMPERATURE SENSOR
F R F R F R F R
-25.0 196871 13.0 56985 53.0 19374 89.0 7507
-24.0 190099 14.0 55284 52.0 18867 90.0 7334
-23.0 183585 15.0 53640 53.0 18375 91.0 7165
-22.0 177318 16.0 52051 54.0 17989 92.0 7000
-21.0 171289 17.0 50514 55.0 17434 93.0 6840
-20.0 165487 18.0 49028 56.0 16984 94.0 6683
-19.0 159904 19.0 47590 57.0 16547 95.0 6531
-18.0 154529 20.0 46200 58.0 16122 96.0 6383
-17.0 149355 21.0 44855 59.0 15710 97.0 6239
-16.0 144374 22.0 43554 60.0 15310 98.0 6098
-15.0 139576 23.0 42295 61.0 14921 99.0 5961
-14.0 134956 24.0 41077 62.0 14544 100.0 5827
-13.0 130506 25.0 39898 63.0 14177 101.0 5697
-12.0 126219 26.0 38757 64.0 13820 102.0 5570
-11.0 122089 27.0 37652 65.0 13474 103.0 5446
-10.0 118108 28.0 36583 66.0 13137 104.0 5326
-9.0 114272 29.0 35548 67.0 12810 105.0 5208
-8.0 110575 30.0 34545 68.0 12492 106.0 5094
-7.0 107010 31.0 33574 69.0 12183 107.0 4982
-6.0 103574 32.0 32634 70.0 11883 108.0 4873
-5.0 100260 33.0 31723 71.0 11591 109.0 4767
-4.0 97064 34.0 30840 72.0 11307 110.0 4663
-3.0 93981 35.0 29986 73.0 11031 111 . 0 4562
-2.0 91008 36.0 29157 74.0 10762 112.0 4464
-1.0 88139 37.0 28355 75.0 10501 113.0 4367
0.0 85371 38.0 27577 76.0 10247 114.0 4274
1.0 82699 39.0 26823 77.0 10000 115.0 4182
2.0 80121 40.0 26092 78.0 9760 116.0 4093
3.0 77632 41.0 25383 79.0 9526 117.0 4006
4.0 75230 42.0 24696 80.0 9299 118.0 3921
5.0 72910 43.0 24030 81.0 9077 119.0 3838
6.0 70670 44.0 23384 82.0 8862 120.0 3757
7.0 68507 45.0 22758 83.0 8653 121.0 3678
8.0 66418 46.0 22150 84.0 8449 122.0 3601
9.0 64399 47.0 21561 85.0 8250 123.0 3526
10.0 62449 48.0 20989 86.0 8057 124.0 3452
11.0 60565 49.0 20435 87.0 7869
12.0 58745 50.0 19896 88.0 7686
3. Check resistance reading to chart of resistance. Use sensor ambient temperature. (Tolerance of part is ± 10%.)
4. If sensor resistance reads very low, then sensor is shorted and will not allow proper operation of the heat pump control.
5. If sensor is out of tolerance, shorted, open or reads very low ohms then it should be replaced.
Manual 2100-527H Page 21 of 29
Page 22
TROUBLESHOOTING
"A"
S**H AIRFLOW
W**H AIRFLOW
MIS-2725 A
FAN BLADE SETTING DIMENSIONS
Shown in Figure 13 is the correct fan blade setting for proper air delivery across the outdoor coil. Refer to
Table 4 for unit specic dimension.
Any service work requiring removal or adjustment in the fan and/or motor area will require that the dimensions below be checked and blade adjusted in or out on the motor shaft accordingly.
FIGURE 13
FAN BLADE SETTING
TABLE 4
FAN BLADE DIMENSION
Model Dimension A
W26H1 W31H1 W38H1 W43H1 W49H1 W61H1
S26H1 S31H1
S38H1 S43H1 S49H1 S61H1
1.00"
1.25"
1.75"
REMOVAL OF FAN SHROUD
1. Disconnect all power to the unit.
2. Remove the screws holding both grilles, one on each side of unit, and remove grilles.
3. Remove screws holding fan shroud to condenser and bottom. Nine (9) screws.
4. Unwire condenser fan motor.
5. Slide complete motor, fan blade, and shroud assembly out the left side of the unit.
6. Service motor/fan as needed.
7. Reverse steps to reinstall.
R-410A
REFRIGERANT CHARGE
This unit was charged at the factory with the quantity of refrigerant listed on the serial plate. AHRI capacity and
efciency ratings were determined by testing with this
refrigerant charge quantity.
The following pressure tables show nominal pressures
for the units. Since many installation specic situations
can affect the pressure readings, this information should
only be used by certied technicians as a guide for
evaluating proper system performance. They shall not be used to adjust charge. If charge is in doubt, reclaim, evacuate and recharge the unit to the serial plate charge.
