AW-Lake LLC-E-BA Data sheet

8809 Industrial Drive, Franksville, WI 53126 Phone: (262) 884-9800 Fax: (262) 884-9810
Email: awinfo@aw-lake.com www.awflowmeters.com
T
echnical Specifications:
· Nine programmable batch amounts · Batch counter & totalizer
· 4-20 mA batch fill indicator · Two relays for solenoid valve control
· NEMA 12 & 13 enclosure · Batch error compensator
· Ability to count up or to count down · Good for small to medium sized systems
Mounted in a prewired NEMA 12 industrial enclosure, the LLC-E-BA is an easy to use batch controller designed as a central controller for small to medium sized fluid batching systems. Nine different batch amounts can be pre-programmed into long term memory and selected by the operator. Two relays provide control for either single or dual stage valve operation. Two totalizers are provided, one acts as the batch totalizer and the other totalizes continuously with reset protection. The batch counter has a user selectable option to either count up from zero or count down from the batch amount. The unit’s smart programming automatically compensates for variations from the selected batch amount. Inputs provide operator remote control for batch selection, start, stop and reset.
LLC-E-BA
Batch Controller in an Industrial Enclosure
Rev. 05/04
8809 Industrial Drive, Franksville, WI 53126 Phone: (262) 884-9800 Fax: (262) 884-9810
Email: awinfo@aw-lake.com www.awflowmeters.com
Power Supply:
110 VAC
Sensor Input:
Voltage triggered, 2.00 Vp-p min. 0-4 KHz, 10 Kohm imp.
Main Board:
87C51FB processor, EEPROM memory
Sensor Supply Output:
Approx. 20 mA at 15 VDC
Display:
LCD, 16 Character alpha-numeric
0.35 inch character height
Enclosure:
NEMA 12 & 13
Controller Technical Data
LLC-E-BA
Batch Controller in an Industrial Enclosure
Rev. 05/04
Products may be subject to change without notice – Contact factory for current information
Relay Contact Ratings: Maximum Switch Voltage: 220V DC, 250 VAC Maximum Switch Current: 2A
Maximum Switched Power Resistive Load: DC 60W / AC 125 VA Inductive Load: DC 30W / AC 60 VA
Rated Load Resistive Load: DC 30V, 2A / AC 110V 0.5A Inductive Load: DC 30V, 1A / AC 110V 0.3A
Two Form C Relay Output
s:
BATCH DONE
BATCH PROGRESS
DELAY
SLOW START
4 mA (typ.)
20 mA
0
LOW FLOW
PRECUT
SLOW STOP
SLOW START
DELAY
ANALOG OUTPUT
BATCH RESET
RELAY2
START
START/ STOP
RELAY1
START
STOP
START
BATCH RESET
BATCH TOTAL
HIGH FLOW
LOW FLOW
HIGH FLOW
R U N
BATCH
AW COMPANY
Franksville, WI
BATCH BATCH
Programming
START/ STOP
Flow
Flow
Tot-1 Tot-2
MODE
PROGBATCHMODERESET
SELECT RESET
SELUPDN ENT
PROG
OFF
POWER
ON
INPUT
FLOWMETER
LLC BATCH CONTROL
Loading...