Balluff BISM4XX07 User Manual

BIS M-4xx-045-00x-07-S4
Technical Description, User's Guide
English
www.balluff.com
BIS M-4xx IO-Link Device Read/Write Device
1
1.1 Conformity and user safety 5
1.2 Scope of delivery 5
1.3 About this manual 5
1.4 Structure of the manual 5
1.5 Typographical conventions 5
1.6 Symbols 6
1.7 Abbreviations 6
2
2.1 Intended use 7
2.2 General safety notes 7
2.3 Meaning of the warnings 7
3
3.1 Mechanical connection 8
3.2 Electrical connection 11
4
4.1 Function principle of Identification Systems 12
4.2 Example 13
4.3 Read distance/offset 14
4.4 Product description 14
4.5 Data integrity 14
4.6 Autoread 15
4.7 Supported data carrier types 15
4.8 IO-Link basic knowledge 15
5
5.1 Electrical data 16
5.2 Operating conditions 16
5.3 BIS M-400-045-001-07-S4 16
5.4 BIS M-400-045-002-07-S4 17
5.5 BIS M-401-045-001-07-S4 18
5.6 BIS M-402-045-002-07-S4 19
5.8 BIS M-451-045-001-07-S4 21
5.9 Dynamic mode 22
6
6.1 Digital point-to-point connection 24
6.2 Process data container 25
6.3 Identificationdata and device information 25
7
7.1 Required data 26
7.2 Mapping of parameterization data 27
7.3 Storing the parameterization data 29
8
9
9.1 Functional principle 31
9.2 Functional principle 31
9.3 Process data 32
www.balluff.com 3
4
BIS M-4xx IO-Link Device Read/Write Device
9.4 Protocol sequence 36
9.5 Protocol examples 37
9.6 Error codes 43
9.7 Data transmission timing 44
Type designation code 47 Accessories 47 ASCII table 48
www.balluff.com
5
BIS M-4xx IO-Link Device Read/Write Device
User instructions
1
1.1 Conformity and user safety
1.2 Scope of delivery
This product was developed and manufactured in accordance with applicable European stan­dards and directives.
Declaration of Conformity
This product was developed and manufactured in accordance with applicable Euro­pean standards and directives.
Note
You can request a Declaration of Conformity separately. For additional safety instruction, refer to Chapter "Safety“ on page 7.
UL listing
Control No. 3TLJ File No. E227256
Included in the scope of delivery:
BIS M-4xx IO-Link device – BIS software CD – Condensed manual in printed form (DE, EN)
1.3 About this manual
1.4 Structure of the manual
1.5 Typographical conventions
Enumerations
Actions
This manual describes the read/write device of the BIS M-4xx-IO-Link Identification System and includes startup instructions for immediate operation. This manual does not describe:
The start-up, function and safe operation of the host device (PC, PLC, IO-Link Master). – The installation and function of accessories and expansion devices.
The manual is organized so that the sections build on each other. Chapter 2: Basic safety information. Chapter 3: The key steps for installing the Identification System. Chapter 4: Introduction to the material. Chapter 5: Technical data for the read/write device. Chapter 6: Basics on the IO-Link communications standard. Chapter 7: User-defined settings for the read/write device. Chapter 8: Integration into a fieldbus system using Profibus as an example. Chapter 9: Processor and host system interaction.
The following conventions are used in this manual.
Enumerations are shown as a list with an en-dash.
Entry 1, – Entry 2.
Action instructions are indicated by a preceding triangle. The result of an action is indicated by an arrow.
6
BIS M-4xx IO-Link Device Read/Write Device
User instructions
1
Action instruction 1.
Action instruction 2.
Action result.
Syntax
Cross-references
1.6 Symbols
1.7 Abbreviations
Numbers:
Decimal numbers are shown without additional indicators (e.g. 123), – Hexadecimal numbers are shown with the additional indicator
Parameters:
Parameters are shown in italics (e.g. CRC_16).
Directory paths:
References to paths in which data are stored or are to be saved are shown in small caps (e.g.
r o j e c t :\Da t a ty P e s \Us e r De f i n e D ).
P
Cross-references indicate where additional information on the topic can be found (see "Technical Data“ starting on page 16).
Attention!
This symbol indicates a safety instruction that absolutely must be followed.
Note, tip
This symbol indicates general notes.
BIS Balluff Identification System CRC Cyclic Redundancy Code
DPP Direct Parameter Page EMC Electromagnetic Compatibility LSB Least Significant Bit MSB Most Significant Bit PC Personal Computer SIO Standard IO SPDU Service Protocol Data Unit PLC Programmable Logic Controller TCP Transmission Control Protocol
hex (e.g. 00hex).
www.balluff.com 7
BIS M-4xx IO-Link Device Read/Write Device
Safety
2
2.1 Intended use
2.2 General safety notes
The BIS M-4xx-... read/write device, together with other components of the BIS M, form the Identification System. They may only be used for this purpose in an industrial environment corresponding to Class A of the EMC law. This description applies for the read/write devices of the BIS M-4xx-... series.
Installation and startup
Installation and startup are only to be performed by trained specialists. Any damage resulting from unauthorized manipulation or improper use voids the manufacturer's guarantee and war­ranty. When connecting the read/write device to an external controller, pay attention to the choice and polarity of the connection as well as the power supply. The read/write device must only be powered using approved power supplies (see Chapter 5
"Technical data" beginning on page 16).
Attention!
This is a Class A device. This device may cause RF disturbances in residential areas; in such a case the operator may be required to take appropriate countermeasures.
Operation and testing
The operator is responsible for ensuring that locally applicable safety regulations are observed. In the event of defects and non-correctable faults in the Identification System, take the system out of service and secure it from unauthorized use.
2.3 Meaning of the warnings
Attention!
The pictogram used with the word "Attention" warns of a possible hazardous situation affecting the health of persons or equipment damage. Failure to observe these warning notes may result in injury or damage to equipment.
Always observe the described measures for preventing this danger.
8
BIS M-4xx IO-Link Device Read/Write Device
Getting started
3
3.1 Mechanical connection
BIS M-400-...-001
BIS M-400-...-002
BIS M-400-045-001-07-S4 read/write device, values in mmFig.1:
1 Maximum tightening torque 40 Nm 2 Sensing surface
BIS M-400-045-002-07-S4 read/write device, values in mmFig.2:
1 Maximum tightening torque 40 Nm 2 Sensing surface
www.balluff.com
9

 













0
[

0
[



A
A
BIS M-4xx IO-Link Device Read/Write Device
Getting started
3
BIS M-401-...-001
BIS M-402-...-002
BIS M-401-045-001-07-S4 read/write device, values in mmFig.3:
1 Maximum tightening torque 3 Nm 2 Earthing connector
3 Sensing surface
BIS M-402-045-002-07-S4 read/write device, values in mmFig.4:
1 Sensing surface 2 Maximum tightening torque 25 Nm
3 Cable length 0.5 m 4 Maximum tightening torque 2 Nm
10







0
[



 



A
A

 






