This manual contains instructions for installing, operating and programming the iSonic 4000 flow meter.
MPORTANTI
Read this manual carefully before attempting any installation or operation. Keep the manual accessible for future reference.
SAFETY PRECAUTIONS AND INSTRUCTIONS
Some procedures in this manual require special safety considerations. In such cases, the text is emphasized with the
following symbols:
SymbolExplanation
Warning indicates the potential for severe personal injury, death or substantial property damage.
Comply with the instructions and proceed with care.
Caution indicates the potential for minor personal injury or property damage. Comply with the
instructions and proceed with care.
Before installing or using this product, please read this instruction manual thoroughly. Only qualified personnel should install
and/or repair this product. If a fault appears, contact your distributor.
Installation
• Do not place any unit on an unstable surface that may allow it to fall.
• Never place the units above a radiator or heating unit.
• Route all cabling away from potential hazards.
• Isolate from the mains before removing any covers.
Power Connection
• Use only the type of power source suitable for electronic equipment. If in doubt, contact your distributor. Ensure that any
power cables are of a sufficiently high current rating.
• All units must be earthed to eliminate risk of electric shock. Failure to properly earth a unit may cause damage to that unit
or data stored within it.
Protection Class
The device has protection class IP 67 and needs to be protected against dripping water, water, oils, etc.
Setup and Operation
Adjust only those controls that are covered by the operating instructions. Improper adjustment of other controls may result in
damage, incorrect operation or loss of data.
Cleaning
Switch off all units and isolate from mains before cleaning. Clean using a damp cloth. Do not use liquid or aerosol cleaners.
Repairing Faults
Disconnect all units from power supply and have it repaired by a qualified service person if any of the following occurs:
• If any power cord or plug is damaged or frayed
• If a unit does not operate normally when operating instructions are followed
• If a unit exposed to rain/water or if any liquid has been spilled into it
• If a unit has been dropped or damaged
• If a unit shows a change in performance, indicating a need for service.
Page 5 November 2018HYB-UM-02509-EN-04
System Description
WARNING
FAILURE TO ADHERE TO THESE SAFETY INSTRUCTIONS MAY RESULT IN DAMAGE TO THE PRODUCT OR SERIOUS BODILY
INJURY.
RoHs
Our products are RoHs compliant.
Battery Disposal
The batteries contained in our products need to be disposed of as per your local legislation, according to EU directive
2006/66/EG.
SYSTEM DESCRIPTION
The iSonic 4000 Ultrasonic flow meter is designated for flow measurements in open channels and partially filled pipes and
volume measurements of liquids in tanks. You can connect one ultrasonic level sensor with 4…20 mA output to the unit.
Flows are consequently calculated from measured levels using pre-programmed formulas for various primary flow elements
(flumes, weirs) or from the Q/h table. The unit can also calculate flow rates in partially filled pipes and angular open channels
using the Manning equation.
• The iSonic 4000 flow meter is an IP67 device in a robust wall-mounted metal case, with a large graphic display.
• The flow meter menu is operated with three front panel high endurance buttons.
• The flow meter is powered externally by 92…275V AC / 50…60 Hz. The DC version is powered externally by 9…36V DC
(maximum 9 W).
• You can operate the flow meter via connection to a USB or Ethernet interface with Flow Meter Tool software, which can be
used for parameter setup and datalogger download.
• The flow meter has an internal datalogger with 2 MB capacity for approximately 130,000 logged lines. You can download
the logged data with the Flow Meter Tool software and save it in .csv format to a PC.
• USB, Ethernet, ADE, RS232, Modbus RS485/RS422 galvanic isolated interfaces are mounted on the board.
• The flow meter has one analog output (0…20 mA or 4…20 mA) and two galvanic isolated pulse outputs.
Nameplate
Look at the device nameplate to make sure the device is delivered according to your order. Check for the correct supply
voltage printed on the nameplate.