Manual 2100-527H Page 22 of 29
Page 23
Model
S26H1
S31H1
S38H1
S43H1
S49H1
S61H1
Return Air
Temperature
75 deg. DB
62 deg. WB
80 deg. DB
67 deg. WB
85 deg. DB
72 deg. WB
75 deg. DB
62 deg. WB
80 deg. DB
67 deg. WB
85 deg. DB
72 deg. WB
75 deg. DB
62 deg. WB
80 deg. DB
67 deg. WB
85 deg. DB
72 deg. WB
75 deg. DB
62 deg. WB
80 deg. DB
67 deg. WB
85 deg. DB
72 deg. WB
75 deg. DB
62 deg. WB
80 deg. DB
67 deg. WB
85 deg. DB
72 deg. WB
75 deg. DB
62 deg. WB
80 deg. DB
67 deg. WB
85 deg. DB
72 deg. WB
TABLE 5A
COOLING PRESSURE TABLE
Pressure 75 80 85 90 95 100 105 110 115 120
Low SIde High Side
Low SIde High Side
Low SIde High Side
Low SIde High Side
Low SIde High Side
Low SIde High Side
Low SIde High Side
Low SIde High Side
Low SIde High Side
Low SIde High Side
Low SIde High Side
Low SIde High Side
Low SIde High Side
Low SIde High Side
Low SIde High Side
Low SIde High Side
Low SIde High Side
Low SIde High Side
129 298
133 306
143 317
122 312
130 320
135 331
125 314
134 322
139 333
128 329
137 337
142 349
131 338
140 347
145 359
122 336
131 345
136 357
130 320
134 328
144 339
124 329
133 337
138 349
127 332
136 340
141 352
130 343
139 352
144 364
131 355
140 364
145 377
123 353
132 362
137 375
131 342
135 351
145 363
126 347
135 356
140 368
129 351
138 360
143 373
132 361
141 370
146 383
132 372
141 382
146 395
125 371
134 381
139 394
132 366
136 375
145 388
129 368
136 377
143 390
131 371
140 381
145 394
134 381
143 391
148 405
133 392
142 402
147 416
126 392
135 402
140 416
133 390
137 397
147 414
131 390
137 405
145 414
133 394
141 400
147 418
137 404
144 413
151 428
134 413
142 421
148 439
128 416
137 427
142 442
Air Temperature Entering Outdoor Coil °F
134 414
143 425
148 440
133 413
142 424
147 439
135 417
144 428
149 443
138 429
148 440
153 455
136 437
145 448
150 464
130 442
139 453
144 469
135 440
144 451
149 467
135 439
144 450
149 466
137 442
146 453
151 469
140 457
150 469
155 485
137 461
147 473
152 490
132 470
141 482
146 499
137 466
146 478
151 495
137 466
146 478
151 495
138 468
148 480
153 497
143 488
153 501
158 519
139 488
149 501
154 519
133 500
142 513
147 531
138 493
148 506
153 524
138 494
147 507
152 525
140 496
150 509
155 527
145 522
155 535
160 554
142 517
152 530
157 549
136 532
145 546
150 565
140 522
150 535
155 554
139 525
149 538
154 557
141 526
151 539
156 558
148 558
158 572
164 592
145 547
155 561
160 581
137 567
147 582
152 602
Low side pressure ± 4 PSIG High side pressure ± 10 PSIG
Tables are based upon rated CFM (airow) across the evaporator coil. If there is any doubt as to correct operating charge being in the system, the charge
should be removed, system evacuated and recharged to serial plate charge weight.
NOTE: Pressure table based on high speed condenser fan operation. If condensing pressures appear elevated check condenser fan wiring. See
“Condenser Fan Operation”.
HEATING PRESSURES – (ALL TEMPERATURES °F)
Model
S26H1 70 Deg.
S31H1 70 Deg.
S38H1 70 Deg.
S43H1 70 Deg.
S49H1 70 Deg.
S61H1 70 Deg.