BIS M-4xx IO-Link Device Read/Write Device
Getting started
3
BIS M-402-...-004
BIS M-451-...-001
BIS M-402-045-004-07-S4 read/write device, values in mmFig.5:
1 Sensing surface 2 Maximum tightening torque 1 Nm
3 Cable length 0.5 m 4 Maximum tightening torque 2 Nm
BIS M-451-045-001-07-S4 read/write device, values in mmFig.6:
1 Maximum tightening torque 3 Nm 2 Read/write axis
3 Earthing connector 4 Sensing surface
www.balluff.com
11
BIS M-4xx IO-Link Device Read/Write Device
Getting started
3
Distance between the data carriers
Distance between the read/write devices
Data carrier Distance
BIS M-101-...
BIS M-106-...
BIS M-107-...
BIS M-108-...
BIS M-110-...
BIS M-111-...
BIS M-115-...
BIS M-400-045-... > 10 cm > 15 cm > 10 cm
BIS M-401-045-... > 20 cm > 20 cm > 25 cm
BIS M-402-045-... > 10 cm > 10 cm
BIS M-451-045-... > 25 cm
BIS M-102-...
BIS M-112-...
BIS M-105-...
BIS M-122-...
BIS M-120-... BIS M-150-...
BIS M-151-...
Read/write device Minimum distance
BIS M-400-045-0xx-... 20 cm
BIS M-401-045-001-... 60 cm
BIS M-402-045-001-... 20 cm
BIS M-451-045-001-... 60 cm
Note
When installing two BIS M-4xx-...on metal, there is normally no mutual interference. Unfavorable use of a metal frame can result in problems when reading a data carrier. In this case, the read distance is reduced to 80% of the maximum value. In critical applications, a pre-test is recommended.
3.2 Electrical connection
IO-Link port (M12, A-coded, female)
PIN Function
1 +24 V
2 NC
3 GND
4 C/Q
Connect data line to IO-Link Master. (See Balluff IO-Link catalog for connection cable and accessories) Shielded cables are recommended in electromagnetically distorted environments.
Note
For all variants, the ground connection of the read/write device or of the function ground are, depending on the system, to be connected to ground either directly / with low impedance or via a suitable RC combination.
12
BIS M-4xx IO-Link Device Read/Write Device
Basic knowledge
4
4.1 Function principle of Identification Systems
The BIS M-4xx-045 Identification System is a contactless read and write system. The read/write device consists of evaluation electronics with permanently connected read/write head. The system can be used to program and to read information on a data carrier. The data and current status messages are transmitted from the Identification System to the host system via a defined protocol. This protocol can also be used to transmit additional commands to the device, such as switching off the read-head antenna.
The primary components of the BIS M-4xx-045 Identification System are:
Read/write device, – Data carrier.
Data is transmitted to the host system via an IO-Link Master.
Schematic representation of an Identification SystemFig.7:
1 Connection to the IO-Link Master
3 Data carriers 4 Read/write device
The data carrier is an autonomous unit that is supplied with power by the read/write head. The read/write head continuously sends a carrier signal that is picked up by the data carrier from within a certain distance. As soon as the data carrier is powered up by the carrier signal, a static read operation takes place.
The read/write device manages the data transfer between read/write head and data carrier, serves as a buffer storage device, and sends the data to the host controller. The data is passed to the IO-Link Master using IO-Link protocol, and the Master then passes it to the host system.
Host systems may be the following:
a control computer (e.g. industrial PC), – as PLC.
The main areas of application are:
in production for controlling material flow (e.g. in model-specific processes, in workpiece – transport with conveying systems, for acquiring safety-relevant data), in warehousing for monitoring material movements, – transportation, and – conveying technology.
2 Read/write device
www.balluff.com
13
1
3
4
5
6
2
BIS M-4xx IO-Link Device Read/Write Device
Basic knowledge
4
4.2 Example
Topology of a BIS M-4xx-045 Identification SystemFig.8:
1 PLC 2 PC
3 Fieldbus
5 Connection to the host system 6 BIS M-4xx-045 read/write device
4 IO-Link
Master
14
BIS M-4xx IO-Link Device Read/Write Device
Basic knowledge
4
4.3 Read distance/ offset
4.4 Product description
To ensure that data carriers are detected without error and the data can be reliably read, do not exceed a maximum distance and maximum offset between the data carriers and read heads (see Chapter 5 "Technical data“, page 16). The "distance" value refers to the maximum distance from the data carrier to the sensing surface of the read/write head. The "offset" value indicates the maximum offset between the center axis of the data carrier and the center axis of the sensing surface. Data carriers can only be reliably detected and the data reliably read within the permissible read distance and offset. Data carrier detection is indicated by an LED on the device ("TP – Tag Present", see Chapter 5
"Technical data“, page 16). At the same time, the CP bit is set in the input buffer ("CP – Codetag
Present“, see Chapter 9.3 "Process data“, page 32).
BIS M-400-045-0xx-07-S4 read/write device:
M30 threaded tube, – round connector terminations, – integrated read/write head, – the read/write head is suitable for dynamic or static operation, – data carrier is powered by the read/write head using a carrier signal.
BIS M-4x1-045-0xx-07-S4 read/write device:
plastic housing, – round connector terminations, – integrated read/write head, – the read/write head is suitable for dynamic or static operation, – data carrier is powered by the read/write head using a carrier signal.
4.5 Data integrity
BIS M-402-045-0xx-07-S4 read/write device:
metal housing, – round connector terminations, – integrated read/write head, – the read/write head is head suitable for dynamic or static operation, – data carrier is powered by the read/write head using a carrier signal. – read/write head in plastic (...-004-...) or metal housing (...-002-...).
To ensure data integrity, data transfer between the data carrier and read/write device can be monitored using a CRC_16 data check. With the CRC_16 data check, a checksum is written to the data carrier which enables the data to be checked for validity at any time.
Advantages of the CRC_16 data check:
Very high data integrity, even during the non-active phase (data carrier outside the read/write – head)
Restrictions of the CRC_16 data check:
Longer write times, as the CRC must also be written. – User bytes are lost on the data carrier (see table on page 15).
Use of CRC_16 can be parameterized by the user (see Chapter 7 "Parameterizing the read/write
device“, page 26).
www.balluff.com
15
BIS M-4xx IO-Link Device Read/Write Device
Basic knowledge
4
4.6 Autoread
4.7 Supported data carrier types
The Autoread function is used to immediately read out a specific memory area of the data carrier when the data carrier enters the vicinity of the read head. The data quantity in this case is always 8 bytes; the start address can be parameterized.
If a read error occurs during autoread or if the specified data area lies outside the capacity of the data carrier, no error is displayed. In this case, no data is output.
Mifare
Balluff data carrier type
Manufac-
turer
Description Memory
capacity
Usable
bytes with
Memory
type
CRC
BIS M-1_ _-01 NXP Mifare Classic 752 bytes 658 bytes EEPROM
ISO15693
Balluff data carrier type
Manufac-
turer
Description Memory
capacity
Usable
bytes with
Memory
type
CRC
BIS M-1_ _-02 Fujitsu MB89R118 2000 bytes 1750 bytes FRAM
BIS M-1_ _-03 NXP SL2ICS20 112 bytes 98 bytes EEPROM
BIS M-1_ _-04 Texas Inst. TAG-IT Plus 256 bytes 224 bytes EEPROM
BIS M-1_ _-05 Infineon SRF55V02P 224 bytes 196 bytes EEPROM
BIS M-1_ _-06 EM EM4135 288 bytes 252 bytes EEPROM
BIS M-1_ _-07 Infineon SRF55V10P 992 bytes 868 bytes EEPROM
BIS M-1_ _-08 NXP SL2IC553 160 bytes 140 bytes EEPROM
BIS M-1_ _-09 NXP SL2ICS50 32 bytes 28 bytes EEPROM
4.8 IO-Link basic knowledge
Advantages of IO-Link:
Uniform, simple wiring of different devices – Host system can be used to change the device parameters – Remote querying of diagnostic information is possible – Centralized data retention of the device parameters is possible
The manufacturer-specific standard IO-Link sends not only the actual process signal, but also all relevant parameter and diagnostic data on the process level over a single standard cable. Communication is based on a standard UART protocol with 24V pulse modulation; no separate power supply is required.
The BIS M-4xx-045-... is an IO-Link device which uses three-conductor technology (Physics 2). The transfer rate can be configured to 4800 (COM1), 38400 (COM2) or 230400 (COM3) baud. The data quantity of the process data is 10 bytes in each direction (see Chapter 9 "Device
function“, page 31).
16