Page 6 November 2018HYB-UM-02509-EN-04
System Settings
Flow Meter Tool SettingsSettings Control Panel
System Description
Driver Details
Page 7 November 2018HYB-UM-02509-EN-04
Installation
INSTALLATION
WARNING
INSTALLATION INSTRUCTIONS GIVEN IN THE FOLLOWING ARE TO BE OBSERVED IN ORDER TO PROVIDE
FUNCTIONALITY AND SAFE OPERATION OF THE METER.
Installation the EchoPod DL-10 Sensor
Sensor EchoPod
Viton Gasket
1. Insert the gasket onto the threaded end of the sensor.
2. Screw the sensor into the stainless steel mounting bracket.
OTE:NInstall the sensor at a maximum of 49.21 in. (125 cm) above the flume bottom (minimal measured level) with a
minimum of 1.97 in. (5 cm) distance above the maximal measured level.
Max
125 cm
3. Connect the sensor to the 4…20 mA input terminal on the bottom side of display board.
Active 24V DC, 20 mA, (can be powered by analog output if not used)
1 (-)
2 (+)
3Solid-state relays max. 230V AC, 500 mA, max. 1 Hz (function is linked to Output 2)S1 and S2
Digital input*5…30V DC5 (-) and 6 (+)
RS interfaces*RS232, RS485 and RS422 with Modbus RTU.
Mode can be configured by DIP switches also termination ON or OFF. For the
RS485, connect the A wire to the Y terminal and the B wire to the Z terminal.
422232485
ARxD
B
ZTxDB
YA
G (GND)
USBUSB Device CDC (Host Mass Storage)Micro USB
Ethernet*Ethernet Interface connectionRJ45 socket
* All marked inputs and outputs are according to safety data TNV-1 IEC 60950-1.
Input and Output Cable Connections
For the normal I/Os, use shielded cables. Connect the shield of the cable to one of the grounding screws. Recommended
cable is LiYCY size min. 0.06 sq. in. (0.14 mm²).
Solid-State Output
If using a second cable gland for the normal I/Os, use one cable and cable gland for the power supply and solid-state relay.
Recommended cable size is min. 0.3 sq. in. (0.75 mm²).
• USE SEPARATE CABLE INLETS FOR CABLES CONNECTED TO THE SOLID-STATE RELAY OUTPUT AND CABLES
CONNECTED TO THE OTHER INPUT/OUTPUTS.
• WITH MULTIPHASE POWER, SOLID-STATE RELAY SHOULD HANDLE ONLY THE SAME PHASE THAT IS USED FOR
POWERING THE METER.
Page 11 November 2018HYB-UM-02509-EN-04
Operation
OPERATION
Function Buttons
All programming is accomplished using the three function buttons on the front of the unit. Screen
navigation and digit and parameter selection is performed by a combination of these buttons.
Use the up-arrow to scroll through the menu screens or to advance numerical digits to change values.
Use the right-arrow to select digits from left to right and allows or to enter a submenu.
Use EXIT SAVE to save changed values, return to a previous menu or toggle between Measuring mode and Programing mode.
Display Icons
Minor battery power (Realtime clock)WSensor warming
Device error0Sensor not connected
No keyword activeMSensor measuring
USB activeSSimulation active
Menu Header
MainMenu
MeterSetup
Submenu
Indicates a Submenu
Scroll Bar
Initial Screens
From the Main Menu, press EXIT SAVE to display the current values and system information. The rst screen to display
depends on the application type (open channel or tank).
First screen for
open channel applications:
ParameterValue
Volume 305.6 m
Level 0.50 m
Flow 8.85 m
M
Unit of
Measure
3
3
/s
Icons
First screen for tank applications:Second screen for both applications.
ParameterValue
Unit of
Measure
Application
Version
Tag
Tag: iSonic 4000
1.2.00
Volume 50.3 m
Level 0.503 m
1
3
Icons
Date & Time
Parameter,
Value & Unit
2017-07-30 10:05
Current 10.184 mA
Page 12 November 2018HYB-UM-02509-EN-04
Operation
Setting a PIN
The iSonic 4000 flow meter security feature allows the option to restrict access to the meter by way of a 6-digit Personal
Identification Number (PIN). The system administrator can set up a single PIN for each of the three different levels of access:
• Administration – allows access to all iSonic 4000 flow meter menu configuration screens.
