Bard QC501 User Manual

INSTALLATION INSTRUCTIONS
CHILLED WATER UNIT
Model:
QC501
Bard Manufacturing Company Bryan, Ohio 43506
Since 1914...Moving ahead, just as planned.
MIS-1554
Manual No.: 2100-416C Supersedes: 2100416B File: Vol II Tab 14 Date: 12-22-03
© Copyright 2003
CONTENTS
Getting Other Information and Publications
For more information, contact these publishers: ..... 1
QC General Information
QC Model Nomenclature ......................................... 2
Shipping Damage .................................................... 5
Unit Removal From Skid.......................................... 5
Handling Unit After Removal From Skid .................. 5
Removal of Wall Bracket from Shipping Location ... 6
General.................................................................... 6
Minimum Installation Height .................................... 6
Duct Work................................................................ 9
Filters....................................................................... 9
Condensate Drain.................................................. 10
Mist Eleminator Service ..........................................11
Figures
Figure 1 Unit Dimensions..................................... 4
Figure 2 Removal of Unit From Skid .................... 5
Figure 3 Proper Handling of Unit After Removal
from Skid................................................ 6
Figure 4 Installation of Unit w/Wall Sleeve .......... 7
Figure 5 Installation With Free Blow Plenum....... 8
Figure 6 Ducted Application................................. 8
Figure 7 Supply Duct Connections ...................... 9
Figure 8 Filter Location ........................................ 9
Figure 9A Side Drain (Side View)......................... 10
Figure 9B Optional Rear Drain ............................. 10
Figure 9C Rear Drain (Top View).......................... 10
Figure 10 Fresh Air Damper Removal ................. 12
Figure 11 Removal of QT Figure 12 Remove Locking Screws from Wheels 14
Figure 13 Unit Mounting Without Wall Sleeve ..... 15
Figure 14 Component Location............................ 16
Figure 15 Low Voltage Wire Harness Plug .......... 18
Figure 16 Remote Thermostat Wiring "X" Option 19 Figure 17 Remote Thermostat Wiring "D" Option 20
Figure 18 Internal 2-Way Valve Piping................. 24
Figure 19 Internal 3-Way Valve Piping................. 25
EC ERV......................... 13
Installation Instructions
Mounting the Unit .................................................. 14
Wiring – Main Power ............................................. 17
Wiring – Low Voltage Wiring ................................. 17
General Information ............................................... 17
Fluid Connections.................................................. 17
Low Voltage Connections...................................... 18
Start Up
Optional CFM ........................................................ 21
Important Installer Note ......................................... 21
Service Hints ......................................................... 21
Sequence of Operation.......................................... 21
Troubleshooting ECM Blower Motors ............. 22-23
Tables
Table 1 Factory Built-In Electric Heat ................... 2
Table 2 Electrical Specifications ........................... 2
Table 2A Cooling Performance Chart...................... 3
Table 3 Operating Voltage Range....................... 17
Table 4 Wall Thermostats and Subbase
Combinations ......................................... 17
Table 5 Indoor Blower Performance ................... 21
i
GETTING OTHER INFORMATION AND PUBLICATIONS
These publications can help you install the air conditioner or heat pump. You can usually find these at your local library or purchase them directly from the publisher. Be sure to consult current edition of each standard.
National Electrical Code ......................ANSI/NFPA 70
Standard for the Installation ..............ANSI/NFPA 90A
of Air Conditioning and Ventilating Systems
Standard for Warm Air...................... ANSI/NFPA 90B
Heating and Air Conditioning Systems
Load Calculation for Residential ...... ACCA Manual J
Winter and Summer Air Conditioning
Duct Design for Residential ............. ACCA Manual D
Winter and Summer Air Conditioning and Equipment Selection
Closed-Loop/Ground Source Heat Pump........ IGSHPA
Systems Installation Guide
Grouting Procedures for Ground-Source ........ IGSHPA
Heat Pump Systems
Soil and Rock Classification for the Design ...IGSHPA of Ground-Coupled Heat Pump Systems
Ground Source Installation Standards.............IGSHPA
Closed-Loop Geothermal Systems – Slinky ... IGSHPA Installation Guide
FOR MORE INFORMATION, CONTACT THESE PUBLISHERS:
ACCA Air Conditioning Contractors of America
1712 New Hampshire Avenue Washington, DC 20009 Telephone: (202) 483-9370 Fax: (202) 234-4721
ANSI American National Standards Institute
11 West Street, 13th Floor New York, NY 10036 Telephone: (212) 642-4900 Fax: (212) 302-1286
ASHRAE American Society of Heating Refrigerating,
and Air Conditioning Engineers, Inc.
