Bard QA241D, QA421D, QA301D, QA361D, QA481D Installation Instructions Manual

...
QTEC SERIES
PACKAGED INSTALLATION INSTRUCTIONS
AIR CONDITIONER
Bard Manufacturing Company Bryan, Ohio 43506
Since 1914 . . . Moving ahead, just as planned.
MIS-1554
Manual: 2100-438C Supersedes: 2100-438B File: Vol II Tab 14 Date: 06-02-04
© Copyright 2004
CONTENTS
Getting Other Information and Publications
For more information, contact these publishers: .......... 1
EC General Information
QT
EC Model Nomenclature .......................................... 2
QT
Shipping Damage ......................................................... 7
Unit Removal From Skid .............................................. 7
Handling Unit After Removal From Skid....................... 8
General ......................................................................... 8
Minimum Installation Height ......................................... 8
Duct Work .................................................................. 10
Filters .......................................................................... 10
Fresh Air Intake .......................................................... 11
Condensate Drain ...................................................... 11
Separate Evaporator Drain Connection ..................... 11
Service Light ............................................................... 12
Installation Instructions
Mounting the Unit ....................................................... 13
Wiring — Main Power ................................................. 14
Wiring — Low Voltage Wiring..................................... 14
Low Voltage Connections........................................... 15
General ....................................................................... 15
Start Up
Description of Standard Equipment ............................... 20
Optional CFM (QA361, QA421, QA481
and QA601 Only) ........................................................... 20
Important Installer Note.................................................. 20
Phase Monitor ................................................................ 20
Three Phase Scroll Compressor Start Up
Information ................................................................ 20
Compressor Control Module .......................................... 21
Adjustments ................................................................... 21
Service Hints .................................................................. 21
Mist Eliminator Service .................................................. 22
Vent Options .................................................................. 22
Sequence of Operation .................................................. 26
CRV / QERV Operation.................................................. 26
Optional Climate Controls Sequence
of Operation .............................................................. 26
Pressure Service Ports .................................................. 26
Troubleshooting
Troubleshooting Table .................................................... 29
Fan Blade Setting Dimensions ...................................... 30
Refrigerant Charge ........................................................ 30
Pressure Chart ............................................................... 31
Figures
Figure 1 Unit Dimensions .......................................... 6
Figure 2 Air Seal on Bottom of Unit ........................... 7
Figure 3 Removal of Unit From Skid ......................... 7
Figure 4 Unit on Appliance Cart for Moving ............... 8
Figure 5 Installation With Free Blow Plenum ............ 9
Figure 6 Ducted Application ....................................... 9
Figure 7 Supply Duct Connections .......................... 10
Figure 8 Filter Location ............................................ 10
Figure 9 Side Drain .................................................. 11
Figure 10 Optional Rear Drain ................................... 11
Figure 11 Rear Drain (Top View) ............................... 12
Figure 12 Unit Mounting ............................................ 12
Figure 13 Screws in Wheels of Unit .......................... 13
Figure 14 Component Location ................................. 14
Figure 15 Thermostat Plug Terminals ........................ 16
Figure 16 Thermostat Wiring Diagram "X" Option .... 17
Figure 17 Thermostat Wiring Diagram "G" Option ... 18
Figure 18 Thermostat Wiring Diagram "E" Option .... 19
Figure 19 Fresh Air Damper Removal ....................... 24
Figure 20 QERV Removal ......................................... 25
Figure 21 Air Conditioning Mode Circuit Diagram ..... 27
Figure 22 Dehumidification Mode Circuit Diagram .... 27
Figure 23 Fan Blade Setting ...................................... 30
Tables
Table 1 Factory Built-In Electric Heat Table .............. 3
Table 2 Electrical Specifications ................................ 4
Table 2A Electrical Specifications ................................ 5
Table 3 Operating Voltage Range ........................... 14
Table 4 Wall Thermostats and Subbase
Combinations .............................................. 16
Table 5 Troubleshooting .......................................... 29
Table 6 Fan Blade Dimensions ............................... 30
Table 7 Super Heat at Compressor ......................... 30
Table 8 Indoor Blower Performance ........................ 30
Table 9 Cooling Pressure ........................................ 31
i
GETTING OTHER INFORMATION AND PUBLICATIONS
These publications can help you install the air conditioner or heat pump. You can usually find these at your local library or purchase them directly from the publisher. Be sure to consult current edition of each standard.
National Electrical Code ..................... ANSI/NFPA 70
Standard for the Installation ............. ANSI/NFPA 90A
of Air Conditioning and Ventilating Systems
Standard for Warm Air ...................... ANSI/NFPA 90B
Heating and Air Conditioning Systems
Load Calculation for .......................ACCA Manual J or
Winter and Summer Manual N Air Conditioning
Low Pressure, Low Velocity ........ ACCA Manual D or
Duct System Design Manual Q Winter and Summer Air Conditioning
FOR MORE INFORMATION, CONTACT THESE PUBLISHERS:
ACCA Air Conditioning Contractors of America
1712 New Hampshire Avenue Washington, DC 20009 Telephone: (202) 483-9370 Fax: (202) 234-4721
ANSI American National Standards Institute
11 West Street, 13th Floor New York, NY 10036 Telephone: (212) 642-4900 Fax: (212) 302-1286
ASHRAE American Society of Heating, Refrigeration,
and Air Conditioning Engineers, Inc.
1791 Tullie Circle, N.E. Atlanta, GA 30329-2305 Telephone: (404) 636-8400 Fax: (404) 321-5478
NFPA National Fire Protection Association
Batterymarch Park P.O. Box 9101 Quincy, MA 02269-9901 Telephone: (800) 344-3555 Fax: (617) 984-7057
Manual 2100-438 Page 1
QT
EC
Series General Information
QTEC MODEL NOMENCLATURE
QA 36 1 D A 10 X X V X X X
MODEL NUMBER |
QA - QTEC Model
CAPACITY |
24 - 2 Ton 30 - 2-1/2 Ton 36 - 3 Ton 42 - 3-1/2 Ton 48 - 4 Ton 60 - 5 Ton
DEHUMDIFICATION | REHEAT CYCLE
REVISION |
VOLTS & PHASE |
A - 230/208/60/1 B - 230/208/60/3 C - 460/60/3
KW
0Z -0KW 05 - 5KW 06 - 6KW 09 - 9KW 10 - 10KW 12 - 12KW 15 - 15KW
VENTILATION OPTIONS
X - Barometric Fresh Air Damper (Standard) B - Blank-off Plate V - Commercial Ventilator - Motorized w/Exhaust
Spring Return
P - Commercial Ventilator - Motorized w/Exhaust
Power Return
R - Energy Recovery Ventilator w/Exhaust
FILTER OPTIONS
X - 1 Inch Fiberglass
(Standard) F - 2 Inch Fiberglass P - 2 Inch Pleated
COLOR OPTIONS
V - Platinum w/Slate
Front (Vinyl)
4 - Gray paint
COIL OPTIONS
X - Standard 1 - Coated Evap. Coil 2 - Coated Cond.