• Service – allows access to service-level and user-level menu configuration screens.
• User – allows access only to user-level menu configuration screens.
OTE:NFor a lost PIN, Contact Badger Meter Technical Support at 800-456-5023 for a replacement PIN.
Not all levels of access need to be set. If no PINs are set up, any user will have access to all functions.
1. From the Main Menu, press the right-arrow.
2. From the Meter Setup menu, press the up-arrow until the Pin menu is displayed.
3. Press the right-arrow to display the PINS Control menu.
4. Press the right-arrow to highlight ON or OFF.
5. With either ON or OFF highlighted, press the up-arrow to display ON.
6. Press EXIT SAVE to save the ON setting.
7. With the Control menu highlighted, press the up-arrow to display the required security level (user, service, or admin).
8. With the required security level highlighted, press EXIT SAVE to display the rst of six zeros (digits).
9. Press the up-arrow to change the rst digit, followed by pressing the right-arrow to select the next digit.
10. Press the EXIT SAVE button to save the PIN number for that security level.
Logging In
To change any parameter, the PIN entered must provide the proper security privilege required by the parameter.
To enter a PIN, go to the Login menu and enter the PIN for the required security level.
Once you are properly logged in, the unlocked icon appears on the meter display.
OTE:NA PIN Error message displays if the incorrect PIN is entered.
Logging Out
To log out, follow steps 1 through 8 under "Setting a PIN". At step 9, enter an invalid PIN, then press EXIT SAVE.
Page 13 November 2018HYB-UM-02509-EN-04
Programming
PROGRAMMING
Main Menu
From the Main Menu, you can access these submenus, each of which is described on the following pages:
• Meter Setup
• Measurements
• Input and Outputs
• Totalizer Reset
• Communication
• Miscellaneous
• Information
• Pin
The security levels are:
A
Administrative
S
Service
U
User
Parameters indicated by the battery icon, if changed, will affect battery performance.
To program the security levels, see "Setting a PIN" on page 13. No passwords were set at the factory.
Page 14 November 2018HYB-UM-02509-EN-04
Meter Setup Menu
Programming
ApplicationTank
A
Open Channel
A
SensorInterval
S
WarmUpTime
S
LowerRangeValue
A
UpperRangeValue
A
Offset
S
Select for a tank application.
Select for an open channel application.
Setup of time measurement interval(s); default value is 1 second; larger
interval (for instance, 300 seconds) is set when unit is powered from
battery
Powering time of sensor(s) before measurement; larger interval is set
when unit is powered from battery
The minimum level value of used sensor = 4 mA in selected level units
The maximum level value of used sensor = 20 mA in selected level units
Level offset in selected level units, depends of sensor mounting position
Page 15 November 2018HYB-UM-02509-EN-04
Programming
Measurement Menu
Length
U
Flow Rate
U
Volume
U
Establishes the unit of measure for the length
DisplayLength Unit
ft Feet
mMeter
in.Inch
cmCentimeter
mmMillimeter
DecimalPlaces – set of the decimal places of the Length values
Establishes the unit of measure for the flow rate
Maximum Water Level /SetDefaultVal.
Set of the Maximum Water Level for the selected primary element – the value is possible to
edit further.
Upper Range Value /Calculate
Is calculating the maximal Flow Rate value for Maximal Water Level - the value is possible to edit
further – this parameter is used also for outputs (Upper Range Value=100% - full range)
Programming
Page 17 November 2018HYB-UM-02509-EN-04
Programming
Open Channel Calculation
Volumetric flow is calculated from actual water level. Actual water level is limited by the maximum water level.
