capacities indicated by the suffixinthesystem’snameundertheconditionslisted
For example, the D
at the listed operating test conditions.
U
OPERATION SPECIFICATIONS
FLOW RATES
are designed to produce permeate
00 gallons per day of
OPERATING LIMITS
REMOVE ANY CA
TION, WARNING,
.
SYSTEM’S PRODUCTION.
DT-Series r
above.
DT – Series User’s Manual
MKTF-208
T-10000 produces 100
5
water at the
permeate water
06/12
The amount of total dissolved solids (TDS) rejected by the membrane is expressed as a
percentage. For example, a 98.5% rejection rate means that 98.5% of total dissolved
solids do not pass through the membrane. To calculate the % rejection, use the
following formula:
NOTE:ALLFLOW RATES MUST BE EXPRESSED IN THE SAME UNITS,
TYPICALLYGALLONS PER MINUTE (GPM).
SYSTEM REQUIREMENTS AND OPERATION GUIDELINES
PLUMBING
The membranes and high pressure pumps used on DT-Series systems require a
continuous flow of water with a minimum feed pressure of 45 psi, not to exceed 85°F.
FEED WATER CONNECTION
1. Locate the 2” FNPT feed water inlet on the 18” FSI bag filter housing.
(Figure 1A, Page 15)
2. Attach the inlet piping to the 2” FNPT feed water inlet.
DT – Series User’s Manual
MKTF-20806/12
6
3.
Be certain that all ofthecomponentsofthefeedwateraresolubleatthe
ttainedinthesystem.
NOTE: FEED LINE MUSTBE
PERMEATE (PRODUCT WATER)CONNECTION
labeledpermeateandattachtostoragetank
permeate water can flow freely
damage to the membraneelements.
with PVC fittings,orotherFDAapprovedmaterials
ssolveintothepermeatewater.
THE PH OFTHEREVERSEO
2 POINTS LOWERTHANTHEFEEDWATERPH.ALOWPHCAN
BE VERY AGGRESSIVE TO SOMEPLUMBINGMATERIALSSUCHASCOPPER
CONCENTRATE (WASTE WATER)CONNECTION
labeled
to anopendraininafreeandunrestrictedmanner(nobackpressure).
CAUTION: ANY RESTRICTIONSORBLOCKAGEINTHEDRAINLINECAN
CAUSE BACKPRESSURE, WHICHWILLINCREASETHE
PRESSURE. THIS CAN RESULTINDAMAGETOTHESYSTEM’SMEMBRANESAND
-
/380/460Volt,
system is equipped with a 5 footelectricalcord
nsure that the electrical circuitsupplyingthesystemiscompatiblewiththe
uirements of the specific D
Backpressure cancause
” permeate line
Thisissothematerial
SMOSIS PERMEATEWATERWILL
drain. Run
SYSTEM’SOPERATING
pump and motor combination
phase
concentrations a
MINIMUM 1” INCH.
Locate the 1” connection
irreversible
holding tank
being used does not di
CAUTION
TYPICALLY BE 1-
PIPING.
Locate the 1” connection
line
with no backpressure.
The 1
concentrateandattachtoa
. Ensure that the
can be run to the
.
the concentrate
COMPONENTS.
ELECTRICAL
The motor used on the DT
motor is available in 220
Series systems are a
50/60 Hertz, 1 Phase/3
. Each DT-Series
.
E
req
DT – Series User’s Manual
MKTF-208
T model you are installing.
7
. The
06/12
NOTE: IT’S
RECOMMEND
SYSTEM IN ACCORDANCE WITHLOCALANDNATIONALELECTRICALCODES
WARNING: TO REDUCETHERISKOFELECTRICALSHOCK,THE
INCOMING POWER SUPPLYMUSTINCLUDEAPROTECTIVEEARTHGROUND.
If a liquid level switchistobeused,installitatthistime.
suppliedwitha10MicronFSIBagFilteranda4.5”x20”5
Micron polypropylene sedimentfilter
ists betweenthepre
Filtration systems, if required.
NOTE:THESYSTEMMUSTBEOPERATEDONFILTEREDWATERONLY.
type used on the DT
alsoavailable
Follow these guidelines to ensureproperoperationofthepump:
NEVER
will damage thepump.
feed the pumpwithfilteredwater.Thepumpissusceptibletodamage
from sediment and debris.
