AW-Lake LLC-BA Operating Manual

FLOW
TRANSMITTERS
ELECTRONICS FOR
INSTRUMENTATION
LLC - BA
Batch Unit
Manual Rev. 4
Software Versions 1.15 to 1.19
8809 Industrial Drive, Franksville, WI 53126-9337
Tel: 262-884-9800 Fax: 262-884-9810
E-Mail: awinfo@aw-lake.com Web: www.aw-lake.com
LLC-BA Batch Unit Manual
Rev. 4.0 for LLC-BA Software Version 1.15-1.19
Table of Contents
Introduction.................................................... page 3
Features.......................................................... page 3
Technical Data............................................... page 3
Relay Contact Ratings...................... page 4
Dimensional Drawings..................... page 4
Input & Output Connections.......................... page 5, 6
Typical Connection Diagram............ page 7
LLC Initial Messages..................................... page 8
Display Modes............................................... page 8
RATE Display Mode......................... page 8
TO1 Display Mode............................ page 8
TO2 Display Mode............................ page 9
BATCH Status Display Mode........... page 9
TO1- Reverse Display Mode............. page 9
Operation/Reset of Totalizers........................ page 9
Totalizer 1......................................... page 9
Totalizer 2......................................... page 9
Operating Modes........................................... page 10
RUN Mode..................................................... page 10
Batch Operation................................ page 10
Automatic Overrun Compensation... page 10
Batch Selection/Activation............... page 11
Batch Input & Output Functions....... page 11
Batch Function Timing Diagram...... page 12
Programming the LLC................................... page 13
Programming Label Diagram........................ page 13
Program Mode............................................... page 13
Entering/Editing the Variables..................... page 13
Delay.................................................. page 13
Precut................................................. page 14
Gate Time.......................................... page 14
0-set mA’s......................................... page 14
KFR-Factor........................................ page 15
Decimal Point for KFR..................... page 15
Engineering Units KFR..................... page 16
KFT-Factor........................................ page 16
Decimal Point for KFT...................... page 17
Engineering Units KFT..................... page 17
Batch Programming....................................... page 18
Limited Warranty Statement.......................... page 19
3
Introduction
The LLC-BA Batch Unit provides accurate and repeatable batch control, stores up to nine different programmable batch quantities, and is a rate, total or batch indicator. The LLC-BA provides relay outputs to initiate and stop the flow. The relay outputs can be used to control two solenoids with different flow rates to allow for a slow stop/start of the flow.
In batching operations, the LLC-BA activates the low flow solenoid on the START input and after a programmed variable DELAY, the high flow solenoid is activated producing a combined high flow rate. The high flow solenoid is deactivated before the batch amount has been reached by means of the PRECUT variable reducing the flow for a slow stop. The low flow solenoid is de-activated when the programmed batch amount is reached.
The LLC-BA compensates for a valve or fluid delay in the batch system with the Automatic Over-run Compensation feature. Any over-run is detected by the A.O.C. feature and the LLC­BA anticipates and corrects for the delay on the next batch. This feature is always active and adapting continuously to correct for long term changes in valves and fluid characteristics.
Features
* 87C51FB Microprocessor based design * Dust-proof LEXAN front panel, resistant to chemicals compatible with LEXAN. * 16 character alpha numeric LCD display, .35 inch character height * All wiring via two rear mounted removable 10 pin screw terminals * EEPROM variable storage with 5 year minimum life
Technical Data
Enclosure: DIN #43700, panel mount, plastic
Height 67mm/2.6in Height w/ flange 69mm/2.8in Width 92mm/3.6in Width w/ flange 97mm/3.8in Depth 132mm/5.2in Depth w/ flange 139mm/5.5in
Weight: 12 0z. (approx. 360 grams) without power supply.
Environment: Storage -40 to 85 deg. C
Operating 0 to 50 deg. C (standard) Humidity 10-90% non-condensing
Power Supply: Supplied:
110VAC wall plug unit -16VAC/1000mA.. output w/6ft. cable to
standard 2.1mm I.D. x 5.5mm O.D. female plug.