Coil
3 - Coated Evap. &
Cond. Coil
I
NTERNAL CONTROLS
X - Standard
• High Pressure Switch
• Compressor Time Delay
G - LPC (Low Pressure
Control)
CLIMATE CONTROL OPTIONS
X - None G - Electronic/Non Prog/Man C/O
with Humidistat
E - Electronic/Prog/Man/Auto
with Humidistat
Manual 2100-438 Page 2
CD163AQ
CD124AQ
CD184AQAD106AQBD106AQCD106AQ
BD163AQ
BD124AQ
BD184AQ
AD163AQ
AD124AQ
AD184AQ
TABLE 1
FACTORY BUILT-IN ELECTRIC HEAT TABLE
AD142AQ
AD103AQBD142AQBD103AQCD142AQCD103AQ
1-V0421-V8021-V0421-V8021-V0421-V8023-V0843-V0841-V0421-V8021-V0421-V8023-V0841-V0421-V8021-V0421-V8023-V084
sledoM
0.5083,61092,21 083,61092,21
WKHUTBHUTBHUTBHUTBHUTBHUTBHUTBHUTBHUTBHUTBHUTBHUTBHUTBHUTBHUTBHUTBHUTBHUTB
0.9007,03000,32007,03000,32007,03007,03007,03000,32007,03007,03000,32007,03
0.6005,02063,51005,02063,51005,02005,02005,02063,51005,02
0.21000,14007,03000,14
0.01076,23075,42 076,23075,42076,23075,42
0.51 051,94068,63051,94068,63051,94051,94068,63051,94068,63051,94
Manual 2100-438 Page 3
TABLE 2
ELECTRICAL SPECIFICATIONS
TIUCRICELGNIS TIUCRICLAUD
D 51A
D 51B
D 51C
3
DETAR
SLEDOM
Z0AD142AQ 50AD 01AD
Z0BD142AQ 60BD 90BD
Z0CD142AQ 60CD 90CD
Z0AD103AQ 50AD 01AD
Z0BD103AQ 60BD 90BD 21BD
Z0CD103AQ 60CD 90CD 21CD
Z0AD163AQ 50AD 01AD
Z0BD163AQ 60BD 90BD
Z0CD163AQ 60CD 90CD
&STLOV SESAHP
1-802/032
3-802/032
3-064
1-802/032
3-802/032
3-064
3-802/032
3-802/032
3-064
.ON
DLEIF
REWOP
STIUCRIC
1 1 1
1 1 1
1 1 1
1 1 1
1 1 1 1
1 1 1 1
1 1 1
2RO1
1 1 1 1
1 1 1 1
MUMINIM TIUCRIC
02 03 55
51 42 33
8
21 71
52 23 75
81 52 43 34
01 41 81 32
82 33 85 38
12 62 53 35
11 41 81 72
1
YTICAPMA
03 03 06
02 52 53
51 51 02
53 53 06
52 52 53 54
51 51 02 52
53 53 06 09
03 03 53 06
51 51 02 03
2
MUMIXAM
LANRETXE ROESUF TIUCRIC
REKAERB
ERIW
EZIS
01 01
6
21 01
8
41 41 21
8 8 6
01
01 8 6
41
41
21
01
8 8 6 4
01
01 8 6
41
41
21
01
2
DLEIF
REWOP
ERIW
EZIS
01 01 01
21 01 01
41 41 21
01 01 01
01 01 01 01
41 41 21 01
01
01 8 8
01
01
01
01
41
41
21
01
3
MUMINIM TIUCRIC
DNUORG
YTICAPMA
TKC
A
B
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
85
52
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
1
MUMIXAM
ROESUF TIUCRIC
TKC
TKC
A
B
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
06
52
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
2
LANRETXE
REKAERB
TKC
DLEIF
REWOP
TKC
A
B
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
6
01
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
2
EZISERIW
TKC
DNUORG
EZISERIW
TKC
TKC
A
B
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
01
01
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
Maximum size of the time delay fuse or HACR type circuit breaker for protection of field wiring conductors.
!
Based on 75° C copper wire. All wiring must conform to the National Electrical Code and all local codes.
"
These “Minimum Circuit Ampacity” values are to be used for sizing the field power conductors. Refer to the National
#
Electric Code (latest revision), article 310 for power conductor sizing. CAUTION: When more than one field power conductor circuit is run through one conduit, the conductors must be derated. Pay special attention to Note 8 of Table 310 regarding Ampacity Adjustment Factors when more than three conductors are in a raceway.
ELECTRICAL SPECIFICATIONS CONTINUED ON PAGE 5 TABLE 2A
Manual 2100-438 Page 4
D51A
D51B
D51C
D51A
D51B
D51C
D51A
D51B
D51C
TABLE 2A
ELECTRICAL SPECIFICATIONS
TIUCRICELGNIS TIUCRICLAUD
3
.ON
DETAR
LEDOM
Z0AD124AQ 50AD 01AD
Z0BD124AQ 60BD 90BD
Z0CD124AQ 60CD 90CD
Z0AD184AQ 50AD 01AD
Z0BD184AQ 50BD 01BD
Z0CD184AQ 60CD 90CD
Z0AD106AQ 01AD
Z0BD106AQ 90BD
Z0CD106AQ 90CD
&STLOV
ESAHP
1-802/032
3-802/032
3-064
1-802/032
3-802/032
3-064
1-802/032
3-802/032
3-064
DLEIF
REWOP
STIUCRIC
1 1 1
2RO1
1 1 1 1
1 1 1 1
1 1 1
2RO1
1 1 1 1
1 1 1 1
1 1
2ro1
1 1 1
1 1 1
MUMINIM TIUCRIC
33 33 85 38
52 62 53 35
31 41 81
72
53 53 85 38
62 62 53 35
41 41 81
72
64 95 48
23 63 55
71 91 82
1
YTICAPMA
05 05 06 09
53 53 53 06
51 51 02 03
05 05 06 09
53 53 04 06
51 51 02 03
06 06 09
54 54 06
02 02 03
2
MUMIXAM
LANRETXE ROESUF TIUCRIC
REKAERB
ERIW
EZIS
8 8 6 4
8 8 8 6
41 41 21 01
8 8 6 4
8
8 8 6
21 21 21 01
8 6 4
8 8 6
21 21 01
2
DLEIF
REWOP
ERIW
EZIS
01
01 8 8
01
01
01
01
41
41
21
01
01
01
01 8
01
01
01
01
21
21
21
01
01
01 8
01
01
01
21
21
01
3
MUMINIM
TIUCRIC
DNUORG
YTICAPMA
TKC
A
B
--
--
--
--
--
--
85
52
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
85
52
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
95
52
--
--
--
--
--
--
--
--
--
--
--
--
1
MUMIXAM
ROESUF TIUCRIC
REKAERB
TKC
TKC
A
B
--
--
--
--
--
--
06
52
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
06
52
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
06
52
--
--
--
--
--
--
--
--
--
--
--
--
2
LANRETXE
TKC
DLEIF
REWOP
EZISERIW
TKC
A
B
--
--
--
--
--
--
6
01
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
8
01
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
8
01
--
--
--
--
--
--
--
--
--
--
--
--
2
DNUORG
EZISERIW
TKC
TKC
A
TKC
B
--
--
--
--
--
--
01
01
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
01
01
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
01
01
--
--
--
--
--
--
--
--
--
--
--
--
Maximum size of the time delay fuse or HACR type circuit breaker for protection of field wiring conductors.
!
