Avtec Ventilation System Service Manual

OPERATOR MANUAL
IMPORTANT INFORMATION, KEEP FOR OPERATOR
This manual provides information for:
VENTILATION SYSTEMS
NOTIFY CARRIER OF DAMAGE AT ONCE
It is the responsibility of the consignee to inspect the container upon receipt of same and to determine the possibility of any damage, including concealed dam­age. Unified Brands suggests that if you are suspicious of damage to make a notation on the delivery receipt. It will be the responsibility of the consignee to file a claim with the carrier. We recommend that you do so at once.
Manufacture Service/Questions 888-994-7636.
Information contained in this document is known to be current and accurate at the time of printing/creation. Unified Brands recommends referencing our product line websites, unifiedbrands.net, for the most updated product information and specifications.
PART NUMBER OMANUAL_VMR-0507 Rev. A (0507)
1055 Mendell Davis Drive
Jackson, MS 39272
888-994-7636, fax 888-864-7636
avtecind.com
TABLE OF CONTENTS
4 4 4 5 5
5/6
6 6
7 7 7
9 9 9/10/11 13 13
13 13 13 13 13 13 13 14
15 15 15 15 15/16 16/17 16/17 17 17 17 17 17 17 17 17 17 17 17/18 17/18 18 18 18 18 19 19 19 19 20 20 20 20 22
A. Baffle Filter . .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
B. Modular Grease Extractors [Energy Aire] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
C. Auto Wash [Energy Aire] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
D. Airflow Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . . .
E. Fire Extinguishing Systems .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
A. Ec oArch C anopi es . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
B. Ec oArch C anopi es With Ceiling Mounted Make-Up Air Plenum . . . . . . . . . . . . . .
A. Wall Attachment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
A. VCW Control Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
B. PAWS Control Panel . . . . . . . . . . .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
C. Damper and Detectors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
D. Ventilator Lights . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
A. Hot Water Wash . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
B. Cold Water Mist [optional] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
C. Drains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
D. Field Joints . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
E. Detergent Pump and Tank . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
F. Interconnecting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
G. Detergent Flow Chart . . . . . . . . . .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
A. VCW Control Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1. Adjustment . . . . . . . . . . .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2. Sequence Of Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3. Trouble-Shooting . . . . . . . . . .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
B. PAWS Control Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1. Manual Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
a. Fan Start . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
b. Fan Stop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
c. Wash Start . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
d. Wash Stop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2. Trouble Conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
a. Low Detergent Indicator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
b. Supervised Valve [optional] . . . . . . . . . .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3. Hood Plenum Fire Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
a. Automatic Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
b. Manual Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4. Programming Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
a . Setting The Clock . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
b. Setting The PAWS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1. Single Wash Models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2. Multi-Wash Models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
c. Setting The Fire Delay . . . . . . . . . .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
d. Reviewing The Daily Event Schedule . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
e. Changing The Daily Event Schedule . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
f. Repeating The Daily Event Schedule . . . . . . . .. . . . . . . . . . . . . . . . . . . . . . . . . . . .
g. Holiday Feature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
h. Fan On During Recovery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
i. Power Loss . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
j. Last Command Indicator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
k. Diagnostic Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
l. Detergent Pump and Tank . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2 OM-VMR
A. Baffle Filter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
B. Modular Grease Extractors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
C. Auto Wash Grease Extractors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
D. Air Adjustment Baffle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
E. Fire Dampers . . . . . . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . . . . . . . .. .. . . . . . . .. .. .
F. Air Make-Up [Supply] Plenums . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .. .. .
G. Auto Wash . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
H. Cold Water Mist [Optional] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
I. Lights . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
A. Baffle Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
B. Modular Grease Extractors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
C. Grease Trough . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
D. Grease Collection Receptacle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
E. Hood Canopy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
F. Detergent System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
G. Fusible Link Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
A. PAWS Panel - Electrical . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
B. VCW Panel - Electrical . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
C. PAWS/VCW Panel - Plumbing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
D. EVAC Detergent . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
E. Electro-Mechanical Damper . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
F. Fusible Link Damper . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
G. Hood Canopy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SGNIWARDDNAATADREHTO.X
A. EVAC Cleaner Cut Sheet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
B. Air Movement Recordings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
C. Calculating and Recording Air Movement Readings . . . . . . . . . . . . . . . . . . . . . .
D. Calculating and Recording Air Movement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
22 22 22 23 23 24 24 25 25 25
25 25 25 25 26 26 26 26
27 27 27 27 28 28 29 29
30 30 31 32 33
34
OM-VMR 3
1
I. TYPES OF SYSTEMS
This manual covers three [3] of the basic types of systems offered by AVTEC - Baffle Filter [AF], Modular Grease Extractor [AX] and Auto W ash Down [AW].
