Axeon LT-200, LT-300 User Manual

Reverse Osmosis
User’s Manual
Model
LT-200, LT-300
LT-300 Pictured
Left Blank
LT – Series User’s Manual MKTF-210 06/12
2
Table of Contents
INTRODUCTION.................................................................................................................................4
SAFETY..............................................................................................................................................4
FEED WATER AND OPERATION SPECIFICATIONS .........................................................................5
REJECTION, RECOVERY AND FLOW RATES...................................................................................5
SYSTEM INSTALLATION AND START-UP PROCEDURES................................................................6
MEMBRANE ELEMENTS....................................................................................................................8
LT-200, LT-300 SYSTEM IDENTIFICATION......................................................................................11
LT-200 MEMBRANE FLOW DIAGRAM .............................................................................................15
LT-300 MEMBRANE FLOW DIAGRAM .............................................................................................16
DESIGN BASIS FOR LT-200, LT 300 ................................................................................................17
OPERATING DO’s AND DON’Ts.......................................................................................................18
MAINTENANCE PROCEDURES.......................................................................................................18
MEMBRANE REMOVAL AND REPLACEMENT ................................................................................20
PREPARING UNIT FOR STORAGE OR SHIPMENT.........................................................................22
REVERSE OSMOSIS TROUBLESHOOTING....................................................................................23
TEMPERATURE CORRECTION FACTORS FOR MEMBRANE ........................................................25
OPERATION .....................................................................................................................................27
DRAWINGS.......................................................................................................................................28
LT – Series User’s Manual MKTF-210 06/12
3
Your LT-Series
system is a durable piece of equipment which, with proper care, will last
for many years. This User’s Manual
troubleshooting details vital to the sustained performance of your system.
The test results which are included with this Users Manual indicate your systems
concentrate (
ed at the site of operation
ease contact your local dealer or distributor to determine the proper recovery for your
NOTE: IN ORDER TO MAINTAIN
OPERATING LOG MUST BE MAINTAINED AND COPIES WILL NEED TO BE SENT TO
YOUR LOCAL DEALER OR DISTRIBUTOR FOR REVIEW.
NOTE: PRIOR TO
SYSTEM, THIS USERS MANUAL MUST BE READ AND FULLY UNDERSTOOD. KEE
THIS AND OTHER ASSOCIATED INFORMATION FOR FUTURE REFERENCE AND
FOR NEW OPERATORS OR QUALIFIED PERSONNEL NEAR THE SYSTEM
The Safety section of this Users Manual outlines the various safety headings used
throughout this manuals text and are enha
NOTE: INDICATES STATEMENTS THAT PROVIDE FURTHER INFORMATION AND
CAUTION: INDICATES STATEMENTS THAT ARE USED TO IDENTIFY
CONDITIONS OR PRACTICES THAT COULD RESULT IN EQUIPMENT OR OTHER
WARNING: INDICATES STATEMENTS THAT ARE USED TO IDENTIFY
CONDITIONS OR PRACTICES THAT COULD RESULT IN INJURY OR LOSS OF LIFE.
FAILURE TO FOLLOW WARNINGS COULD RESULT IN SERIOUS INJURY OR EVEN
,
or if the feed water conditions
THE MANUFACTURERS
REVERSE OSMOSIS
INTRODUCTION
outlines installation, operation
maintenance and
permeate (product) and If your system is alter
pl application.
SAFETY
waste) test results.
change,
WARRANTY, AN
OPERATING OR SERVICING THE
P
.
CLARIFICATION.
PROPERTY DAMAGE.
DEATH.
LT – Series User’s Manual MKTF-210
nced and defined below:
4
06/12
DO NOT UNDER ANY CIRCUMSTANCE
OR OTHER DESCRIPTIVE LABELS FROM THE SYSTEM.
FEED WATER AND
Nothing has a greater effect on a reverse osmosis system than the feed water quality
NOTE: IT IS VERY IMPORTANT TO MEET THE MINIMUM FEED WATER
REQUIREMENTS.
FAILURE TO DO SO WILL CAUSE THE MEMBRANES TO FOUL
AND VOID THE MANUFACTURERS WARRANTY.
NOTE: HIGHER TDS AND/OR LOWER TEMPERATURES WILL REDUCE THE
REJECTION, RECOVERY AND
everse osmosis systems
capacities indicated by the suffix in the systems name under the conditions listed
T
test conditions.