Based on 75° C copper wire. All wiring must conform to the National Electrical Code and all local codes.
"
These “Minimum Circuit Ampacity” values are to be used for sizing the field power conductors. Refer to the National
#
Electric Code (latest revision), article 310 for power conductor sizing. CAUTION: When more than one field power conductor circuit is run through one conduit, the conductors must be derated. Pay special attention to Note 8 of Table 310 regarding Ampacity Adjustment Factors when more than three conductors are in a raceway.
Manual 2100-438 Page 5
FIGURE 1
UNIT DIMENSIONS
Manual 2100-438 Page 6
SHIPPING DAMAGE
Upon receipt of equipment, the carton should be checked for external signs of shipping damage. The skid must remain attached to the unit until the unit is ready for installation. If damage is found, the receiving party must contact the last carrier immediately, preferably in writing, requesting inspection by the carrier’s agent.
UNIT REMOVAL FROM SKID
WARNING
This unit is heavy and requires more than one person to handle and remove from the skid. Check unit wheels to ensure that wheels are locked before removing from skid. Extreme caution must be taken to prevent injury to personnel and damage to the unit.
It is recommended that the unit not be removed from the skid with a fork lift since the air seal under the unit could be damaged. See Figure 2.
The shipping brackets on each side of the unit must be removed and discarded. See Figure 3-A. The return air grille panel can be removed to provide a place to hold
FIGURE 2
AIR SEAL UNDER QT
Air Seal
the unit. The unit can be slid forward on the skit until the front wheels hang over the edge of the skid. See Figure 3-B. The unit can be tipped forward and slid down the edge of the skid until the front wheels touch the ground. See Figure 3-C. The wheels will not roll. They are shipped from the factory locked so they will not roll. The back of the skid will have to be held down to keep it from tipping up. The skid can be slid out from under the unit. The unit can then be set upright.
EC
UNIT
MIS-1008
FIGURE 3
REMOVAL OF UNIT FROM SKID
Hold Skid Down
A Shipping Brackets B Front Wheels Over Edge C Front Wheels On Floor
MIS-1007
Manual 2100-438 Page 7
HANDLING UNIT AFTER REMOVAL FROM SKID
WARNING
Exercise extreme caution when pushing the unit on the rollers. Handle and push from the lower 1/3 of the unit. Insure that debris is not on the floor where the unit is to be moved on the rollers. Failure to do so could result in the unit tipping over and causing bodily injury and/ or damage to the unit.
The unit will have to be turned sideways and removed from the skid to fit through a 36” doorway. If the door height allows, the unit can be slid sideways through the door.
If the unit can not be slid through the door, then the unit will have to be put on a cart and tipped down to roll through the door. It is recommended that an appliance cart by used with a strap to hold the unit on the cart.
The wheels of the unit must be locked. If the wheels were allowed to roll, the unit could roll off the cart. The unit should always be carted from the left side. This is the side where the compressor is located. See Figure 4. The blade of the appliance cart should be slid under the wheels of the unit. The strap of the appliance cart should be placed around the unit and strapped tightly. Help will be required to tip the unit back onto the cart. The unit can be leaned far enough back to be rolled through the door. Be careful when setting the unit back up to keep from damaging the unit.
GENERAL
The equipment covered in this manual is to be installed by trained, experienced service and installation technicians.
The unit is designed for use with or without duct work. For use without duct work, Plenum Box QPB42 is recommended.
These instructions explain the recommended method to install the air cooled self-contained unit and the electrical wiring connections to the unit.
APPLIANCE
CART
FIGURE 4
UNIT ON APPLIANCE CART
QTEC UNIT
(Right Side)
STRAP
These instructions and any instructions packaged with any separate equipment required to make up the entire air conditioning system should be carefully read before beginning the installation. Note particularly “Start Procedure” and any tags and/or labels attached to the equipment.
While these instructions are intended as a general recommended guide, they do not supersede any national and/or local codes in any way. Authorities having jurisdiction should be consulted before the installation is made. See Page 1 for information on codes and standards.
Size of unit for a proposed installation should be based on heat loss calculation made according to methods of Air Conditioning Contractors of America (ACCA). The air duct should be installed in accordance with the Standards of the National Fire Protection Systems of Other Than Residence Type, NFPA No. 90A, and Residence Type Warm Air Heating and Air Conditioning Systems, NFPA No. 90B. Where local regulations are at a variance with instructions, installer should adhere to local codes.
COMPRESSOR
Manual 2100-438 Page 8
MIS-1555
MINIMUM INSTALLATION HEIGHT
The minimum installation height of the unit with a Free Blow Plenum is 8 ft. 6 in. This provides enough clearance for the plenum to be removed. See Figure 5.
The minimum installation height for ducted applications is 8 ft. 4-1/2 in. This provides enough clearance to install the duct work. See Figure 6.
8 FT. - 5 IN.
FIGURE 5
INSTALLATION WITH FREE BLOW PLENUM
CEILING
8 FT. - 6 IN.
MINIMUM RECOMMENDED
CEILING HEIGHT
7 FT. - 4 IN.
UNIT HEIGHT
20 IN.
MINIMUM
FIGURE 6
DUCTED APPLICATION
SUSPENDED
CEILING
MINIMUM RECOMMENDED
FIXED CEILING
12 IN.
MINIMUM
2 IN. MINIMUM
FROM DUCT FLANGE
TO DUCT BOTTOM
8 FT. - 7 IN.
CEILING HEIGHT
FLOOR
MIS-1574
DUCT
DUCT FLANGE
8 FT. - 4.5 IN.
MINIMUM REQUIRED
INSTALLATION HEIGHT
FLOOR
MIS-1573
Manual 2100-438 Page 9
DUCT WORK
All duct work must be properly sized for the design air flow requirement of the equipment. Air Conditioning Contractors of America (ACCA) is an excellent guide to proper sizing. All duct work or portions thereof not in the conditioned space should be properly insulated in order to both conserve energy and prevent condensation or moisture damage. When duct runs through unheated spaces, it should be insulated with a minimum of one inch of insulation. Use insulation with a vapor barrier on the outside of the insulation. Flexible joints should be used to connect the duct work to the equipment in order to keep the noise transmission to a minimum.
The QTEC series unit has provision to attach a supply air duct to the top of the unit. Duct connection size is 12 inches x 20 inches. The duct work is field supplied and must be attached in a manner to allow for ease of removal when it becomes necessary to slide the unit out from the wall for service. See Figure 7 for suggested attachment method.
FIGURE 7
SUPPLY DUCT CONNECTIONS
SUPPLY DUCT TO BE FIELD SUPPLIED
For hot water coil option a QPBHWxx-F for free blow or QPBHWxx-D for ducted airflow is used
When used with a ducted supply, a QCX Cabinet Extension can be used to conceal the duct work above the unit to the ceiling. This extends 20” above the unit for a total height above the floor of 10’-7/8”. The unit is equipped with a variable speed indoor blower motor which increases in speed with an increase in duct static pressure. The unit will therefore deliver proper rated air flow up to the maximum ESP shown in Table 8. However, for quiet operation of the air system, the duct static should be kept as low as practical, within the guidelines of good duct design.
FILTERS
Two 1 inch throw away filters [(1) 16x16 and (1) 16x20] are supplied with each unit. The filters slide into filter brackets. Refer to Figure 8.
