These publications can help you install the air
conditioner or heat pump. You can usually find these at
your local library or purchase them directly from the
publisher. Be sure to consult current edition of each
standard.
National Electrical Code ..................... ANSI/NFPA 70
Standard for the Installation ............. ANSI/NFPA 90A
of Air Conditioning and
Ventilating Systems
Standard for Warm Air ...................... ANSI/NFPA 90B
Heating and Air
Conditioning Systems
Load Calculation for .......................ACCA Manual J or
Winter and SummerManual N
Air Conditioning
Low Pressure, Low Velocity ........ ACCA Manual D or
Duct System DesignManual Q
Winter and Summer
Air Conditioning
FOR MORE INFORMATION, CONTACT
THESE PUBLISHERS:
ACCAAir Conditioning Contractors of America
1712 New Hampshire Avenue
Washington, DC 20009
Telephone: (202) 483-9370
Fax: (202) 234-4721
ANSIAmerican National Standards Institute
11 West Street, 13th Floor
New York, NY 10036
Telephone: (212) 642-4900
Fax: (212) 302-1286
ASHRAE American Society of Heating, Refrigeration,
Maximum size of the time delay fuse or HACR type circuit breaker for protection of field wiring conductors.
!
Based on 75° C copper wire. All wiring must conform to the National Electrical Code and all local codes.
"
These “Minimum Circuit Ampacity” values are to be used for sizing the field power conductors. Refer to the National
#
Electric Code (latest revision), article 310 for power conductor sizing. CAUTION: When more than one field
power conductor circuit is run through one conduit, the conductors must be derated. Pay special attention to Note
8 of Table 310 regarding Ampacity Adjustment Factors when more than three conductors are in a raceway.
ELECTRICAL SPECIFICATIONS CONTINUED ON PAGE 5 TABLE 2A
Manual 2100-438
Page 4
D51A
D51B
D51C
D51A
D51B
D51C
D51A
D51B
D51C
TABLE 2A
ELECTRICAL SPECIFICATIONS
TIUCRICELGNISTIUCRICLAUD
3
.ON
DETAR
LEDOM
Z0AD124AQ
50AD
01AD
Z0BD124AQ
60BD
90BD
Z0CD124AQ
60CD
90CD
Z0AD184AQ
50AD
01AD
Z0BD184AQ
50BD
01BD
Z0CD184AQ
60CD
90CD
Z0AD106AQ
01AD
Z0BD106AQ
90BD
Z0CD106AQ
90CD
&STLOV
ESAHP
1-802/032
3-802/032
3-064
1-802/032
3-802/032
3-064
1-802/032
3-802/032
3-064
DLEIF
REWOP
STIUCRIC
1
1
1
2RO1
1
1
1
1
1
1
1
1
1
1
1
2RO1
1
1
1
1
1
1
1
1
1
1
2ro1
1
1
1
1
1
1
MUMINIM
TIUCRIC
33
33
85
38
52
62
53
35
31
41
81
72
53
53
85
38
62
62
53
35
41
41
81
72
64
95
48
23
63
55
71
91
82
1
YTICAPMA
05
05
06
09
53
53
53
06
51
51
02
03
05
05
06
09
53
53
04
06
51
51
02
03
06
06
09
54
54
06
02
02
03
2
MUMIXAM
LANRETXE
ROESUF
TIUCRIC
REKAERB
ERIW
EZIS
8
8
6
4
8
8
8
6
41
41
21
01
8
8
6
4
8
8
8
6
21
21
21
01
8
6
4
8
8
6
21
21
01
2
DLEIF
REWOP
ERIW
EZIS
01
01
8
8
01
01
01
01
41
41
21
01
01
01
01
8
01
01
01
01
21
21
21
01
01
01
8
01
01
01
21
21
01
3
MUMINIM
TIUCRIC
DNUORG
YTICAPMA
TKC
A
B
--
--
--
--
--
--
85
52
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
85
52
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
95
52
--
--
--
--
--
--
--
--
--
--
--
--
1
MUMIXAM
ROESUF
TIUCRIC
REKAERB
TKC
TKC
A
B
--
--
--
--
--
--
06
52
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
06
52
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
06
52
--
--
--
--
--
--
--
--
--
--
--
--
2
LANRETXE
TKC
DLEIF
REWOP
EZISERIW
TKC
A
B
--
--
--
--
--
--
6
01
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
8
01
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
8
01
--
--
--
--
--
--
--
--
--
--
--
--
2
DNUORG
EZISERIW
TKC
TKC
A
TKC
B
--
--
--
--
--
--
01
01
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
01
01
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
01
01
--
--
--
--
--
--
--
--
--
--
--
--
Maximum size of the time delay fuse or HACR type circuit breaker for protection of field wiring conductors.
!
Based on 75° C copper wire. All wiring must conform to the National Electrical Code and all local codes.