1791 Tullie Circle, N.E. Atlanta, GA 30329-2305 Telephone: (404) 636-8400 Fax: (404) 321-5478
NFPA National Fire Protection Association
Batterymarch Park P.O. Box 9101 Quincy, MA 02269-9901 Telephone: (800) 344-3555 Fax: (617) 984-7057
IGSHPA International Ground Source
Heat Pump Association
490 Cordell South Stillwater, OK 74078-8018
Manual 2100-416 Page 1
QC SERIES WATER SOURCE GENERAL INFORMATION
QC MODEL NOMENCLATURE
QC 50 1 – A 10 X X X X X X
Model Number
QC - QTec Model
Capacity
50 - 4 ton
NOTE 1: Electric heat available for -A models only
Revision
Volts & Phase
A - 230/208-60-1 K - 115-60-1
FACTORY BUILT-IN ELECTRIC HEAT TABLE
Filter Options
KW
0Z - 0KW 05 - 5 KW 10 - 10KW 15 - 15KW (Note 1)
Ventilation Option
B - Blank Off Plate (no ventilation) X - Barometric Fresh Air Damper (no exhaust) V - Commercial Ventilator (w/Exhaust) P - Commercial Ventilator (w/Exhaust)
Motorized, Power Return
R - Energy Recovery Ventilator (w/Exhaust) - 230/208-60-1 versions only
X - 1 Inch Fiberglass
(Standard) F - 2 Inch Fiberglass P - 2 Inch pleated
Color
V - Platinum w/Slate Front (vinyl) 4 - Gray Paint
TABLE 1
Valve Options
4 - 2-way valve 5 - 3-way valve
Internal Controls
X - None
Climate Control
X - None D - Electronic/prog/man/auto
sledoMA-105CQ
1-V0421-V802
WKHUTBHUTB
0.5083,61092,21
0.01076,23075,42
0.51051,94068,63
TABLE 2
ELECTRICAL SPECIFICATIONS
tiucriCelgniStiucriClauD
3
.oN
detaR
&stloV
sledoM
Z0A-105CQ 50A­01A­51A-
Z0K-105CQ1-511101514141 ––––––––
sesahP
1-802/032
dleiF
rewoP
stiucriC
1 1 1
2ro1
muminiM tiucriC
7
33 85 38
1
yticapmA
51 53 06 09
2
mumixaM
lanretxE
roesuF
tiucriC
rekaerB
41 8 6 4
2
dleiF
rewoP eriW eziS
eriW eziS
41 01 01
8
3
muminiM tiucriC
dnuorG
yticapmA
TKC
A
B
33
05
1
mumixaM
lanretxE
roesuF
tiucriC
rekaerB
TKC
TKC
A
B
04
05
2
dleiF
rewoP
eziSeriW
TKC
TKC
A
B
8
8
2
TKC
TKC
A
– – –
01
dnuorG
eziSeriW
TKC
B
– – –
01
Q R
S
Manual 2100-416 Page 2
Maximum size of the time delay fuse or HACR type circuit breaker for protection of field wiring conductors. Based on 75° C copper wire. All wiring must conform to the National Electrical Code and all local codes. These Minimum Circuit Ampacity values are to be used for sizing the field power conductors. Refer to the National Electric Code (latest revision), article 310 for power conductor sizing. CAUTION: When more than one field
power conductor circuit is run through one conduit, the conductors must be derated. Pay special attention to Note 8 of Table 310 regarding Ampacity Adjustment Factors when more than three conductors are in a raceway.
TABLE 2A
COOLING PERFORMANCE CHART
)0001(yticapaCHUTB)0001(yticapaCHUTB
MPGTWEMFC
6
84.611.113.55.148.627.413.35.7
014.717.117.52.344.728.519.43.11
6
81.516.015.44.834.520.313.35.7
010.611.119.40.040.620.419.43.11
6
89.311.018.33.530.423.113.35.7
017.416.011.49.636.423.219.43.11
6
86.216.90.32.236.226.93.35.7
016.640.013.37.332.325.019.43.11
6
84.712.212.50.646.034.513.35.7
018.818.210.63.949.134.719.43.11
6
82.617.115.47.242.925.313.35.7
014.713.211.56.544.032.519.43.11
6
89.413.116.35.939.726.113.35.7
011.617.111.10.240.920.319.43.11
6
87.318.019.22.635.627.93.35.7
017.412.115.33.835.728.019.43.11
240001
440001
640001
840001
240021
440021
640021
840021
latoTelbisneStnetaLlatoTelbisneStnetaLGISP.dH.tF
1.515.016.45.833.522.319.14.4
9.310.019.38.532.426.119.14.4
8.216.92.30.330.320.019.14.4
6.111.95.23.039.124.89.14.4
9.515.114.41.240.921.319.14.4
8.411.117.33.937.726.119.14.4
6.317.019.24.635.629.99.14.4
5.213.012.26.332.524.89.14.4
lioCretaW
porDerusserP1egatS2dna1egatS
Manual 2100-416 Page 3
Manual 2100-416
Page 4
FIGURE 1
UNIT DIMENSIONS
SHIPPING DAMAGE
Upon receipt of equipment, the carton should be checked for external signs of shipping damage. The skid must remain attached to the unit until the unit is ready for installation. If damage is found, the receiving party must contact the last carrier immediately, preferably in writing, requesting inspection by the carrier’s agent.
