Bard QW242D, QW481D, QW601D, QW302D, QW361D Installation Instructions Manual

...
QW SERIES WATER SOURCE
INSTALLATION INSTRUCTIONS
PACKAGED HEAT PUMP
Models:
Earth Loop Fluid
Temperatures 25 – 110
Ground Water Temperature 45 – 75
© Copyright 2003
Bard Manufacturing Company, Inc. Bryan, Ohio 43506
Since 1914...Moving ahead, just as planned.
Manual No.: 2100-418F Supersedes: 2100-418E File: Vol II Tab 14 Date: 06-28-07
Manual 2100-418F Page 1 of 49
CONTENTS
Getting Other Information and Publications
For more information, contact these publishers:...... 4
QW General Information
QW Model Nomenclature ........................................ 5
Shipping Damage .................................................... 7
Unit Removal From Skid .......................................... 7
Handling Unit After Removal From Skid .................. 7
Removal of Wall Bracket from Shipping Location ... 8
General .................................................................... 8
Minimum Installation Height..................................... 8
Duct Work ............................................................... 11
Filters ...................................................................... 11
Condensate Drain ........................................... 11 - 13
Mist Eliminator Service .......................................... 13
Installation Instructions
Mounting the Unit .................................................. 16
Wiring – Main Power ............................................. 19
Wiring – Low Voltage Wiring ................................. 19
General .......................................................... 19 & 20
Low Voltage Connections ...................................... 20
Start Up
Description of Standard Equipment ....................... 24
Compressor Control Module .................................. 24
Adjustments ........................................................... 24
Optional CFM ........................................................ 25
Important Installer Note ......................................... 25
Phase Monitor ....................................................... 25
Service Hints ......................................................... 25
Sequence of Operation .................................. 25 & 26
Optional Climate Controls Sequence of
Operation ....................................................... 26 & 27
Refrigerant Tube Schematic for Reheat Coil ......... 27
Pressure Service Ports .......................................... 27
Pressure Tables .............................................. 32 - 33
Optional Accessories ............................................. 34
Closed Loop (Earth Coupled Ground Loop Applications)
Circulation System Design .................................... 35
Copper Water Coil Application ............................... 35
Start Up Procedure for Closed Loop System ......... 36
Open Loop (Well System Applications)
Water Connections ................................................ 38
Copper Water Coil Limitations ....................... 38 & 39
Well Pump Sizing .................................................. 39
Start Up Procedure for Open Loop System ... 39 & 40
Water Corrosion .................................................... 40
Remedies of Water Problems................................ 40
Lake and Pond Installations .................................. 41
Cooling Tower / Boiler Application ......................... 43
Service
Service Hints ......................................................... 44
Unbrazing System Components ............................ 44
Troubleshooting GE ECM™ Blower Motors . 45 - 46
Quick Reference Troubleshooting Chart for
Water to Air Heat Pump .......................................... 47
Ground Source Heat Pump
Performance Report ........................................ 48 - 49
Manual 2100-418F Page 2 of 49
CONTENTS
Figures
Figure 1 Unit Dimensions ..................................... 6
Figure 2 Removal of Unit From Skid .................... 7
Figure 3 Proper Handling of Unit After Removal
