Bard QW5S1, QW2S1, QW4S1, QW3S1 User Manual

INSTALLATION
MIS-2736
INSTRUCTIONS
QW SERIES GEOTHERMAL R-410A STAGED CAPACITY PACKAGED HEAT PUMP
QW2S1 QW3S1 QW4S1 QW5S1
Earth Loop Fluid
Temperatures 25 – 110
Ground Water Temperature 45 – 75
Bard Manufacturing Company, Inc. Bryan, Ohio 43506
Since 1914...Moving ahead, just as planned.
Manual No.: 2100-532B Supersedes: 2100-532A File: Vol II Tab 14 Date: 07-19-10
Manual 2100-532B Page 1 of 46
CONTENTS
Getting Other Information and Publications
For more information, contact these publishers:...... 4
QW General Information
QW Model Nomenclature ........................................ 5
Shipping Damage .................................................... 7
Unit Removal From Skid .......................................... 7
Handling Unit After Removal From Skid .................. 7
Removal of Wall Bracket from Shipping Location ... 8
General .................................................................... 8
Minimum Installation Height..................................... 8
Duct Work ............................................................... 11
Filters ...................................................................... 11
Condensate Drain ........................................... 11 – 13
Mist Eliminator Service .................................. 13 & 14
Installation Instructions
Mounting the Unit .................................................. 15
Wiring – Main Power ............................................. 18
Wiring – Low Voltage Wiring ................................. 18
General .................................................................. 18
Low Voltage Connections ...................................... 19
Start Up
Description of Standard Equipment ....................... 23
Compressor Control Module .................................. 23
Adjustments ........................................................... 23
Optional CFM ........................................................ 24
Important Installer Note ......................................... 24
Phase Monitor ....................................................... 24
Service Hints ......................................................... 24
Sequence of Operation .................................. 24 & 25
Pressure Service Ports .......................................... 25
Pressure Tables ..................................................... 28
Optional Accessories ............................................. 29
Closed Loop (Earth Coupled Ground Loop Applications)
Circulation System Design .................................... 30
Copper Water Coil Application ............................... 30
Start Up Procedure for Closed Loop System ......... 31
Open Loop (Well System Applications)
Water Connections ................................................ 33
Well Pump Sizing .................................................. 34
Start Up Procedure for Open Loop System ... 34 & 35
Water Corrosion .................................................... 35
Remedies of Water Problems................................ 35
Lake and Pond Installations .................................. 36
Cooling Tower / Boiler Application ......................... 38
Service
Unbrazing System Components ............................ 41
Troubleshooting GE ECM™ Blower Motors ... 42-43
Quick Reference Troubleshooting Chart for
Water to Air Heat Pump .......................................... 44
Ground Source Heat Pump
Performance Report .......................................... 45-46
Manual 2100-532B Page 2 of 46
CONTENTS
Figures
Figure 1 Unit Dimensions ..................................... 6
Figure 2 Removal of Unit From Skid .................... 7
Figure 3 Proper Handling of Unit After Removal
from Skid ................................................ 8
Figure 4 Installation of Unit w/Wall Sleeve .......... 9
Figure 5 Installation With Free Blow Plenum ..... 10
Figure 6 Ducted Application ............................... 10
Figure 7 Supply Duct Connections ..................... 11
Figure 8A Condensate Drain ................................ 12
Figure 8B Optional Rear Drain ............................. 12
Figure 8C Rear Drain (Top View).......................... 13
Figure 9 Removal of Q-T Figure 10 Remove Locking Screws from Wheels 15
Figure 11 Unit Mounting Without Wall Sleeve ..... 16
Figure 12 Component Location ............................ 17
Figure 13 Low Voltage Wire Harness Plug .......... 19
Figure 14 Remote Thermostat Wiring "X" Option 20 Figure 15 Remote Thermostat Wiring "D" Option 21 Figure 16 Remote Thermostat Wiring "H" Option 22 Figure 17 Fluid Connections w/Ventilation
Wall Sleeve .......................................... 26
Figure 18 Fluid Connections w/o Ventilation
Wall Sleeve .......................................... 27
Figure 19 Circulation System ............................... 30
Figure 20 Water Temperature and Pressure
Test Procedure .................................. 31
Figure 21 Performance Model WGPM-1C ........... 32
Figure 22 Performance Model WGPM-2C ........... 32
Figure 23 Piping Diagram .................................... 33
Figure 24 Cleaning Water Coil ............................. 36
Figure 25 Water Well System .............................. 37
Figure 26 Water Source H/P Cooling Cycle......... 39
Figure 27 Water Source H/P Heating Cycle ........ 40
Figure 28 Control Disassembly ............................ 43
Figure 29 Winding Test ........................................ 43
Figure 30 Drip Loop ............................................. 43
EC ERV ........................ 14
Tables
Table 1 Electrical Specifications ........................... 5
Table 2 Operating Voltage Range ....................... 18
Table 3 Wall Thermostats ................................... 18
Table 4 Indoor Blower Performance ................... 25
Table 5 Pressures ............................................... 28
Table 6 Optional Accessories ............................. 29
Table 7 Constant Flow Valves ............................. 33
Table 8 Water Flow and Pressure Drop .............. 38
Manual 2100-532B Page 3 of 46
GETTING OTHER INFORMATION AND PUBLICATIONS
These publications can help you install the air conditioner or heat pump. You can usually find these at your local library or purchase them directly from the publisher. Be sure to consult current edition of each standard.