The filters are serviced from the inside of the building by opening the hinged door. This door is attached by 1/4 turn fasteners and one locking latch.
The internal filter brackets are adjustable to accommodate 2 inch filters. The tabs for the 1 inch filters must be bent down to allow the 2 inch filters to slide in place.
FIGURE 8
FILTER LOCATION
ATTACHMENT SCREWS TO BE FIELD SUPPLIED
ROOM SIDE OF QTEC UNIT
DUCT FLANGE
MIS-978
PROVIDED WITH UNIT
NOTE: Unit cabinet, supply air duct and free blow
plenum are approved for “0” clearance to combustible material.
The QTEC series units are designed for use with free return (non-ducted) and either free blow with the use of QPB Plenum Box or a duct supply air system.
The QPB and QPBHW Plenum Box mounts on top of the unit and has both vertically and horizontally adjustable louvers on the front discharge grille.
FILTERS
RETURN AIR GRILLE
Manual 2100-438 Page 10
MIS-1575
FRESH AIR INTAKE
This unit is equipped with a fresh air damper assembly. The damper blade is locked in the closed position when the unit is shipped from the Factory. To allow the damper to operate remove the two plastic locking pins, one on each end of the blade. This will allow for maximum fresh air flow. The Damper blade will now open when the indoor blower is operating. If less than maximum fresh air flow is required, reinsert the plastic pins to limit damper blade opening to desired level. Two extra pins are provided (taped to the inside of the assembly) which may be used to hold the blade in some position other than minimum or maximum position. This fresh air assembly is located in the rear of the unit and to gain access to make these adjustments remove the air filter service door.
All capacity, efficiency and cost of operation information as required for Department of Energy “Energyguide” Fact Sheets are based upon the fresh air blank-off plate in place and is recommended for maximum energy efficiency.
The blank-off plate is available upon request from the factory and is installed in place of the fresh air damper shipped with each unit.
For details on energy recovery ventilation see separate section.
CONDENSATE DRAIN
There are two drain connections on the unit. The rear drain is the primary drain, and is located on the right lower rear panel of the unit. The optional side drain is located on the bottom right side of the unit. The side drain is shipped with a plug installed.
The side drain requires a water trap for proper drainage. See Figure 9. The drain can be routed through the floor or through the wall. If the drain is to be routed
through an unconditioned space, it must be protected from freezing. The drain line must be able to be
removed from the unit if it is necessary to remove the unit from the wall. When the side drain is used, the plug must be removed and installed in the rear drain.
The rear drain can be used with wall thickness of up to 10 inches where a water trap can be installed between the unit and the interior wall. See Figure 10. The trap cannot extend beyond the edge of the unit or it will interfere with the wall mounting bracket. The drain can be routed through the floor or through the wall. If the drain is routed through the wall, the drain line must be positioned such that it will not interfere with the sleeve flange or the grille. See Figure 11. If the drain is to be
routed through an unconditioned space, it must be protected from freezing.
Optional rear drain kits, both standard and heated versions, are available to facilitate easy installation, and also removability of heat pump for service.
SEPARATE EVAPORATOR DRAIN CONNECTION (OPTIONAL)
A knockout is provided in the back right corner of the units for use when draining the evaporator drain pan separately from the condenser. This knockout is 5 inches above the back condenser drain opening. To utilize a separate evaporator drain connection remove the knockout and route the existing evaporator drain hose out this knockout and then to an appropriate drain line.
FIGURE 9
SIDE DRAIN (SIDE VIEW)
QTEC UNIT
FIGURE 10
OPTIONAL REAR DRAIN
PLUG SIDE DRAIN
MIS-975
Manual 2100-438 Page 11
FIGURE 11
REAR DRAIN (TOP VIEW)
DRAIN LINE
WALL (MAXIMUM 10” FOR REAR DRAIN)
SERVICE LIGHT
The unit is equipped with a service light which signals the user that service is required. The light is located in the upper control panel and is visible only when the hinged service/filter access door is open.
The Service Unit light indicates that the unit has been shut off by a high or low pressure device. This indicates that the unit needs to be serviced.
SLEEVE
WATER TRAP
MIS-977
COUPLINGS NOT SHOWN BUT RECOMMENDED FOR EASE OF REMOVABILITY FOR SERVICE.
WALL BRACKET
UNIT
FIGURE 12
UNIT MOUNTING
SIDE TRIM (2 PCS.)
BOTTOM
TRIM PIECE
Manual 2100-438 Page 12
BOTTOM TRIM EXTENSION
MIS-1576
SIDE TRIM (2 PCS.)
#8 SCREW
PROVIDED
(LIGHT COLOR)
MOUNTING BRACKET
CABINET SIDE PANEL
ENLARGED VIEW OF MOUNTING
BRACKET SHOWING SLEEVE TO
CABINET ATTACHMENT
MOUNTING BRACKET
MIS-1061
WALL SLEEVE
#10 HEX
HEAD SCREW
PROVIDED
INSTALLATION INSTRUCTIONS
MOUNTING THE UNIT
When installing a QTEC unit near an interior wall on the left side, a minimum of 8 inches is required; 12 inches is preferred.
When installing a QTEC unit near an interior wall on the right side, a minimum of 18 inches is required as additional space is required to connect the side drain. If the rear condensate drain kit QCDS48 is used the minimum can be reduced to 8 inches.
This clearance is required to allow for the attachment of the unit to the sleeve and side trim pieces to the wall.
This unit is to be secured to the wall sleeve with mounting brackets provided. The unit itself, the supply duct and the free blow plenum are suitable of “0” clearance to combustible material.
Following are the steps for mounting the QT reference see Figure 12 (page 11).
1. Attach mounting brackets to the wall sleeve with screws provided.
2. Position the unit in front of the sleeve with the condenser section toward the sleeve.
3. Remove the locking screws from the wheels. Refer to Figure 13.
4. Roll the unit into the sleeve. Make sure to check both sides of the unit as it is being rolled to keep it centered in the sleeve. Also check the
EC
, for
alignment to the mounting brackets. This unit must be level from side to side. If adjustments are necessary, shim up under the rollers with sheets of steel or any substance that is not affected by moisture.
5. Make sure the gasket on the rear of the unit is touching the sleeve across the top and down both sides. This is a rain water seal.
6. Secure the mounting brackets to the unit with screws provided, #10 hex head sheet metal screws.
7. Bottom trim extensions are provided for use when wall is less than 14 inches but greater than 10.5 inches. Secure to wall with screws (not provided).
8. Attach the bottom trim piece to the unit with the screws provided (dark colored).
9. Position side trim pieces to wall and attach with field supplied screws. There are two long pieces and two short pieces supplied. The long pieces are to enclose the gap behind the unit. The short pieces are to fill the gap behind the cabinet extension or the free blow plenum box. The may be cut to suit your ceiling height or overlap the unit side trim. There is sufficient length to trim up to a 10’2” ceiling.
NOTE: If the exterior wall thickness is between 5
inches to 10.5 inches, a side trim extension
piece kit, model QSTX42A, is available.