from Skid ................................................ 8
Figure 4 Installation of Unit w/Wall Sleeve .......... 9
Figure 5 Installation With Free Blow Plenum ..... 10
Figure 6 Ducted Application ............................... 10
Figure 7 Supply Duct Connections ..................... 11
Figure 8 Condensate Drain ................................ 12
Figure 8A Side Drain (Side View)......................... 12
Figure 8B Optional Rear Drain ............................. 12
Figure 8C Rear Drain (Top View).......................... 13
Figure 9 Fresh Air Damper Removal.................. 14
Figure 10 Removal of QT Figure 11 Remove Locking Screws from Wheels 16
Figure 12 Unit Mounting Without Wall Sleeve ..... 17
Figure 13 Component Location ............................ 18
Figure 14 Low Voltage Wire Harness Plug .......... 20
Figure 15 Remote Thermostat Wiring "X" Option 21 Figure 16 Remote Thermostat Wiring "E" Option 22 Figure 17 Remote Thermostat Wiring "G" Option 23 Figure 18 Heat Pump Dehumidification Mode
Circuit Diagram .................................... 28
Figure 19 Heap Pump Cooling Mode Circuit
Diagram ............................................... 28
Figure 20 Fluid Connections w/Ventilation
Wall Sleeve .......................................... 30
Figure 21 Fluid Connections w/o Ventilation
Wall Sleeve .......................................... 31
Figure 22 Circulation System ............................... 35
Figure 23 Water Temperature and Pressure
Test Procedure .................................. 36
Figure 24 Performance Model WGPM-1C ........... 37
Figure 25 Performance Model WGPM-2C ........... 37
Figure 26 Piping Diagram .................................... 38
Figure 27 Cleaning Water Coil ............................. 41
Figure 28 Water Well System .............................. 42
Figure 29 Control Disassembly ............................ 46
Figure 30 Winding Test ........................................ 46
Figure 31 Drip Loop ............................................. 46
EC ERV ......................... 15
Tables
Table 1 Electrical Specifications ........................... 5
Table 2 Operating Voltage Range....................... 19
Table 3 Wall Thermostats ................................... 19
Table 4 Indoor Blower Performance ................... 27
Table 5 Dehumidification Relay Logic Board ...... 29
Table 6 Cooling Pressure Table .......................... 32
Table 7 Heating Pressure ................................... 33
Table 8 Optional Accessories ............................. 34
Table 9 Constant Flow Valves ............................. 38
Table 10 Water Flow and Pressure Drop .............. 43
Manual 2100-418F Page 3 of 49
GETTING OTHER INFORMATION AND PUBLICATIONS
These publications can help you install the air conditioner or heat pump. You can usually find these at your local library or purchase them directly from the publisher. Be sure to consult current edition of each standard.
National Electrical Code ...................... ANSI/NFPA 70
Standard for the Installation .............. ANSI/NFPA 90A
of Air Conditioning and Ventilating Systems
Standard for Warm Air ...................... ANSI/NFPA 90B
Heating and Air Conditioning Systems
Load Calculation for Residential ....... ACCA Manual J
Winter and Summer Air Conditioning
Duct Design for Residential ............. ACCA Manual D
Winter and Summer Air Conditioning and Equipment Selection
Closed-Loop/Ground Source Heat Pump ........ IGSHPA
Systems Installation Guide
Grouting Procedures for Ground-Source ......... IGSHPA
Heat Pump Systems
Soil and Rock Classification for the Design .... IGSHPA
of Ground-Coupled Heat Pump Systems
FOR MORE INFORMATION, CONTACT THESE PUBLISHERS:
ACCA Air Conditioning Contractors of America
1712 New Hampshire Avenue Washington, DC 20009 Telephone: (202) 483-9370 Fax: (202) 234-4721
ANSI American National Standards Institute
11 West Street, 13th Floor New York, NY 10036 Telephone: (212) 642-4900 Fax: (212) 302-1286
ASHRAE American Society of Heating Refrigerating,
and Air Conditioning Engineers, Inc.
