AXEON R1 User Manual

Reverse Osmosis
User’s Manual
Model
R1-1140, R1-2140, R1-3140, R1-4140, R1-5140, R1-6140
R1-6140 Pictured
MKTF - 211 07/26/12
Left Blank
MKTF - 211 07/26/12
2
TABLE OF CONTENTS
INTRODUCTION ................................................................................................................................... 4
SAFETY ................................................................................................................................................ 4
FEED WATER AND OPERATION SPECIFICATIONS .................................................................................. 5
REJECTION, RECOVERY AND FLOW RATES............................................................................................ 5
SYSTEM REQUIREMENTS AND OPERATION GUIDELINES....................................................................... 6
MEMBRANE ELEMENTS ....................................................................................................................... 8
R1-1140, R1-2140, R1-3140, R1-4140, R1-5140, R1-6140 ................................................................... 16
SYSTEM IDENTIFICATION ................................................................................................................... 16
SYSTEM PURGING.............................................................................................................................. 21
INITIAL START-UP .............................................................................................................................. 22
OPERATING DO’s AND DON’Ts........................................................................................................... 24
OPERATION AND MAINTENANCE....................................................................................................... 24
MEMBRANE REMOVAL AND REPLACEMENT ...................................................................................... 26
FLUSHING THE SYSTEM...................................................................................................................... 28
PREPARING UNIT FOR STORAGE OR SHIPMENT ................................................................................. 28
REVERSE OSMOSIS TROUBLESHOOTING ............................................................................................ 29
TEMPERATURE CORRECTION FACTORS FOR MEMBRANE................................................................... 31
OPERATION ....................................................................................................................................... 33
DRAWINGS ........................................................................................................................................ 34
MKTF - 211 07/26/12
3
211
Your R1-Series
system is a durable piece of equipment which, with proper care, will last for many years.
outlines installation, operation
sustained performance of your system.
The test results which are included with this Users Manual indicate your system’s permeate (product) and
If your system is altered at the site of operation
your local dealer or distributor to determine the proper recovery for your application.
NOTE: IN ORDER TO MAINTAIN
MUST BE MAINTAINED AND COPIES WILL NEE
OPERATING OR SERVICING THE
MANUAL MUST BE READ AND FULLY UNDERSTOOD. KEEP THIS AND OTHER ASSOCIATED
INFORMATION FOR FUTURE REFERENCE AND FOR N
PERSONNEL NEAR THE SYSTEM
The Safety section of this User’s Manual outlines the various safety headings used throughout this
manual’s text and are enhanced and defined below:
NOTE: INDICATES STATEMENTS THAT PROVIDE
CAUTION: INDICATES STATEMENTS THAT ARE USED TO IDENTIFY CONDITIONS OR
PRACTICES THAT COULD RESULT IN EQUIPMENT OR OTHER PROPERTY DAMAGE.
WARNING: INDICATES STATEMENTS THAT ARE USED TO IDENTIFY CONDITIONS OR
RACTICES THAT COULD RESULT IN INJURY OR LOSS OF LIFE. FAILURE TO FOLLOW
WARNINGS COULD RESULT IN SERIOUS INJURY OR EVEN DEATH.
DO NOT UNDER ANY CIRCUMSTANCE; REMOVE ANY CA
DESCRIPTIVE LABELS FROM THE SYSTEM.
, maintenance, and troubleshooting
or if the feed water conditions
WARRANTY, AN OPERATING LOG
D TO BE SENT TO YOUR LOCAL DEALER OR
REVERSE OSMOSIS SYSTEM, THIS USERS
EW OPERATORS OR QUALIFIED
FURTHER INFORMATION AND CLARIFICATION.
TION, WARNING, OR OTHER
This User’s Manual
concentrate (waste) test results.
DISTRIBUTOR FOR REVIEW. NOTE: PRIOR TO
INTRODUCTION
details vital to the
change, please contact
THE MANUFACTURER’S
.
SAFETY
P
U
MKTF -
4
07/26/12
FEED WATER & OPERATION SPECIFICATIONS
Nothing has a greater effect on a reverse osmosis system than the feed water quality.
NOTE: IT IS VERY IMPORTANT TO MEET THE MINIMUM FEED WATER REQUIREMENTS. FAILURE TO DO SO WILL CAUSE THE MEMBRANES TO FOUL AND VOID THE MANUFACTURER’S WARRANTY.
