Baldor BC141, BC142, BC142-5, BC142-6 Installation & Operating Manual

5/17 Installation & Operating Manual MN704
BC141, BC142, BC142-5 & BC142-6 DC Control
Any trademarks used in this manual are the property of their respective owners.
Important: Be sure to check www.baldor.com to download the latest version of this manual in Adobe Acrobat PDF format.
i
MN704
Chapter 1 Introduction
Introduction ................................................................ 1-1
Safety Notice ............................................................... 1-1
Receiving ................................................................. 1-2
Chapter 2 Installation
Mounting Instructions ........................................................ 2-1
Electrical Connections ........................................................ 2-1
AC Line Fusing .............................................................. 2-1
AC Line Connection .......................................................... 2-2
Ground Connection .......................................................... 2-2
Permanent Magnet (PM) Motor Connection ........................................ 2-3
Motor Field Connection (Shunt Wound Motors Only) .................................. 2-3
Full Voltage Field ............................................................ 2-3
Plug-In Horsepower Resistor® & Armature Fuse Kit* ................................. 2-3
Armature Fuse* ............................................................. 2-3
Remote Main Speed Potentiometer Connection ..................................... 2-4
Voltage Following Connection .................................................. 2-4
Enable Circuit Connection ..................................................... 2-5
Inhibit Circuit Connection ...................................................... 2-6
DC Tachometer Connection .................................................... 2-6
Armature Switching and Dynamic Braking ........................................ 2-8
Startup & Adjustments ........................................................ 2-8
Trimpot Adjustments ......................................................... 2-9
Operation ................................................................. 2-11
Troubleshooting ............................................................ 2-11
Optional Accessories ........................................................ 2-12
Table of Contents
1-1
MN704
Chapter 1
Introduction
Introduction
Thank you for purchasing the BC141, BC142, BC142-5 or BC142-6 full-wave variable speed DC motor control. The control, with Surface Mount (SMT) construction, offers the user the ultimate in reliability and performance at an affordable price. The controls contain a unique patented super-fast Direct­Fed™ current limit circuit that protects the SCR power bridge against direct shorts1. The reliability of the control is further enhanced with the use of high-surge, 25 Amp SCRs, and AC line and armature fusing2,3. The control is designed with exclusive Plug-In Horsepower Resistor® 3, which eliminates the need for recalibrating IR Comp and Current Limit when the control is used on various horsepower motors. In addition, the rating of the control can be extended to 1.5 HP for controls with 90 Volt DC output and 3 HP for controls with 180 Volt DC output, by the use of an Auxiliary Heat Sink4. Catalog Nos. BC142, BC142-5 and BC142-6 also allow operation of 90 Volt DC motors when used on 208/230 Volt AC line input5.
The versatility of the control is confirmed by its extensive list of standard features, such as: selectable armature or tach feedback and adjustment trimpots for minimum speed, maximum speed, current limit, IR compensation, and linear acceleration and deceleration. The control includes Auto-Inhibit®, which eliminates surging during rapid AC line switching; pulse transformer triggering, which provides cogless operation at low speed; and superior noise rejection circuitry, which eliminates false starts and blown SCRs. Enable (normally closed) and Inhibit (normally open) functions provide electronic switching of control output.
The output voltage of the control is a linear function of the Main Speed Potentiometer setting. In addition, the control can be used in a voltage following mode by supplying an isolated analog input signal to Terminals P2 (+) and P1 (-). The control is compact in size (only 4.30 X 3.64 X 1.25) and easily replaces all competitive speed controls. The control is supplied with a factory installed 25 Amp AC line fuse, a 5 kΩ Main Speed Potentiometer and QD terminals. All models are UL Listed (USA and Canada) and CE Approved.
SAFETY NOTICE
A Warning statement indicates a potentially hazardous situation which, if not avoided, could result in injury or death.
A Caution statement indicates a potentially hazardous situation which, if not avoided, could result in damage to property.
A Note indicates additional information that is not critical to the installation or operation.
WARNING: This equipment may contain voltages as high as 1000 volts! Electrical shock can cause serious or fatal
injury. Only qualified personnel should attempt the start-up procedure or troubleshoot this equipment.
WARNING: Be sure the system is properly grounded before applying power. Do not apply AC power before you
ensure that all grounding instructions have been followed. Electrical shock can cause serious or fatal injury.
WARNING: Electrical shock can cause serious or fatal injury. Be sure that all power is disconnected and there is
no voltage present from this equipment or equipment to which it is or will be connected. Electrical shock can cause serious or fatal injury. Only qualified personnel should attempt the installation and start-up procedures.
WARNING: Electrical shock can cause serious or fatal injury. Verify there is no voltage phase-to-phase or phase-
to-neutral at the motor leads before connecting motor to this control. Motor may have high voltage present even when disconnected from this control.
WARNING: Do not use motor overload relays with an automatic reset feature. These are dangerous since the
process may injure someone if a sudden or unexpected automatic restart occurs. If manual reset relays are not available, disable the automatic restart feature using external control wiring.