REMOVING LOCKING SCREWS FROM WHEELS
FIGURE 13
REMOVE SCREWS FROM WHEELS BEFORE ROLLING INTO PLACE
MIS-1018
Manual 2100-438 Page 13
WIRING – MAIN POWER
Refer to the unit rating plate and/or Table 2 for wire sizing information and maximum fuse or “HACR Type” circuit breaker size. Each unit is marked with a “Minimum Circuit Ampacity”. This means that the field wiring used must be sized to carry that amount of current. Depending on the installed KW of electric heat, there may be two field power circuits required. If this is the case, the unit serial plate will so indicate. All models are suitable only for connection with copper wire. Each unit and/or wiring diagram will be marked “Use Copper Conductors Only”. These instructions MUST BE adhered to. Refer to the National Electrical Code (NEC) for complete current carrying capacity data on the various insulation grades of wiring material. All wiring must conform to NEC and all local codes.
The electrical data lists fuse and wire sizes (75° C copper) for all models, including the most commonly used heater sizes. Also shown are the number of field power circuits required for the various models with heaters.
The unit rating plate lists a “Maximum Time Delay Relay Fuse” or “HACR Type” circuit breaker that is to be used with the equipment. The correct size must be used for proper circuit protection, and also to assure that
there will be no nuisance tripping due to the momentary high starting current of the compressor motor.
The disconnect access door on this unit may be locked to prevent unauthorized access to the disconnect.
See Start Up section for information on three phase scroll compressor start-ups.
The field wiring connections are located behind the top and hinged panel in the circuit breaker panel. See Figure 14.
WIRING – LOW VOLTAGE WIRING
230/208V, 1 PHASE AND 3 PHASE EQUIPMENT DUAL PRIMARY VOLTAGE TRANSFORMERS.
All Equipment leaves the factory wired on 240V tap. For 208V operation, reconnect form 240V to 208V tap. The acceptable operating voltage range for the 240 and 208V taps are as noted in Table 3.
TABLE 3
OPERATING VOLTAGE RANGE
PATEGNAR
V042612352
V802791–022
ELECTRIC HEATERS
UNIT MOUNTED THERMOSTAT LOCATION
DEHUMIDIFICATION CONTROL (OPTIONAL)
FIGURE 14
COMPONENT LOCATION
SIDE FIELD WIRE ENTRANCE
REMOTE THERMOSTAT TERMINAL BLOCK
I
NDOOR
BLOWER
CIRCUIT BREAKER PANEL & CONTROLS
LOWER CONTROL PANEL
NOTE: The voltage should be measured at the filed
power connection point in the unit and while the unit is operating at full load (maximum amperage operating condition).
The standard Climate Control Option X is a remote thermostat connection terminal block. See Figure 16 for wiring diagram. Compatible thermostats are listed in Table 4.
The Climate Control Option G is an electronic, non- programmable manual or auto changeover thermostat. The subbase of the thermostat is factory wired to the front panel of the unit. The humidistat is included. See Figure 17 for wiring diagram. Compatible for use with Bard CS2000 Controller and Energy Recovery Ventilator.
The Climate Control Option E is an electronic, programmable thermostat. The subbase of the thermostat is factory wired to the front panel of the unit. The humidistat is included. See Figure 18 for wiring diagram. Compatible for use with Energy Recovery Ventilator.
NOTE: On option X or G the CS2000 (or other field
provided means to control ventilation) must be used if any of the motorized ventilation options are installed.
Manual 2100-438 Page 14
MIS-1577
LOW VOLTAGE CONNECTIONS
These units use a grounded 24 volt AC low voltage circuit.
LOW VOLTAGE CONNECTIONS
FOR DDC CONTROL
The “R” terminal is the hot terminal and the “C” terminal is grounded.
“G” terminal or pin 6 of P2 are the fan inputs. If the climate control option is abandoned and connections are made directly to P2 pin 6 of P2 must be energized for proper operation.
“Y” terminal or pin 7 of P2 is the compressor input.
“W1” terminal or pin 8 of P2 is the fist stage heat.
“R” terminal or pin 10 of P2 is 24 VAC hot.
“C” terminal or pin 11 of P2 is 24 VAC grounded.
Terminal “1” or pin 4 of P2 is the dehumidification circuit.
Terminal “2” or pin 12 of P2 is the dehumidification circuit. A contact must connect terminals 4 and 5.
“W2” terminal or pin 9 of P2 is second stage heat (if equipped). If the unit is equipped with an optional hot water coil plenum box or electric heat these will be energized by this terminal.
“F” terminal of pin 5 of P2 is the ventilation input. This terminal energizes any factory installed ventilation option.
Fan Only Energize G
Cooling Mode Energize Y, G
1st Stage Heating Energize G, W1
2nd State Heating Energize G, W2 (if employed)
Ventilation Energize G, O1
Dehumidification Energize contact
between 1 and 2
GENERAL
This unit is equipped with a variable speed ECM motor. The motor is designed to maintain rated airflow up to the maximum static allowed. It is important that the
blower motor plugs are not plugged in or unplugged while the power is on. Failure to remove power prior to unplugging or plugging in the motor could result in motor failure.
NOTE: For total and proper control using DDC, a
total of 6 controlled outputs are required (5 if no ventilation system is installed).
CAUTION
Do not plug in or unplug blower motor connectors while the power is on. Failure to do so may result in motor failure.
Manual 2100-438 Page 15
TABLE 4
WALL THERMOSTATS AND SUBBASE COMBINATIONS
tatsomrehTesabbuSserutaeFtnanimoderP
940-3048
)083-39F1(
050-3048
)5101D4258T(
A/N
A/N
elbammargorP
looC/taeH/otuA/launaM
looC/taeH/otuA/launaM
cinortcelEelbammargorP-noN
FIGURE 15
THERMOSTAT PLUG TERMINALS
P2 AND P4
(VIEWED FROM PIN END)
BLOWER MOTOR
LOW VOLTAGE PLUG
(VIEWED FROM PIN END)
Manual 2100-438 Page 16
MIS-1285
FIGURE 16
REMOTE THERMOSTAT WIRING DIAGRAM
“X” THERMOSTAT OPTION
NOTE: On option X or G the CS2000 (or other field
provided means to control ventilation) must be used if any of the motorized ventilation options are installed.
Manual 2100-438 Page 17
FIGURE 17
UNIT MOUNTED THERMOSTAT WIRING DIAGRAM
“G” THERMOSTAT OPTION
NOTE: On option X or G the CS2000 (or other field
provided means to control ventilation) must be used if any of the motorized ventilation options are installed.
Manual 2100-438 Page 18
FIGURE 18
UNIT MOUNTED THERMOSTAT WIRING DIAGRAM
“E” THERMOSTAT OPTION
Manual 2100-438 Page 19
START UP
DESCRIPTION OF STANDARD EQUIPMENT
High Pressure Switch
Provides refrigerant circuit high pressure protection. Includes lockout circuit that is resettable from room thermostat.
Compressor Control Module
Provides short cycle protection for the compressor which extends compressor life. High and low pressure switch monitoring and alarm functions.
Service Lights
One service light indicates when service is required.
• Check System – detects high or low pressure switch operation for compressor protection.
OPTIONAL CFM (QA361, QA421, QA481 AND QA601 ONLY)
These units are shipped from the factory set to operate at the optional CFM level shown in Table 8. This provides lower operating sound levels for non-ducted, free discharge applications. This CFM level will reduce the system capacity performance by approximately 2% at the same energy efficiency.