THAT A LICENSED ELECTRICIANWIREYOUR
monthorwhena10
rordistributorabout
centrifugal
in stainless steel
be run dry. Operating the pump withoutsufficientfeed
(NEC).
DT-Series systems are
off when the tank is full.
distributor.
PRE-FILTRATION
DT-Series systems are
15 psi differential ex
Pre-
ED
. Change thecartridgeoncea
-filter.Askyourlocaldeale
-
PUMP
The pump
pump. These pumps are
The pump must
water
ALWAYS
DT – Series User’s Manual
MKTF-208
-Series systems is a multi-stage
as an option
8
carbon steel
.
06/12
If any damage occurs to your system’s pump, a re-build kit may be available.
Contact your local dealer or distributor and inform them of your system’s model
and pump size.
MOUNTING
The free standing system should be bolted down in compliance with local regulation
standards or securely fastened.
MEMBRANE ELEMENTS
DT-Series reverse osmosis systems come pre-loaded with Thin Film Composite (TFC)
HF1 High Flow Low Energy membranes, unless otherwise specified. General
membrane element performance characteristics are listed on the next page:
DT – Series User’s Manual
MKTF-20806/12
9
HF1-STANDARD
DT – Series User’s Manual
10
MKTF-20806/12
HF4-OPTIONAL
DT – Series User’s Manual
11
MKTF-20806/12
HF5-OPTIONAL
DT – Series User’s Manual
12
MKTF-20806/12
NF3-OPTIONAL
DT – Series User’s Manual
13
MKTF-20806/12
NF4-OPTIONAL
DT – Series User’s Manual
14
MKTF-20806/12
DT-10000, DT-15000, DT-20000 SYSTEM IDENTIFICATION
FIGURE 1A
DT – Series User’s Manual
MKTF-20806/12
15
NUMBER IDENTIFICATION
1. Solenoid Valve – Turns On/Off Feed Water
2. 10 Micron Sediment – Removes particulates
3. 5 Micron Sediment – Removes particulates
4. Pressure Gauge - Measures feed pressure
5. Pressure Gauge - Measures pressure after filters
6. Pressure Gauge - Measures pump pressure
7. Pressure Gauge – Measures concentrate pressure
8. Computer Control - Controls RO system
9. Recycle Valve – Recycles concentrate back to feed (if applicable)
10.Concentrate Valve – Controls flow of concentrate (waste) water to the drain
11.RO Pump and Motor - Pressurizes RO System
12.Throttle Valve – Controls flow of the pump
13.Flow Meter - Measures flow of permeate water
14.Flow Meter - Measures flow of concentrate (waste) water
15.Flow Meter - Measures flow of concentrate recycle water(ifapplicable)
16.Pressure Switch – Turns the pump off at 15 PSIfeedpressure
Note:Aportionoftheframehasbeenremoved to expose components.
DT – Series User’s Manual
MKTF-20806/12
19
DT-10000 MEMBRANE FLOW DIAGRAM
FIGURE 1G
Note: Black arrows represent concentrate water and white arrows represent permeate
water.
DT – Series User’s Manual
MKTF-20806/12
20
DT-15000 MEMBRANE FLOW DIAGRAM
FIGURE 1H
Note: Black arrows represent concentrate water and white arrows represent permeate
water.
DT – Series User’s Manual
MKTF-20806/12
21
DT-20000 MEMBRANE FLOW DIAGRAM
FIGURE 1I
Note: Black arrows represent concentrate water and white arrows represent permeate
water.
DT – Series User’s Manual
MKTF-20806/12
22
SYSTEM PURGING
Carefully inspect your system before initial start-up. Check that all plumbing and
electrical connections are not loose or have not come undone during shipment. A user’s
manual, test results, and filter housing wrench will accompany your DT-Series reverse
osmosis system.
NOTE: LEAVE THE POWER TO THE SYSTEM OFF FOR THIS PROCEDURE.