Return Air
Temperature
Pressure 0 5 10 15 20 25 30 35 40 45 50 55 60 65
Low Side
High Side373044330550307573116331771325783358534693352
Low Side
High Side382814429150300573106432171332793438635494366
Low Side
High Side37270432764928255289622966930476313833229133399343
Low Side
High Side492735027553278572826228767294743038231291323
Low Side
High Side32310373114131553320643287333782348893619537799394
Low Side
High Side44283462924730249313523245733563347713608037391387
TABLE 5B
101 360
102 379
100 335
109
117 410
119 404
116 367
123 363
104 433
117 416
126 430
127 418
125 380
136 379
105 456
133 431
391
110 391
107 355
111 348
102 413
103 401
Manual 2100-527H Page 23 of 29
134 452
136 432
134 393
150 396
104 481
149 447
Page 24
Model
W26H1
W31H1
W38H1
W43H1
W49H1
W61H1
Return Air
Temperature
75 deg. DB
62 deg. WB
80 deg. DB
67 deg. WB
85 deg. DB
72 deg. WB
75 deg. DB
62 deg. WB
80 deg. DB
67 deg. WB
85 deg. DB
72 deg. WB
75 deg. DB
62 deg. WB
80 deg. DB
67 deg. WB
85 deg. DB
72 deg. WB
75 deg. DB
62 deg. WB
80 deg. DB
67 deg. WB
85 deg. DB
72 deg. WB
75 deg. DB
62 deg. WB
80 deg. DB
67 deg. WB
85 deg. DB
72 deg. WB
75 deg. DB
62 deg. WB
80 deg. DB
67 deg. WB
85 deg. DB
72 deg. WB
TABLE 6A
COOLING PRESSURE TABLE
Pressure 75 80 85 90 95 100 105 110 115 120
Low SIde
High Side
Low SIde
High Side
Low SIde
High Side
Low SIde
High Side
Low SIde
High Side
Low SIde
High Side
Low SIde
High Side
Low SIde
High Side
Low SIde
High Side
Low SIde
High Side
Low SIde
High Side
Low SIde
High Side
Low SIde
High Side
Low SIde
High Side
Low SIde
High Side
Low SIde
High Side
Low SIde
High Side
Low SIde
High Side
131 309
140 317
145 328
123
311
132 319
137 330
126 313
135 321
140 332
131 325
140 333
145 345
128 315
137 323
142 334
123 336
132 345
137 357
132 326
141 334
146 346
125 330
134 338
139 350
127 330
136 338
141 350
131 343
140 352
145 364
129 337
138 346
143 358
123 353
132 362
137 375
133 345
142 354
147 366
128 350
137 359
142 372
129 348
138 357
143 369
132 363
141 372
146 385
130 361
139 370
144 383
124 371
133 381
138 394
135 366
144 375
149 388
130 371
139 381
144 394
131 370
140 379
145 392
134 384
143 394
148 408
131 385
140 395
145 409
125 392
134 402
139 416
136 390
145 400
150 414
133 395
140 405
147 419
133 394
140 397
147 418
135 408
143 418
149 433
132 411
141 430
146 437
127 415
137 437
141 441
Air Temperature Entering Outdoor Coil °F
137 415
146 426
151 441
135 419
144 430
149 445
135 420
144 431
149 446
137 432
147 443
152 459
134 439
143 450
148 466
128 441
137 452
142 468
138 444
148 455
153 471
137 446
146 457
151 473
137 449
146 461
151 477
139 458
149 470
154 486
136 467
145 479
150 496
130 469
139 481
144 498
139 474
149 486
154 503
138 474
148 486
153 503
139 482
149 494
154 511
142 487
152 499
157 516
137 496
147 509
152 527
133 499
142 512
147 530
141 506
151 519
156 537
140 504
150 517
155 535
141 516
151 529
156 548
145 516
155 529
160 548
140 527
150 541
155 560
136 532
145 546
150 565
142 541
152 555
157 574
142 535
152 549
157 568
144 553
154 567
159 587
148 547
158 561
164 581
143 560
153 574
158 594
138 567
148 582
153 602
Low side pressure ± 4 PSIG High side pressure ± 10 PSIG
Tables are based upon rated CFM (airow) across the evaporator coil. If there is any doubt as to correct operating charge being in the system, the charge
should be removed, system evacuated and recharged to serial plate charge weight.
NOTE: Pressure table based on high speed condenser fan operation. If condensing pressures appear elevated check condenser fan wiring. See
“Condenser Fan Operation”.
HEATING PRESSURES – (ALL TEMPERATURES °F)
Model
W26H1 70 Deg.
W31H1 70 Deg.
W38H1 70 Deg.
W43H1 70 Deg.
W49H1 70 Deg.
W61H1 70 Deg.