Rated CFM is required for ducted applications for maximum performance rating. To obtain full CFM on these models, connect jumper wire as follows:
1. Disconnect all power to the unit. Failure to do so may result in damage to the motor.
2. Open return air service panel
3. Open inner control panel cover
4. Locate low voltage terminal strip. There is a pink jumper wire with both ends attached to terminal marked “G2”. Move one end of this jumper to terminal “Y”.
5. Reverse steps to reassemble.
IMPORTANT INSTALLER NOTE
For improved start-up performance, wash the indoor coil with a dishwasher detergent.
This unit is equipped with a variable speed ECM motor. The motor is designed to maintain rated airflow up to the maximum Static allowed. It is important that the
blower motor plugs are not plugged in or unplugged while the power is on. Failure to remove power prior to unplugging or plugging in the motor could result in motor failure.
CAUTION
Do not plug in or unplug blower motor connectors while the power is on. Failure to do so may result in motor failure.
PHASE MONITOR
All units with three phase scroll compressors are equipped with a 3 phase line monitor to prevent compressor damage due to phase reversal.
The phase monitor in this unit is equipped with two LEDs. If the Y signal is present at the phase monitor and phases are correct the green LED will light and the compressor contactor is allowed to energize.
If phases are reversed, the red fault LED will be lit and compressor operation is inhibited.
If a fault condition occurs, reverse two of the supply leads to the unit. Do not reverse any of the unit factory wires as damage may occur.
THREE PHASE SCROLL COMPRESSOR START UP INFORMATION
Scroll compressors, like several other types of compressors, will only compress in one rotational direction. Direction of rotation is not an issue with single phase compressors since they will always start and run in the proper direction.
However, three phase compressors will rotate in either direction depending upon phasing of the power. Since there is a 50-50 chance of connecting power in such a way as to cause rotation in the reverse direction,
verification of proper rotation must be made.
Verification of proper rotation direction is made by observing that suction pressure drops and discharge pressure rises when the compressor is energized. Reverse rotation also results in an elevated sound level over that with correct rotation, as well as, substantially reduced current draw compared to tabulated values.
Verification of proper rotation must be made at the time the equipment is put into service. If improper rotation is corrected at this time there will be no negative impact on the durability of the compressor. However, reverse operation for oven one hour may have a negative impact on the bearing due to oil pump out.
Manual 2100-438 Page 20
All three phase scroll compressors used in the QT
EC
series are wired identically internally. As a result, once the correct phasing is determined for a specific system or installation, connecting properly phased power leads to the same Fusite terminal should maintain proper rotation direction. The direction of rotation of the motor may be changed by reversing any two line connections to the unit.
COMPRESSOR CONTROL MODULE
The compressor control module is standard on all models covered by this manual. The compressor control is an anti-short cycle/lockout timer with high and low pressure switch monitoring and alarm relay output.
Adjustable Delay On Make And Break Timer
On initial power up or any time power is interrupted to the unit the delay on make period begins which will be 2 minutes plus 10% of the delay on break setting. When the delay on make is complete and the high pressure switch (and low pressure switch if employed) is closed, the compressor contactor is energized. Upon shutdown the delay on break timer starts and prevents restart until the delay on break and delay on make periods have expired.
During routine operation of the unit with no power interruptions the compressor will operate on demand with no delay.
High Pressure Switch and Lockout Sequence
If the high pressure switch opens, the compressor contactor will de-energize immediately. The lockout timer will go into a soft lockout and stay in soft lockout until the high pressure switch closes and the delay on break time has expired. If the high pressure switch opens again in this same operating cycle the unit will go into manual lockout condition and the alarm relay circuit will energize. Recycling the wall thermostat resets the manual lockout.
Low Pressure Switch, Bypass, and Lockout Sequence
If the low pressure switch opens for more than 120 seconds, the compressor contactor will de-energize and go into a soft lockout. Regardless the state of the low pressure switch, the contactor will reenergize after the delay on make time delay has expired. If the low pressure switch remains open, or opens again for longer than 120 seconds the unit will go into manual lockout condition and the alarm relay circuit will energize. Recycling the wall thermostat resets the manual lockout.
Alarm Relay Output
Alarm terminal is output connection for applications where alarm relay is employed. This terminal is powered whenever compressor is locked out due to HPC or LPC sequences as described.
NOTE: Both high and low pressure switch controls are
inherently automatic reset devices. The high pressure switch and low pressure switch cut out and cut in settings are fixed by specific air conditioner or heat pump unit model. The lockout features, both soft and manual, are a function of the Compressor Control Module.
ADJUSTMENTS
Adjustable Delay on Make and Delay on Break Timer
The potentiometer is used to select Delay on Break time from 30 seconds to 5 minutes. Delay on Make (DOM) timing on power-up and after power interruptions is equal to 2 minutes plus 10% of Delay on Break (DOB) setting:
0.5 minute (30 seconds) DOB = 123 second DOM
1.0 minute (60 seconds) DOB = 126 second DOM
2.0 minute (120 seconds) DOB = 132 second DOM
3.0 minute (180 seconds) DOB = 138 second DOM
4.0 minute (240 seconds) DOB = 144 second DOM
5.0 minute (300 seconds) DOB = 150 second DOM
During routine operation of the unit with no power interruptions the compressor will operate on demand with no delay.
Typical Settings for Dual Unit Installation:
Unit 1: DOB set at 2 minutes, and DOM is 132 seconds
Unit 2: DOB set at 4 minutes, and DOM is 144 seconds
SERVICE HINTS
1. Caution user to maintain clean air filters at all times. Also, not to needlessly close off supply air registers. This may reduce air flow through the system, which shortens equipment service life as well as increasing operating costs and noise levels.
2. Check all power fuses or circuit breakers to be sure they are the correct rating.
3. Periodic cleaning of the outdoor coil to permit full and unrestricted airflow circulation is essential.
Manual 2100-438 Page 21
6. Some service requires the need to remove the unit from the wall including replacement of the indoor coil and/or the outdoor coil. Also servicing the outdoor fan motor or fan blade will require removing the unit from the wall if the unit is installed at a height that is not easily accessible from the outside of the building.
In order to remove the unit from the wall the following procedure must be used:
a. Turn off power to the unit at the remote
location. Some units may have more than one power supply.
b. Disconnect field wiring at unit terminal block
and remove from unit.
c. Disconnect condensate drain.
d. Remove the lower skirting around the unit.
e. Remove wall mounting brackets from wall on
each side of the unit.
It is recommended that the mist eliminator be inspected annually and serviced as required. The mist eliminator can be inspected from the outside of the building by looking through the outdoor grille. The mist eliminator can be serviced from the outside by using a vacuum cleaner. The outdoor grille must be removed. Use the vacuum to remove dirt and debris from the surface of the mist eliminator. If additional cleaning is required, the mist eliminator will have to be removed from the sleeve.
The ventilation package will have to be removed to gain access to the mist eliminator. If the blank off plate option is used, it is not necessary to service the mist eliminator. The steps necessary to remove each of the vent options are listed on the following pages.
The mist eliminator can be cleaned by washing with soap and water. The excess water should be shaken off the mist eliminator before it is reinstalled.
f. If unit is attached to duct work, remove upper
cabinet extension by removing the top center screw only from the cabinet side panel.
g. Remove screws that attach the duct work to
the unit flanges.