National Electrical Code ...................... ANSI/NFPA 70
Standard for the Installation .............. ANSI/NFPA 90A
of Air Conditioning and Ventilating Systems
Standard for Warm Air ...................... ANSI/NFPA 90B
Heating and Air Conditioning Systems
Load Calculation for Residential ....... ACCA Manual J
Winter and Summer Air Conditioning
Duct Design for Residential ............. ACCA Manual D
Winter and Summer Air Conditioning and Equipment Selection
Closed-Loop/Ground Source Heat Pump ........ IGSHPA
Systems Installation Guide
Grouting Procedures for Ground-Source ......... IGSHPA
Heat Pump Systems
Soil and Rock Classification for the Design .... IGSHPA
of Ground-Coupled Heat Pump Systems
FOR MORE INFORMATION, CONTACT THESE PUBLISHERS:
ACCA Air Conditioning Contractors of America
1712 New Hampshire Avenue Washington, DC 20009 Telephone: (202) 483-9370 Fax: (202) 234-4721
ANSI American National Standards Institute
11 West Street, 13th Floor New York, NY 10036 Telephone: (212) 642-4900 Fax: (212) 302-1286
ASHRAE American Society of Heating Refrigerating,
and Air Conditioning Engineers, Inc.
1791 Tullie Circle, N.E. Atlanta, GA 30329-2305 Telephone: (404) 636-8400 Fax: (404) 321-5478
NFPA National Fire Protection Association
Batterymarch Park P.O. Box 9101 Quincy, MA 02269-9901 Telephone: (800) 344-3555 Fax: (617) 984-7057
Ground Source Installation Standards ............. IGSHPA
Closed-Loop Geothermal Systems – Slinky .... IGSHPA
Installation Guide
Manual 2100-532B Page 4 of 46
IGSHPA International Ground Source
Heat Pump Association
490 Cordell South Stillwater, OK 74078-8018
QW SERIES GEOTHERMAL R-410A STAGED CAPACITY GENERAL INFORMATION
QW MODEL NOMENCLATURE
QW 3 S 1 A 0Z B X 4 X C X
MODEL NUMBER |
Q-Tec™ Model
CAPACITY |
2 - 2 Ton 3 - 3 Ton 4 - 4 Ton 5 - 5 Ton
STEP CAPACITY |
SPECIALTY PRODUCTS
VOLTS & PHASE
A - 230/208/60/1
REVISION |
VENTILATION OPTIONS
B - Blank-off Plate V - Commercial Room Ventilator w/Multi-Position Control.
Can also be modulating with CO2 control.
R - Energy Recovery Ventilator w/Independent Intake/Exhaust
Control.
B - 230/208/60/3 C - 460/60/3
KW
0Z - OKW
TABLE 1
ELECTRICAL SPECIFICATIONS
FILTER OPTIONS
X - 2-Inch Pleated (MERV6)
COLOR
4 - Buckeye Gray paint X - Beige paint V - Platinum w/Slate Front (Vinyl)
CLIMATE CONTROL
Standard ­ X - None D - Electronic/Prog/Man/Auto H - Electronic/Prog with CO
COIL OPTIONS
C - Copper (water) N - Cupronickel
INTERNAL CONTROLS
X
• High Pressure Switch
• Low Pressure Switch
• Compressor Control Module w/Time Delay
• Phase Monitor (3-PH)
control
2
TIUCRICELGNIS
2
1
1
MUMIXAM
LANRETXE
DETAR
zH,STLOV
LEDOM
Z0A-1S2WQ Z0B-1S2WQ Z0C-1S2WQ
Z0A-1S3WQ Z0B-1S3WQ Z0C-1S3WQ
Z0A-1S4WQ Z0B-1S4WQ Z0C-1S4WQ
Z0A-1S5WQ Z0B-1S5WQ Z0C-1S5WQ
1 Maximum size of the time delay fuse or HACR type circuit breaker for protection of field wiring conductors. 2 These “Minimum Circuit Ampacity” values are to be used for sizing the field power conductors. Refer to the National Electric
Code (latest revision), article 310 for power conductor sizing.