1. Redirect permeate water to the drain for this procedure.
2. Fully open the concentrate valve #10 (counter clockwise). (Figure 1B, Page 17)
3. Fully close the recycle valve # 9 (clockwise) (if applicable). (Figure 1B, Page 17)
4. Offset the position of the bypass white lever on the solenoid valve #1. (Figure 2,
Page 23)
5. Turn the feed water on and let the system purge until no visible bubblesappear from
concentrate flow meter #14. (Figure 1B, Page 17)
6. Fully open the throttle valve #12 (Counter Clockwise).(Figure1B,Page17)
Lever InlineLever Offset
Operating PositionBypass Position
FIGURE 2
DT – Series User’s Manual
MKTF-20806/12
23
INITIAL START-UP
1. Keep the permeate water line to drain for this procedure.
2. Fully open the concentrate valve #10 (counter clockwise). (Figure 1B, Page 17)
3. Fully close the recycle valve # 9(clockwise)(if applicable). (Figure 1B, Page 17)
4. Fully open the throttle valve #12 (counter clockwise). (Figure 1B, Page 17)
5. Return position of the bypass white lever inline on the solenoid valve #1. (Figure 1B,
Page 16)
6. Turn the RO system on #8 and adjust the concentrate (waste) valve #10, recycle
valve # 9 (if applicable), and the throttle valve to the designed flow and pressure.
(Figure 1B, Page 17)
7. Inspect the system for leaks.
8. Allow the system to run for one hour to flush the preservative solution from the
system.
9. After one hour, shut down the system.
10.Re-direct the permeate water back to the tank and then turnthesystemback on.
11.Record the readings daily for a week. After a week,recordthereadingsonce a
week.
Adjustthepumpthrottlevalveandconcentrate valve until the correct flow
is achieved.Forexample,DT-10000should be adjusted until it produces about
10000 GPDor6.94GPMofpermeate (product water) at 77˚F. Design flow might be
achieved below150PSI.
GPM = GPD/1440
Example:
6.94 =10000/1440
DT – Series User’s Manual
MKTF-20806/12
24
DESIGN
BASIS
WARNING: NEVER EXCEEDTHEMAXIMUMPRESSURE
15000, DT
FOR DT-10000,DT-
-20000
YOUR SYSTEM
DT – Series User’s Manual
MKTF-208
25
RATING OF
06/12
OPERATING DO’s AND DON’Ts
DO:
Change the cartridge filters regularly
Monitor the system and keep a daily log
Run the system as much as possible on a continuous basis.
Adjust the system recovery to the recommended value
Always feed the pump with filtered water.
DON’T
Permit chlorine to enter or be present in the feed water.
Shut down the system for extended periods.
Close the throttle valve completely.
Operate the system withinsufficientfeedflow.
Operatethepumpdry.
OPERATION AND MAINTENANCE
The reverse osmosis process causes the concentration of impurities. The impurities
may precipitate (come out of solution) when their concentration reaches saturation
levels.
NOTE: PRECIPITATION CAN SCALE OR FOUL MEMBRANES AND MUST
BE PREVENTED.
Check your feed water chemistry and pre-treat the water and/or reduce the system’s
recovery as required. If necessary, consult with your local dealer or distributor.
DT – Series User’s Manual
MKTF-20806/12
26
PRE-FILTER PRESSURE GAUGES
These gauges measure the feed water pressure when it enters and exits the pre-filters.
A pressure differential of 10 - 15 psi or more on the two pressure gauges indicates that
the pre-filters require servicing. For example, if the inlet pressure is 40 psi, the filter
should be changed when the outlet pressure is 30 psi or below.
PERMEATE (PRODUCT) FLOW METER AND CONCENTRATE (WASTE) FLOW
METER
These flow meters indicate the flow rates of the permeate and concentrate water. The
measurements, when added together, also indicate the feed water flow rate or (total
flow rate); if the system is not equipped with a concentrate recycle valve.
CAUTION: EXCESSIVE RECYCLING MAY CAUSEPREMATUREFOULING
OR SCALING OF THE MEMBRANE ELEMENTS.
LOW PRESSURESWITCH
The lowpressureswitchshutsoffthesystem when the feed water pressure drops
below 15PSI,preventingdamagetothe pump. The system restarts automatically when
there is aconstantpressureof 35 PSI or more.
If you notice the pressure fluctuating, and the system cycling off and on,
turn the system off and ensure that proper feed flow and pressure are available to
the system.
PUMP THROTTLE VALVE
This valve is installed as a standard feature on the DT-Series reverse osmosis systems.
It provides an adjustment for pump pressure, which will vary as the required system
pressure changes. As the feed water temperature decreases, and/or the feed water
TDS increases, the system will require a higher operating pressure to produce the
specified permeate flow. A DT system installed in Florida may provide the specified
permeate flow of 6.94 gpm at 100 psi; however the same system installed in Maine –
DT – Series User’s Manual
MKTF-20806/12
27
much colder feed water – may require 150 psi to produce the same amount of
permeate. Never exceed 150 psi.