1791 Tullie Circle, N.E. Atlanta, GA 30329-2305 Telephone: (404) 636-8400 Fax: (404) 321-5478
NFPA National Fire Protection Association
Batterymarch Park P.O. Box 9101 Quincy, MA 02269-9901 Telephone: (800) 344-3555 Fax: (617) 984-7057
Ground Source Installation Standards ............. IGSHPA
Closed-Loop Geothermal Systems – Slinky .... IGSHPA
Installation Guide
Manual 2100-418F Page 4 of 49
IGSHPA International Ground Source
Heat Pump Association
490 Cordell South Stillwater, OK 74078-8018
QW SERIES WATER SOURCE GENERAL INFORMATION
QW MODEL NOMENCLATURE
QW 36 1 D A 0Z B X V X X X
MODEL NUMBER
QTEC Model Water Source Heat Pump
CAPACITY
24 - 2 Ton 30 - 2½ Ton 36 - 3 Ton 42 - 3½ Ton 48 - 4 Ton 60 - 5 Ton
VENTILATION OPTIONS
B - Blank-off Plate X - Barometric Fresh Air Damper (Standard) V-
Commercial Ventilator - Motorized Spring Return w/Exhaust P - Commercial Ventilator - Motorized Power Return w/Exhaust R - Energy Recovery Ventilator w/Exhaust
REVISION
DEHUMIDIFICATION
KW
0Z - None
VOLTS & PHASE
A - 230/208-60-1 B - 230/208-60-3 C - 460-60-3
FILTER OPTIONS
X - 1-Inch Fiberglass
F - 2-Inch Fiberglass P - 2-Inch Pleated
COLOR OPTIONS
V - Platinum w/Slate
4 - Gray (Painted)
(Standard)
TABLE 1
ELECTRICAL SPECIFICATIONS
Front (Vinyl)
CLIMATE CONTROL OPTIONS 1
X - None E - Electronic/Prog/Man/Auto/Humidistat F - Electronic Non-Prog/Man or Auto
C/O/Humidistat/6-hr. timer
G - Electronic Non-Prog/Man or Auto
C/O/Humidistat
TIUCRICELGNIS
INTERNAL CONTROLS
X - Standard
• High Pressure Switch
• Low Pressure Switch
• Compressor Time Delay
COIL OPTIONS
X - Standard Cupronickel
Water Coil
4 - Copper Water Coil
3
1
2
2
MUMIXAM
LANRETXE
DETAR
&STLOV
LEDOM
Z0AD242WQ Z0BD242WQ Z0CD242WQ
Z0AD203WQ Z0BD203WQ Z0CD203WQ
Z0AD163WQ Z0BD163WQ Z0CD163WQ
Z0AD124WQ Z0BD124WQ Z0CD124WQ
Z0AD184WQ Z0BD184WQ Z0CD184WQ
Z0AD106WQ Z0BD106WQ Z0CD106WQ
ESAHP
1-802/032
3-802/032
3-064
1-802/032 3-802/032
3-064
1-802/032 3-802/032
3-064
1-802/032 3-802/032
3-064
1-802/032 3-802/032
3-064
1-802/032 3-802/032
3-064
DLEIF.ON
REWOP
STIUCRIC
1 1 1
1 1 1
1 1 1
1 1 1
1 1 1
1 1 1
MUMINIM TIUCRIC
YTICAPMA
91 41 8
12 61 01
42 91 01
72 02
11
13 42 21
54 43
61
ROESUF
TIUCRIC
REKAERB
52 02 51
03 02 51
53 52 51
04 03 51
54 53 51
06 54 02
DLEIF
REWOP
EZISERIW
01 21 41
01 21 41
01 01 41
8 01 41
8 8 41
8 8 21
DNUORG
EZISERIW
01 21 41
01 21 41
01 01 41
01 01 41
01 01 41
01 01 21
1 Maximum size of the time delay fuse or HACR type circuit breaker for protection of field wiring conductors. 2 Based on 75°C copper wire. All wiring must conform to the National Electrical Code and all local codes. 3 These “Minimum Circuit Ampacity” values are to be used for sizing the field power conductors. Refer to the National Electric
Code (latest revision), article 310 for power conductor sizing.
CAUTION: When more than one field power conductor circuit is run through one conduit, the conductors must be derated.
Pay special attention to Note 8 of Table 310 regarding Ampacity Adjustment Factors when more than three conductors are in a raceway.
Manual 2100-418F Page 5 of 49
FIGURE 1
UNIT DIMENSIONS
Manual 2100-418F Page 6 of 49
SHIPPING DAMAGE
Upon receipt of equipment, the carton should be checked for external signs of shipping damage. The skid must remain attached to the unit until the unit is ready for installation. If damage is found, the receiving party must contact the last carrier immediately, preferably in writing, requesting inspection by the carrier’s agent.
UNIT REMOVAL FROM SKID
WARNING
HANDLING UNIT AFTER REMOVAL FROM SKID
WARNING
Exercise extreme caution when pushing the unit on the rollers. Handle and push from the lower 1/3 of the unit. Insure that debris is not on the floor where the unit is to be moved on the rollers. Failure to do so could result in the unit tipping over and causing bodily injury and/or damage to the unit.
