The Energy Recovery Ventilator was designed to
provide energy efficient, cost effective ventilation to
meet I. A. Q. (Indoor Air Quality) requirements while
still maintaining good indoor comfort and humidity
control for a variety of applications such as schools,
classrooms, lounges, conference rooms, beauty salons
and others. It provides a constant supply of fresh air
for control of airborne pollutants including CO2,
smoke radon, formaldehyde, excess moisture, virus
and bacteria.
The ventilator incorporates patented rotary heat
exchange state-of-the-art technology to remove both
heat and moisture.
It is designed as a single package which is factory
installed. The package consists of a unique rotary
Energy Recovery Cassette that can be easily removed
for cleaning or maintenance. It has two 15 inch
diameter heat transfer wheels for efficient heat
transfer. The heat transfer wheels use a permanently
bonded dry desiccant coating for total heat recovery.
1. Indoor blower motor must be run when ever the
QERV is run.
2. Select the correct motor speed on the QERV.
Using Table 1 of the QERV Installation Instructions
determine the motor speed needed to get the desired
amount of ventilation air needed. For instance, do
not use the high speed tap on a QERV if only 200
CFM of ventilation air is needed. Use the low
speed tap. Using the high speed tap would serve no
useful purpose and would effect the overall
efficiency of the air conditioning system. System
operation costs would also increase.
3. Run the QERV only during periods when the
conditioned space is occupied. Running the QERV
during unoccupied periods wastes energy, decreases
the expected life of the QERV, and can result in a
large moisture buildup in the structure. The QERV
removes 60 to 70% of the moisture in the incoming
air, not 100% of it. Running the QERV when the
structure is unoccupied allows moisture to build up
in the structure because there is little or no cooling
load. Thus, the air conditioner is not running
enough to remove the excess moisture being
brought in. Use a control system that in some way
can control the system based on occupancy.
Ventilation is accomplished with 2 blower/motor
assemblies each consisting of a drive motor and dual
blowers for maximum ventilation at low sound levels.
Air is exhausted at the same rate that fresh air is
brought into the structure thus not pressuring the
building. The rotating energy wheels provide the heat
transfer effectively during both summer and winter
conditions. Provides required ventilation to meet the
requirements of ASHRAE 62-2001 standard.
NOTE: Operation is not recommended below 5°F
outdoor temperature because freezing of
moisture in the heat transfer wheel can occur.
IMPORTANT
Operating the QERV during unoccupied
periods can result in a build up of moisture in
the classroom.
Manual 2100-310D
Page1
RECOMMENDED CONTROL
SEQUENCES
Several possible control scenarios are listed below:
1. Use a programmable electronic thermostat with
auxiliary terminal to control the QERV based on
daily programmed occupancy periods. Bard
markets and recommends the White-Rodgers
1F94-80 (Bard Part No. 8403-034), programmable
electronic thermostat for heat pump applications.
2. Use a motion sensor in conjunction with a
mechanical thermostat to determine occupancy in
the classroom. Bard markets the CS2000 for this
use.
3. Use a DDC control system to control the QERV
based on a room occupancy schedule to control the
QERV.
4. Tie the operation of the QERV into the light
switch. The lights in a room are usually on only
when occupied.
5. Use a manual timer that the occupants turn to
energize the QERV for a specific number of hours.
6. Use a programmable mechanical timer to energize
the QERV and indoor blower during occupied
periods of the day.
VENTILATION AIR FLOW
The QERV is equipped with a 3 speed motor to
provide the capability of adjusting the ventilation rates
to the requirements of the specific application by
simply changing motor speeds.
TABLE 1
VENTILATION AIR (CFM)
deepShgiH
kcalB(
MFC
054573003
The units are wired from the factory on low speed.
The speed can be changed by switching the toggle
switch on the front of the QERV to the desired speed.
The QERV2-A4B is equipped with independently
controlled 3-speed motor to provide the capability of
adjusting the ventilation rates to the requirements of
the specific application and to be able to provide
positive pressure in the structure. This is
accomplished by setting the intake blower on a higher
speed than the exhaust blower.
The ability to clean exposed surfaces within air
moving systems is an important design consideration
for the maintenance of system performance and air
quality. The need for periodic cleaning will be a
function of operating schedule, climate, and
contaminants in the indoor air being exhausted and in
the outdoor air being supplied to the building. All
components exposed to the airstream, including energy
recovery wheels, may require cleaning in most
applications.
Rotary counterflow heat exchanges (heat wheels) with
laminar airflow are “self-cleaning” with respect to dry
particles. Smaller particles pass through; larger
particles land on the surface and are blow clear as the
flow direction is reversed. For this reason the primary
need for cleaning is to remove films of oil based
aerosols that have condensed on energy transfer
surfaces. Buildup of material over time may
eventually reduce airflow. Most importantly, in the
case of desiccant coated (enthalpy) wheels, such films
can close off micron sized pores at the surface of the
desiccant material, reducing the efficiency with which
the desiccant can adsorb and desorb moisture.