BIS M-4xx IO-Link Device Read/Write Device
Technical data
5
5.1 Electrical data (valid for all device versions)
5.2 Operating conditions (valid for all device versions)
5.3 BIS M-400-045­001-07-S4
Operating voltage VS 18...30 VDC LPS/Class 2 supplied only
Ripple 1.3 Vss
Current draw 150 mA
Load current capacity in SIO mode Maximum 50 mA
Output C/Q Short-circuit protected
Device interface IO-Link
Storage temperature -20 °C … +85 °C
Ambient temperature 0 °C … +70 °C
EMC
EN 301 489-1/-3 – EN 61000-4-2/-3/-4/-6 – EN 300 330-1
Vibration/shock EN 60068 Part 2 6/27/29/64/32
*For 230.4 kBaud, use shielded cable. **Verified with shielded cable.
Class B Severity 2A/2A/4B*/XA** Power Class 5
Mechanical data
BIS M-400-045-001-07-S4 read/write deviceFig.9:
1 LED 2 Maximum tightening torque 40 Nm
Housing material Nickel-plated brass
Connection M12, 4-pin plug connection
Enclosure rating IP 67
Weight 100 g
www.balluff.com
17

$
/('
/('
/('
/('
$
BIS M-4xx IO-Link Device Read/Write Device
Technical data
5
LED
5.4 BIS M-400-045­002-07-S4
LED Status Function
LED 1 Green Power
LED 1 Yellow Data carrier detected
LED 1 Green flashing
(1 s on / 100 ms off)
IO-Link connection active
BIS M-400-045-002-07-S4 read/write deviceFig.10:
1 LED 2 Maximum tightening torque 40 Nm
Mechanical data
LED
Housing material Nickel-plated brass
Wiring M12, 4-pin plug connection
Enclosure rating IP 67
Weight 100 g
LED Status Function
LED 1 and LED 2 Green Power
LED 1 and LED 2 Yellow Data carrier detected
LED 1 and LED 2 Green flashing
(1 s on / 100 ms off)
IO-Link connection active
18
BIS M-4xx IO-Link Device Read/Write Device
Technical data
5
5.5 BIS M-401-045­001-07-S4
Mechanical data
LED
BIS M-401-045-001-07-S4 read/write deviceFig.11:
1 Maximum tightening torque 3 Nm 2 Earthing connector
3 Sensing surface
Housing material PBT
Connection M12, 4-pin plug connection
Enclosure rating IP 67
Weight 190 g
LED Status Function
LED 1 Green Power
LED 2 Yellow Data carrier detected
LED 1 Green flashing
(1 s on / 100 ms off)
IO-Link connection active
www.balluff.com
19

BIS M-4xx IO-Link Device Read/Write Device
Technical data
5
5.6 BIS M-402-045­002-07-S4
Mechanical data
LED
BIS M-402-045-002-07-S4 read/write device, values in mmFig.12:
1 Maximum tightening torque 25 Nm 2 Maximum tightening torque 2 Nm
3 LED
Housing material AlMGSIO5
Read/write head housing material Nickel-plated brass
Connection M12, 4-pin plug connection
Enclosure rating IP 67
Weight 220 g
LED Status Function
LED 1 Green Power
LED 1 Yellow Data carrier detected
LED 1 Green flashing
(1 s on / 100 ms off)
IO-Link connection active
20
BIS M-4xx IO-Link Device Read/Write Device
Technical data
5
5.7 BIS M-402­045-004-07-S4
Mechanical data
LED
BIS M-402-045-004-07-S4 read/write deviceFig.13:
1 Sensing surface 2 Maximum tightening torque 1 Nm
3 LED
Housing material AlMGSIO5
Read/write head housing material ABS-GF16
Connection M12, 4-pin plug connection
Enclosure rating IP 67
Weight 220 g
LED Status Function
LED 1 Green Power
LED 1 Yellow Data carrier detected
LED 1 Green flashing
(1 s on / 100 ms off)
IO-Link connection active.
www.balluff.com
21
BIS M-4xx IO-Link Device Read/Write Device
Technical data
5
5.8 BIS M-451-045­001-07-S4
Mechanical data
LED
BIS M-451-045-001-07-S4 read/write deviceFig.14:
1 Maximum tightening torque 3 Nm 2 Read/write axis
3 Earthing connector
Housing material PBT
Connection M12, 4-pin plug connection
Enclosure rating IP 67
Weight 360 g
LED Status Function
LED 1 Green Power
LED 2 Yellow Data carrier detected
LED 1 Green flashing
(1 s on / 100 ms off)
IO-Link connection active
22
BIS M-4xx IO-Link Device Read/Write Device
Technical data
5
5.9 Dynamic mode
Memory access
Data carrier detection time
Read times
Write times
The read/write device can read or write each individual byte on the data carrier. But since the data carrier is divided into 16-byte memory blocks, the actual writing can only be performed in blocks. Our processor electronics convert this time accordingly. To calculate the read/write times, the block read or write time must, therefore, always be estima­ted.
Data-carrier detection time
[mm]
BIS M1xx-02 data carrier 40 - 27
BIS M1xx-01 data carrier 30 18 -
Data carrier with 16 byte blocks BIS M-1xx-01 BIS M-1xx-02
First block to be read 20 35
Other started 16 bytes 10 25
Data carrier with 16 bytes per block BIS M-1xx-01 BIS M-1xx-02
First block to be read 40 65
Other started 16 bytes 30 55
All BIS M1xx-01 BIS M1xx-02
Parameter "Used data carrier type“
Maximum speed
Note
Fluctuations in the ms range are possible. Electrical noise effects may increase the read/write time.
To calculate the permissible speed at which the data carrier and head may move relative to one another, the static distance values are used (see Chapter 5 "Technical data“, pages 16 to 23).
The permissible speed is:
Path 2 * |offset value|

max. perm..
V
The offset value is dependent on the read/write distance actually used in the system.
Processing time =
1
Number of started blocks
=
Time Processing time

=
Data-carrier detection time
Read/write time
+
of first block to be read
+ n
Read/write time
1
X
for other started blocks
www.balluff.com
23
BIS M-4xx IO-Link Device Read/Write Device
Technical data
5
Note
The texts, such as "Read time of first block to be read", can also be represented as variables: t
L1.
Example calculation
Read and write 44 bytes starting with address 15 of a BIS M-102-01/L data carrier with EEPROM memory and parameter setting of ALL for "Used data carrier type" using the BIS M-400-045-001-07-S4 read/write device
The distance from the sensing surface of the read/write head to the data carrier is 12 mm. A maximum clear zone is assumed, i.e. installation completely in plastic frame.
Address 15 is in block 1 (15/16 = 0.94 block 1) Address 58 is in block 4 (58/16 = 3.63 block 4)
Therefore, a total of 4 blocks will be processed, where the first block always has a slightly longer read or write time.
Calculation of read/write time:
Total read time = 30 ms + 20 ms + 3 x 10 ms = 80 ms Total write time = 30 ms + 40 ms + 3 x 30 ms = 160 ms
For the specified values, this yields an offset of ± 20 mm.
Calculation of maximum speed:
max.perm.read = 40 mm/80 ms = 0.5 m/s
V
max.perm.write = 40 mm/160 ms = 0.25 m/s
V
Note
Fluctuations in the ms range are possible. Electrical noise effects may increase the read/write time.
24