WARNING: This unit has an automatic restart feature that will start the motor whenever input power is applied
and a RUN (FWD or REV) command is issued. If an automatic restart of the motor could cause injury to personnel, the automatic restart feature should be disabled.
WARNING: Using a jumper to eliminate the start/stop function will cause the motor to run at the Main Speed
Potentiometer setting when the AC line is applied.
1-2
MN704
SAFETY NOTICE Continued
WARNING: If possible, do not adjust trim pots with the main power applied. Electrical shock can cause serious or
fatal injury. If adjustments are made with the main power applied, an insulated adjustment tool must be used to prevent shock hazard and safety glasses must be worn.
WARNING: Do not use this drive in an explosive environment. An explosion can cause serious or fatal injury.
This drive is not explosion proof.
WARNING: When the Enable jumper is installed, the drive and motor will start and run when AC power is applied,
when power is restored after a momentary power loss, or after an overload or TCL fault is reset. The user must ensure that automatic start up of the driven equipment will not cause injury to operating personnel or damage to the driven equipment. The user is responsible for providing suitable audible or visual alarms or other devices to indicate that the drive may start at any moment. Failure to observe this warning could result in severe bodily injury or loss of life.
WARNING: Do not use start/stop, inhibit or enable functions as a safety disconnect. Use only an AC line
disconnect for that purpose. Failure to observe this warning could result in severe bodily injury or loss of life.
Caution: Disconnect motor leads (A1 and A2) from control before you perform a Dielectric Withstand test on the
motor. Failure to disconnect motor from the control will result in extensive damage to the control. The control is tested at the factory for high voltage / leakage resistance as part of Underwriter Laboratory requirements.
Caution: Do not connect AC power to the Motor terminals A1 and A2. Connecting AC power to these terminals
may damage the control.
Caution: Baldor recommends not to use Grounded Leg Delta transformer power leads that may create ground
loops. Instead, we recommend using a four wire Wye.
Caution: Suitable for use on a circuit capable of delivering not more than 5,000 RMS symmetrical short circuit
amperes listed here at rated voltage.
Caution: Adjusting the current limit above 150% of the motor nameplate rating can cause overheating and
demagnetization of the PM motor.
Caution: Do not leave the motor in a locked rotor condition for more than a few seconds since motor damage
may occur.
Caution: Shunt wound motors may be damaged if field windings remain energized for an extended period of
time without armature rotation.
Receiving
Each control is thoroughly tested at the factory and carefully packaged for shipment. When you receive your control, there are several things you should do immediately.
1. Observe the condition of the shipping container and report any damage immediately to the commercial carrier that delivered your control.
2. Verify that the part number you received is the same as the part number listed on your purchase order.
3. Do not unpack until ready for use.
1-3
MN704
Table 1-1 Electrical Ratings
Catalog Number
AC Line VAC
(±15%, 50/60Hz)
Motor VDC
Rating without Auxiliary Heat Sink
Rating with Auxiliary Heat Sink
Field VDC (1.13 Amps Max)
Max AC Line Current Amps
Max DC Load Current
Amps
Max Power HP (kW)
Max AC Line Current Amps
Max DC Load Current
Amps
Max Power HP (kW)
BC141 115 0-90 12 8 .75 (.6) 24 16 1.5 (1.1) 50, 100
BC142 230
0-180 12 8 1.5 (1.1) 24 16 3 (2.3) 100, 200
0-90* 12 8 .75 (.6) 24 16 1.5 (1.1) 100
BC142-5
115 0-90 9 6 .75 (.6) 18 12 1.5 (1.1) 50, 100
230
0-180 9 6 1.5 (1.1) 18 12 3 (2.3) 100, 200
0-90* 9 6 .75 (.6) 18 12 1.5 (1.1) 100
BC142-6
115 0-90 12 8 .75 (.6) 24 16 1.5 (1.1) 50, 100
230
0-180 12 8 1.5 (1.1) 24 16 3 (2.3) 100, 200
0-90* 12 8 .75 (.6) 24 16 1.5 (1.1) 100
Table 1-2 General Performance Specifications
Description Specification Factory
Setting
Speed Range (Ratio) 50:1
Armature Feedback Load Regulation (0 - Full Load, 50:1 Speed Range) (% Base Speed)
1
Tachometer Feedback Load Regulation (0 - Full Load, 50:1 Speed Range) (% Set Speed)
1
Line Voltage Regulation (at Full Load, ± 10% Line Variation) (% Speed) 0.5
Control Linearity (% Speed vs. Dial Rotation) 2
Acceleration (ACCEL) Trimpot Range (Seconds) 0.2 – 10 2
Deceleration (DECEL) Trimpot Range (Seconds) 0.2 – 10 2
Maximum Speed (MAX) Trimpot Range (% Base Speed) 50 – 110 100
Minimum Speed (MIN) Trimpot Range (% Base Speed) 0 – 30 0
Current Limit (CL) Trimpot Range (% Full Load) 0 – 200 150
IR Compensation (IR) Trimpot Range (at Specified Full Load @ 90, 180 Volts DC Output) (Volts DC)
0 – 24, 48 3, 6
Maximum Operating Ambient Temperature at Full Load - °C / °F 40 / 104