CAUTION: When more than one field power conductor circuit is run through one conduit, the conductors must be derated.
Pay special attention to Note 8 of Table 310 regarding Ampacity Adjustment Factors when more than three conductors are in a raceway.
ESAHP&
1-06-802/032
3-06-802/032
3-06-064
1-06-802/032
3-06-802/032
3-06-064
1-06-802/032
3-06-802/032
3-06-064
1-06-802/032
3-06-802/032
3-06-064
DLEIF.ON
REWOP
STIUCRIC
1 1 1
1 1 1
1 1 1
1 1 1
MUMINIM TIUCRIC
YTICAPMA
91 41
7
62 02
9
13 72 11
93 92 71
ROESUF
TIUCRIC
REKAERB
03 02 51
04 03 51
05 04 02
06 54 52
Manual 2100-532B Page 5 of 46
VENT
EXHAUST
VENT
INTAKE
5 1/4"
5 15/16"
33 9/16"
20"
MIS-2737 B
UNIT DIM. "A" DIM. "B" DIM. "C" DIM. "D"
QW2S, QW3S 8 5/8" 42" 30" 43"
QW4S, QW5S 8 3/4" 48" 40" 49"
FIGURE 1
ELECTRICAL ENTRANCE
UNIT DIMENSIONS
(OPTIONAL) HIGH VOLTAGE
2 15/16"
(OPTIONAL) LOW VOLTAGE
ELECTRICAL ENTRANCE
LOW VOLTAGE
ELECTRICAL ENTRANCE
ELECTRICAL ENTRANCE
(OPTIONAL) LOW VOLTAGE
6 3/4"
3 3/16"
7/8"
1 15/16"
3 3/8"
(OPTIONAL) HIGH VOLTAGE
ELECTRICAL ENTRANCE
3 3/8"
3 3/4"
(OPTIONAL)
PLENUM BOX
FREEBLOW
1 1/8"
1 11/16"
11 3/4"
CIRCUIT BREAKER
3 1/16"
(OPTIONAL) HIGH
ACCESS AND LOCKING
COVER
ACCESS
VOLTAGE
ENTRANCE
ELECTRICAL
GRILLE
RETURN AIR
FOR FLUID
CONNECTION FOR
DORFC PUMP
15 5/8"
8"
3"
6 7/8"
APPLICATION
68 3/4"
36 7/8"
19"
FLUID CONNECTION
POINTS FOR FACTORY
BACK VIEW
INSTALLED PUMP OPTIONS
3, 4, OR 5 (INLET ON LEFT,
OUTLET ON RIGHT AS VIEWED
FROM BACK OF UNIT)
RIGHT SIDE VIEW
1 3/4"
2 1/16"
2 7/16"
SUPPLY AIR OPENING
Manual 2100-532B Page 6 of 46
9 15/16"
(DUCT SIZE)
20 3/8"
"A"
24 15/16"
(DUCT SIZE)
TOP VIEW
(SHOWN WITHOUT
FREEBLOW PLENUM)
"B"
"C"
GRILLE
SUPPLY AIR
14"
THERMOSTAT
(OPTIONAL)
16 5/8"
FILTER
(OPTIONAL)
ACCESS
CO2 SENSOR
37 1/8"
104"
DOOR
"C"
"D"
FRONT VIEW
DOOR
CONDENSER
36 1/16"
SHIPPING DAMAGE
Upon receipt of equipment, the carton should be checked for external signs of shipping damage. The skid must remain attached to the unit until the unit is ready for installation. If damage is found, the receiving party must contact the last carrier immediately, preferably in writing, requesting inspection by the carrier’s agent.
UNIT REMOVAL FROM SKID
WARNING
HANDLING UNIT AFTER REMOVAL FROM SKID
WARNING
Exercise extreme caution when pushing the unit on the rollers. Handle and push from the lower 1/3 of the unit. Insure that debris is not on the floor where the unit is to be moved on the rollers. Failure to do so could result in the unit tipping over and causing bodily injury and/or damage to the unit.