Allowable supply range: 12-16VAC/300mA. or 17-22VDC/300mA.
AW-Lake Company 8809 Industrial Drive, Franksville, WI 53126 web: www.aw-lake.com
Tel: 262-884-9800  Fax: 262-884-9810  Email: awinfo@aw-lake.com
REV. 4 01/11 LLC-BA Manual.DOC
Frequency Input: Voltage triggered, 2.00 Volt min. input level, 0 - 4KHz, 10KOhm imp.
Supply Output: (to sensor) Approx. 20mA.. at approx. 15VDC
Relay Outputs: 2 Form C relay outputs. See Table 1 for contact r ating inf o rmation
Table 1
Rela y C o n ta c t R a tin g s
Maximum
Switched
Power
Maximum Switch Voltage Maximum Switch Current
Rate d
Load
Resistive Load
Inductive Load
Resistive Load
Inductive Load
DC : 60 W AC: 125VA
DC : 30 W AC: 60VA
220 V D C , 2 5 0 V AC 2A
DC : 30 V , 2 A AC : 110V, 0.5A
DC : 30 V , 1 A AC : 110V, 0.3A
Dimensional Drawings
4
AW-Lake Company 8809 Industrial Drive, Franksville, WI 53126 web: www.aw-lake.com
Tel: 262-884-9800  Fax: 262-884-9810  Email: awinfo@aw-lake.com
REV. 4 01/11 LLC-BA Manual.DOC
5
Input & Output Wiring Connections
All customer connections are made in the back of the unit. Power is delivered to the LLC-BA unit through a plug-in connector from the wall plug type power supply normally supplied with the unit. If necessary, any standard AC wall plug unit providing 12-16VAC/300 mA. or 17­22VDC/300mA. to a standard female plug (2.1mm I.D. x 5.5mm O.D.) may be used.
All other connections are accomplished through the two 10 pin screw terminals that are removable for ease of wiring. These are referred to as the upper and lower connectors. Connection information is labeled on the connectors. See the LLC-BA Connection Diagram on page 7 for connector detail and typical batch application connections.
The connections on the upper connector are as follows:
TERM 1 +15VDC Power supply for the transmitter. Approx. 15VDC (power supply dependant), approx. 20mA.. max. Source for pull-up resistor if required.
TERM 2 GROUND (floating), power supply negative for the transmitter.
TERM 3 SIGNAL frequency input from the transmitter. 0-4KHz , 2 volts minimum,
10KOhm input impedance. A pull-up resistor is required for pickups with a sinking output. Size resistor not to exceed rated output current of pickup. Typical pull-up values range from 2.2Kohm to 5.1Kohm
TERM 4 RUN/PROG Input. Enables RUN-Mode and EXTERNAL functions when connected to GROUND (TERM 2). When open, LLC-BA is in the PROGRAM Mode. This input must be activated with a dry contact!
TERM 5 REL2COM is the common contact of Relay 2 (Form C). Relay 2 is used in batching applications for control of the high flow solenoid valve in a two valve system with slow start/stop function. See Connection Diagram page 7 for solenoid connection details. See Table 1 on page 4 for relay contact ratings.
TERM 6 REL2NC is the normally closed contact for Relay 2.
TERM 7 REL2NO is the normally open contact for Relay 2.
TERM 8 REL1COM is the common contact of Relay 1 (Form C). Relay 1 is used in batching applications for control of the low flow solenoid valve in a two valve system with slow start/stop function. See Connection Diagram page 7 for solenoid connection details. See Table 1 contact ratings.
TERM 9 REL1NC is the normally closed contact for Relay 1.