Manual 2100-527H Page 24 of 29
Return Air
Temperature
Pressure 0 5 10 15 20 25 30 35 40 45 50 55 60 65
Low Side High Side42279462855029256299623086831775327833389135099362
Low Side High Side39274442834929355303613146832575336823489036198373
Low Side High Side25251342604326952278602876829675306823159032596335
Low Side High Side34265402704627553278602816728774294813048931797331
Low Side High Side48283492935130354313583236333469345773568636896380
Low Side High Side34270362783928643296493065531762328703418035490369
TABLE 6B
108 376
107 386
103 345
105 348
107 392
101 384
118 390
116 400
109 355
114 368
119 405
113 399
128 405
126 414
115 365
123 389
133 418
126 416
139 420
135 428
120 375
132 413
147 431
141 433
Page 25
TABLE 7A
Electrical Specications — S**H Series
Single Circuit Multiple Circuit
Minimum Circuit
Ampacity
Ckt. ACkt. BCkt. CCkt. ACkt. BCkt. CCkt. ACkt. BCkt. CCkt. ACkt. BCkt.
10 10 10
12 10
14 12
10 10 10
10 10
14 12
10 10
8 8 8
10 10 10 10
14 10 10 10
10 10
8 8 8 8
10 10 10 10
12 10 10 10
10
8 8 8 8
10 10 10 10
12 10 10 10
10
8 8 8 8
10 10 10
12 10 10
42
32
52
32
52
35
34
26
34
42
34
52
35
52
39
26
39
42
39
52
39
52
43
26
43
52
43
52
43
52 26
Circuit
22 43 47
16 34
10 19
27 48 48
19 37
10 19
32 58 74 84 87
26 44 53 54
14 23 27 28
34 55 60 76 86 87
27 45 54 54
14 23 27 28
39 65 80 91 91
29 47 57 57
15 24 28 28
43 69 95 95
113
30 57 57
16 29 29
Maximum
External Fuse or
Circuit
Breaker
30 50 50
20 40
15 20
35 50 50
25 40
15 20
45 60 80 90 90
35 50 60 60
15 25 30 30
50 60 70 80 90 90
35 50 60 60
20 25 30 30
50 70
90 100 100
40
50
60
60
20
25
30
30
60
80
100 100 125
40
60
60
20
30
30
Field
Power
Wire Size
10
8 8
12
8
14 12
8 8 8
10
8
14 12
8 6 4 4 3
8 8 6 6
14 10 10 10
8 6 6 4 3 3
8 8 6 6
12 10 10 10
8 6 4 3 3
8 8 6 6
12 10 10 10
8 4 3 3 2
8 6 6
12 10 10
Ground
WIre Size
No. of
Models
S26H1-A00, A0Z
-A04
-A08
S26H1-B00, B0Z
-B06
S26H1-C00, C0Z
-C06
S31H1-A00, A0Z
-A04
-A08
S31H1-B00, B0Z
-B06
S31H1-C00, C0Z
-C06
S38H1-A00, A0Z
-A05
-A08
-A10
-A15
S38H1-B00, B0Z
-B06
-B09
-B15
S38H1-C00, C0Z
-C06
-C09 C15
S43H1-A00, A0Z
-A04
-A05
-A08
-A10
-A15
S43H1-B00, B0Z
-B06
-B09
-B15
S43H1-C00, C0Z
-C06
-C09
-C15
S49H1-A00, A0Z
-A05
-A08
-A10
-A15
S49H1-B00, B0Z
-B09
-B15
-B18
S49H1-C00, C0Z
-C06
-C09
-C15
S61H1-A00, A0Z
-A05
-A10
-A15
-A20
S61H1-B00, B0Z
-B09
-B15
S61H1-C00, C0Z
-C09
-C15
These “Minimum Circuit Ampacity” values are to be used for sizing the eld power conductors. Refer to the National Electrical Code (latest version),
Article 310 for power conductor sizing.
Caution: When more than one eld power circuit is run through one conduit, the conductors must be derated. Pay special attention to note 8 of Table 310 regarding Ampacity Adjustment Factors when more than three (3) conductors are in a raceway.
Maximum size of the time delay fuse or HACR type circuit breaker for protection of eld wiring conductors. Based on 75°C copper wire. All wiring must conform to the National Electrical Code and all local codes. Maximum KW that can operate with the heat pump on is 10KW. Maximum KW that can operate with the heat pump on is 5KW. Maximum KW that can operate with the heat pump on is 4KW.
IMPORTANT: While this electrical data is presented as a guide, it is important to electrically connect properly sized fuses & conductor wires in accordance with the National Electrical Code & all local codes.
