COMPANY
HUB - 4xEX Explosion-Proof
Frequency Output Sensor
Installation, Operating &
Maintenance Manual
©2016 AW-Lake Company. All rights reserved. Doc ID:HUB 4EXMAN08242016
Table of Contents
Introduction .............................................................................3
Technical Specications ........................................................3
Supply Voltage .............................................................................3
Supply Current ............................................................................3
Sensor/Monitor Frequency Output .........................................3
Output Amplitude .......................................................................3
Duty Signal ...................................................................................3
Connections .................................................................................3
Temperature Ratings: .................................................................3
HUB-40Ex Certications .............................................................3
Enclosure Certications .............................................................3
HUB-4xEx Dimensions ............................................................4
Hazardous Area Environments ............................................4
Hazardous Area Certication Tag .............................................5
Installation ...............................................................................6
Wiring Guide .............................................................................6
2
Introduction
The HUB-4xEx is a frequency output, pickup sensor certified for use in explosion
proof areas. The sensor detects the rotation of an approved flow meter’s gears
and emits a frequency signal proportional to the flow. The output signal is a
square wave pulse, which has a duty cycle of approximately 50%. MAG signal
outputs are protected with a self-resetting fuse. This fuse has a 50 mA nominal
trip point. When a trip occurs, turn off power to the sensor and remove output
load to reset the fuse.
Compatible flow meters include:
• JVM-zzz-Ex Models
• JVS-zzz-Ex Models
• JVHS-zzz-Ex Models
• ZHM-zzz-Ex Models
• HPM-zzz-Ex Models
• HM-zzz-AC-Ex Models
Technical Specications
Supply Voltage
10-24 VDC
Supply Current
• 8 mA @ 12 VDC
• 12 mA @ 24 VDC
• 65 mA MAXIMUM
Sensor/Monitor Frequency
Output
Flow dependent, 0.5 Hz minimum
Output Amplitude
VHIGH = VSUPPLY – 0.7 Volts
VLOW = 0 Volts
Duty Signal
50% + 15%
Connections
Terminal block, ½” NPT (FEMALE)
con-duit entrance.
Temperature Ratings:
-20°C to +60°C (-4°F to +140°F)
ambient
85°C (185°F) maximum fluid
temperature
HUB-40Ex Certifications
CSA:
• CL. I, DIV. 1, GR. C,D
• CL. II, DIV. 1, GR. E,F,G
• CL. III
Enclosure Certifications
TYPE 4X
3