BIS M-4xx IO-Link Device Read/Write Device
IO-Link basics
6
6.1 Digital point-to­point connection
Three-conductor physics
IO-Link integrates conventional and intelligent actuators and sensors into automation systems. Mixed use of traditional and intelligent devices is possible with no additional expense. IO-Link is intended as a communications standard below the traditional fieldbus level. Fieldbus­neutral IO-Link transmission uses existing communications systems (fieldbuses or Ethernet­based systems). The actuators and sensors are connected in point-to-point connection using conventional unshielded cables. IO-Link devices can send application-specific parameters and data (e.g. diagnostics data) using a serial communication procedure. Flexible telegrams are possible for sending larger quantities of data. Communication is based on a standard UART protocol with 24V pulse modulation. Only one data line is used for communication. This carries both the controller telegram as well as the device telegram. This means that conventional 3-conductor physics is possible.
IO-Link supports both communication mode as well as standard IO mode (SIO). Standard IO provides a switching signal on the communication line, as is used by normal binary switching sensors. This mode is only possible with devices using 3-conductor connection technology.
Three-conductor physics of the IO-LinkFig.15:
Communication mode
Interleave mode
The BIS M-4xx-045... supports both modes. In SIO mode, the "Data carrier in range" (24 V) or "No data carrier in range" (0 V) signal is made available to the host system as a switching signal. If the BIS M-4xx-045… is not used with an IO-Link Master and without triggering IO-Link com­munication, it works in SIO mode and can be operated on a digital input.
The BIS M-4xx-045-... works in communication mode with Frame Type 1. In this transmission type, 2 bytes of process data or required data are sent per frame (data block). This can take place either from the IO-Link Master to the device or vice-versa.Process data are the application­specific data; required data may contain parameters, service or diagnostic data.
So-called "Interleave Mode" makes it possible to send larger quantities of data. There, multiple type 1 frames must be combined into a sequence. One frame with process data and one with required data are sent in alternation. With the BIS M-4xx-045-..., a sequence consists of 20 individual frames. 10 bytes of process data are sent in each direction per sequence. This process data is described in greater detail in
Section 9.3 "Process data“ on page 32.
www.balluff.com
25
BIS M-4xx IO-Link Device Read/Write Device
IO-Link basics
6
6.2 Process data container
6.3 Identification data and device information
The IO-Link protocol provides a process data container 32 bytes in size. Addressing occurs in the command byte, which is sent by the IO-Link Master. When process data is sent, addressing is directly to the subindices 00
hex … 1Fhex.
The BIS M-4xx-045-... processes 10 bytes of input and 10 bytes of output data (input buffer/output buffer). The process data is mapped to the first 10 bytes of the process data container (subindices 00
IO-Link protocol Subaddress
hex
00
...
09hex
hex…09hex).
BIS M-4xx IO-Link device Subaddress
hex
00
...
...
hex
09
0Ahex
...
1Fhex
Via the Service-PDu, in addition to the application-specific parameters, information stored on the device can also be read.
SPDU Object name Length Information
Index Subindex
0hex 8
Vendor ID 2 bytes Balluff Vendor ID = 0378hex
9
10
Device ID 3 bytes Balluff Device ID = 0602xxhex 11 12
10hex 0 Vendor name 7 bytes Balluff
hex 0 Vendor text 15
11
www.balluff.com
bytes
hex 0 Product name 23
12
Device designation
bytes
Identification data
hex 0 Product ID 7 bytes Order code
13
hex 0 Product text 27
14
bytes
hex 0 Hardware revision 5 bytes Hardware version
16
hex 0 Firmware revision 5 bytes Firmware version
17
IO-Link RFID read-write head
26
BIS M-4xx IO-Link Device Read/Write Device
Parameterizing the read/write device
7
7.1 Required data The device-specific parameters of the Identification System can be parameterized via the SPDU. The parameterization data of the BIS M-4xx-045-... is described in the following in greater detail.
Access Description Data
SPDU
Index Subindex
40hex 1hex CRC yes/no 1 byte 0 = without CRC
hex 2hex Dynamic mode
40
- yes/no
hex 3hex Action if tag
40
present
hex 4hex Low byte of start
40
address for
Parameterization data
hex 5hex High byte of start
40
hex 6hex Used data-carrier
40
41
hex 1hex Baud rate 1 byte 00hex = 4800 baud
autoread
address for
autoread
type
width
1 = with CRC
1 byte 0 = no
1 = yes
1 byte 0 = no action
1 = serial number and tag type
7 = automatically read 8 bytes of data beginning at
a set start address after subindex 4 and 5
2 bytes Observe data-carrier specifications. 0
1 byte See Chapter 7.2 "Mapping of parameterization
data“, page 27
hex=ALL
00
hex=BIS M1xx-01
FE
hex=BIS M1xx-02
FF
hex = 38400 baud
01
hex = 230400 baud
02
Value range Factory
setting
0
0
1
0
1
Note
An entire index can be addressed via subindex 0 . For example, with index 40 subindex 1
hex, only the "CRCCheck" parameter is accessed. With index 40hex/subin-
hex/
dex 0, on the other hand, all parameters from "RCCheck" to "Used data carrier type" can be addressed. The parameters are then arranged in byte blocks.
www.balluff.com 27
BIS M-4xx IO-Link Device Read/Write Device
Parameterizing the read/write device
7
7.2 Mapping of parameterization data
CRC_16 Data check
To ensure data integrity, data transfer between the data carrier and read/write device can be monitored using a CRC_16 data check.
With the CRC_16 data check, a checksum is written to the data carrier which enables the data to be checked for validity at any time.
Advantages of the CRC_16 data check:
Very high data integrity, even during the non-active phase (data carrier outside the read/write – head)
Restrictions of the CRC_16 data check:
Longer write times, as the CRC must also be written. – User data capacity is sacrificed. (see table on page 15).
Note
The CRC_16 data check can only be used in combination with data carriers that have been appropriately initialized. If a data carrier is not initialized and this parameter is nevertheless set, CRC errors occur during reading and writing (see Chapter 9.6 "Error
codes" page 43).
The data carriers can be initialized for using CRC16 with command designator 12 The checksum is written on the data carrier as 2 bytes (per block) of information. Thus, 2 bytes of user data is lost per block.
hex.
Dynamic mode
The following figure applies for this parameter:
Index 40hex, subindex 1hex - 1 byte
7-MSB 6 5 4 3 2 1 0-LSB
not relevant 1/0*
* 0 = CRC_16 data check is not used (default setting). 1 = CRC_16 data check is used.
If dynamic mode is activated, a job can be sent even if no data carrier is located in the read/write range of the read/write head, which would result in errors without dynamic mode. The job is then stored and is executed as soon as a data carrier is detected.
The following figure applies for this parameter:
Index 40hex, subindex 2hex - 1 byte
7-MSB 6 5 4 3 2 1 0-LSB
not relevant 1/0*
* 0 = dynamic mode not activated (default setting). 1 = dynamic mode activated.
28
BIS M-4xx IO-Link Device Read/Write Device
