Industrial Registers
Model ER-9 and ER-9/R (Remote) Digital Resettable Totalizer
DESCRIPTION
The Badger Meter® Model ER-9 register is a meter-mounted
totalizer and rate indicator with scaled pulse output
designed for use with all meters in the Badger Meter
product line.
The ER-9/R is the remote version and can be used with any
Badger Meter flow meter that is equipped with a compatible
pulse endpoint. A rear adapter plate is provided with the
remote version for attachment to a wall or other suitable
surface.
The unit is battery powered with two lithium batteries.
Optical sensors and other electronic sensors with open
collector outputs must be externally powered.
The totalizing function uses an easy-to-read, 8-digit numeric
LCD display. The rate mode uses a similar 4-digit display.
Step-by-step independent programming of scale factors for
the rate and totalization functions allows you to program
any engineering unit such as gallons per minute and total
gallons. The scaled pulse output has its own independent
scaler.
When the indicator is used as a totalizer, the display can be
reset to zero from the front panel button or from an external
switch wired directly to a rear terminal. The front panel Reset
function can be inhibited.
You can backlight the display by connecting a DC power
source to the unit.
When the battery is low, an indicator appears on the screen
several weeks before the end of the battery life to remind
the operator that the battery is in need of replacement. The
unit operates off the batteries for a minimum of 6 months
when using pulse output. When connected to a DC power
source, the back-up battery life is 5 years.
FEATURES
• All solid-state components for long life
• Battery powered
• Low battery indicator
• Corrosion-resistant plastic housing built to
NEMA 4X specifications
• Programmable for rate of flow and totalization
• Backlit display available
• Front panel totalizer Reset function can be disabled
• Reprogramming can be inhibited
OPERATION
Fluid flowing through the meter causes pulses to be
generated by the sensor. Each pulse represents a specific
fluid volume.
Example: the Model 25 Disc meter generates 198 pulses
for every gallon of fluid passing through the meter. Using
a scale factor, the pulse indication on the display will be
changed to a meaningful unit of measure.
REG-DS-00200-EN-05 (August 2013)
• Scaled pulse output
Product Data Sheet
SPECIFICATIONS
Count Input (Terminal 2)
Type NPN signal, contact closure
Count speed NPN, 280 Hz maximum,
Contact, 95 Hz maximum
Logic Low < 1.0V DC, High > 2.0V DC
Minimum pulse
NPN=1.78 μs, Contact=5 ms
width
Maximum input 28V DC
Impedance 1 Meg to V BATT
Front Panel Program Enable (Terminal 5)
Type NPN signal, contact closure; level
sensitive
Maximum input 28V DC
Remote Reset Input (Terminal 4)
Type NPN signal, contact closure; edge
sensitive
Frequency
30 Hz (50% duty cycle)
response
Maximum input 28V DC
Output (Terminals 6 & 7)
Type Isolated Photomos relay
Load rating 0.1 Amp @ 30V AC/V DC
Transition time < 5 ms
Operating Temperature
Indicator 32…140° F (0…60° C)
Power Source
Type Dual 3V Lithium battery
Replacement
62576-001
part #
Battery life
expectancy
5 years typical if using external DC
supply
6 months if used alone with 50% duty
cycle output
Low power
indicator
“Low Bat” flashes on display approx. 2
weeks prior to end of battery life
Display
Type Supertwist LCD for use with or without
backlighting
Number 8 digits count value, 4 digits (plus
dummy zero) for rate value
Height 12 mm (0.472")
Backlighting Green Illumination over whole
viewable area with a 10…28V DC
supply
(Terminal 8)
Physical
Dimensions 36 mm × 72 mm, 38 mm deep
1.417" × 2.835", 1.496" deep
Mounting Panel mount (mounting bracket
supplied)
33 mm × 68 mm (+ 0.3 mm) panel
cutout
1.299" × 2.677", (+ 0.012") panel cutout
Connections Up to 8 screw terminals
Weight Approximately 13 ounces
WIRING TERMINALS
1
4 5
3
2
1
Trademarks appearing in this document are the property of their respective entities.
Due to continuous research, product improvements and enhancements, Badger Meter reserves the right to change product or system specications without notice, except to the
extent an outstanding contractual obligation exists. © 2013 Badger Meter, Inc. All rights reserved.
6
7
8
www.badgermeter.com
The Americas | Badger Meter | 4545 West Brown Deer Rd | PO Box 245036 | Milwaukee, WI 53224-9536 | 800-876-3837 | 414-355-0400
México | Badger Meter de las Americas, S.A. de C.V. | Pedro Luis Ogazón N°32 | Esq. Angelina N°24 | Colonia Guadalupe Inn | CP 01050 | México, DF | México | +52-55-5662-0882
Europe, Middle East and Africa | Badger Meter Europa GmbH | Nurtinger Str 76 | 72639 Neuen | Germany | +49-7025-9208-0
Czech Republic | Badger Meter Czech Republic s.r.o. | Maříkova 2082/26 | 621 00 Brno, Czech Republic | +420-5-41420411
Slovakia | Badger Meter Slovakia s.r.o. | R acianska 109/B | 831 02 Bratislava, Slovakia | +421-2-44 63 83 01
Asia Pacic | Badger Meter | 80 Marine Parade Rd | 21-04 Parkway Parade | Singapore 449269 | +65-63464836
China | Badger Meter | 7-1202 | 99 Hangzhong Road | Minhang District | Shanghai | China 201101 | +86-21-5763 5412 Legacy Document Number: ITB-095-04
DC common
2
Count input – NPN signal 280 Hz max. or dry contact
3
Not Used
4
Remote reset – resets count value when switched to common
5
Front panel program enable – allows access to program mode
when connected to common
6
Solid-state relay, pulse output (+)
7
Solid-state relay, pulse output (–)
8
DC supply input, 1…28V DC for backlighting and/or powering
the output