The Exponential Equation for general Parshall or Manhole flume: Q=K.Q
exp
Q – Volumetric flow [m³/s]
K – Coefficient [m
(3-n)
/s]
h – Water level [m]
exp – Exponent [-]
Predefined FlumeEquation [m³/s, m]Max. Water Level [m]
Parshall flume 1 in.Q = 0.0604 • h
Parshall flume 2 in.Q = 0.1207 • h
Parshall flume 3 in.Q = 0.1771 • h
Parshall flume 6 in.Q = 0.3810 • h
Parshall flume 9 in.Q = 0.5350 • h
Parshall flume 12 in.Q = 0.7050 • h
Parshall flume 18 in.Q = 1.0670 • h
Parshall flume 24 in.Q = 1.4290 • h
Parshall flume 36 in.Q = 2.1900 • h
Parshall flume 48 in.Q = 2.9600 • h
Parshall flume 60 in.Q = 3.7500 • h
Manhole flume 4 in.Q = 0.2343 • h
Manhole flume 6 in.Q = 0.3026 • h
Manhole flume 8 in.Q = 0.3424 • h
Manhole flume 10 in.Q = 0.3868 • h
Manhole flume 12 in.Q = 0.4345 • h
1.55
1.55
1.55
1.55
1.55
1.55
1.55
1.55
1.57
1.58
1.59
1.95
1.95
1.95
1.95
1.95
0.230
0.260
0.667
0.724
0.876
0.925
0.925
0.925
0.925
0.925
0.925
0.149
0.227
0.313
0.396
0.457
Contracted rectangular weir
Equation Q = 1.84 • (L - 0.2 • h) • h
1.5
Q – Volumetric flow [m³/s]
1.84 – Coefficient [√m/s]
L – Width [m]
h – Water level [m]
Suppressed rectangular weir
Equation Q = 1.84 • L • h
1.5
Q – Volumetric flow [m³/s]
1.84 – Coefficient [√m/s]
L – Width [m]
h – Water level [m]
Cipoletti rectangular weir
Equation Q = 1.84 • L • h
1.5
Q – Volumetric flow [m³/s]
1.84 – Coefficient [√m/s]
L – Width [m]
h – Water level [m]
V-notch weir 30°
2
Equation Q=8å tan
12
2 • g
30
2
(
)
Q – Volumetric flow [m³/s]
g – Standard gravity 9.80665 [m/s2]
h – Water level [m]
• 0.586 • (h + 0.0021)
2.5
Page 18 November 2018HYB-UM-02509-EN-04
V-notch weir 45°
2
Equation Q=8å tan
Q – Volumetric flow [m³/s]
g – Standard gavity 9.80665 [m/s2]
h – Water level [m]
V-notch weir 60°
Equation Q=8å tan
Q – Volumetric flow [m³/s]
g – Standard gavity 9.80665 [m/s2]
h – Water level [m]
V-notch weir 90°
Equation Q=8å tan
Q – Volumetric flow [m³/s]
g – Standard gavity 9.80665 [m/s2]
h – Water level [m]
12
12
12
2 • g
2 • g
2 • g
45
2
(
2
60
2
(
2
90
2
(
• 0.580 • (h + 0.0015)
)
• 0.577 • (h + 0.0012)
)
• 0.578 • (h + 0.0008)
)
Programming
2.5
2.5
2.5
2/3
2/3
)
)
2
2
1/2
I
A Rh=A/P
• √I• h • L +
2/3
• √ I •
| h > r
)
| h ≤ r
)
Manning equation: Q = 1/n Rh
Manning rectangular
Equation Q =
1
n
(
Q – Volumetric flow [m³/s]
n – Gauckler-Manning coefficient [s/3√m]
L – Width [m]
h – Water level [m]
a – Angle [°]
I – Water surface slope [m/m]
Manning pipe
Equation Q =
2 • π - 2 • arcsin
a =
2 • arcsin
Q – Volumetric flow [m³/s]
n – Gauckler-Manning coefficient [s/3√m]
L – Width [m]
h – Water level [m]
I – Water surface slope [m/m]
Establishes the range of the analog output signal: 0…100% (= full scale). The
following current output ranges are available:
• 0…20 mA
• 4…20 mA
• 0…10 mA
Analog output active
Analog output passive
OTE:NIf an error message displays, set the current according the
programing of the Alarm Mode below. When you select bidirectional
operation, you can signal the flow direction via digital outputs.
This parameter configures the behavior of the analog output during alarm
conditions. The options are OFF, 3.5 mA and 23 mA.