Parameterizing the read/write device
7
Action if tag present
Start address for autoread
Data carrier
The "Action on tag present" parameter specifies how the read/write device is to react if a new data carrier is detected in the field. The default setting is to send the UID (serial number). In addition, it is possible to set that nothing or a selected range of 8 bytes is to be sent immediately as read data. The following values are permissible:
Index 40hex, subindex 3hex - 1 byte
0
hex No action
1
hex Send UID immediately
7
hex Immediately send 8 bytes of data beginning at a set address
(parameter "Autoread start address“)
This parameter is only valid if "Autoread“ was selected as the action on tag present. The start address can be set via subindices 4
hex (low byte) and 5hex (high byte). The value range is depen-
dent on the specification of the data carrier; take this into account. An incorrect setting prevents autoread from functioning; no data is output.
This parameter offers the possibility of specifying certain data carrier models that are to be detected. All models, all BIS M1xx-01 models or all BIS M1xx-02 models can be selected. The data carriers are detected more quickly if only those that are used are parameterized. The fol­lowing values are permissible:
Index 40hex, subindex 6hex - 1 byte
0
hex All data carrier models supported by Balluff
FE
hex All BIS M1xx-01 model data carriers
FE
hex All BIS M1xx-02 model data carriers
Baud rate
The Baud Rate parameter can be used to set the used transfer rate. The Min Cycle Time, i.e. the time intervals at which the device may be queried by the IO-Link Master, is dependent on the setting of this parameter. The following table applies:
Index 41hex, subindex 1hex - 1 byte
IO Link
designation
COM1 4800 00
COM2 38400 01
COM3 230400 02
Baud Rate
[baud]
Parameter
Min Cycle Time
setting
hex 60hex = 12.8 ms
hex 35hex = 5.3 ms
hex 20hex = 3.2 ms
Note
Not all IO-Link Masters support COM3. This must absolutely be checked before parameterizing! After the speed has been parameterized once, the device is only parameterized for this speed and can only be reparameterized using a COM3-capa­ble IO-Link Master. The Balluff-USB-Master is recommended for this purpose. Please contact Balluff Sales for further information. After saving the parameter, the M-4xx-045-... performs a reset. During this process, IO Link communication is interrupted and errors can be displayed in the controller. Only after this reset does the device restart with the newly set baud rate.
www.balluff.com 29
BIS M-4xx IO-Link Device Read/Write Device
Parameterizing the read/write device
7
7.3 Storing the parameterization data
The set parameters are stored in the EEPROM memory of the BIS M-4xx-045-... On restart, the most recently used parameters are used.
Note
Should it be necessary to exchange a BIS M-400-045-... in the system, make certain that the correct parameter settings are programmed in the new device.
30
BIS M-4xx IO-Link Device Read/Write Device
Startup
8
For information on starting up, please read the instructions for your IO-Link Master. BIS M4-xx IO-Link devices use a process buffer of 10 bytes for both the input and the output.
www.balluff.com 31
BIS M-4xx IO-Link Device Read/Write Device
Device function
9
9.1 Functional principle
The BIS M-4xx-045 Identification System is a contactless read and write system. The read/write device consists of evaluation electronics with permanently connected read/write head.
The primary components of the BIS M-4xx-045 Identification System are:
Read/write device, – Data carrier.
9.2 Functional principle
Schematic representation of an Identification SystemFig.16:
1 Connection to the IO-Link Master
3 Data carriers 4 Read/write device
The data carrier is an autonomous unit which is supplied with power by the read/write head. The read/write head continuously sends a carrier signal which is picked up by the data carrier from within a certain distance. Once the data carrier is powered, a static read operation takes place.
The processor manages the data transfer between read/write head and data carrier, serves as a buffer storage device, and sends the data to the controller. The data is passed to the IO-Link Master using IO-Link protocol, and the Master then passes it to the host system.
Host systems may be the following:
A control computer (e.g. industrial PC), – A PLC.
The BIS M-4xx-045 supports cyclical data exchange via IO-Link protocol and standard IO mode. Detection of a data carrier (Codetag Present, 24 V) or no data carrier present (0 V) is sent on data line C/Q as a digital switching signal. With cyclical data exchange, read data from the BIS M-4xx-045 are cyclically exchanged with the controller. It is also possible to read or enter parameter data in this operating mode.
2 Read/write device
32
BIS M-4xx IO-Link Device Read/Write Device
Device function
9
9.3 Process data
Output/Input buffer
Data exchange occurs via the process data, which, depending on the control system that is used, is mapped in the input and output buffer or in a memory field. The BIS M-4xx-045 uses 10 bytes of input data and 10 bytes of output data; the assignments are described in the following. Subaddress 00
hex
corresponds to the respective start address in the corresponding data field.
To transfer commands and data between the BIS M-4xx-045 read/write device and the host sys­tem, the BIS M-4xx-045 provides two fields:
– Output buffer – Input buffer
These fields are embedded in process data transmission via the IO-Link Master. As already described, 10 bytes of process data are sent in each direction. The mapping of this process data is described in the following:
Output buffer:
Bit-No.
7 6 5 4 3 2 1 0
Subaddress
hex - 1st bit header TI KA GR AV
00 01
hex Command designator or data
02
hex Start address (low byte) or data
03
hex
04
hex Number of bytes (low byte) or data
05
hex Number of bytes (high byte) or data
06
hex Data
07
hex Data
08
hex Data
09
hex - 2nd bit
TI KA GR AV
Start address (high byte) or data
header
Explanations for output buffer:
Subaddress Bit
Meaning Function description
name
hex 1st bit header
00
TI Toggle bit A state change during a job indicates that the
KA Head on/off 1 = Head off (read/write head switched off)
GR Ground state 1 = Software reset - causes the BIS to switch to
AV Job 1 = New job pending
controller is ready to receive additional data made available by the read/write device.
0 = Head on (read/write head in operation)
the ground state 0 = Normal operation
0 = No new job or job no longer pending
www.balluff.com
33
BIS M-4xx IO-Link Device Read/Write Device
Device function
9
Subaddress Bit
Meaning Function description
name
hex Command
01
designator
or data Data that is to be written on the data carrier
hex Start address
02
Low byte or data Data that is to be written on the data carrier
hex Start address
03
High byte or data Data that is to be written on the data carrier
hex No. of bytes
04
Low byte or data Data that is to be written on the data carrier
hex No. of bytes
05
High byte or data Data that is to be written on the data carrier
00hex = No command 01
hex = Read data carrier
02
hex = Write data carrier
12
hex = Initialize the CRC_16 data check on the
data carrier
hex = Write a constant value on the data carrier
32
