HUB-40EX
EXPLOSION-PROOF FREQUENCY OUTPUT SENSOR
OperaƟon & InstallaƟon Manual
Rev. 1.2
HUB-40Ex Sensor
8809 Industrial Drive, Franksville, WI 53126
web: www.awgearmeters.com
Email: aw@awcompany.com
HUB-40Ex User Manual rev1.2.docxError! Unknown document property name., 1/18/2012
User Manual
HUB-40Ex USER MANUAL
Introduction/ Features:
The HUB-40Ex is a frequency output, pickup sensor certified for use in explosion proof areas. The sensor detects the
rotation of an approved flow meter’s gears and emits a frequency signal proportional to the flow. The output signal is a
square wave pulse, which has a duty cycle of approximately 50%. MAG signal outputs are protected with a self-resetting
fuse. This fuse has a 50 mA nominal trip point. When a trip occurs, turn off power to the sensor and remove output load to
reset the fuse.
Compatible flow meters include:
JVM-zzz-Ex Models
JVS-zzz-Ex Models
JVHS-zzz-Ex Models
ZHM-zzz-Ex Models
HPM-zzz-Ex Models
HM-zzz-AC-Ex Models
Specifications:
Supply Voltage: 10 to 24 VDC
Supply Current:
o 8 mA @ 12 VDC
o 12 mA @ 24 VDC
o 65 mA MAXIMUM
Sensor/Monitor Frequency Output: Flow dependent,
0.5 Hz minimum
Output Amplitude:
o V
o V
= V
HIGH
= 0 Volts
LOW
SUPPLY
– 0.7 Volts
Duty Signal: 50% + 15%
HUB-40Ex Dimensions:
Connections: terminal block, ½” NPT (FEMALE)
conduit entrance.
Temperature Ratings:
o -20°C to +60°C (-4°F to +140°F) ambient
o 85°C (185°F) maximum fluid temperature
HUB-40Ex Certifications:
o CSA
CL. I, DIV. 1, GR. C,D
CL. II, DIV. 1, GR. E,F,G
CL. III
Enclosure Certifications: TYPE 4X