A.Baffle Filter [AF Series] [See fig. #1
] Model AF ventilators are listed by Underwriters Laboratories Inc. [UL] and are built in accordance with the National Fire Protection Association [NFPA] Standard No. 96 for use with UL Listed fire extinguishing systems for duct hood protection. They are available with or without an automatic exhaust fire damper. They utilize UL Classified removable baffle filters to extract grease and provide a limited fire barrier. The canopy contains an integral grease trough and removable grease receptacle(s). Surface, plenum and duct collar fire extinguishing systems may be factory supplied.
Vent Control Panels may be supplied with these systems. See additional wiring diagrams for options.
Installation shall be in accordance with NFPA 96.
B.Modular Grease Extractors [AX Series] Energy
Aire [see fig. #2] Model AX ventilators are listed by UL and built in accordance with NFPA Standard No. 96 for use with UL Listed fire extinguishing systems for duct and hood protection. They are available with or without an automatic exhaust fire damper.
These models utilize high velocity removable grease extractors. This exclusive design extracts up to 95%* of airborne grease contaminants. The
1
*Data from independent tests not a part of UL test
procedure.
canopy contains an integral grease trough and grease collection receptacle(s). Surface, plenum and duct collar fire extinguishing systems are
required and may be factory supplied.
Vent control panels may be supplied with these systems. See additional wiring diagrams for options.
Installation shall be in accordance with NFPA 96.
C.Auto Wash Down [AW Series] Energy Aire [see
fig. #3] Model AW ventilators are listed by UL and built in accordance with NFPA Standard No. 96 for use with UL Listed fire extinguishing systems for duct and hood protection. They are available with or without an automatic exhaust fire damper.
These systems utilize a high velocity grease extractor. This exclusive design extracts up to 95%* of airborne grease contaminants. An
4 OM-VMR
integral water wash system cleans the inside of the grease extraction chamber either by manual activation of the Wash Start button or by a programmable timer. The duration of the wash is electrically controlled. The wash system is also activated by an electrical thermostat or a manual switch in the event of a fire condition. A surface fire extinguishing system is required and may be factory supplied.
Auto Wash control panels are provided with these systems. Wiring diagrams are provided with this manual.
Installation shall be in accordance with NFPA 96.
D.Airflow Requirements
Minimum exhaust airflow requirements and
maximum make-up airflow requirements [where air is introduced directly inside the canopy] are shown on the chart below. These flow rates were established under laboratory conditions. Greater exhaust airflows and/or reduced make-up airflows may be required for complete capture.
CFM REQUIREMENTS
400°F Cooking 600°F Cooking 700°F Cooking Model No. Surface Equip. Surface Equip. Surface Equip. AFWO,AFBO 200 300 525 AFDO,AFWP AFBP,AFDP AFWE,AFDE AFBE AFWI,AFBI 250[175] N/R N/R AFDI,AFWD AFBD,AFDD AFIO,AFIP 250 400 600 AFIE AFII,AFID 300[150] N/R N/R AXWO,AXBO 200 275 525 AXDO,AXWP AXBP,AXDP AXWE,AXDE AXBE AXWI,AXBI 250[175] N/R N/R AXDI,AXWD AXBD,AXDD AXIO,AXIP 250 400 600 AXII 300[150] N/R N/R AWWO,AWWP 194 270 *525 AWWE,AWDO AWDP,AW DE AWBO,AW BP AWBE AWWI,AWBI 250[190] 270[146] N/R AWDI,AWWD AWBD,AW DD AWTE,AW TP 400 420 N/R AWTO N/R = Not Recommended
*=Manufacturer's test results not yet submitted to U.L. for capture tests.
E.Fire Extinguishing Systems
There are two basic types of ventilator fire extinguishing systems in use today:
Wet Chemical and Water Mist. Wet Chemical Systems may be all or partially factory installed [by the Fire System Manufacturer]; final hook up and certification at job site is done by the Fire System Manufacturer's local representative. These systems must be periodially inspected, and critical parts replaced. It is suggested that a service contract be purchased from the local representative. For further details refer to the manufacturer's technical manual.
AVTEC manufactures and installs a water mist fire extinguishing system, "MIST-A-FIRE", that connects to the building fire sprinkler system [must be "wet" type system]. Final connect of this system must be done in the field by the sprinkler contractor or authorized plumber. A certification/inspection report is done by an authorized AVTEC representative. Periodic inspection is generally required, but replacement of parts and periodic maintenance is virtually eliminated. For further details, refer to the AVTEC MIST-A-FIRE Installation and Operating Technical Manual.
II. INSTALLING THE VENTILATOR
The ventilator is supplied with brackets to facilitate the attachment of hanger rods to the vent. Hanger rods should be attached to all brackets to ensure proper support.
A.Ascertain that the ceiling/roof structure is strong
enough to support the weight of the hood and support system. The approximate weight of the hood is shown below:
45 lbs/linear ft. for hoods w/o AMU plenums. 55 lbs/linear ft. for hoods w/AMU plenums. 125 lbs for fire control cabinet.