Low byte of the start address on the data carrier for the current job
High byte of the start address on the data carrier for the current job
Low byte of the data length for the current job
High byte of the data length for the current job
hex Data Data that is to be written on the data carrier
06
hex Data Data that is to be written on the data carrier
07
hex Data Data that is to be written on the data carrier
08
hex 2nd bit header
09
TI, KA, GR, AV
If 1st and 2nd bit headers agree, valid commands or data are present.
Note
To specify the start address and the number of bytes, the specifications of the used data carrier and the maximum job size of 256 bytes are to be observed!
34
BIS M-4xx IO-Link Device Read/Write Device
Device function
9
Input buffer:
Bit-No. Subaddress
hex - 1st bit header BB HF TO AF AE AA CP
00
hex Error code or data or high-byte version
01
hex Data or low-byte version
02
hex Data
03
hex Data
04
hex Data
05
hex Data
06
hex Data
07
he Data
08
hex - 2nd bit
09 header
7 6 5 4 3 2 1 0
BB HF TO AF AE AA CP
Explanations for input buffer:
Subaddress Bit
Meaning Function description
name
hex 1st bit header
00
BB Power 1 = Device is ready
HF Head Failure 1 = Head is turned off
TO Toggle Bit A state change during a job indicates that the read/
AF Job Error 1 = Job incorrectly processed
AE Job End 1 = Job processed without errors
AA Job accepted 1 = The job was detected and accepted. Is being
CP Codetag Present Data carrier is in the read range of the read/write
0 = Device is in ground state
0 = Head is turned on
write device is ready to transfer other data
0 = Job processed without errors
0 = No job or job running
processed.
0 = No job active
head
No data carrier in read range
www.balluff.com
35
BIS M-4xx IO-Link Device Read/Write Device
Device function
9
Subaddress Bit
Meaning Function description
name
hex Error code Error number is entered if the job was incorrectly
01
processed or canceled. Only valid with AF bit!
hex = No error
00
hex = No data carrier in read/write range
01
hex = Error during reading
02
hex = Data carrier was removed from the read
03 range of the head during reading
hex = Error during writing
04
hex = Data carrier was removed from the write
05 range of the read/write head during writing.
hex = AV-bit is set but command designator is
07 invalid or missing. Or: number of bytes is 00
hex = The CRC on the data carrier does not
0E
agree with the calculated CRC for the read data.
hex = 1st and 2nd bit header of the output buffer
0F do not agree.
hex = Addressing of the job lies outside of the
20 memory range of the data carrier
hex = Calls up a function that is not possible with
21 the current data carrier.
or data Data which was read from the data carrier
or SW version High byte of the software version
hex.
hex Data Data which was read from the data carrier
02
or SW version Low byte of the software version
hex Data Data which was read from the data carrier
03
hex Data Data which was read from the data carrier
04
hex Data Data which was read from the data carrier
05
hex Data Data which was read from the data carrier
06
hex Data Data which was read from the data carrier
07
hex Data Data which was read from the data carrier
08
hex 2nd bit header
09
BB, HF, TO, AF, AE, AA, CPIf 1st and 2nd bit headers agree, there is valid data
present
36
BIS M-4xx IO-Link Device Read/Write Device
Device function
9
Note
The 1st and 2nd headers must be compared by the user (host system) in order to query the validity of the sent data.
9.4 Protocol sequence
When communication is initiated by the IO-Link Master, transmission of the current process data begins.
As long as no data carrier was detected after start-up of the device, the firmware version of the device is displayed in the first two user bytes (see Chapter 9.5 "Protocol examples“, page 37). If a data carrier is detected, the "Reaction to Tag Present" set in the parameterization is execu­ted. If, for example, display serial number is set here, the serial number of the currently detected data carrier is displayed in index 01
The bit headers of the output buffer can be used to control the device. For example, a device restart can be triggered by setting the GR bit or a new job can be passed by setting the AV bit. Furthermore, the write data can be passed to the device here.
The state of the device is displayed in the input buffer. Here, for example, the AF bit indicates an error in the current job and the HF bit indicates that the head is currently switched off. In addi­tion, the input buffer is used to pass read data and status codes. If no data carrier is present, the most recent data is displayed in the input buffer. The deleted CP bit indicates that no data carrier is in the field.
By means of this method, all functions of the read/write device can be used. This includes
reading, – writing, – dynamic reading, – dynamic writing, – writing a constant value, – initializing CRC16 on the data carrier.
hex...08hex.
Note
Note here that a job is limited to a maximum of 256 bytes. If more than 256 bytes are to be processed, multiple, individual jobs must be started.
Functions can only be executed if a data carrier is in the read/write range. If a command is to be sent that is not to be executed until the next tag is encountered, the device must be paramete­rized for dynamic mode (see Chapter 7 "Parameterizing the read/write device“, page 26).
www.balluff.com
37
BIS M-4xx IO-Link Device Read/Write Device
Device function
9
9.5 Protocol examples
1st example
2nd example
The following examples show the protocol sequence in various situations.
Start the device, still no data in the output buffer:
Command from controller
BIS M-4xx-045-... reaction
1. Process output buffer: 2. Process input buffer:
hex GR, KA, AV = 0 00hex Set BB
00
hex GR, KA, AV = 0 01hex e.g. 10hex
09
02
hex e.g. 10hex
09hex Set BB
Reaction to Tag Present = no and new data carrier in the read range:
Command from controller
BIS M-4xx-045-... reaction
1. Process output buffer: 2. Process input buffer:
hex GR, KA, AV = 0 00hex Set CP
00
hex GR, KA, AV = 0 09hex Set CP
09
= V 1.00
3rd example
4th example
Reaction to Tag Present = serial number and new data carrier in the read range:
Command from controller
BIS M-4xx-045-... reaction
1. Process output buffer: 2. Process input buffer:
hex GR, KA, AV = 0 00hex Set CP
00
hex GR, KA, AV = 0 01 ... 08hex UID
09
hex Set CP
09
Reaction to TagPresent = read (start address 5) and data carrier in the read range:
Command from controller
BIS M-4xx-045-... reaction
1. Process output buffer: 2. Process input buffer:
hex GR, KA, AV = 0 00hex Set CP
00
hex GR, KA, AV = 0 01hex Address 5 read data
09
...
01 ... 08
hex Set CP
09
Address 12 read data
hex UID
38
BIS M-4xx IO-Link Device Read/Write Device
Device function
9
5th example
6th example
Data carrier no longer in detection range of the read/write head:
Command from controller
BIS M-4xx-045-... reaction
1. Process output buffer: 2. Process input buffer:
hex GR, KA, AV = 0 00hex Delete CP
00
hex GR, KA, AV = 0 09hex Delete CP
09
Initialization of the CRC_16 data check on the data carrier (256 bytes beginning with address 0):
Command from controller
1. Process subaddresses in the order
BIS M-4xx-045-... reaction
2. Process input buffer:
shown:
hex Command designator 12hex 00hex/09hex Set AA
01
hex Start address 00hex
02
03hex
