M-Series® M2000
M2000-to-M2000 Interchangeability Procedure
SCOPE
This document defines the process for updating an M2000 amplifier.
LIMITATIONS
For M2000-to-M2000 replacement, all detector sizes are allowed for exchange.
M2000-TO-M2000 ACCURACY STATEMENT
The M2000 amplifier will be within ±0.10% of Full Scale.
M2000-TO-M2000 UPDATE PROCEDURE
1.Record the amplifier pipe diameter: ______________
2.Record the amplifier detector factor: ______________
3.Record the amplifier detector offset: ______________
4.Record all applicable setup parameters in the tables provided in this document.
5.Disconnect power to the amplifier before removing connections.
6.Remove all wiring connections from the amplifier.
7.Remove amplifier PCB/enclosure and replace with new PCB/enclosure.
8.Reconnect Coil/Electrode connections. Reconnect all other pluggable inputs and outputs.
9.Apply power to the amplifier.
10.Configure Pipe Diameter with original value recorded in step 1.
11.Configure Detector Factor with original value recorded in step 2.
12.Configure Detector Offset with original value recorded in step 3.
13.Configure M2000 to remaining parameters recorded in step 4.
RECORD SETUP PARAMETERS
Main Menu
METER SETUP
Scale Factor
Empty Pipe
Power Line Freq
Excitation Freq
Pipe Diameter
Amplifier Factor
Detector Factor
Detector Current
Detector Offset
MEASUREMENTS
Flow Unit
Totalizer Unit
Full Scale Flow
Low Flow Cut Off
Flow Direction
Damping Factor
INPUTS/OUTPUTS
Analog Output
Digital Input
Digital Outputs |
#1 |
#2 |
#3 |
#4 |
|
|
|
|
|
Pulses/Unit |
|
|
N/A |
N/A |
|
|
|
|
|
Pulse Width |
|
|
N/A |
N/A |
|
|
|
|
|
Full Scale Freq |
N/A |
N/A |
|
N/A |
|
|
|
|
|
Preset Amount |
|
|
|
|
|
|
|
|
|
Set Point Min |
|
|
|
|
|
|
|
|
|
Set Point Max |
|
|
|
|
|
|
|
|
|
Output Type |
|
|
|
|
|
|
|
|
|
Select Function |
|
|
|
|
|
|
|
|
|
NNOTE: Tables continue on the next page.
MAG-AS-01086-EN-02 (August 2014)