NOTE: HIGHER FEED TDS AND/OR LOWER TEMPERATURES WILL REDUCE THE SYSTEM’S
PRODUCTION.
REJECTION, RECOVERY AND FLOW RATES
R1-Series reverse osmosis systems are designed to produce permeate water at the capacities indicated in the “design basis section on page 21 of this manual. For example, the R1-6140 produces 6.25 gallons per minute of permeate water at the listed operating test conditions.
The amount of total dissolved solids (TDS) rejected by the membrane is expressed as a percentage. For example, a 99% rejection rate means that 99% of total dissolved solids do not pass through the membrane. To calculate the % rejection, use the following formula:
% Rejection = [(Feed TDS – Product TDS) / Feed TDS] x 100
Example:
99% = [(550-5.5)/550] x 100
NOTE: ALL TDS FIGURES MUST BE EXPRESSED IN THE SAME UNITS, TYPICALLY PARTS PER MILLION (PPM) OR MILLIGRAMS PER LITER (MG/L).
R1-Series reverse osmosis systems are designed to reject up to 99% NaCl, unless computer projections have been provided or stated otherwise.
MKTF - 211 07/26/12
5
211
The amount of permeate
water recovered for use is expressed as a percentage. To calculate % recovery,
% Recovery = (Product Water Flow Rate / Feed Water Flow Rate) x 100
% Rejection = [(Feed TDS
NOTE: ALL FLOW RATES MUST BE EXPRESSED IN THE SAME UNITS.
SYSTEM REQUIREMENTS
gh pressure pumps used on R1
feed pressure of 4
FEED WATER CONNECTION
FNPT Sole
inlet piping to the 1
Be certain that all of the
PERMEATE (PRODUCT WATER) CONNECTION
n (Depending on the unit)
sure that the permeate water can flow freely
damage to the membrane elements.
with PVC fittings, or other FDA approved materials
into the permeate water.
H OF THE REVERSE O
LOWER THAN THE FEED WATER PH. A LOW PH CAN BE VERY AGGRESSIVE
TO SOME PLUMBING MATERIALS SUCH AS COPPER PIPING.
Product TDS) / Feed TDS] x 100
OPERATION GUIDELINES
systems require a continuo
the feed water are soluble at the concentrations
labeled permeate and attach to storage tank
Backpressure can cause
1” or 3/4” (Depending on the unit)
.
SMOSIS PERMEATE WATER WILL TYPICA
.
use the following formula:
PLUMBING
Example:
26% = (1.04/4.00) x 100
Example:
99% = [(550-5.5)/550] x 100
AND
The membranes and hi with a minimum
1. Locate the 1 (Figure 1A, Page 14)
2. Attach the
3.
attained in the system.
Locate the 1” or 3/4” connectio En irreversible be run to the holding tank being used does not leach
CAUTION THE p
BE 1-2 pH UNITS
-Series
5 psi, not to exceed 90°F.
noid Valve feed water inlet.
FNPT Solenoid Valve feed water inlet.
dissolved solids within
with no backpressure.
The
us flow of water
.
permeate line can
This is so the material
LLY
MKTF -
6
07/26/12
211
CONCENTRATE (WASTE WATER) CONNECTION
Locate the
1” or 3/4” connection (Depending on the unit)
to an open drain in a free and unrestricted manner (no backpressure).
break be used on the concentrate line to prevent siphoning of water from the pressure vessels
CAUTION: ANY RESTRICTIONS OR BLOCKAGE IN THE DRAIN LINE CAN CAUSE
BACKPRESSURE, WHICH WILL INCREASE THE SYSTEMS OPERATING PRESSURE. THIS CAN
RESULT IN DAMAGE TO THE SYSTEMS MEMBRANES AND COMPONENTS.
Series
hase
nsure that the electrical circuit supplying the system is compatible with the re
ED
ACCORDANCE WITH LOCAL AND NATIONAL ELECTRICAL CODES (NEC).
WARNING: TO REDUCE THE RISK OF ELECTRICAL SHOCK, THE INCOMING
SUPPLY MUST INCLUDE A PROTECTIVE EARTH GROUND.
systems are typically controlled with a liquid level switch in a storage tank. The liquid level
switch turns the system on when the water level in the tank drops, and off when the tank is full
level switches can be obtained by your local dealer or distributor. If a liquid level switch is to be used,
systems are supplied with a
ists between the two pre
Filtration systems, if required.