Start address 00hex
04hex No. of bytes 00hex
05hex No. of bytes 01hex
00hex/09hex Set AV
3. Process subaddresses: 4. Copy received data, process subaddres­ses of the input buffer:
hex... 08hex Enter the first 8 bytes of data 00hex/09hex Invert TO
01
hex... 07hex Invert TI
00
5. Process subaddresses: 6. Copy received data, process subaddres­ses of the input buffer:
hex... 08hex Enter the second 8 bytes of
01
00hex/09hex Invert TO
data
hex... 09hex Invert TI
00
65. Process subaddresses: 66. Copy received data, process sub­addresses of the input buffer:
01
hex... 08hex Enter the last 8 bytes of data 00hex/09hex Set AE
hex... 09hex Invert TI
00
67. Process subaddresses: 68. Process subaddresses:
00
hex/09hex Delete AV 00hex/09hex Delete AA and AE
Note
Repeat the process with the new addresses until the entire memory range of the data carrier is initialized.
www.balluff.com
39
BIS M-4xx IO-Link Device Read/Write Device
Device function
9
7th example
Read 17 bytes starting at data carrier address 10:
Command from controller
1. Process subaddresses in the order
BIS M-4xx-045-... reaction
2. Process input buffer:
shown:
hex Command designator 01hex 00hex/09hex Set AA
01
hex Start address 0Ahex 01hex... 08hex Enter the first 8 bytes of data
02
hex Start address 00hex
03
04hex No. of bytes 11hex
05hex No. of bytes 00hex
00hex/09hex Set AV
3. Copy received data, process subaddres­ses of the input buffer:
hex... 09hex Invert TI 01hex... 08hex Enter second 8 bytes of data
00
5. Copy received data, process subaddres­ses of the input buffer:
hex... 09hex Invert TI 01hex Enter last byte of data
00
4. Process subaddresses of the input buffer:
hex/09hex Invert TO
00
6. Process subaddresses of the input buffer:
hex... 08hex 0x00 (empty)
02
hex/09hex Invert TO, set AE
00
7. Copy received bytes, process sub­addresses of the input buffer:
hex... 09hex Delete AV 00hex/09hex Delete AF and AA
00
8. Process subaddresses of the input buffer:
40
BIS M-4xx IO-Link Device Read/Write Device
Device function
9
8th example Read 30 bytes starting at address 10 with read error:
Command from controller
1. Process subaddresses in the order
BIS M-4xx-045-... reaction
2. Process input buffer:
shown:
hex Command designator 01hex *Error occurred immediately*
01
hex Start address 0Ahex 00hex/09hex Set AA
02
hex Start address 00hex 01hex Enter error number
03
hex No. of bytes 1Ehex 00hex/09hex Set AF
04
hex No. of bytes 00hex
05
00hex/09hex Set AV
3. Evaluate error number and process
subaddresses of the output buffer:
hex... 09hex Delete AV 00hex/09hex Delete AF and AA
00
4. Process subaddresses of the input buffer:
www.balluff.com
41
BIS M-4xx IO-Link Device Read/Write Device
Device function
9
9th example Write 18 bytes starting at data carrier address 20
Command from controller
1. Process subaddresses in the order
BIS M-4xx-045-... reaction
2. Process input buffer:
shown:
hex Command designator 02hex 00hex/09hex Set AA
01
hex Start address 14hex
02
03hex Start address 00hex
04hex No. of bytes 12hex
05hex No. of bytes 00hex
00hex/09hex Set AV
3. Process subaddresses: 4. Copy received data, process subaddres­ses of the input buffer:
hex... 08hex Enter the first 8 bytes of data 00hex/09hex Invert TO
01
hex... 07hex Invert TI
00
5. Process subaddresses: 6. Copy received data, process subaddres­ses of the input buffer:
hex... 08hex Enter the second 8 bytes of
01
00hex/09hex Invert TO
data
hex... 09hex Invert TI
00
7. Process subaddresses: 8. Copy received data, process subaddres­ses of the input buffer:
01
hex... 02hex Enter the remaining 2 bytes of
00hex/09hex Set AE
data
hex... 09hex Invert TI
00
9. Process subaddresses: 10. Process subaddresses:
00
hex/09hex Delete AV 00hex/09hex Delete AA and AE
42
BIS M-4xx IO-Link Device Read/Write Device
Device function
9
10th example
11th example
Write constant data. 20 bytes, value 5A
Command from controller
1. Process subaddresses in the order
hex, starting at address 0:
BIS M-4xx-045-... reaction
2. Process input buffer:
shown:
hex Command designator 32hex 00hex/09hex Set AA
01
hex Start address 00hex
02
03hex Start address 00hex
04hex No. of bytes 14hex
05hex No. of bytes 00hex
06hex Value 5Ahex
00hex/09hex Set AV
3. Data is written
hex/09hex Set AE
00
4. Process subaddresses: 5. Process subaddresses:
00
hex/09hex Delete AV 00hex/09hex Delete AA and AE
Move read/write device to ground state:
Command from controller
BIS M-4xx-045-... reaction
1. Process subaddresses: 2. Process input buffer:
12th example
hex/09hex Set GR 01...08hex 00hex (empty)
00
hex/09hex Delete BB
00
3. Process subaddresses: 4. Process input buffer:
00
hex/09hex Delete GR 00hex/09hex Set BB
Perform head shutdown:
Command from controller
BIS M-4xx-045-... reaction
1. Process subaddresses: 2. Process input buffer:
hex/09hex Set KA 00hex/09hex Set HF, delete CP
00
New data carriers are not detected, antenna is shut down.
3. Process subaddresses: 4. Process input buffer:
hex/09hex Delete KA 00hex/09hex Set HF
00
New data carriers are now detected again.
www.balluff.com
43
BIS M-4xx IO-Link Device Read/Write Device
Device function
9
9.6 Error codes Error
Meaning Remedy
code
hex No data carrier in read/write range Data carriers must already be in the
01
read/write range when a command is sent; otherwise dynamic mode must be parameterized.
hex Read error Repeat job.
02
hex Data carrier was removed from the read
03
range of the head during reading.
hex Write error Repeat job.
04
hex Data carrier was removed from the write
05
range of the read/write head during writing.
hex AV is set, but the command designator is
07
Please check and correct.
invalid or missing. Or: number of bytes is
hex.
00
0E
hex CRC error Data carrier was not successfully read.
Possible causes:
Data carrier defective – Transmission failed – Data carrier not CRC capable
hex Bit header error The two headers in the output buffer and
0F
in the host system do not agree. The headers must be matched (see
"Output buffer“, page 32).
hex Addressing of the job lies outside of the
20
memory range of the data carrier.
hex Calls up a function that is not possible
21
with the current data carrier.
Please correct addressing, taking into account the used data carrier.
Observe permissible commands for the current data carrier.
Note
If an error occurs, a new command cannot be executed until the AV has first been deleted, i.e. the faulty job has been completed in full.
44
BIS M-4xx IO-Link Device Read/Write Device
Device function
9
9.7 Data transmission timing
The sequence of the IO-Link communication is shown in the following diagram. Exchange alter­nates between the input buffer and the output buffer. As soon as current data is pending in one of the buffers, it is exchanged on the next in or out data cycle. The problem arises here that the transmission times can vary greatly. If data is updated shortly before the start of the respective exchange cycle, the transfer lasts just over 10 x cycle time (e.g. t2). If, however, data is updated shortly after the start of an exchange cycle, it lasts a maximum of 3 x 10 x cycle time (e.g. t3).
The processing sequence of a command is shown on the next page using a read job of 9…16 bytes (2 x input buffer for read data) as an example.
IO-Link transmission sequenceFig.17:
t1 Cycle time In-Data: Input data
t2 Polling time Out-Data: Output data