"
These “Minimum Circuit Ampacity” values are to be used for sizing the field power conductors. Refer to the National
#
Electric Code (latest revision), article 310 for power conductor sizing. CAUTION: When more than one field power
conductor circuit is run through one conduit, the conductors must be derated. Pay special attention to Note 8 of
Table 310 regarding Ampacity Adjustment Factors when more than three conductors are in a raceway.
Manual 2100-438
Page 5
FIGURE 1
UNIT DIMENSIONS
Manual 2100-438
Page 6
SHIPPING DAMAGE
Upon receipt of equipment, the carton should be
checked for external signs of shipping damage. The
skid must remain attached to the unit until the unit is
ready for installation. If damage is found, the receiving
party must contact the last carrier immediately,
preferably in writing, requesting inspection by the
carrier’s agent.
UNIT REMOVAL FROM SKID
WARNING
This unit is heavy and requires more than one
person to handle and remove from the skid.
Check unit wheels to ensure that wheels are
locked before removing from skid. Extreme
caution must be taken to prevent injury to
personnel and damage to the unit.
It is recommended that the unit not be removed from
the skid with a fork lift since the air seal under the unit
could be damaged. See Figure 2.
The shipping brackets on each side of the unit must be
removed and discarded. See Figure 3-A. The return air
grille panel can be removed to provide a place to hold
FIGURE 2
AIR SEAL UNDER QT
Air Seal
the unit. The unit can be slid forward on the skit until
the front wheels hang over the edge of the skid. See
Figure 3-B. The unit can be tipped forward and slid
down the edge of the skid until the front wheels touch
the ground. See Figure 3-C. The wheels will not roll.
They are shipped from the factory locked so they will
not roll. The back of the skid will have to be held down
to keep it from tipping up. The skid can be slid out from
under the unit. The unit can then be set upright.
EC
UNIT
MIS-1008
FIGURE 3
REMOVAL OF UNIT FROM SKID
Hold Skid Down
A Shipping BracketsB Front Wheels Over EdgeC Front Wheels On Floor
MIS-1007
Manual 2100-438
Page 7
HANDLING UNIT AFTER REMOVAL
FROM SKID
WARNING
Exercise extreme caution when pushing the
unit on the rollers. Handle and push from the
lower 1/3 of the unit. Insure that debris is not
on the floor where the unit is to be moved on
the rollers. Failure to do so could result in the
unit tipping over and causing bodily injury and/
or damage to the unit.
The unit will have to be turned sideways and removed
from the skid to fit through a 36” doorway. If the door
height allows, the unit can be slid sideways through the
door.
If the unit can not be slid through the door, then the unit
will have to be put on a cart and tipped down to roll
through the door. It is recommended that an appliance
cart by used with a strap to hold the unit on the cart.
The wheels of the unit must be locked. If the wheels
were allowed to roll, the unit could roll off the cart. Theunit should always be carted from the left side. This is
the side where the compressor is located. See Figure 4.
The blade of the appliance cart should be slid under the
wheels of the unit. The strap of the appliance cart
should be placed around the unit and strapped tightly.
Help will be required to tip the unit back onto the cart.
The unit can be leaned far enough back to be rolled
through the door. Be careful when setting the unit back
up to keep from damaging the unit.
GENERAL
The equipment covered in this manual is to be installed
by trained, experienced service and installation
technicians.
The unit is designed for use with or without duct work.
For use without duct work, Plenum Box QPB42 is
recommended.
These instructions explain the recommended method to
install the air cooled self-contained unit and the
electrical wiring connections to the unit.
APPLIANCE
CART
FIGURE 4
UNIT ON APPLIANCE CART
QTEC UNIT
(Right Side)
STRAP
These instructions and any instructions packaged with
any separate equipment required to make up the entire
air conditioning system should be carefully read before
beginning the installation. Note particularly “Start
Procedure” and any tags and/or labels attached to the
equipment.
While these instructions are intended as a general
recommended guide, they do not supersede any national
and/or local codes in any way. Authorities having
jurisdiction should be consulted before the installation
is made. See Page 1 for information on codes and
standards.
Size of unit for a proposed installation should be based
on heat loss calculation made according to methods of
Air Conditioning Contractors of America (ACCA).
The air duct should be installed in accordance with the
Standards of the National Fire Protection Systems of
Other Than Residence Type, NFPA No. 90A, and
Residence Type Warm Air Heating and Air
Conditioning Systems, NFPA No. 90B. Where local
regulations are at a variance with instructions, installer
should adhere to local codes.
COMPRESSOR
Manual 2100-438
Page 8
MIS-1555
MINIMUM INSTALLATION HEIGHT
The minimum installation height of the unit with a Free
Blow Plenum is 8 ft. 6 in. This provides enough
clearance for the plenum to be removed. See Figure 5.
The minimum installation height for ducted applications
is 8 ft. 4-1/2 in. This provides enough clearance to
install the duct work. See Figure 6.
Loading...
+ 23 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.