NOTE: THE SYSTEM MUST BE OPERATED
Series systems is of the
Follow these guidelines to ensure proper operation of the pump:
and
The motor is available
system is equipped with a 5 foot electrical
uirements of the specific
THAT A LICENSED ELECTRICIAN WIRE YOUR SYSTEM IN
. Change the cartridge
. Ask your local deale
WATER ONLY.
stainless
be run dry. Operating the pump without sufficient feed water will damage
uirements of the specific
the concentrate line that an air­when the system is in standby.
ELECTRICAL
labeled concentrate
attach to a drain. Run
It is advised
The motor used on the R1­220/460 Volt, 50/60 Hertz, 1 P cord.
E R1 model you are installing.
NOTE: IT’S RECOMMEND
R1-Series
install it at this time.
PRE-FILTRATION
R1-Series when a 10-15 psi differential ex about Pre-
systems are pump and motor combination.
/3 phase. Each R1-Series
5 micron sediment filter
-filter gauges
in
q
POWER
. Liquid
once a month or
r or distributor
USING FILTERED FEED
PUMP
The pump used on the R1-
The pump must NEVER
the pump.
MKTF -
multi-stage centrifugal
7
steel type.
07/26/12
ALWAYS feed the pump with filtered water. The pump is susceptible to damage from sediment
and debris.
If any damage occurs to your system’s pump a re-build kit may be available. Contact your local
dealer or distributor and inform them of your system’s model and pump size.
MOUNTING
The free standing system should be bolted down in compliance with local regulation standards or securely fastened.
MEMBRANE ELEMENTS
R1-Series reverse osmosis systems come pre-loaded with Thin Film Composite (TFC) HF4 High Flow Extra Low Energy membranes, unless otherwise specified. General membrane element performance characteristics are listed on the following pages:
HF4-STANDARD
MKTF - 211 07/26/12
8
HF5-OPTIONAL
MKTF - 211 07/26/12
9
NF3-OPTIONAL
MKTF - 211 07/26/12
10
NF4-OPTIONAL
MKTF - 211 07/26/12
11
LC LE-4040-OPTIONAL
MKTF - 211 07/26/12
12
MKTF - 211 07/26/12
13
LC HR-4040-OPTIONAL
MKTF - 211 07/26/12
14
MKTF - 211 07/26/12
15
R1-1140, R1-2140, R1-3140, R1-4140, R1-5140, R1-6140
SYSTEM IDENTIFICATION
FIGURE 1A
MKTF - 211 07/26/12
16
NUMBER IDENTIFICATION
1. SOLENOID VALVE – TURNS ON/OFF FEED WATER
2. 5 MICRON SEDIMENT – REMOVES PARTICULATES
3. PRESSURE GAUGE – MEASURES FEED PRESSURE
4. PRESSURE GAUGE – MEASURES PRESSURE AFTER FILTERS
5. PRESSURE GAUGE – MEASURES PUMP PRESSURE
6. PRESSURE GAUGE – MEASURES CONCENTRATE PRESSURE
7. COMPUTER CONTROL – CONTROLS RO SYSTEM FUNCTIONS
8. RECYCLE VALVE – RECYCLES CONCENTRATE BACK TO FEED (IF APPLICABLE)
9. CONCENTRATE VALVE– CONTROLS FLOW OF CONCENTRATE (WASTE) WATER TO THE DRAIN
10. RO PUMP AND MOTOR – PRESSURIZES RO SYSTEM
11. THROTTLE VALVE CONTROLS FLOW OF PUMP
12. FLOW METER MEASURES FLOW OF PERMEATE WATER
13. FLOW METER MEASURES FLOW OF CONCENTRATE (WASTE) WATER
14. FLOW METER MEASURES FLOW OF CONCENTRATE RECYCLE WATER
15. PRESSURE SWITCH – TURNS OFF RO PUMP WHEN FEED PRESSURE FALLS BELOW 15PSI
16. PERMEATE CHECK VALVE – PROTECTS MEMBRANE ELEMENTS FROM BACKPRESSURE
17. PRESSURE VESSELS – HOUSES MEMBRANE ELEMENTS
18. PERMEATE SAMPLE VALVE- MEASURES THE QUALITY OF EACH MEMBRANE
MKTF - 211 07/26/12
17
FIGURE 1B
MKTF - 211 07/26/12
18
Loading...
+ 40 hidden pages