This unit is equipped with four rollers mounted to the base. For ease of pulling unit out from the wall, you may want to remove the bottom service door which requires removal of the return air panel, and grip the front flange of the base pan then pull straight out.
7. Annual maintenance is required to make sure that all of the systems are functioning properly.
a. Check to make sure that the drains are not
obstructed in any way.
b. Remove any debris in the condenser section of
the unit.
c. Inspect and clean mist eliminator as described
below.
d. Inspect and wash outdoor coil as necessary.
VENT OPTIONS
BAROMETRIC FRESH AIR DAMPER (Standard)
Before starting, make sure the power has been turned off. The return air grille panel must be removed. The fresh air damper assembly can be seen on the back of the unit. See Figure 19.
1. The fresh air damper is attached to the back of the unit with one screw on either side of the assembly. Both of the screws must be removed.
2. Once the mounting screws are removed, tilt the assembly down and lift it out.
The mist eliminator can be seen through the opening. The mist eliminator must be raised up and the bottom can be pulled toward the front of the unit.
COMMERCIAL ROOM VENTILATOR (Option)
Before starting, make sure the power has been turned off. The return air grille panel must be removed. The commercial room ventilator (CRV) can be seen after the panel has been removed. The CRV must be removed to gain access to the mist eliminator.
MIST ELIMINATOR SERVICE
A mist eliminator is supplied with the wall sleeve. The mist eliminator is constructed of an aluminum frame and mesh. The mist eliminator is located in the top section of the wall sleeve and can be removed from the inside of the building without removing the unit from the wall. This requires that the ventilation package must be removed.
Manual 2100-438 Page 22
1. The two mounting screws in the front of the CRV must be removed.
2. The power connectors for the CRV (located on the right side of the unit) must be disconnected. Squeeze the tabs on the sides of the connector and pull straight out. Unplug both of the connectors.
3. Slide the CRV straight out of the unit.
The mist eliminator can be seen through the opening in the back of the unit. The mist eliminator must be raised up and the bottom can be pulled toward the front of the unit and removed.
EC
R ENERGY RECOVERY VENTILATOR
QT (Option)
Before starting, make sure that the power has been turned off. The return air grille panel must be removed. The energy recovery ventilator (QERV) can be seen after the panel has been removed. To gain access to the mist eliminator, the QERV must be removed. See Figure 20.
1. The front fill plate of the QERV must be removed. There is one screw on either side of the plate. Remove these screws and remove the plate.
2. On either side of the QERV there are mounting screws that hold the QERV in place. Remove both of these screws.
3. Underneath the heat recovery cassette there is a power connector for the lower blower assembly. To disconnect this plug, the tabs on both sides of the plug must be squeezed to release the plug. While squeezing the tabs, pull the plug out of the socket.
4. The QERV is plugged into the unit in the right side of the unit. Both of these plugs must be disconnected to remove the QERV. Squeeze the tabs on the sides of the connector and pull straight out.
5. Slide the QERV assembly straight out of the unit, being careful not to let the cassette slide out of the QERV.
The mist eliminator can be seen through the opening in the back of the unit. The mist eliminator must be raised up and the bottom can be pulled toward the front of the unit and removed.
Manual 2100-438 Page 23
FIGURE 19
FRESH AIR DAMPER REMOVAL
MOUNTING SCREW
MIS-1627
Manual 2100-438 Page 24
FIGURE 20
QERV REMOVAL
MOUNTING SCREWS
FRONT FILL
POWER
CONNECTORS
LOWER BLOWER
ASSEMBLY POWER
CONNECTOR
MIS-1039
Manual 2100-438 Page 25
SEQUENCE OF OPERATION
CRV / QERV OPERATION
Cooling – Circuit R-Y makes the thermostat pull in the compressor contactor starting the compressor and outdoor motor. The G (indoor motor) circuit is automatically completed on any call for cooling operation, or can be energized by manual fan switch on subbase for constant air circulation.
Heating – Circuit is completed for R-W1 on each heating “on” cycle, energizing the electric heat contactor. R-G also makes starting indoor blower motor.
Second stage heat – Energized circuit R-W2 and the electric heat contactor for the second bank of heaters (if equipped) is energized.
High / Low Pressure control provides protection for the compressor. In the advent system pressures go above 450 PSI or below 15 PSI in cooling mode the compressor will be stopped. This will activate the red light located in the control panel. The lockout circuit will hold compressor off line. When the system problem is corrected, the unit operation can be restored by turning of the main power supply off and then back on, or reset the room thermostat. The low pressure control has a bypass to eliminate nuisance lockout on cold start up.
Dehumidification / Reheat Circuit – Both cooling and heating take precedence over dehumidification.
QERV is energized by applying 24 VAC to the “F” terminal of the low voltage terminal strip on units with “X” climate control option. It is energized by the “A1” terminal of the thermostat on units with “E” climate control option. It is energized by applying power to the “O1” terminal of the low voltage strip on units with “G” climate control options.
OPTIONAL CLIMATE CONTROLS SEQUENCE OF OPERATION
The Climate Control Option G is an electronic, non­programmable manual or auto changeover thermostat. The thermostat may be manually set to heat or cool mode. The thermostat will maintain the temperature set on the thermostat in the mode in which it is set.
The Climate Control Option E is an electronic, programmable thermostat. The thermostat can be set in the heat, cool or automatic mode. When the thermostat is set in the heat mode, it can heat only to maintain the temperature set on the thermostat. When the thermostat is set in the cool mode, it can cool only to maintain the temperature set on the thermostat. When the thermostat is set in the automatic mode, the thermostat can change automatically to the heat or cool modes to maintain the temperature set on the thermostat.
Reheat Circuit There is a small capillary tube inserted between the reheat coil return line and suction line that will prevent liquid from accumulating in the reheat coil when it is inactive. This drain does not affect the normal operation of the system.
There is a check valve located in the reheat coil return line. It has a soft spring to hold the ball on the seat. This will make the method of checking the ball freedom with a magnet difficult. Refer to Figures 18 and 19 for the location of the check valve and drain back capillary.
When the system is operating in the dehumidification mode the suction pressure will be reduced by 4 to 8 psig and the discharge pressure will be reduced by 19 to 22 psig.
PRESSURE SERVICE PORTS
High and low pressure service ports are installed on all units so that the system operating pressures can be observed. Pressure curves can be found later in the manual covering all models on both cooling and heating cycles. It is imperative to match the correct pressure curve to the unit by model number. Upper and lower service doors must be attached to obtain proper reading.
