Installation, Operation, and Maintenance Manual
Save these instructions. This document is the property of the owner of this equipment and is
required for future maintenance. Leave this document with the owner when installation or
service is complete.
RECEIVING AND INSPECTION
Upon receiving unit, check for any interior and exterior damage, and if found, report it
immediately to the carrier. Also check that all accessory items are accounted for and are
damage free.
WARNING!!
Installation of this control should only be performed by a qualified professional who has read
and understands these instructions and is familiar with proper safety precautions. Improper
installation poses serious risk of injury due to electric shock, and other potential hazards.
Read this manual thoroughly before installing or servicing this equipment. ALWAYS
disconnect power prior to working on module.
March 2011, Rev 3
A0017477
TABLE OF CONTENTS
WARRANTY .................................................................................................................................................. 3
PIPING SIZE SELECTION ............................................................................................................................ 4
INSTALLATION ............................................................................................................................................. 7
Plumbing ................................................................................................................................................... 7
Site Preparation .................................................................................................................................... 7
Assembly .............................................................................................................................................. 7
Electrical ................................................................................................................................................... 7
Field Wiring ........................................................................................................................................... 7
MAINTENANCE .......................................................................................................................................... 11
Start-Up and Maintenance Documentation ........................................................................................ 12
Factory Service Department ............................................................................................................... 12
2
WARRANTY
This equipment is warranted to be free from defects in materials and workmanship, under normal use and
service, for a period of 12 months from date of shipment. This warranty shall not apply if:
1. The equipment is not installed by a qualified installer per the MANUFACTURER’S installation
instructions shipped with the product,
2. The equipment is not installed in accordance with federal, state and local codes and regulations,
3. The equipment is misused or neglected,
4. The equipment is not operated within its published capacity,
5. The invoice is not paid within the terms of the sales agreement.
The MANUFACTURER shall not be liable for incidental and consequential losses and damages
potentially attributable to malfunctioning equipment. Should any part of the equipment prove to be
defective in material or workmanship within the 12-month warranty period, upon examination by the
MANUFACTURER, such part will be repaired or replaced by MANUFACTURER at no charge. The
BUYER shall pay all labor costs incurred in connection with such repair or replacement. Equipment shall
not be returned without MANUFACTURER’S prior authorization and all returned equipment shall be
shipped by the BUYER, freight prepaid to a destination determined by the MANUFACTURER.
3
PIPING SIZE SELECTION
Equivalent Pipe Length For Various Pipe Fittings
Pressure Drop (PSI) per Equivalent Foot of Waterline - Pipe Size
Waterline Pipe Size (PSI per foot of pipe)
To ensure proper operation of the Self Cleaning System, a minimum of 30 PSI water operating pressure
during spraying must be achieved at the hood nozzles. For this to occur, proper sizing of the water line is
required. Use the following steps to calculate the piping minimum size.
1. Use the Minimum Pressure Requirements for Lengths of Hood chart and find the minimum PSI
required at the hood inlet. Subtract this value from the available PSI at the panel pressure gauge.
Maximum panel operating pressure is 50 PSI. This will be your maximum allowable pressure
drop for field installed pipes between the panel and the hood.
2. Most fittings add an equivalent pipe length to the total run. Use the chart below to calculate the
equivalent pipe length for installed fittings. If you have multiple fittings of one type, simply multiply
the number below by the total number of the fitting and add to the total run length.
3. To calculate the total flowing pressure drop between the panel and the hood, take the total
equivalent length found in step 2 and add the total linear field installed pipe length. Multiply this
number by the value found in the table below, Pressure Drop (PSI) per Equivalent Foot of
Waterline. (Gallons per minute is calculated by multiplying the length of the hood by 0.7 GPM)
This will be the friction pressure drop between the hood and the panel.
4. Add in the pressure drop due to gravity. This must be evaluated to overcome any rise in pipe
elevation between the panel and the hood. There is .43 PSI/ft of vertical rise of pressure drop..
5. Now, compare the maximum allowable pressure drop from step 1 to the calculated pressure drop
from step 3. If the calculated pressure drop exceeds the maximum allowable pressure drop,
increase the pipe size and recalculate steps 2 and 3. Continue this step until the calculated
pressure drop is below the maximum allowable.
4