• OFF: Analog signal is based on flow rate and always within the
configured range.
• 3.5 mA: During alarm conditions, the analog signal is 3.5.
• 23 mA: During alarm conditions, the analog signal is 23 mA.
For example, if the analog range is 4…20 mA and the alarm mode is set
to 23 mA, then during a full scale flow alarm condition, the analog output
current will be 23 mA.
Correction of the current value output.
S
Digital Input
Digital input lets you reset totalizers (remote reset), interrupt flow measurement (PosZeroReturn) or
ADE. Input switching is provided by applying an external potential of 5…30V DC
S
or by an internal voltage source of 24V DC (analog output if not used).
Page 20 November 2018HYB-UM-02509-EN-04
Digital OutputsYou can configure functional operation of the 2 digital outputs. For example, you can select
Forward Pulse for the digital output and define the pulses per totalizer unit via pulse scale.
Digital Outputs 1 and 2SThe two outputs can be operated as open collector passively or actively.
Passive output
Active output (if analog output is not used)
Programming
Solid-State Relay
S
The solid-state relay is functionally linked with Output 2.
See "Out 1 / 2 Function" below.
Page 21 November 2018HYB-UM-02509-EN-04
Programming
Digital OutputsPulse Width
S
Pulse/Unit
S
Out 1 /2 Function
S
Output 1 /2 Type
This parameter establishes the ON duration of the transmitted pulse. The
configurable range is from 0…2000 ms. If 0 ms is configured, pulse width is
automatically adapted depending on pulse frequency
(pulse/pause ratio 1:1).
During the configuration the program checks if pulses/unit and pulse width
are in accordance with full scale defined. If not, an error alarm displays and
scale, pulse width or full scale need to be adapted.
The Pulses/Unit parameter lets you set how many pulses per unit of measure
to transmit. The maximum output frequency of 10,000 pulses/sec. (10 kHZ)
must not be exceeded.
The following functions can be selected for the Output 1, Output 2 and the
Solid-State Relay. The Solid-State Relay function is linked functionally with
Output 2.
FunctionOut1Out2 / Solid-State Relay
OffXX
Forward pulseXX
Min/Max AlarmXX
Error alarmXX
Pump ControlXX
TestXX
ADEX
• OFF: Digital output is switched off.
• Forward pulse: Generates pulses during forward flow conditions.
• Min/Max Alarm: Indicates when flow rate exceeds thresholds defined by
Set Min. or Set Max. in % of full scale. See “Figure 3: Tank volume or open-
channel flow rate” on page 23.
• Error alarm: Indicates when the meter has error an condition.
• Pump Control: Starts or stops the pump. See “Figure 3: Tank volume or
open-channel flow rate” on page 23.
• Test: Used only for the Verification Device.
• ADE: Used for BEACON and AquaCUE connectivity.
The output type parameter lets you set the output switch to “normally
closed“ or “normally open“.
S
Output 1 /2 Set Min
S
Output 1 /2 Set MaxSThe Flow Max Set Point establishes, as a percentage of full scale flow, the
Flow SimulationSFlow Simulation provides analog and digital output simulation based on a percentage of the full scale
flow in cases where no real flow is occurring. The range of simulation includes 0…100% in steps of 10%
of the full scale flow. This function remains active when you exit the menu. You must set it to Off to
deactivate it. If the simulation is still active, a character “S” displays in the Measuring mode.
The flow Min Set Point establishes, as a percentage of full scale flow, the
minimum threshold at which the output alarm activates. Select thresholds in
1% steps. Flow rates below or above the threshold activate the output alarm.
maximum threshold at which the output alarm activates. Select thresholds in
1% steps. Flow rates below or above the threshold activate the output alarm.
Page 22 November 2018HYB-UM-02509-EN-04
Programming
Clear Total
Total
A
Figure 3: Tank volume or open-channel flow rate
Resets the totalizer within the ClearTot item on the Flow Meter Tool software.
Page 23 November 2018HYB-UM-02509-EN-04
Programming
Communications Menu
InterfacesModbus® RTURS232, RS485 and RS422 with Modbus RTU.