FREQUENCY
In a reasonably clean indoor environment such as a
school, office building, or home, experience shows that
reductions of airflow or loss of sensible (temperature)
effectiveness may not occur for ten or more years.
However, experience also shows that measurable
changes in latent energy (water vapor) transfer can
occur in shorter periods of time in commercial,
institutional and residential applications experiencing
moderate occupant smoking or with cooking facilities.
In applications experiencing unusually high levels of
occupant smoking, such as smoking lounges,
nightclubs, bars and restaurants, washing of energy
transfer surfaces, as frequently as every six months,
may be necessary to maintain latent transfer efficiency.
Similar washing cycles may also be appropriate for
industrial applications involving the ventilation of high
levels of smoke or oil based aerosols such as those
found in welding or machining operations, for
example. In these applications, latent efficiency losses
of as much as 40% or more may develop over a period
of one to three years.
Manual 2100-310D
Page4
CLEANABILITY AND PERFORMANCE
In order to maintain energy recovery ventilation
systems, energy transfer surfaces must be accessible
for washing to remove oils, grease, tars and dirt that
can impede performance or generate odors. Washing
of the desiccant surfaces is required to remove
contaminate buildups that can reduce adsorption of
water molecules. The continued ability of an enthalpy
wheel to transfer latent energy depends upon the
permanence of the bond between the desiccant and the
energy transfer surfaces.
Bard wheels feature silica gel desiccant permanently
bonded to the heat exchange surface without
adhesives; the desiccant will not be lost in the washing
process. Proper cleaning of the Bard energy recovery
wheel will restore latent effectiveness to near original
performance.
MAINTENANCE PROCEDURES
NOTE: Local conditions can vary and affect the
required time between routine maintenance
procedures, therefore all sites (or specific
units at a site) may not have the same schedule
to maintain acceptable performance. The
following timetables are recommended and
can be altered based on local experience.
QUARTERLY MAINTENANCE
6. Use a shop vacuum with brush attachment to clean
both sides of the energy recovery wheels.
7. Reverse shop vacuum to use as a blower and blow
out any residual dry debris from the wheel.
NOTE: Discoloration and staining of the wheel
does not affect its performance. Only
excessive buildup of foreign material needs
to be removed.
8. If any belt chirping or squealing noise is present,
apply a small amount of LPS-1 or equivalent dry
film lubricant to the belt.
ANNUAL MAINTENANCE
1. Inspect and conduct the same procedures as
outlined under Quarterly Maintenance.
2. To maintain peak latent (moisture) removal
capacity, it is recommended that the energy
recovery wheels be sprayed with a diluted nonacid
based evaporator coil cleaner or alkaline detergent
solution such as 409.
NOTE: Do not use acid based cleaners, aromatic
solvents, temperatures in excess of 170°F or
steam. Damage to the wheel may result.
Do not disassemble and immerse the entire
heat wheel in a soaking solution, as bearing
and other damage may result.
1. Inspect mist eliminator/prefilter and clean if
necessary. This filter is located in the wall sleeve
and can be accessed by either removing the
exterior louver grille, the vent package from inside
the unit, or by disconnecting the unit from the wall
brackets, and rolling the unit away from the sleeve
on its integral wheel system. The filter is an
aluminum mesh filter and can be cleaned with
water and any detergent not harmful to aluminum.
2. Inspect the comfort air filter and clean or replace
as necessary. This filter is located behind the
front-hinged service door.
3. Inspect energy recovery ventilator for proper wheel
rotation and dirt buildup. This can be done in
conjunction with Item 2 above. Energize the
energy recovery ventilator after inspecting the filter
and observe for proper rotation and/or dirt buildup.
4. Recommended energy recovery wheel cleaning
procedures follow: Disconnect all power to the
unit. Open the front-hinged service door to the
unit.
5. Remove the front cassette retaining panel from the
front of the QERV. Unplug the amp connectors to
the cassette drive motor. Slide energy recovery
cassette out of the ventilator.
3. Rinse wheel thoroughly after application of the
cleaning solution, and allow to drain before
reinstalling.
4. No re-lubrication is required to heat wheel
bearings of the drive motor, or to the intake and
exhaust blower motors.
5. If any belt chirping or squealing noise is present,
apply a small amount of LPS-1 or equivalent dry
film lubricant to the belt.
Manual 2100-310D
Page5
If belt "squeaks" or "chirps"
lubricate lightly with LPS-1
or equivalent "dry film"
lubricant.
FIGURE 1
BELT REPLACEMENT INSTRUCTIONS
Belt Replacement
Instructions
Route this part of replacement
belt in top groove of pulley.
Route this part of replacement
belt in bottom groove of pulley.
Manual 2100-310D
Page6
MIS-1890
FIGURE 2
HUB ASSEMBLY WITH BALL BEARINGS
Manual 2100-310D
Page7
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.