This unit is heavy and requires more than one person to handle and remove from the skid. Check unit wheels to ensure that wheels are locked before removing from skid. Extreme caution must be taken to prevent injury to personnel and damage to the unit.
It is recommended that the unit not be removed from the skid with a forklift.
The shipping brackets on each side of the unit must be removed and discarded. See Figure 2-A. The return air grille panel can be removed to provide a place to hold the unit. The unit can be slid forward on the skid until the front wheels hang over the edge of the skid. See Figure 2-B. The unit can be tipped forward and slid down the edge of the skid until the front wheels touch the ground. See Figure 2-C. The wheels will not roll. They are shipped from the factory locked so they will not roll. The back of the skid will have to be held down to keep it from tipping up. The skid can be slid out from under the unit. The unit can then be set upright.
REMOVAL OF UNIT FROM SKID
The unit will have to be turned sideways and removed from the skid to fit through a 36" doorway. If the door height allows, the unit can be slid sideways through the door.
If the unit can not be slid through the door, then the unit will have to be put on a cart and tipped down to roll through the door. It is recommended that an appliance cart be used with a strap to hold the unit on the cart. The wheels of the unit must be locked. If the wheels were allowed to roll, the unit could roll off the cart. The unit should always be carted from the left side. This is the side where the compressor is located. See Figure 3. The blade of the appliance cart should be slid under the wheels of the unit. The strap of the appliance cart should be placed around the unit and strapped tightly. Help will be required to tip the unit back onto the cart. The unit can be leaned far enough back to be rolled through the door. Be careful when setting the unit back up to keep from damaging the unit.
FIGURE 2
A SHIPPING BRACKETS
HOLD SKID DOWN
B FRONT WHEELS OVER EDGE C FRONT WHEELS ON FLOOR
Manual 2100-532B Page 7 of 46
FIGURE 3
PROPER HANDLING OF UNIT
AFTER REMOVAL FROM SKID
Q-Tec UNIT (RIGHT SIDE)
APPLIANCE CART
COMPRESSOR
REMOVAL OF WALL BRACKET FROM SHIPPING LOCATION (UNITS WITH BLANK OFF PLATE ONLY)
The wall brackets are attached to the back of the unit. Remove and retain the wall brackets for use when attaching the unit to the wall. In units equipped with a ventilator a wall sleeve is required and these two wall brackets are not included. A different style bracket is supplied with the sleeve assembly.
GENERAL
The equipment covered in this manual is to be installed by trained, experienced service and installation technicians.
The unit is designed for use with or without duct work. For use without duct work, Plenum Box QPB** is recommended.
These instructions explain the recommended method to install the water source self-contained unit and the electrical wiring connections to the unit.
These instructions and any instructions packaged with any separate equipment required to make up the entire air conditioning system should be carefully read before beginning the installation. Note particularly “Start Procedure” and any tags and/or labels attached to the equipment.
STRAP
While these instructions are intended as a general recommended guide, they do not supersede any national and/or local codes in any way. Authorities having jurisdiction should be consulted before the installation is made. See Page 4 for information on codes and standards.
Size of unit for a proposed installation should be based on heat loss calculation made according to methods of Air Conditioning Contractors of America (ACCA). The air duct should be installed in accordance with the Standards of the National Fire Protection Systems of Other Than Residence Type, NFPA No. 90A, and Residence Type Warm Air Heating and Air Conditioning Systems, NFPA No. 90B. Where local regulations are at a variance with instructions, installer should adhere to local codes.
MINIMUM INSTALLATION HEIGHT
The minimum installation height of the unit with a Free Blow Plenum is 8 ft. 9 in. This provides enough clearance for the plenum to be removed. See Figure 5.
The minimum installation height for ducted applications is 8 ft. 9 in. This provides enough clearance to install the duct work. See Figure 6.