Rated Volts, HZ
and Phase
230/208-60-1
230/208-60-3
460-60-3
230/208-60-1
230/208-60-3
460-60-3
230/208-60-1
230/208-60-3
460-60-3
230/208-60-1
230/208-60-3
460-60-3
230/208-60-1
230/208-60-3
460-60-3
230/208-60-1
230/208-60-3
460-60-3
Circuits
Field
Power
1 1 1
1 1
1 1
1 1 1
1 1
1 1
1
1 1 or 2 1 or 2 1 or 2
1
1
1
1
1
1
1
1
1
1 1 or 2 1 or 2 1 or 2 1 or 2
1
1
1
1
1
1
1
1
1 1 or 2 1 or 2 1 or 2 1 or 2
1
1
1
1
1
1
1
1
1 1 or 2 1 or 2 1 or 2 1 or 3
1
1
1
1
1
1
Minimum
Ampacity
Maximum Circuit
Exterior Fuse or
Circuit Breaker
45
45
45
60
45
60
50
30
50
45
50
60
50
60
50
30
50
45
50
60
50
60
60
30
60
60
60
60
60
60 30
Field Power Wire
Size
8
8
8
6
8
6
8
10
8
8
8
6
8
6
8
10
8
8
8
6
8
6
8
10
8
6
8
6
6
6 10
Ground WIre Size
10 10 10
10 10 10 10
10 10 10 10
10 10 10 10
Manual 2100-527H Page 25 of 29
10 10 10
10 10 10 10
10 10 10 10
10 10 10 10 10
C
Page 26
TABLE 7B
Electrical Specications — W**H Series
Single Circuit Multiple Circuit
Minimum Circuit
Ampacity
Ckt. ACkt. BCkt. CCkt. ACkt. BCkt. CCkt. ACkt. BCkt. CCkt. ACkt. BCkt.
10 10 10
10 10
14 12
10 10 10
10 10
14 12
10 10
8 8 8
10 10 10 10
14 10 10 10
10 10
8 8 8 8
10 10 10 10
12 10 10 10
10 10
8 8 8 8
10 10 10 10
12 10 10 10
10
8 8 8 8
10 10 10
12 10 10
42
32
52
32
52
35
34
26
34
42
34
52
35
52
37
26
37
42
37
52
37
52
43
26
43
52
43
52
43
52 26
Circuit
25 46 47
18 36
11 10
26 47 47
19 37
9
18
32 58 74 84 87
26 44 53 54
14 23 27 28
34 55 60 76 86 87
27 45 54 54
14 23 27 28
37 58 63 78 89 89
28 46 55 55
14 23 28 28
43 69 95 95
113
30 57 57
16 29 29
Maximum
External
Fuse or
Circuit
Breaker
30 50 50
25 40
15 20
35 50 50
25 40
15 20
45 60 80 90 90
35 50 60 60
15 25 30 30
50 60 70 80 90 90
35 50 60 60
20 25 30 30
50 60 70 90 90 90
40 50 60 60
20 25 30 30
60
80 100 100 125
40
60
60
20
30
30
Field
Power
Wire Size
10
8 8
10
8
14 12
8 8 8
10
8
14 12
8 6 4 4 3
8 8 6 6
14 10 10 10
8 6 6 4 3 3
8 8 6 6
12 10 10 10
8 6 6 4 3 3
8 8 6 6
12 10 10 10
8 4 3 3 2
8 6 6
12 10 10
Ground
WIre Size
No. of
Models
W26H1-A00, A0Z
-A04
-A08
W26H1-B00, B0Z
-B06
W26H1-C00, C0Z
-C06
W31H1-A00, A0Z
-A04
-A08
W31H1-B00, B0Z
-B06
W31H1-C00, C0Z
-C06
W38H1-A00, A0Z
-A05
-A08
-A10
-A15
W38H1-B00, B0Z
-B06
-B09 B15
W38H1-C00, C0Z
-C06
-C09
C15
W43H1-A00, A0Z
-A04
-A05
-A08
-A10 A15
W43H1-B00, B0Z
-B06
-B09 B15
W43H1-C00, C0Z
-C06
-C09
-C15
W49H1-A00, A0Z
-A04
-A05
-A08
-A10
-A15
W49H1-B00, B0Z
-B06
-B09
-B15
W49H1-C00, C0Z
-C06
-C09
-C15
W61H1-A00, A0Z
-A05
-A10
-A15
-A20
W61H1-B00, B0Z
-B09
-B15
W61H1-C00, C0Z
-C09
-C15
These “Minimum Circuit Ampacity” values are to be used for sizing the eld power conductors. Refer to the National Electrical Code (latest version), Article
310 for power conductor sizing.
Caution: When more than one eld power circuit is run through one conduit, the conductors must be derated. Pay special attention to note 8 of Table 310 regarding Ampacity Adjustment Factors when more than three (3) conductors are in a raceway.
Maximum size of the time delay fuse or HACR type circuit breaker for protection of eld wiring conductors. Based on 75°C copper wire. All wiring must conform to the National Electrical Code and all local codes. Maximum KW that can operate with the heat pump on is 10KW. Maximum KW that can operate with the heat pump on is 5KW. Maximum KW that can operate with the heat pump on is 4KW.