Mode can be configured by DIP switches also if termination ON or OFF.
Parity: Even, Odd, Mark, Received Packets, Sent Packets
EthernetModbus TCP/IP with MEAP-Header
IP AddressIPv4 address default 192.168.1.60
IP MaskIPv4 subnetting reference default 255.255.255.0
IP GatewayGateway address default 192.168.1.1
MAC AddressMedia-Access-Control-Address
Power upThe number of times that the unit has been powered on.
LanguageThe unit supports these languages: English, German, Czech, Spanish, French, Russian
DateSet the system date in the format [DD.MM.YY]; used for data logging.
TimeSet the system time in the format [HH.MM.SS]; used for data logging.
ContrastThe contrast of the display can be adjusted between 14 (low) and 49 (high).
Datalog PeriodThe data logging period can be adjusted to every 10 min / 20 min / 30 min / 1 h / 24 h.
There is a 2 MB memory with about 130,000 data records for data logging available. The logging
capacities (uni-directional mode) and durations are:
10 min up to 2.50 years
20 min up to 5 years
30 min up to 7.5 years
1 h up to 15 years
24 h up to 260 years
The logging information can be downloaded by a PC program Flow Meter Tool.
Page 24 November 2018HYB-UM-02509-EN-04
Programming
Info Menu
Serial NumberSerial number of the electronic board.
VersionSoftware version of the device.
Compilation DateDate of the software version.
Otp CRCChecksum of software update
Application CRCChecksum of application
PIN Menu
The menus and parameters can be secured via three password levels. See "Setting a PIN" on page 13.
• Administrator PIN
• Service PIN
• User PIN
The password protection is a 6-digit PIN [000000] and is deactivated at the factory.
The first time you use the unit, activate the password protection Control = On and enter login with the password 000000.
Then go back to the PIN again and enter [User], [Service] and [Admin] password.
Once the password protection has been activated, enter your PIN under Login and the lock open symbol appears.
The PIN grants you access to Administrator, Service or User levels with the respective access rights. You can now move to the
menu and enter parameters.
Without a login, you can read all parameters, but cannot change them.
ControlActivate and deactivate the PIN
UserUser logged in with this PIN can access all User levels, but do not have access to Service or
Admin functions.
ServiceUser logged in with this PIN will have access to both service and user-level procedures. User at this
level will not have access to administrative functions.
AdminUser logged in with this PIN will have access to both service and user-level procedures.
Random NumberIn case of losing PIN read the random number. This number has to be sent to Badger Meter support,
which is able to generate the Emergency PIN. Between reading random number and entering received
emergency PIN, do no try to play with emergency PIN and do not restart the meter.
Emergency PINIn case of losing PIN read the random number. This number has to be sent to Badger Meter support,
which is able to generate the emergency PIN. Between reading random number and entering received
emergency PIN, do no try to play with emergency PIN and do not restart the meter.
Login Menu
LoginOnce the password protection has been activated, enter your PIN.
Page 25 November 2018HYB-UM-02509-EN-04
Main Board
LED1
LED2
LED3
LED10
Troubleshooting
TROUBLESHOOTING
The following error messages may display:
DescriptionPossible CauseRecommended Action
Pulse OutputPulse rate exceeds the maximum
EEPROMConfiguration file is missingContact support
ConfigurationConfiguration file is corruptedContact support
Low BatteryLow backup battery (memory)Contact support
Measure
Timeout
Measurement was not completed within specific timeContact support
The following LEDs on the board control the operation of the device:
LED1 No function attached
LED3 Communication – transmit (On = active)
LED5 Flash memory activity (DISK)
LED6 Digital output #1 (On = active)
LED7 Digital output #2 (On = active)
LED8 No function attached
LED10 Power ON (On = active)
LED13 USB, HOST mode (On = active)
Replace Meter’s Electronics
WARNING
DISCONNECT AUXILIARY POWER BEFORE OPENING THE BODY COVER.