3 Cycle time Process Data Cycle: Process data cycle
t
Byte a+b: Process data
x: Required data
Cycle time t1:
Time until the data of a data carrier that enters the read range is read. The read time is 70 ms x number of parameterized data comparison counts, default = 2 (see Chapter 7.2 "Mapping of
parameterization data“, page 27).
Polling time t
Time until it is recognized that the data carrier is no longer in the read range (polling time). The polling time is xx ms.
Cycle time t
Time between the sending of two frames. The cycle time is dependent on the set baud rate and on the respective Master.
2:
3:
www.balluff.com 45
BIS M-4xx IO-Link Device Read/Write Device
Device function
9
In-Data/Out-Data: Sending of the input data and output data. 10 frames of 2 bytes each are sent, alternating between process data and required data (x).
Process Data Cycle: A process data cycle consists of the complete sending of the input and output data. At the beginning of each process data cycle, the current data are polled and immediately sent.
IO-Link transmission sequenceFig.18:
1 The command is passed on to the IO-Link Master by the controller via a bus system. 2 After the synchronization time t1, the command is passed on to the BIS M-400-045-… via IO-Link. The
duration is dependent on the bus system, the Master, the cycle time and the current state of the IO­Link communication (see problem described above).
3 The processing time begins with the arrival of the command at the M-400-045-…This is composed of
the time for the command processing t2, the time for the actual read operation t3 and the evaluation time for the read data t4. A flat value of max. 3 ms can be estimated for t2 and t3. The pure read time is calculated as described (see Chapter 5.9 "Dynamic mode", page 22). Please note: If the data carrier that is to be read was already detected by the device, the time for data carrier detection is eliminated.
4 The pure time for data carrier processing is shown here. 5 Following another synchronization time t5, the first data is passed on to the IO-Link Master with the next
In-Data cycle. In addition, the AE-bit is set in the bit header. The time for this is t7 = 10 x cycle time.
6 The data is only passed on to the controller via the host bus system. The latency period t6 is dependent
on the bus system and the IO-Link Master.
7 After the first data arrives at the controller, the toggle-bit in the output buffer must be inverted (see
Chapter 9 "Device function“, page 31). In the example, it is assumed that the this occurs immediately
and that the transfer to the IO-Link Master happens fast enough that the BIS M-400-045-… receives the new data on the next Out-Data cycle.
46
BIS M-4xx IO-Link Device Read/Write Device
Device function
9
8 Now, the device places the next and, thus, the last bytes of the read data in the input buffer and inverts
the toggle bit.
9 The controller retrieves the data and deletes the AV bit. 10 The re-updated output buffer is sent to the BIS M-400-045-…. 11 The device ends the read command and deletes the bits in the bit header in the input buffer that belong
to the job .
A maximum command processing time can be approximated as follows:
Note
The sequence for a write command occurs analogously. Here, the data is transfered via IO-Link and the actual writing on the data carrier is interchanged.
proc.max = 40 x tcyc + read/write speed + 5 ms + 30 x tcyc + 20 x tcyc x n
Ttot 5 ms + t
1
2
3
read/write speed
Number of bytes/8 (rounded to the next whole number) Calculated time for data carrier processing (see Chapter 5.9 "Dynamic mode“, page 22) Master Cycle Time.
2
+ tcyc3 x (70 + 20 x n)
1
=
Note
The actual required time may be considerably less than the maximum processing duration.
Note
Prerequisite for calculating the maximum command processing time is that no delays occur in the host bus system and in the controller.
www.balluff.com
47
BIS M-4xx IO-Link Device Read/Write Device
Appendix
Type designation
code
Accessories
(optional, not included)
BIS M – 4xx – 045 – 0xx –07–S4
Balluff Identification System
Series
M = Read and write system, 13.56 MHz
Hardware type
4xx = Read/write device
Software type
045 = Software number, IO-Link
Version
001 = Standard 002 = Tapered
interface
0 7 = IO-Link
module
S4 = M12 4-pin male
Accessories for the BIS M-4xx-... can be found in the Balluff IO-Link catalog.
The catalog can be downloaded on the Internet at "www.balluff.de".
48
BIS M-4xx IO-Link Device Read/Write Device
Appendix
ASCII table
Decimal Hex Control
code
0 00 Ctrl @ NUL 43 2B + 86 56 V
1 01 Ctrl A SOH 44 2C , 87 57 W
2 02 Ctrl B STX 45 2D - 88 58 X
3 03 Ctrl C ETX 46 2E . 89 59 Y
4 04 Ctrl D EOT 47 2F / 90 5 A Z
5 05 Ctrl E ENQ 48 30 0 91 5B [
6 06 Ctrl F ACK 49 31 1 92 5C \
7 07 Ctrl G BEL 50 32 2 93 5D [
8 08 Ctrl H BS 51 33 3 94 5E ^
9 09 Ctrl I HT 52 34 4 95 5F _
10 0 A Ctrl J LF 53 35 5 96 60 `
11 0B Ctrl K VT 54 36 6 97 61 A
12 0C Ctrl L FF 55 37 7 98 62 B
13 0D Ctrl M CR 56 38 8 99 63 c
14 0E Ctrl N SO 57 39 9 100 64 d
15 0F Ctrl O SI 58 3 A : 101 65 e
16 10 Ctrl P DLE 59 3B ; 102 66 f
17 11 Ctrl Q DC1 60 3C < 103 67 g
18 12 Ctrl R DC2 61 3D = 104 68 h
19 13 Ctrl S DC3 62 3E > 105 69 i
20 14 Ctrl T DC4 63 3F ? 106 6 A j
21 15 Ctrl U NAK 64 40 @ 107 6B k
22 16 Ctrl V SYN 65 41 A 108 6C L
23 17 Ctrl W ETB 66 42 B 109 6D m
24 18 Ctrl X CAN 67 43 C 110 6E n
25 19 Ctrl Y EM 68 44 D 111 6F o
26 1 A Ctrl Z SUB 69 45 E 112 70 p
27 1B Ctrl [ ESC 70 46 F 113 71 q
28 1C Ctrl \ FS 71 47 G 114 72 r
29 1D Ctrl ] GS 72 48 H 115 73 s
30 1E Ctrl ^ RS 73 49 I 116 74 t
31 1F Ctrl _ US 74 4 A J 117 75 u
32 20 SP 75 4B K 118 76 V
33 21 ! 76 4C L 119 77 W
34 22 " 77 4D M 120 78 X
35 23 # 78 4E N 121 79 Y
36 24 $ 79 4F O 122 7 A Z
37 25 % 80 50 P 123 7B {
38 26 & 81 51 Q 124 7C |
39 27 82 52 R
40 28 ( 83 53 S 126 7E ~
41 29 ) 84 54 T 127 7F DEL
42 2 A * 85 55 U
ASCII Decimal Hex ASCII Decimal Hex ASCII
125 7D }
www.balluff.com 49
BIS M-4xx IO-Link Device Read/Write Device
Appendix
A
Dimensions 16, 18, 19, 21, 22 Distance
between the data carriers 11
between the read/write devices 11 Sensing surface 8, 9, 10, 16, 17, 18, 20 ASCII table 48 Output buffer 25, 32, 37, 43, 44, 45, 46
B
Baud rate 26, 28, 44 Intended use 7 Operating conditions 16
C
CRC check
Error message 31
D
Data carrier
ISO 15693 15, 26
Mifare 15, 22, 26 Data transfer 12, 14, 27, 31 Data transmission 12
E
Input buffer 14, 25, 32, 34, 36, 38, 39,
40, 41, 42, 44, 46 Electrical data 17 Ground 11 Earthing connector 9, 10, 18, 21
F
Clear zone 23 Function indicators 20 Functional principle 12
I
Startup 5, 7 Installation 5, 7
K
Cable length 9, 10, 19, 20 Characteristic data in combination with
data carriers 22, 23
Communications standard 5, 24
L
Read distance 11, 14, 22
M
Mechanical data 16, 17, 18, 19, 20, 21
P
Protocol examples 36 Process data 14, 15, 24, 25, 32, 36,
44, 45
S
Safety 7
Operation 7 Startup 7 Installation 7
Safety regulations 7
T
Technical data
Operating conditions 16 Electrical data 17 Function indicators 20 Characteristic data in combination
with data carriers 22, 23
Mechanical data 16, 17, 18, 19, 20,
21
Type designation code 47
Z
Accessories 47
www.balluff.com
Balluff GmbH Schurwaldstraße 9 73765 Neuhausen a.d.F. Germany Tel. +49 7158 173-0 Fax +49 7158 5010 balluff@balluff.de
www.balluff.com
Edition 1005; Subject to modifications.
.
No. 870554 E
Loading...