IMPORTANT: While this electrical data is presented as a guide, it is important to electrically connect properly sized fuses & conductor wires in accordance with the National Electrical Code & all local codes.
Rated Volts, HZ
and Phase
230/208-60-1
230/208-60-3
460-60-3
230/208-60-1
230/208-60-3
460-60-3
230/208-60-1
230/208-60-3
460-60-3
230/208-60-1
230/208-60-3
460-60-3
230/208-60-1
230/208-60-3
460-60-3
230/208-60-1
230/208-60-3
460-60-3
Field
Power
Circuits
1 1 1
1 1
1 1
1 1 1
1 1
1 1
1
1 1 or 2 1 or 2 1 or 2
1
1
1
1
1
1
1
1
1
1 1 or 2 1 or 2 1 or 2 1 or 2
1
1
1
1
1
1
1
1
1
1 1 or 2 1 or 2 1 or 2 1 or 2
1
1
1
1
1
1
1
1
1 1 or 2 1 or 2 1 or 2 1 or 3
1
1
1
1
1
1
Minimum
Ampacity
Manual 2100-527H Page 26 of 29
Maximum Circuit
Exterior Fuse or
Circuit Breaker
45
45
45
60
45
60
50
30
50
45
50
60
50
60
50
30
50
45
50
60
50
60
60
30
60
60
60
60
60
60 30
Field Power Wire
Size
8
8
8
6
8
6
8
10
8
8
8
6
8
6
8
10
8
8
8
6
8
6
8
10
8
6
8
6
6
6 10
Ground WIre Size
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10 10
C
Page 27
TABLES 8
INDOOR BLOWER PERFORMANCE CFM
AT 230 OR 460 VOLTS
S26H1, S31H1
ESP in Inches Water Column
High Speed
Dry/Wet Coil
W26H1, W31H1
Low Speed
Dry/Wet Coil
.0 1050/1000 950/900
.1 900/850 540/800
.2 750/700 700/650
Above data is with 1" standard disposable or 1" washable lter For optional 2" pleated lter - reduce ESP by 0.08 in. Reconnect to next lower speed for free blow (non-ducted) installation.
TABLE 9A
S**H INDOOR BLOWER PERFORMANCE - CFM (0.00" — 0.50" H20)
Model
Rated
ESP
Max ESP
Blower
Only
Cooling
Electric
Heat
S38H .15 .50 1100 1100 1100
S43H .15 .50 1250 1250 1250
S49H .20 .50 1400 1400 1400
S61H .20 .50 1450 1450 1450
NOTE: These units are equipped with a variable speed (ECM) indoor motor that automatically adjusts itself to maintain approximately the same rate of indoor airow in both heating & cooling, dry & wet coil conditions and at both 230/208 or 460 volts.
Maximum ESP (inches WC) shown is with 2" thick disposable lter.
Blower only CFM is the total air being circulated during continuous fan mode.
CFM output on Cooling or Electric Heat.
TABLE 9B
W**H INDOOR BLOWER PERFORMANCE - CFM (0.00" — 0.50" H20)
Max ESP
Model
Rated
ESP
W38H .15 .50 800 1100 1100
W43H .15 .50 825 1250 1250
W49H .20 .50 825 1400 1400
W61H .20 .50 850 1450 1450
Blower
Only
Cooling
Electric
Heat
NOTE: These units are equipped with a variable speed (ECM) indoor motor that automatically adjusts itself to maintain approximately the same rate of indoor airow in both heating & cooling, dry & wet coil conditions and at both 230/208 or 460 volts.
Maximum ESP (inches WC) shown is with 2" thick disposable lter.
Blower only CFM is the total air being circulated during continuous fan mode.
CFM output on Cooling or Electric Heat.
Manual 2100-527H Page 27 of 29
Page 28
TROUBLESHOOTING GE ECM
MOTORS
CAUTION:
Disconnect power from unit before removing or replacing connectors, or servicing motor. To avoid electric shock from the motor’s capacitors, disconnect power and wait at least 5 minutes before opening motor.
Symptom Cause/Procedure
Motor rocks slightly This is normal start-up for ECM when starting
Motor won’t start Check blower turns by hand
• No movement
• Check low voltage (24 Vac R to C) at motor
• Check low voltage connections (G, Y, W, R, C) at motor
• Check for unseated pins in connectors on motor harness
• Test with a temporary jumper between R - G
• Check motor for tight shaft
• Perform motor/control replacement check
Perform Moisture Check
• Motor rocks, • Check for loose or compliant motor mount but won’t start
• Perform motor/control replacement check
Motor oscillates up • It is normal for motor to oscillate with no load & down while being on shaft
tested off of blower
Motor starts, but runs erratically
• Varies up and down • Check line voltage for variation or “sag”
or intermittent • Check low voltage connections (G, Y, W, R, C) at motor, unseated pins in motor harness connectors
• Check “Bk” for erratic CFM command (in
variable-speed applications)
• Check out system controls, Thermostat
Perform Moisture Check
• “Hunts” or “puffs” at • Does removing panel or lter reduce
high CFM (speed) “pufng”?