This unit is heavy and requires more than one person to handle and remove from the skid. Check unit wheels to ensure that wheels are locked before removing from skid. Extreme caution must be taken to prevent injury to personnel and damage to the unit.
It is recommended that the unit not be removed from the skid with a forklift.
The shipping brackets on each side of the unit must be removed and discarded. See Figure 2-A on Page 7. The return air grille panel can be removed to provide a place to hold the unit. The unit can be slid forward on the skid until the front wheels hang over the edge of the skid. See Figure 2-B. The unit can be tipped forward and slid down the edge of the skid until the front wheels touch the ground. See Figure 2-C. The wheels will not roll. They are shipped from the factory locked so they will not roll. The back of the skid will have to be held down to keep it from tipping up. The skid can be slid out from under the unit. The unit can then be set upright.
REMOVAL OF UNIT FROM SKID
The unit will have to be turned sideways and removed from the skid to fit through a 36" doorway. If the door height allows, the unit can be slid sideways through the door.
If the unit can not be slid through the door, then the unit will have to be put on a cart and tipped down to roll through the door. It is recommended that an appliance cart by used with a strap to hold the unit on the cart. The wheels of the unit must be locked. If the wheels were allowed to roll, the unit could roll off the cart. The unit should always be carted from the left side. This is the side where the compressor is located. See Figure 3. The blade of the appliance cart should be slid under the wheels of the unit. The strap of the appliance cart should be placed around the unit and strapped tightly. Help will be required to tip the unit back onto the cart. The unit can be leaned far enough back to be rolled through the door. Be careful when setting the unit back up to keep from damaging the unit.
FIGURE 2
A SHIPPING BRACKETS B FRONT WHEELS OVER EDGE C FRONT WHEELS ON FLOOR
HOLD SKID DOWN
Manual 2100-418F Page 7 of 49
APPLIANCE CART
COMPRESSOR
FIGURE 3
PROPER HANDLING OF UNIT
AFTER REMOVAL FROM SKID
QT
EC
UNIT
(RIGHT SIDE)
STRAP
REMOVAL OF WALL BRACKET FROM SHIPPING LOCATION (UNITS WITH BLANK OFF PLATE ONLY)
The wall brackets are attached to the back of the unit. Remove and retain the wall brackets for use when attaching the unit to the wall. In units equipped with a ventilator a wall sleeve is required and these two wall brackets are not included. A different style bracket is supplied with the sleeve assembly.
GENERAL
The equipment covered in this manual is to be installed by trained, experienced service and installation technicians.
The unit is designed for use with or without duct work. For use without duct work, Plenum Box QPB** is recommended.
These instructions explain the recommended method to install the water source self-contained unit and the electrical wiring connections to the unit.
These instructions and any instructions packaged with any separate equipment required to make up the entire air conditioning system should be carefully read before beginning the installation. Note particularly “Start Procedure” and any tags and/or labels attached to the equipment.
While these instructions are intended as a general recommended guide, they do not supersede any national and/or local codes in any way. Authorities having jurisdiction should be consulted before the installation is made. See Page 4 for information on codes and standards.
Size of unit for a proposed installation should be based on heat loss calculation made according to methods of Air Conditioning Contractors of America (ACCA). The air duct should be installed in accordance with the Standards of the National Fire Protection Systems of Other Than Residence Type, NFPA No. 90A, and Residence Type Warm Air Heating and Air Conditioning Systems, NFPA No. 90B. Where local regulations are at a variance with instructions, installer should adhere to local codes.
MINIMUM INSTALLATION HEIGHT
The minimum installation height of the unit with a Free Blow Plenum is 8 ft. 6 in. This provides enough clearance for the plenum to be removed. See Figure 5.
The minimum installation height for ducted applications is 8 ft. 4½ in. This provides enough clearance to install the duct work. See Figure 6.
