Axiom Industries SF100 User Manual

MODEL SF100 PACKAGED HYDRONIC SYSTEM FEEDER
The SF100 contains everything required to feed and pressurize closed hydronic heating or cooling systems in a neat, simple package that is easy to install and operate. It is compatible with both water and water/glycol solutions.
FEATURES and BENEFITS
208 litre (55 US gallon) tank for storage and mixing
Plugs into any standard 115 VAC outlet
Fluid level switch shuts the pump off if the storage tank level gets low
Accumulator tank prevents excessive pump cycling
No direct connection to potable water supply eliminates need for backflow prevention
Make-up fluid stored in the feeder tank can be pre-treated
Diverter valve for purging of air on initial start-up and manual agitation of solution
Prevents major floods - in the event of system rupture, only the contents of the tank can be pumped into the system
Provides leak detection - dropping fluid level provides immediate notice that the system has developed a leak
Fluid drained for service can easily be put back into the system
Flexible connection hose with system check valve makes installation easy
Represented By:
SF100 HYDRONIC SYSTEM FEEDER TECHNICAL INFORMATION
WEIGHT - 16 kg, 35 lbs.
ELECTRICAL
115/60/1, 0.7 amps 3-prong plug and cord
PUMP PERFORMANCE
0.09 l/s (1.4 gpm) @ free flow
0.06 l/s (1.0 gpm) @ 345KPa (50 psig) Self-priming up to 2.1 m (7 feet) Maximum liquid temp. 77 C (170 F)
Certified to CAN/CSA 9901055 C22.2 No. 68 Conforms to UL73
SPECIFICATION
Hydronic system feeder shall be AXIOM INDUSTRIES LTD. Model SF100. System shall include 208 litre (55 US gallon) storage/mixing tank with cover; pump suction hose with inlet strainer; pressure pump with thermal cut-out; integral pressure switch; integral check valve; cord and plug; pre-charged accumulator tank with EPDM diaphragm; manual diverter valve for purging air and agitating contents of storage tank; pressure regulating valve adjustable (35 – 380 KPa; 5 – 55 psig) complete with pressure gauge; built-in check valve; union connection; 12 mm (½”) x 900 mm (36”) long flexible connection hose with check valve; low level pump cut-out. Pressure pump shall be capable of running dry without damage. Power supply 115/60/1 0.7 A. Unit shall be completely pre-assembled and certified by a recognized testing agency to CSA standard C22.2 No 68.
ACCESSORIES
2PRV – Second Pressure Reducing Valve, Pressure Gauge, System Connector Hose and Check Valve to allow
for independent pressure supply to a second system.
RIA10-1-SAA – Low Level Alarm Panel c/w Remote Monitoring Dry Contacts and Selectable Audible Alarm
LIMITED WARRANTY
24" - 610 mm
Axiom SF100
Mixing &
Storage Tank
55 US Gallons
208 Liters
49" - 1245 mm
The SF100 is warranted against defects in materials and workmanship for one year.
Project Location
Consultant Contractor
Unit Tag Sales Agent
Loading...