- Reduce restriction
- Reduce max airow
• Stays at low CFM • Check low voltage (Thermostat) wires and
despite system call connections for cool or heat CFM • Verify fan is not in delay mode; wait until delay complete
• “R” missing/not connected at motor
• Perform motor/control replacement check
• Stays at high CFM • “R” missing/not connected at motor
• Is fan in delay mode? - wait until delay time
complete
• Perform motor/control replacement check
• Blower won’t shut off
Check for Triac switched thermostat or solid­ state relay
Excessive noise • Determine if it’s air noise, cabinet, duct or motor noise; interview customer, if necessary
• Air noise • High static creating high blower speed?
- Is airow set properly?
- Does removing lter cause blower to slow
down? Check lter
- Use low-pressure drop lter
- Check/correct duct restrictions
• Check power at motor
• Make sure blower wheel is tight on shaft
Current leakage from controls into G, Y or W?
Symptom Cause/Procedure
• Noisy blower or cabinetCheck for loose blower housing, panels, etc.
• High static creating high blower speed?
- Check for air whistling through seams in ducts, cabinets or panels
- Check for cabinet/duct deformation
• “Hunts” or “puffs” atDoes removing panel or lter reduce high CFM (speed)
- Reduce restriction
- Reduce max. airow
Evidence of Moisture
• Motor failure or • Replace motor and malfunction has occurred and moisture is present
• Evidence of moisture
present inside air mover
“pufng”?
Perform Moisture Check
Perform Moisture Check
Do Don’t
• Check out motor, controls, • Automatically assume the motor is bad.
wiring and connections thoroughly before replacing motor
• Orient connectors down so • Locate connectors above 7 and 4 o’clock
water can’t get in positions
- Install “drip loops”
• Use authorized motor and • Replace one motor or control model # with
model #’s for replacement another (unless an authorized replacement)
• Keep static pressure to a • Use high pressure drop lters some have
minimum: H20 drop!
- Recommend high • Use restricted returns
efciency, low static lters
- Recommend keeping lters
clean.
- Design ductwork for min.
static, max. comfort
- Look for and recommend
ductwork improvement, where necessary
• Size the equipment wisely • Oversize system, then compensate with low
airow
• Check orientation before • Plug in power connector backwards
inserting motor connectors • Force plugs
½"
Moisture Check
• Connectors are oriented “down” (or as recommended by equipment
manufacturer)
• Arrange harness with “drip loop” under motor
• Is condensate drain plugged?
• Check for low airow (too much latent capacity)
• Check for undercharged condition
• Check and plug leaks in return ducts, cabinet
Comfort Check
• Check proper airow settings
• Low static pressure for lowest noise
• Set low continuous-fan CFM
• Use humidistat and 2-speed cooling units
• Use zoning controls designed for ECM that regulate CFM
• Thermostat in bad location?
Manual 2100-527H Page 28 of 29
Page 29
TROUBLESHOOTING GE ECM
MOTORS CONT’D.
Replacing ECM Control Module
To replace the control module for the GE variable-speed indoor blower motor you need to take the following steps:
1. You MUST have the correct replacement module. The controls are
factory programmed for specic operating modes. Even though they look
alike, different modules may have completely different functionality.
USING THE WRONG CONTROL MODULE VOIDS ALL PRODUCT WARRANTIES AND MAY PRODUCE UNEXPECTED RESULTS.
2. Begin by removing AC power from the furnace or air handler being serviced. DO NOT WORK ON THE MOTOR WITH AC POWER APPLIED. To avoid electric shock from the motor’s capacitors, disconnect
power and wait at least 5 minutes before opening motor.
3. It is usually not necessary to remove the motor from the blower assembly. However, it is recommended that the whole blower assembly, with the motor, be removed from the furnace/air handler. (Follow the manufacturer’s procedures). Unplug the two cable connectors to the motor. There are latches on each connector. DO NOT PULL ON THE WIRES. The plugs remove easily when properly released.
4. Locate the two standard housing (at the back end of the control opposite the shaft end). Refer to Figure 14. Remove these two bolts from the motor and control assembly while holding the motor in a way that will prevent the motor or control from falling when the bolts are removed. If an ECM2.0 control is being replaced (recognized by an aluminum casting rather that a deep-drawn black steel can housing the electronics), remove only the hex-head bolts.