Manual 2100-418F Page 8 of 49
FIGURE 4
INSTALLATION OF UNIT THROUGH WALL WITH WALL SLEEVE
Manual 2100-418F Page 9 of 49
FIGURE 5
INSTALLATION WITH FREE BLOW PLENUM
CEILING
FIGURE 6
DUCTED APPLICATION
FLOOR
Manual 2100-418F Page 10 of 49
FLOOR
DUCT WORK
Any heat pump is more critical of proper operating charge and an adequate duct system than a straight air conditioning unit. All duct work must be properly sized for the design airflow requirement of the equipment. Air Conditioning Contractors of America (ACCA) is an excellent guide to proper sizing. All duct work or portions thereof not in the conditioned space should be properly insulated in order to both conserve energy and prevent condensation or moisture damage. When duct runs through unheated spaces, it should be insulated with a minimum of one inch of insulation. Use insulation with a vapor barrier on the outside of the insulation. Flexible joints should be used to connect the duct work to the equipment in order to keep the noise transmission to a minimum.
The QTEC series heat pump has provision to attach a supply air duct to the top of the unit. Duct connection size is 12 inches x 20 inches. The duct work is field supplied and must be attached in a manner to allow for ease of removal when it becomes necessary to slide the unit out from the wall for service. See Figure 7 for suggested attachment method.
NOTE: Unit cabinet, supply air duct and free blow
plenum are approved for “0” clearance to combustible material.
EC
The QT
series heat pumps are designed for use with free return (non-ducted) and either free blow with the use of QPB Plenum Box or a duct supply air system.
The QPB Plenum Box mounts on top of the unit and has both vertically and horizontally adjustable louvers on the front discharge grille.
When used with a ducted supply, a QCX Cabinet Extension can be used to conceal the duct work above the unit to the ceiling. This extends 20" above the unit for a total height above the floor of 10'-7/8". The unit is equipped with a variable speed indoor blower motor, which increases in speed with an increase in duct static pressure. The unit will therefore deliver properly rated airflow up to the Maximum ESP shown in Table 4. However, for quiet operation of the air system, the duct static should be kept as low as practical, within the guidelines of good duct design.
FILTERS
Two 1-inch throw away filters are supplied with each unit. The filters fit into a fixed rack.
The filters are serviced from the inside of the building . To gain access to the filters release the latch on the circuit breaker door and one 1/4 turn fastener near the bottom of the door. This door is hinged on the left so it will swing open.
ROOM SIDE OF QW UNIT
FIGURE 7
SUPPLY DUCT CONNECTIONS
SUPPLY DUCT TO BE FIELD SUPPLIED
ATTACHMENT SCREWS TO BE FIELD SUPPLIED
DUCT FLANGE PROVIDED WITH UNIT
The internal filter brackets are adjustable to accommodate 2-inch filters. The tabs for the 1-inch filters must be bent down to allow the 2-inch filters to slide in place.
CONDENSATE DRAIN
The condensate drain hose is routed down from the evaporator drain pan on the right side of the unit into the compressor compartment. There are three locations that the drain can exit the cabinet. For a stand pipe type of drain, the drain hose can exit the rear of the cabinet. There is adequate hose length to reach the floor on the right hand side of the unit.
If the drain is to be hard plumbed, there is a 3/4 inch pipe connection located on the right hand cabinet side near the rear and one on the cabinet rear panel. In these installations the drain tube is to be slipped over the pipe connection inside of the cabinet.
See Figures 8A, 8B and 8C.
NOTE: Whichever type of drain connection is used a
“P” trap must be formed. See Figure 8.
Manual 2100-418F Page 11 of 49
FIGURE 8
CONDENSATE DRAIN
The side drain requires a water trap for proper drainage. See Figure 8A. The drain can be routed through the floor or through the wall.
space, it must be protected from freezing
unit if it is necessary to remove the unit from the wall.
SIDE DRAIN (SIDE VIEW)
QTEC UNIT
FIGURE 8A
If the drain is to be routed through an unconditioned
. The drain line must be able to be removed from the
FIGURE 8B
OPTIONAL REAR DRAIN
Manual 2100-418F Page 12 of 49
The rear drain can be used with wall thickness of up to 10 inches where a water trap can be installed between the unit and the interior wall. See Figure 8B. The trap cannot extend beyond the edge of the unit or it will interfere with the wall mounting bracket. The drain can be routed through the floor or through the wall. If the drain is routed through the wall, the drain line must be positioned such that it will not interfere with the sleeve flange or the grille. See Figure 8C. If the drain is to be
routed through an unconditioned space, it must be protected from freezing.