TERM 10 REL1NO is the normally open contact for Relay 1.
on page 4 for relay
AW-Lake Company 8809 Industrial Drive, Franksville, WI 53126 web: www.aw-lake.com
Tel: 262-884-9800  Fax: 262-884-9810  Email: awinfo@aw-lake.com
REV. 4 01/11 LLC-BA Manual.DOC
6
The connections on the lower connector are as follows:
TERM 11 VOLTAGE SUPPLY OUTPUT - 15 VDC, 25 mA
TERM 12 GROUND for Batch External Function Inputs (Inputs 1-4)
TERM 13 ANALOG OUTPUT SELECT – Connect to TERM 11 to change the function of
the analog output from a Batch Progress Signal to a Batch Number Signal.
(Software revision 1.18 and above only)
TERM 14 INPUT1, START/STOP Input (momentary) for batching applications. Start/Stop is accomplished by momentarily connecting INPUT1 (TERM14) to GROUND (TERM 12). Batch start will occur on rising edge of signal as the connection is opened. If input is closed again before the batch total has been reached, stop will occur on falling edge of the signal as the connection is closed. Batch function will resume on the rising edge of the next momentary closure of the STOP/START input. START/STOP function is active in RUN mode.
TERM 15 INPUT2, BATCH RESET Input (momentary) for batching applications. Batch Reset is accomplished by momentarily connecting INPUT2 (TERM15) to GROUND (TERM 12). When connected, the batch operation will be terminated and the batch totalizing value is reset to zero on the falling edge of the signal as the connection is closed. Reset function is active in RUN mode.
TERM 16 INPUT3, BATCH SELECT Input (momentary) for batching applications. Used for selection of pre-programmed batch quantities (Batch 1- 9) while in the RUN mode. Batch number is incremented and display indicates batch selected and programmed batch quantity while the input is closed.
TERM 17 INPUT4, MODE CHANGE Input (momentary) for batching applications. Used to select the display mode while operating in the RUN mode. Display mode is incremented on each closure of the input.
TERM 18 NO CONNECTION
TERM 19 mA’s (+), Positive of mA’s output – this analog output is a batch progress signal
or with software revision 1.18 or higher can alternately indicate the currently
selected batch number. A Batch Progress Signal directly corresponds with the
progress of the batch where 4mA equals zero progress and 20mA is equal to the
full batch amount. A Batch Number Signal (Software revision 1.18 and above
only) indicates the currently selected batch number in 1 mA increments with 5 –
13mA representing batch numbers 1-9. To assign the output to the Batch
Number Signal function it is necessary to wire a jumper to the back of the LLC-
BA controller between lower connector terminal 11 and terminal 13.
TERM 20 mA’s (- ), Negative of mA’s output - see mA’s (+) above...
AW-Lake Company 8809 Industrial Drive, Franksville, WI 53126 web: www.aw-lake.com
Tel: 262-884-9800  Fax: 262-884-9810  Email: awinfo@aw-lake.com
REV. 4 01/11 LLC-BA Manual.DOC
7
LLC-BA Typical Connection Diagram
110VAC
TO DISPENSE HEAD
LOW FLOW VALVE
FLOW TRANSMITTER
FLUID FLOW
110VAC
OPTIONAL HIGH FLOW VALVE
SIGNAL
GROUND
PROGRAM MODE
RUN MODE
10
7
Opti on al Hard Gro u nd
385421
12-16VAC 300m A. Hot Center
20
17
19
141516
12
BATCH EXTERNAL FUNCTIONS ACTIVE IN RU N M ODE ONL Y
BATCH PROGRESS OUTPUT
START/ STOP (mom.)
BATCH RESET (mom.)
Input Circuit Detail
BATCH SELECT (mom.)
MODE CHANGE (mom.)
Pull-up resistor required for pickups with sinkin g outpu ts
From Pickup
+1 5 Vdc
1
Freq. In put
3
Gnd(-)
2
LLC Input Circuit
To signal processing
AW-Lake Company 8809 Industrial Drive, Franksville, WI 53126 web: www.aw-lake.com
Tel: 262-884-9800  Fax: 262-884-9810  Email: awinfo@aw-lake.com
REV. 4 01/11 LLC-BA Manual.DOC
Loading...
+ 15 hidden pages