1. Pull out all the plugs.
2. Loosen screws S1-S4 and take out circuit board.
3. Insert the new circuit board and attach it by fastening the screws S1-S4.
4. Plug in all plugs.
5. If necessary, congure the new board.
Page 26 November 2018HYB-UM-02509-EN-04
SPECIFICATIONS
TypeiSonic 4000
Auxiliary power92…275V AC (50/60 Hz), < 14 VA optional 9…36V DC, < 4 W
Analog output
Level sensor input4…20 mA from level sensor
Digital outputs
Digital input5…30V DC; totalizer reset, positive return zero, BEACON/AquaCUE connectivity
Programming portMini USB, IP67
Configuration3 front-panel mounted push-buttons
CommunicationRS485 Modbus RTU, Modbus TCP/IP Ethernet, BEACON/AquaCUE connectivity
Pulse lengthConfigurable up to 2000 msec
Datalogger2 MB capacity with 130,000 logged lines: date, level, flow rate, tank volume
DisplayGraphical LCD 64 × 128, backlight, actual flow rate, totalizers, status display
BodyDie cast powder-coated aluminium, protection class IP67
Cable inletSupply and signal cables 2 × M20; cable glands included
Signal cableFrom meter M20; cable gland included
Ambient
temperature
4…20 mA, 0…20 mA, 0…10 mA ≤ 800 Ohm, active or passive; Assigned parameter depends on flow
meter mode
2 open collectors; passive: max. 32V DC, 0…100 Hz 100 mA, 100…10.000 Hz 20 mA; active: 24V DC,
max 20 mA; Select active pulse, min/max alarm, error messages or pump control
Solid-state relay (n.o./n.c.) max 230V AC, 500 mA, 1 Hz; Function is linked with open collector output 2
Serial Number
Version
Compilat. Date
Otp CRC
Applicat. CRC
Pin
Control
User
Service
Admin
Random Number
Emergency PIN
2400
4800
9600
19200
38400
115200
Odd
Italiano
Türkçe
PPolski
Login
Login
Page 30 November 2018HYB-UM-02509-EN-04
Flow Meter ModBus® Register Table
FLOW METER MODBUS® REGISTER TABLE
Address RegistersRightsNameiSonic
0x0000U16Read only PRODUCT_CODE7: iSonic
0x00018Read only PRODUCT_NAME“iSonic 4000”
0x000916Read only FW_NAME"iSonic_A_STM32F107RC"
0x001910Read only APP_VERSIONVersion
0x002316Read only COMPILATION_DATEDate of compilation
0x003316Read only COMPILATION_TIMETime of compilation
0x00435FactoryIDENTIFICATION_NUMBERUnique number
0x00483Read only OTP_BOOT_CHECKSUMChecksum
0x004B3Read only FLASH_OS_CHECKSUMChecksum
0x0115FloatRead only MEASUREDry calibration
0x0119U16Read only MEASURE_COUNTERDry calibration
0: 50 Hz
1: 60 Hz
1: 4…20 mA
2: 0…20 mA
3: 0…10 mA
0 normally open
1 normally closed
0: Off
1: Comparator
3: Error alarm
4: Forward
10: Test
14: Pump
0 normally open
1 normally closed
0 Off
1 Min/Max Alarm
3 Error alarm
4 Forward pulses
10 Test
14 Pump control
0 English
1 German
2 Czech
3 Spanish
4 French
5 Russian
6 Italian
7 Turkish
Page 31 November 2018HYB-UM-02509-EN-04
Flow Meter ModBus® Register Table
Address RegistersRightsNameiSonic
1: save configuration
2: restore configuration
6: save totalizers
7: clear totalizers
8: clear totalizers
14: current loop calibration point A
15: current loop calibration point B
16: current loop calibration complete
22: default save
0x0125U16AdminCOMMAND
23: remote reset
24: default restore
26: make file system
34: press key up
35: press key right
36: press key save exit
38: print screen
41: open channel – calculate upper
range
42: open channel – use default water
0x023E4UserPASSWORD_SET_USERSecurity