U
OPERATION SPECIFICATIONS
FLOW RATES
are designed to produce permeate
T
permeate
OPERATING LIMITS
REMOVE ANY CA
TION, WARNING,
.
SYSTEM’S PRODUCTION.
LT-Series r above. For example, the L
-300 produces 300 gallons per day of
the listed operating
LT – Series User’s Manual MKTF-210
5
water at the
water at
06/12
The amount of total dissolved solids (TDS) rejected by the membrane is expressed as a percentage. For example, a 98.5% rejection rate means that 98.5% of total dissolved solids do not pass through the membrane. To calculate the % rejection, use the following formula:
% Rejection = [(Feed TDS – Product TDS) / Feed TDS] x 100
Example:
98.5% = [(550-8.25)/550] x 100
NOTE: ALL TDS FIGURES MUST BE EXPRESSED IN THE SAME UNITS,
TYPICALLY PARTS PER MILLION (PPM) OR MILLIGRAMS PER LITER (MG/L).
LT-Series reverse osmosis systems are designed to reject up to 98.5% NaCl, unless computer projections have been provided or stated otherwise.
The amount of permeate water recovered for use is expressed as a percentage. To calculate % recovery, use the following formula:
% Recovery = (Product Water Flow Rate / Feed Water Flow Rate) x 100
Example: 28% = (0.14/0.50) x 100
NOTE: ALL FLOW RATES MUST BE EXPRESSED IN THE SAME UNITS,
TYPICALLY GALLONS PER MINUTE (GPM).
SYSTEM INSTALLATION AND START-UP PROCEDURES
1. Inspect the system for any damage that could have occurred during shipment. Although our systems have been individually inspected, complete a quick inspection of the fittings, tubing and other components.
2. Please provide a reasonable amount of space for installation and leave 6 inches of space below the filter housings for ease of maintenance.
LT – Series User’s Manual MKTF-210 06/12
6
NOTE: THE REVERSE OSMOSIS SYSTEM SHOULD BE INSTALLED INDOORS AND IT IS SUGGESTED THAT IT NOT BE IN DIRECT SUNLIGHT OR EXTREME COLD.
3. Connect the 3/8” or 1/4” tube fitting to an incoming water source. The minimum water pressure should be at least 30 psi. The system’s minimum operating pressure is 80 PSI, but the optimum operating pressure is 100 psi.
NOTE: DO NOT OPERATE AT A PRESSURE EXCEEDING 125 PSI. The operating pressure can be increased on the face of the booster pump by turning the hex screw clockwise.
4. Connect the concentrate 1/4” tubing (waste) line to drain.
5. Plug the booster pump transformer into a power supply of 110 or 220 volts.
6. This system has been designed with an auto-flush restrictor. This restrictor automatically flushes the reverse osmosis system for 30 seconds every time it starts up and once every hour when the system is producing water.
NOTE: THE TANK PRESSURE SWITCH WILL SHUT THE SYSTEM OFF
AUTOMATICALLY WHEN THE BLADDER TANK IS FULL.
7. The sediment filter and carbon must be serviced regularly for optimal performance. The filters and water quality should be checked every two weeks minimum.
8. Dispose of the product water until the conductivity of the product water reaches your desired level. Use any TDS or Conductivity meter to monitor the product water quality. A minimum quality of 96% NaCl rejection is recommended.
LT – Series User’s Manual MKTF-210 06/12
7
NOTE: ANY CHLORINE EXPOSURE WILL DAMAGE THE MEMBRANE
PERMANENTLY.
9. This system has been factory wired and preset with a pressure switch at 20 - 40 psi, which is only to be used with a pressurized bladder tank. If using an atmospheric storage tank, a float switch will be required to turn the system on and off.
MEMBRANE ELEMENTS
LT-Series reverse osmosis systems come pre-loaded with Thin Film Composite (TFC) HF4 High Flow Low Energy membranes, unless otherwise specified. General membrane element performance characteristics are listed on the next page.
LT – Series User’s Manual MKTF-210 06/12
8
HF4-STANDARD
LT – Series User’s Manual
9
MKTF-210 06/12
NF3-OPTIONAL
LT – Series User’s Manual
10
MKTF-210 06/12
NF4-OPTIONAL
LT – Series User’s Manual
11
MKTF-210 06/12
Loading...
+ 24 hidden pages