FIGURE 8C
REAR DRAIN (TOP VIEW)
DRAIN LINE
WALL (MAXIMUM 10" FOR REAR DRAIN)
SLEEVE
WATER TRAP
COUPLINGS NOT SHOWN BUT RECOMMENDED FOR EASE OF REMOVABILITY FOR SERVICE
WALL BRACKET
MIST ELIMINATOR SERVICE (Optional – only used with one of the vent options)
A mist eliminator is supplied with the wall sleeve. The mist eliminator is constructed of aluminum frame and mesh. The mist eliminator is located in the top section of the wall sleeve and can be removed from the inside of the building without removing the unit from the wall. This requires that the ventilation package must be removed.
The steps necessary to remove each of the vent options are listed following.
It is recommended that the mist eliminator be inspected annually and serviced as required. The mist eliminator can be inspected from the outside of the building by looking through the outdoor grille. The mist eliminator can be serviced from the outside. The outdoor grille must be removed to do so.
The mist eliminator can be cleaned by washing with soap and water. The excess water should be shaken off the mist eliminator before it is reinstalled.
BAROMETRIC FRESH AIR DAMPER (Optional)
Before starting to remove make sure the power has been turned off. The hinged return air grille panel must be opened. The fresh air damper assembly can be seen on the back of the unit. Refer to Figure 9.
1. The fresh air damper is attached to the back of the unit with one screw on either side of the assembly. Both of the screws must be removed.
2. Once the mounting screws are removed, tilt the assembly down and lift it out.
The mist eliminator can be seen through the opening. The mist eliminator must be raised up and the bottom can be pulled toward the front of the unit.
UNIT
Manual 2100-418F Page 13 of 49
COMMERCIAL ROOM VENTILATOR OPTION
Before starting the removal make sure the power has been turned off. The hinged return air grille must be opened. The commercial room ventilator (CRV) can be seen after the panel has been removed. The CRV must be removed to gain access to the mist eliminator.
1. The two mounting screws in the front of the CRV must be removed.
FRESH AIR DAMPER REMOVAL
2. The power connectors for the CRV (located on the right side of the unit) must be disconnected. Squeeze the tabs on the sides of the connector and pull straight out. Unplug both of the connectors.
3. Slide the CRV straight out of the unit.
The mist eliminator can be seen through the opening in the back of the unit. The mist eliminator must be raised up and the bottom can be pulled toward the front of the unit and removed.
FIGURE 9
MOUNTING SCREW
Manual 2100-418F Page 14 of 49
QTEC ENERGY RECOVERY VENTILATOR OPTION
Before starting the removal make sure that the power has been turned off. The hinged return air grille panel must be opened. The energy recovery ventilator (QERV) can be seen after the panel is opened. To gain access to the mist eliminator, the QERV must be removed. Refer to Figure 10
1. The front fill plate of the QERV must be removed. There is one screw on either side of the plate. Remove these screws and remove the plate.
2. On either side of the QERV there are mounting screws that hold the QERV in place. Remove both of these screws.
REMOVAL OF THE QTEC ENERGY RECOVERY VENTILATOR
3. Underneath the heat recovery cassette there is a power connector for the lower blower assembly. To disconnect this plug, the tabs on both sides of the plug must be squeezed to release the plug. While squeezing the tabs, pull the plug out of the socket.
4. The QERV is plugged into the unit on the right side of the unit. Both of these plugs must be disconnected to remove the QERV. Squeeze the tabs on the sides of the connector and pull straight out.
5. Slide the QERV assembly straight out of the unit being careful not to let the cassette slide out of the QERV.
The mist eliminator can be seen through the opening in the back of the unit. The mist eliminator must be raised up and the bottom can be pulled toward the front of the unit and removed.
FIGURE 10
MOUNTING SCREWS
POWER CONNECTORS
LOWER BLOWER ASSEMBLY POWER CONNECTOR
FRONT FILL
Manual 2100-418F Page 15 of 49
Loading...
+ 34 hidden pages