Example:
As time progresses, the efficiencyofthemembranewillbereduced.Ingeneral,thesalt
rejection does not change significantlyuntiltwoorthreeyearsafterinstallationwhen
operated on properly pretreatedfeedwater.Thepermeateflowratewi
slightly after one year of operation,butcanbeextendedwithdiligentflushingand
cleaning of the system. A highpHand/orprecipitationofhardnesscancause
.
THE MEMBRANEELEMENT:
THE BRINESEALMUSTBEINTHESAMEPOSITIONFOR
ELEMENTHOUSING,SOMARKEACHHOUSINGPRIORTO
THE MEMBRANE
ON ONESIDEOFTHEMEMBRANEAND
MEMBRANE
REPLACEMENT
pressure vessels is an easy process if youhavethe
POWERFROM
SYSTEM.
containing the membrane elementfromtheshipping
SINORDER
om dirt. Examine thebrineseal
rings or brine sealifdamaged.
ELEMENTS. THE BRINE SEAL IS ARUBBERSEAL
IS ALWAYSONTHE
Replacing membranes in
WARNING:
PROCEEDING. BEFORE
REMOVAL AND
, DISCONNECT THE
THE
THE
1.
removing the white
2.
box.
3.
bag may be re-
4. Make
5.
housing.
THE FOLLOWING STEP
age 31)
done by
housing.
NOTTO
and
-
ll begin to decline
premature loss in rejection
REPLACING
WARNING:
EACH MEMBRANE
REMOVING
THAT PROTRUDES
FEED SIDE OF THE
DT – Series User’s Manual
MKTF-208
ELEMENT.
29
06/12
1. Remove one membrane element at a time from the membrane element
housings, from the top of the housing. Long nose pliers may be necessary to pull
the old membrane element out of the membrane element housing.
2. Lubricate the brine seal with non petroleum based lubricant, Silicone DC 111.
3. Install the brine seal side of the membrane element first (Figure 4, Page 31).
When the housings have a direction of flow from bottom to top, the brine seal
should be located at the bottom of the housing.
4. At a slight angle, insert the membrane while slightly rotating the element being
careful not to tear or flip the brine seal. A slow twisting motion should be used to
insert the membrane element, to ensure the brine seal stays in place. Re-lube
the brine seal if necessary.
5. With a smooth and constant motion, push the membrane element into the
housing so the brine seal enters the housing without coming out ofthe brine seal
groove.
6. Re-install the end caps by gently twisting theendcapwhilepushingitonto the
housing. Ensure that you do not pinchorfatigueanyO-ringswhilere-installing
the end plug. Push the end plugonuntiltheouterdiameteroftheplugisflush
with the outer diameterofthemembranehousing.
7. Insert thesnapringuntilitisfullyseated.Installthelocking clip if available.
8. Reconnectanyfittingsthatmayhavebeen disconnected when the membrane
elementhousingsweredisassembled.
9. To start-upthesystem, please refer to the Initial Start-Up section of this manual.
(SeePage 24)
CAUTION: WET MEMBRANES ARE SHIPPED IN A PRESERVATIVE
SOLUTION. THE MEMBRANES MUST BE FLUSHED FOR AT LEAST 1 HOUR TO
REMOVE THE PRESERVATIVE FROM THE MEMBRANE. DISCARD ALL OF THE
PERMEATE AND CONCENTRATE, WHICH IS PRODUCED DURING THE FLUSH
PERIOD.
DT – Series User’s Manual
MKTF-20806/12
30
FIGURE 3
FIGURE 4
View from the right side of DT-10000, DT-15000, DT-20000 reverse osmosis system.
DT – Series User’s Manual
MKTF-20806/12
31
FLUSHING THE SYSTEM
The system should be flushed weekly to remove sediment from the surface of the
membranes. To manually flush the system, follow the preceding steps:
1. The system must be operating during the flush procedure.
2. Fully open the concentrate valve. (Figure 1B, Page 17)
3. Allow the system to run for 10 to 20 minutes.
4. After 10 to 20 minutes, close the concentrate valve to its previous setting. Ensure
the proper concentrate flow rate is going to the drain.