0x02424ServicePASSWORD_SET_SERVICESecurity
0x02464AdminPASSWORD_SET_ADMINSecurity
0x025BU64Read only FS_TOTInternal Disk Size [byte]
0x025FU64Read only FS_FREInternal Disk Free Space [byte]
10: 10 min
20: 20 min
0x0263U16ServiceDATALOGGER_PERIOD
30: 30 min
61: 1 hour
84: 24 hour
0x0267U16ServiceMEDIANFilter setting
0x0268U16ServiceMOVING_AVERAGEFilter setting
0x0279FloatRead only ANALOG_OUTPUT_KDry calibration
0x0281FloatRead only ANALOG_OUTPUT_QDry calibration
0x02B3FloatServiceANALOG_OUTPUT_ COMPENSATIONAnalog Output Compensation
0x02E3U32Read only POWER_UP_COUNTERPower up counter
0x0300U16AdminDATAPROCESSING_TANK_ OPENCHANNEL
0 Tank
1 Open Channel
44 Feet
45 Meters
0x0301U16UserUNITCODES_LENGTH
47 Inches
48 Centimeters
49 Millimeters
15 Cubic Feet Per Minute
16 Gallons Per Minute
17 Liters Per Minute
18 Imperial Gallons Per Minute
19 Cubic Meter Per Hour
22 Gallons Per Second
23 Million Gallons Per Day
24 Liters Per Second
0x0302U16UserUNITCODES_ VOLUMETRICFLOW
0x030CFloatFactorySENSOR_ DIVISIONTOCURRENT_KDry calibration
0x030EFloatFactory SENSOR_ DIVISIONTOCURRENT_QDry calibration
0x0310FloatRead only SENSOR_WATERLEVELActual water level
0x0312FloatRead only DATAPROCESSING_ OPENCHANNELFLOWActual volumetric flow
0x0314FloatRead only DATAPROCESSING_TANKVOLUMEActual tank volume
0x0316FloatRead only TOTALIZERTotalizer
0x0318FloatRead only SENSOR_CURRENTSensor actual current
0x032016UserDESIGNATION_CURRENTUTF-8 Designation of sensor current
0x033016UserDESIGNATION_ WATERLEVELUTF-8 Designation of water level
0x034016UserDESIGNATION_FLOWUTF-8 Designation of flow
0x035016UserDESIGNATION_VOLUMEUTF-8 Designation of volume
0x036032UserDESIGNATION_TAGUTF-8 Designation of device
0x0380FloatServiceSENSOR_ WATERLEVELOFFSETOffset
0x0388FloatAdminSENSOR_ UPPERRANGEVALUE_ ACTUALUNITSensor description
0x0390FloatRead only SENSOR_WATERLEVEL_ ACTUALUNITActual water level
0x0392FloatRead only
0x0394FloatRead only DATAPROCESSING_ TANKVOLUME_ACTUALUNITActual tank volume
0x0396FloatRead only TOTALIZER_ACTUALUNITTotalizer
0x0398FloatServiceSENSOR_ WATERLEVELOFFSET_ ACTUALUNITOffset
0x0500Float, FloatAdminYesYesConversion Table Point 0Water Level [m], Volume [m³] or Flow[m³/s]
……
0x08FCFloat, FloatAdminYesYesConversion Table Point 255—
Points in conversion table have to be sorted in ascending order (higher address higher water level value).
Table can be shorter. First unused point has to contain NAN value.
Rights
1 User
2 Service
3 Admin
4 Factory
Page 35 November 2018HYB-UM-02509-EN-04
iSonic 4000, Open-Channel Flow Meter
WIRING THE ISONIC 4000 METER TO AN ORION® CELLULAR LTE
ENDPOINT
1. Connect the RED Encoder Clock signal wire from the endpoint to the Digital Input on the iSonic 4000.
2. Connect the GREEN Encoder Data signal wire from the endpoint to the Digital Output 1 positive signal on the iSonic 4000.
3. Connect the BLACK Encoder Ground signal wire from the endpoint to the Digital Output 1 negative signal on the
iSonic 4000.
4. Jumper the iSonic 4000 Digital Output 1 negative signal to the Digital Input negative signal.
For detail information on installing and activating ORION Cellular LTE endpoints, see the "ORION Water Endpoints User Manual",
available on our website at www.badgermeter.com.