Manual 2100-532B Page 8 of 46
INSTALLATION OF UNIT THROUGH WALL WITH WALL SLEEVE
QW2S, QW3S - 42.000" QW4S, QW5S - 48.000"
SUPPLY AIR
OPTIONAL FREE BLOW PLENUM BOX
HIGH VOLTAGE ELECTRICAL ENTRANCE (TOP-REAR-SIDE)
RETURN AIR
(X)
FIGURE 4
14" to 5"
18 9/16"
WALL SLEEVE
VENTILATION AIR DIVIDER
35"
29 1/2"
33 7/8"
28 7/8"
17 9/16"
6 1/8"
MIST ELIMINATOR
103 7/8"
84 1/4"
BOTTOM TRIM PIECE
5"
33"
LOW VOLTAG E ELECTRICAL ACCESS (TOP-SIDE)
CIRCUIT BREAKER, ROTARY, OR TOGGLE DISCONNECT AND LOCKING COVER
PERMANENT ROLLERS
MIS-2739 A
Manual 2100-532B Page 9 of 46
FIGURE 5
INSTALLATION WITH FREE BLOW PLENUM
8 FT. - 8 IN.
25 IN.
MINIMUM
8 FT. - 9 IN.
MINIMUM REQUIRED
INSTALLATION HEIGHT
FLOOR
FIGURE 6
DUCTED APPLICATION
SUSPENDED CEILING
FIXED CEILING
12 IN.
MINIMUM
MIS-2740
DUCT
DUCT FLANGE
7 FT. - 6 IN.
UNIT HEIGHT
Manual 2100-532B Page 10 of 46
FLOOR
FROM DUCT FLANGE
TO DUCT BOTTOM
9 FT.
MINIMUM REQUIRED
INSTALLATION HEIGHT
2 IN. MINIMUM
8 FT. - 9 IN.
MINIMUM REQUIRED
INSTALLATION HEIGHT
MIS-2741
DUCT WORK
Any heat pump is more critical of proper operating charge and an adequate duct system than a straight air conditioning unit. All duct work must be properly sized for the design airflow requirement of the equipment. Air Conditioning Contractors of America (ACCA) is an excellent guide to proper sizing. All duct work or portions thereof not in the conditioned space should be properly insulated in order to both conserve energy and prevent condensation or moisture damage. When duct runs through unheated spaces, it should be insulated with a minimum of one inch of insulation. Use insulation with a vapor barrier on the outside of the insulation. Flexible joints should be used to connect the duct work to the equipment in order to keep the noise transmission to a minimum.
The Q-Tec Series heat pump has provision to attach a supply air duct to the top of the unit. Duct connection size is 12 inches x 20 inches. The duct work is field supplied and must be attached in a manner to allow for ease of removal when it becomes necessary to slide the unit out from the wall for service. See Figure 7 for suggested attachment method.
NOTE: Unit cabinet, supply air duct and free blow
plenum are approved for “0” clearance to combustible material.
The Q-Tec Series heat pumps are designed for use with free return (non-ducted) and either free blow with the use of QPB Plenum Box or a duct supply air system.
The QPB Plenum Box mounts on top of the unit and has both vertically and horizontally adjustable louvers on the front discharge grille.
FIGURE 7
SUPPLY DUCT CONNECTIONS
SUPPLY DUCT TO BE FIELD SUPPLIED
ATTACHMENT SCREWS TO BE FIELD SUPPLIED
When used with a ducted supply, a QCX Cabinet Extension can be used to conceal the duct work above the unit to the ceiling. This extends 20" above the unit for a total height above the floor of 10'-7/8". The unit is equipped with a variable speed indoor blower motor which increases in speed with an increase in duct static pressure. The unit will therefore deliver proper rated airflow up to the Maximum ESP shown in Table 4. However, for quiet operation of the air system, the duct static should be kept as low as practical, within the guidelines of good duct design.
FILTERS
Two 2-inch pleated filters are supplied with each unit. The filters fit into a fixed rack.
The filters are serviced from the inside of the building . To gain access to the filters release the latch on the circuit breaker door and one 1/4 turn fastener near the bottom of the door. This door is hinged on the left so it will swing open.
The internal filter brackets are adjustable to accommodate 1-inch filters. The tabs for the 1-inch filters must be bent up to allow the 1-inch filters to slide in place.
CONDENSATE DRAIN
The condensate drain hose is routed down from the evaporator drain pan on the right side of the unit into the compressor compartment. There are three locations that the drain can exit the cabinet.
If the drain is to be hard plumbed, there is a 3/4 inch FPT pipe connection located on the cabinet rear panel. In these installations, the drain tube is to be slipped over the pipe connection inside of the cabinet; this is how it is shipped from the factory. (See Figure 8C.)
For a stand pipe type of drain, the drain hose can exit the rear of the cabinet. There is adequate hose length to reach the floor on the right hand side of the unit. (See Figure 8A.)
NOTE: Whichever type of drain connection is used a
“P” trap must be formed. See Figure 8A.