5. The system is now ready to operate.
PREPARING UNIT FOR STORAGE OR SHIPMENT
Prior to shipping or storing your system,thesystemshouldbecleanedwith an
appropriate cleaner, flushed with waterandprotectedfrombiologicalattackwithan
appropriate solution for membraneelements.Themembranehousing(s)and plumbing
lines of the system mustbecompletelydrained.Anywaterremaining in the plumbing of
a system may freeze,causingseriousdamage.
Preparingsystemforstorage:
1. Totallyimmersetheelements in the membrane housing in a solution of 2 %
Memstor,ventingthe air outside of the pressure vessels. Use the overflow
technique:circulate the Memstor solution in such a way that the remaining air in
the system is minimized after the recirculation is completed. After the pressure
vessel is filled, the Memstor solution should be allowed to overflow through an
opening located higher than the upper end of the highest pressure vessel being
filled.
2. Separate the preservation solution from the air outside by closing all valves. Any
contact with oxygen will oxidize the Memstor.
3. Check the pH once a week. When the pH becomes 3 or lower, change the
preservation solution.
4. Repeat this process at least once a month.
During the shutdown period, the plant must be kept frost-free, or the temperature must
not exceed 113°F (45°C).
DT – Series User’s Manual
MKTF-20806/12
32
Preparing unit for shipment:
5. Disconnect the inlet, concentrate, pre-filter, and permeate plumbing.
6. Drain all water from the pre-filter cartridge housings by unscrewing the housings,
removing the pre-filter cartridges, and drain the water from the housings.
7. Disconnect the tubing from the connectors on the permeate and concentrate
inlets and outlets.
8. Fully open the concentrate valve.
9. Drain the flow meters.
10.Allow the system to drain for a minimum of eight hours or until the opened ports
quit dripping.
11.After draining is complete, reconnect all of the plumbing.
Improve pretreatment to remove
metals. Clean with acid cleaners.
Optimize pretreatment for colloid
removal. Clean with high pH anionic
cleaners.
Increase acid addition and
antiscalant dosage for CaVO3 and
CaCO4. Reduce recovery. Clean
with acid cleaners.
Shock dosage of Sodium Bi-Sulfate.
Continuous feed of Sodium BiSulfate at reduced pH.
Chlorination and de-chlorination.
Replace cartridge filters.
Activated Carbon or other
pretreatment. Clean with high pH
cleaner.
Check Chlorine feed equipment and
de-chlorination system.
Improve pretreatment. Check all
filters for media leakage.
DT – Series User’s Manual
34
MKTF-20806/12
ABNORMAL PERMEATE FLOW
Permeate flow should be within 20% of the rated production, after correcting the feed
water temperatures above or below 77°F. Check your permeate flow meter to
determine the permeate flow rate.
NOTE: TO DETERMINE THE TEMPERATURE CORRECTION FACTOR,
LOCATE THE TEMPERATURE CORRECTION TABLE IN THIS USER’S MANUAL
AND FOLLOW THE DIRECTIONS
DT – Series User’s Manual
MKTF-20806/12
35
TEMPERATURE CORRECTION FACTORS FOR MEMBRANE
Find the temperature correction factor (TCF) from the table below. Divide the rated
permeate flow at 77°F by the temperature correction factor. The result is the permeate
flow at the desired temperature. (See example on the next page)
DT – Series User’s Manual
MKTF-20806/12
36
If a system is rated to produce 5 gpm of permeate water @ 77˚ F, the same system will
produce more water at a higher temperature. It will also produce less water at a lower
temperature. Use the temperature correction table to obtain the correct flow.
Example:
5 gpm @ 59˚ F (5÷1.42=3.52 gpm)
5 gpm @ 77˚ F (5÷1=5 gpm)
5 gpm @ 84˚ F (5÷0.89=5.62 gpm)
SERVICE ASSISTANCE
If service assistance is required, please completethefollowingprocess:
Contact your local dealer or distributor.Priortomakingthecall,havethefollowing
information available: system installationdate,serialnumber,dailylogsheets, current
operating parameters (e.g.flow,operatingpressures,pH,etc.)andadetailed
description of the problem.
DT – Series User’s Manual
MKTF-20806/12
37
OPERATION
Company:
Location:
Week Of:
System Serial #:____________________
Date
Time
Hour of Operation
Filter inlet pressure (psi)
Filter outlet Pressure (psi)
Concentrate Pressure (psi)
Pump Discharge Pressure (psi)
Feed Flow (gpm)