Manual 2100-438 Page 26
FIGURE 21
AIR CONDITIONING MODE
CIRCUIT DIAGRAM
MIS-1200
Manual 2100-438 Page 27
FIGURE 22
DEHUMIDIFICATION MODE
CIRCUIT DIAGRAM
Manual 2100-438 Page 28
MIS-1199
TROUBLESHOOTING
TABLE 5
TROUBLESHOOTING
notpmySesuaCelbissoPkcehCottahWriapeRrokcehCotwoH
rosserpmoC
tonseodrotcatnoc
ezigrene
)gnitaehrognilooc(
gniriwtiucriclortnoC,tinutanoitcennocRrofkcehC
tuokcolrosserpmoC)1
stinuroodtuootnoitcennocRnuR
.C-RneewtebV42dna
C-1LneewtebV42rofkcehC
)1
.lortnocpmuptaehno
nrutC-1LneewtebegatlovonfI
otniaganodnaffotatsomreht
.hctiwserusserphgihteser
)2
.hctiws
erusserphgihssorcakcehC
)2
neposihctiwserusserphgihfI hgihecalper,tesertonlliwdna
.hctiwserusserp
trohsrosserpmoC
noitcetorpelcyc
C-CCneewtebV42rofkcehC
.lortnocpmuptaehnoC-Ydna
repmujC-CCneewtebegatlovonfI
01nihtiwdnalanimretpudeeps
raeppadluohsrewopsdnoces
pudeepsevomeR.C-CCneewteb
.sdnoces01retfarepmuj
evitcefedrotcatnoCliocdetrohsroneporofkcehC
.rotcatnocecalpeR
.gnidniw
rotomroodtuonaF
nurtonseod
evitcefedrotoMrotomdetrohsroneporofkcehC
.rotomecalpeR
.gnidniw
gnitaehrognilooc(
gnirudtpecxe
)tsorfed
roticapacrotoM
evitcefed
kcehC.gnitarroticapackcehC
.roticapacecalpeR
.roticapacdetrohsroneporof
Manual 2100-438 Page 29
FAN BLADE SETTING DIMENSIONS
REFRIGERANT CHARGE
Any service work requiring removal or adjustment in the fan and/or motor area will require that the dimensions in Table 6 be checked and blade adjusted in or out of the motor shaft accordingly.
FIGURE 23
FAN BLADE SETTING
MIS-983
TABLE 6
FAN BLADE DIMENSIONS
ANOISNEMID
LEDOM
142AQ 103AQ 163AQ 124AQ 184AQ 106AQ
)SEHCNI(
057.
057.
057.
057.
057.
057.
The correct system R-22 charge is shown on the unit rating plate. Optimum unit cooling performance will occur with a refrigerant charge resulting in a Super Heat as shown in Table 7. If correct charge is in doubt, recover the refrigerant and recharge per the charge on the unit rating plate.
TABLE 7
SUPER HEAT AT COMPRESSOR
DETAR
LEDOM
142AQ00881-6161-41
103AQ000181-6171-51
163AQ002181-6161-41
124AQ002112-9181-61
184AQ004152-3242-22
106AQ05519-751-31
MFC
DOF°59
ERUTAREPMET
DOF°28
ERUTAREPMET
TABLE 8
INDOOR BLOWER PERFORMANCE
1
ledoMPSEdetaR
5
142AQ
103AQ51.8.000010001019007
163AQ51.8.00021000100015711058
124AQ51.8.00021000100015711058
184AQ51.8.00041001100115711058
106AQ02.5.005510521052100410521
NOTE: These units are equipped with a variable speed (ECM) indoor motor that automatically adjust itself to
1
Maximum ESP (inches WC) shown is with 1” thick disposable filter (reduced by .2 for 2” filter).
Rated CFM for ducted applications – required for maximum performance rating. To obtain full CFM on models QA36, QA421,
2
QA481 and QA601 connect the pink jumper wire (provided) to terminal #G2 and #Y on the low voltage terminal block located in the circuit breaker box.
3
Optional CFM – the unit is shipped from the factory set to operate at the optional CFM level shown. This provides lower operating sound levels for non-ducted, free discharge applications. This reduces system capacity performance by approximately 2% at the same energy efficiency.
Continuous fan CFM is the total air being circulated during continuous fan mode.
4
Models QA241 – when operating on 2nd stage heating the indoor air will increase to 1000 CFM.
5
maintain approximately the same rate of indoor air flow in both heating and cooling, dry and wet coil conditions and at both 230/208 or 460 volts.
01.5.0008008007005
PSE.xaM
2
3
lanoitpO
MFCdetaR
MFC
4
suounitnoC
MFC
@MFC
PSE.xaM
.muheD
MFC
Manual 2100-438 Page 30
TABLE 9
COOLING PRESSURE
(ALL TEMPERATURES IN DEGREES F)
NRUTER
LIOCROODTUOGNIRETNEERUTAREPMETRIA
RIA
LEDOM
.PMETERUSSERP
BD57
ediSwoL
BW26
142AQ
BD08
BW76
BD58
ediSwoL
ediSwoL
BW27
BD57
ediSwoL
BW26
103AQ
BD08
BW76
BD58
ediSwoL
ediSwoL
BW27
BD57
ediSwoL
BW26
163AQ
BD08
BW76
BD58
ediSwoL
ediSwoL
BW27
BD57
ediSwoL
BW26
124AQ
BD08
BW76
BD58
ediSwoL
ediSwoL
BW27
BD57
ediSwoL
BW26
184AQ
BD08
BW76
BD58
ediSwoL
ediSwoL
BW27
BD57
ediSwoL
BW26
106AQ
BD08
BW76
BD58
ediSwoL
ediSwoL
BW27
5708580959001501011511
37
ediShgiH
591
87
ediShgiH
302
48
ediShgiH
57
ediShgiH
622
08
ediShgiH
822
68
ediShgiH
832
47
ediShgiH
212
97
ediShgiH
912
58
ediShgiH
ediShgiH
322
642
57
ediShgiH
28
ediShgiH
96
ediShgiH
57
ediShgiH
ediShgiH
822
732
66
ediShgiH
ediShgiH
742
37
ediShgiH
652
37 991
87 402
48
121
312
57 202
08 332
68 042
47 512
97 022
58 822
17
17
842
67
152
342
28
162
262
17
122
732
67 442
18
28 252
07
142
852
17
57 562
87 472
47 412
97 912
58 822
67 242
18 842
78 752
57 332
08 932
68 742
27 462
77 072
38 972
27 252
67 062
28 962
47 672
97 382
28 392
67 922
08 432
68 442
77 852
28 462
88 372
67
752
78 762
37
87 882
48 892
27 072
77 672
38 582
87 492
38 203
68 313
77 442
28 052
88 952
87 372
38 082
98 092
77
152
962
18
28 672
88 682
47
182
992
97 703
58 813
37 782
87 492
48 403
18
413
78 223
09 333
97 952
48 462
98 472
97 913
48 692
09 603
87 782
38 492
98 503
57 813
08 723
68 033
47 503
97 213
58 323
58 233
19 143
49 353
08 472
58 082
19
092
08 303
58
113
19
323
97 503
48 213
09 423
67 933
18
943
78
163
57 323
08
133
68 243
98 353
59 263
89 573
18
38
982
78 692
39 503
913
68 723
29 933
08 323
58
343
77 263
28
88 483
57 343
08
68 363
39 273
99 283
201 593
403
88 213
49 023
18
28 533
78 343
39 653
18 143
68
133
053
19
29 363
97 583
38
173
593
09 904
67 363
18
153
273
78 583
69 373
301 304
701 714
Low side pressure ± 2 psig High side pressure ± 5 psig
Tables are based upon rated CFM (airflow) across the evaporator coil. If there is any doubt as to correct operating charge being in the system, the charge should be removed, system evacuated and recharged to serial plate instructions.
Manual 2100-438 Page 31
Loading...