ROOM SIDE OF QW UNIT
MIS-2742
DUCT FLANGE PROVIDED WITH UNIT
Manual 2100-532B Page 11 of 46
FLOOR
FIGURE 8A
CONDENSATE DRAIN
LOOP TO FORM A "P" TRAP
DRAIN HOSE
EXTERNAL DRAIN TUBE
ALTERNATE DRAINING OPTION
FRONT VIEW WITH CONDENSER DOOR REMOVED
MIS-2743
The drain can be routed through the floor or through the wall. If the drain is to be routed through an unconditioned space, it must be protected from freezing. The drain line must be able to be removed from the unit if it is necessary
to remove the unit from the wall.
FIGURE 8B
OPTIONAL REAR DRAIN
Manual 2100-532B Page 12 of 46
The rear drain can be used with wall thickness of up to 10 inches where a water trap can be installed between the unit and the interior wall. See Figure 8B. The trap cannot extend beyond the edge of the unit or it will interfere with the wall mounting bracket. The drain can be routed through the floor or through the wall. If the drain is routed through the wall, the drain line must be positioned such that it will not interfere with the sleeve flange or the grille. See Figure 8C.
If the drain is to be routed through an unconditioned space, it must be protected from freezing.
MIST ELIMINATOR SERVICE (Optional – only used with one of the vent options)
A mist eliminator is supplied with the wall sleeve. The mist eliminator is constructed of aluminum frame and mesh. The mist eliminator is located in the top section of the wall sleeve and can be removed from the inside of the building without removing the unit from the wall. This requires that the ventilation package must be removed.
The steps necessary to remove each of the vent options are listed following.
SLEEVE
WATER TRAP
FIGURE 8C
REAR DRAIN (TOP VIEW)
DRAIN LINE
WALL (MAXIMUM 10” FOR REAR DRAIN)
COUPLINGS NOT SHOWN BUT RECOMMENDED FOR EASE OF REMOVABILITY
FOR SERVICE
WALL BRACKET
UNIT
It is recommended that the mist eliminator be inspected annually and serviced as required. The mist eliminator can be inspected from the outside of the building by looking through the outdoor grille. The mist eliminator can be serviced from the outside. The outdoor grille must be removed to do so.
The mist eliminator can be cleaned by washing with soap and water. The excess water should be shaken off the mist eliminator before it is reinstalled.
COMMERCIAL ROOM VENTILATOR OPTION
Before starting the removal make sure the power has been turned off. The hinged return air grille panel must be opened. The commercial room ventilator (CRV) can be seen after the panel has been removed. The CRV must be removed to gain access to the mist eliminator.
1. The two mounting screws in the front of the CRV must be removed.
2. The power connectors for the CRV (located on the right side of the unit) must be disconnected. Squeeze the tabs on the sides of the connector and pull straight out. Unplug both of the connectors.
3. Slide the CRV straight out of the unit.
The mist eliminator can be seen through the opening in the back of the unit. The mist eliminator must be raised up and the bottom can be pulled toward the front of the unit and removed.
Manual 2100-532B Page 13 of 46
Q-TEC ENERGY RECOVERY VENTILATOR OPTION
Before starting the removal make sure that the power has been turned off. The hinged return air grille panel must be opened. The energy recovery ventilator (QERV) can be seen after the panel is opened. To gain access to the mist eliminator, the QERV must be removed. Refer to Figure 9.
1. The front fill plate of the QERV must be removed. There is one screw on either side of the plate. Remove these screws and remove the plate.
2. On either side of the QERV there are mounting screws that hold the QERV in place. Remove both of these screws.
REMOVAL OF THE Q-TEC ENERGY RECOVERY VENTILATOR
3. Underneath the heat recovery cassette there is a power connector for the lower blower assembly. To disconnect this plug, the tabs on both sides of the plug must be squeezed to release the plug. While squeezing the tabs, pull the plug out of the socket.
4. The QERV is plugged into the unit on the right side of the unit. Both of these plugs must be disconnected to remove the QERV. Squeeze the tabs on the sides of the connector and pull straight out.
5. Slide the QERV assembly straight out of the unit being careful not to let the cassette slide out of the QERV.
The mist eliminator can be seen through the opening in the back of the unit. The mist eliminator must be raised up and the bottom can be pulled toward the front of the unit and removed.
FIGURE 9
Manual 2100-532B Page 14 of 46
MOUNTING SCREWS
POWER CONNECTORS
LOWER BLOWER ASSEMBLY POWER CONNECTOR
FRONT FILL
Loading...
+ 32 hidden pages