DO NOT REMOVE THE TORX-HEAD SCREWS.
5. The control module is now free of mechanical attachment to the motor endshield but is still connected by a plug and three wires inside the control. Carefully rotate the control to gain access to the plug at
the control end of the wires. With thumb and forenger, reach the latch
holding the plug to the control and release it by squeezing the latch tab and the opposite side of the connector plug and gently pulling the plug out of the connector socket in the control. DO NOT PULL ON THE
WIRES. GRIP THE PLUG ONLY.
6. The control module is now completely detached from the motor. Verify with a standard ohmmeter that the resistance from each motor lead (in the motor plug just removed) to the motor shell is >100K ohms. Refer to Figure 15. (Measure to unpainted motor end plate.) If any motor lead fails this test, do not proceed to install the control module. THE MOTOR IS DEFECTIVE AND MUST BE REPLACED. Installing the new control module will cause it to fail also.
7. Verify that the replacement control is correct for your application. Refer to the manufacturer's authorized replacement list. USING THE
WRONG CONTROL WILL RESULT IN IMPROPER OR NO BLOWER OPERATION. Orient the control module so that the 3-wire
motor plug can be inserted into the socket in the control. Carefully insert the plug and press it into the socket until it latches. A SLIGHT CLICK WILL BE HEARD WHEN PROPERLY INSERTED. the replacement control per one of the three following paragraphs, 8a, 8b or 8c.
8a. IF REPLACING AN ECM 2.0 CONTROL (control in cast aluminum can with air vents on the back of the can) WITH AN ECM
2.3 CONTROL (control containing black potting for water protection in black deep-drawn steel case with no vents in the bottom of the can), locate the two through-bolts and plastic tab that are packed with the replacement control. Insert the plastic tab into the slot at the perimeter of the open end of the can so that the pin is located on the inside of the perimeter of the can. Rotate the can so that the tab inserts into the tab locater hole in the endshield of the motor. Using the two through-bolts provided with the replacement control, reattach the can to the motor.
THE TWO THROUGH-BOLTS PROVIDED WITH THE REPLACEMENT ECM 2.3 CONTROL ARE SHORTER THAN THE BOLTS ORIGINALLY REMOVED FROM THE ECM 2.0 CONTROL AND MUST BE USED IF SECURE ATTACHMENT OF THE CONTROL TO THE MOTOR IS TO BE ACHIEVED.
DO NOT OVERTIGHTEN THE BOLTS.
¼" hex head bolts at the rear of the control
Finish installing
8b. IF REPLACING AN ECM 2.3 CONTROL WITH AN ECM 2.3 CONTROL, the plastic tab and shorter through-bolts are not needed. The control can be oriented in two positions 180° apart. MAKE SURE THE
ORIENTATION YOU SELECT FOR REPLACING THE CONTROL ASSURES THE CONTROL'S CABLE CONNECTORS WILL BE LOCATED DOWNWARD IN THE APPLICATION SO THAT WATER CANNOT RUN DOWN THE CABLES AND INTO THE CONTROL. Simply orient the new control to the motor's endshield, insert
bolts, and tighten. DO NOT OVERTIGHTEN THE BOLTS.
8c. IF REPLACING AN ECM 2.0 CONTROL WITH AN ECM 2.0
CONTROL (It is recommended that ECM 2.3 controls be used for all replacements), the new control must be attached to the motor using through
bolts identical to those removed with the original control. DO NOT OVERTIGHTEN THE BOLTS.
9. Reinstall the blower/motor assembly into the HVAC equipment. Follow the manufacturer's suggested procedures.
10. Plug the 16-pin control plug into the motor. The plug is keyed. Make sure the connector is properly seated and latched.
11. Plug the 5-pin power connector into the motor. Even though the plug is keyed, OBSERVE THE PROPER ORIENTATION. DO NOT FORCE THE CONNECTOR. It plugs in very easily when properly oriented. REVERSING THIS PLUG WILL CAUSE IMMEDIATE
FAILURE OF THE CONTROL MODULE.
Final installation check. Make sure the motor is installed as follows:
12. a. Unit is as far INTO the blower housing as possible. b. Belly bands are not on the control module or covering vent holes. c. Motor connectors should be oriented between the 4 o’clock and 8
o’clock positions when the blower is positioned in its nal
location and orientation. d. Add a drip loop to the cables so that water cannot enter the motor by draining down the cables. Refer to Figure 16.
The installation is now complete. Reapply the AC power to the HVAC equipment and verify that the new motor control module is working properly. Follow the manufacturer's procedures for disposition of the old control module.
Figure 14
Figure 15
Figure 16
Manual 2100-527H Page 29 of 29
Loading...