UNIT REMOVAL FROM SKID
WARNING
HANDLING UNIT AFTER REMOVAL FROM SKID
W ARNING
Exercise extreme caution when pushing the unit on the rollers. Handle and push from the lower 1/3 of the unit. Insure that debris is not on the floor where the unit is to be moved on the rollers. Failure to do so could result in the unit tipping over and causing bodily injury and/or damage to the unit.
This unit is heavy and requires more than one person to handle and remove from the skid. Check unit wheels to ensure that wheels are locked before removing from skid. Extreme caution must be taken to prevent injury to personnel and damage to the unit.
It is recommended that the unit not be removed from the skid with a fork lift.
The shipping brackets on each side of the unit must be removed and discarded. See Figure 2-A on Page 5. The return air grille panel can be removed to provide a place to hold the unit. The unit can be slid forward on the skid until the front wheels hang over the edge of the skid. See Figure 2-B. The unit can be tipped forward and slid down the edge of the skid until the front wheels touch the ground. See Figure 2-C. The wheels will not roll. They are shipped from the factory locked so they will not roll. The back of the skid will have to be held down to keep it from tipping up. The skid can be slid out from under the unit. The unit can then be set upright.
REMOVAL OF UNIT FROM SKID
The unit will have to be turned sideways and removed from the skid to fit through a 36” doorway. If the door height allows, the unit can be slid sideways through the door.
If the unit can not be slid through the door, then the unit will have to be put on a cart and tipped down to roll through the door. It is recommended that an appliance cart by used with a strap to hold the unit on the cart. The wheels of the unit must be locked. If the wheels were allowed to roll, the unit could roll off the cart. The blade of the appliance cart should be slid under the wheels of the unit. See Figure 3. The strap of the appliance cart should be placed around the unit and strapped tightly. Help will be required to tip the unit back onto the cart. The unit can be leaned far enough back to be rolled through the door. Be careful when setting the unit back up to keep from damaging the unit.
FIGURE 2
MIS-1603
A SHIPPING BRACKETS B FRONT WHEELS OVER EDGE C FRONT WHEELS ON FLOOR
HOLD SKID DOWN
Manual 2100-416 Page 5
APPLIANCE CART
FIGURE 3
PROPER HANDLING OF UNIT
AFTER REMOVAL FROM SKID
QTEC UNIT (RIGHT SIDE)
STRAP
REMOVAL OF WALL BRACKET FROM SHIPPING LOCATION
The wall brackets are attached to the back of the unit. Remove and retain the wall brackets for use when attaching the unit to the wall. In those installations where a wall sleeve is required these two wall brackets are to be discarded. A different style bracket is supplied with the sleeve assembly.
GENERAL
The equipment covered in this manual is to be installed by trained, experienced service and installation technicians.
The unit is designed for use with or without duct work. For use without duct work, Plenum Box QPB** is recommended.
These instructions explain the recommended method to install the water source self-contained unit and the electrical wiring connections to the unit.
These instructions and any instructions packaged with any separate equipment required to make up the entire air conditioning system should be carefully read before beginning the installation. Note particularly “Start Procedure” and any tags and/or labels attached to the equipment.
While these instructions are intended as a general recommended guide, they do not supersede any national and/or local codes in any way. Authorities having jurisdiction should be consulted before the installation is made. See Page 1 for information on codes and standards.
Size of unit for a proposed installation should be based on heat loss calculation made according to methods of Air Conditioning Contractors of America (ACCA). The air duct should be installed in accordance with the Standards of the National Fire Protection Systems of Other Than Residence Type, NFPA No. 90A, and Residence Type Warm Air Heating and Air Conditioning Systems, NFPA No. 90B. Where local regulations are at a variance with instructions, installer should adhere to local codes.
MINIMUM INSTALLATION HEIGHT
The minimum installation height of the unit with a Free Blow Plenum is 8 ft. 6 in. This provides enough clearance for the plenum to be removed. See Figure 5.
The minimum installation height for ducted applications is 8 ft. 4-1/2 in. This provides enough clearance to install the duct work. See Figure 6.
Manual 2100-416 Page 6
FIGURE 4
INSTALLATION OF UNIT THRU WALL WITH WALL SLEEVE
MIS-1564
Manual 2100-416 Page 7
Loading...
+ 18 hidden pages