B.Carefully uncrate the hood so as not to dent or
scratch the outer surface.
C.Position the hood on the floor in approximately
its final installed location.
D.Use 1/2" threaded rods to hang the hood. The
hanger rods should be approximately 1/2" closer to the wall at the structural attachment location than at the top of the hood. [see fig. #4] This ensures that the hood is held tightly against the wall.
Note! Do not remove
Support Brace until Ventilator installation is complete. Upon completion of installation, dispose of Support Brace and replace the Acorn Nuts to their original locations.
OM-VMR 5
Fig 4 E.The hood should be hung so that the bottom of the hood is 6'-6" above the finished floor unless otherwise specified. Carefully lift the hood into position being certain to avoid scratching the finished surfaces. Install 1/2" threaded rod from each bracket and the structural support. Secure rods with heavy duty nuts. [see fig. #5] Be sure that the hood is level.
Fig 5
Tower Interface Detail Place trim collar on tower. Position tower under hood. Fully tighten trim collar retainer hardware after tower and hood are aligned properly. See fig. A, B, and C (next page).
F.The entire exhaust duct system must be con-
tinuously welded. This includes the connection to the duct collar and the roof curb. All welds must be liquid tight.
NOTE: Welds must not impede operation of damper.
G.Connect the lights to the circuit breaker panel
through the light switch. All connections should be in compliance with NFPA 70, National Electric Code [NEC].
H. Install bulbs in the light fixture[s].
I.Install the grease filters [AF] or modules [AX].
J.Install the grease receptacles [AF or AX]
NOTE: A minimum of a three inch [3"] insulated fire barrier and air space must be maintained between the capture area skin of the ventilator and any combustible surface, including wall and ceiling. AVTEC ventilators normally have a 3" air space; insulation is added when specified.
III.CONTROL PANEL [if provided]
Control panels are provided with all auto wash type ventilators [Models AW- ] and are optional with the baffle filter type [AF- ] and modular grease extractor type [AX- ]. Control panels with Models AF- and AX- do not have the auto wash plumbing assembly compartments. Any control panel may be provided with a integral MIST-A- FIRE Extinguishing System alarm panel and sprinkler assembly piping; refer to the MIST-A-FIRE technical manual.
A.Wall Attachment
Control panel dimensions and connection detail are shown on the enclosed shop drawing. Panels may be surface mounted, partially recessed or fully recessed as shown on fig. 6.
1.Surface Mounted Drill four [4] holes in ventilator plumbing compartment as required. Be careful not to damage any components. Avoid drilling into electrical compartments. Bolt to wall with anchor bolts or other acceptable means. Weight of control panel varies from 90 lbs. to 200 lbs.
2.Recessed Cut hole in wall 1/2" greater than O/A dimensions of control box [shown on shop drawing]. Spacers or support angles may be necessary to provide proper support. It is recommended that panel be bolted to wall similar to method used for surface mounted above.
6 OM-VMR
ECOARCH HOOD MODELS
The Avtec EcoArch is the latest addition in premium ventilation systems that continues Avtec’s reputation as an innovative, technology leader focused on providing solutions for our customers needs. The combination of the patent pending arch top and the front mounted high velocity exhaust slot reduces the amount of exhausted CFM by 45% compared to traditional CFM rates. This translates into an annual electric and gas savings of up to 40%.
INSTALLATION INSTRUCTIONS
All EcoArch hoods by Avtec are provided with hanging brackets designed to receive ½” threaded rod with a ½” bolt and washer. Supporting rods (provided by others) must be connected to all factory installed brackets. Recommended hanging height is
between 6’-6” and 7’-0” above the nished oor.
ALL AVTEC VENTILATION SYSTEMS MUST BE INSTALLED IN ACCORDANCE WITH NFPA-96 REMOVAL OF SMOKE AND GREASE-LADEN VAPORS FROM COMMERCIAL COOKIGN EQUIPMENT.
A. EcoArch Canopies
1. Check all local codes prior to installation. Special requirements may be necessary depending upon building construction.
8. For make-up air hoods, the supply collar with built-in UL listed re damper and air volume damper must be
installed per instructions on collar.
9. Provide a removable service door in supply duct near
re damper.
B. EcoArch Canopies equipped with a Ceiling Mounted Make up Air Plenum
If your EcoArch hood comes equipped with a ceiling mounted make up air plenum please refer to the follow­ing steps.
Follow steps 1-3 as outlined at left.
4. Suspend hood from adequate roof supports using ½” threaded rods with nuts and washers.
5. Level hood left to right and front to back.
6. The make up air plenum is designed to mount against the front face of the hood.
2. Move crated hood to location of installation and very carefully uncrate hood.
3. Front Mounted Exhaust Plenum: The EcoArch is different from almost all other kitchen exhaust hoods on the market today. The exhaust plenum is in the front of the hood versus the traditional rear location to minimize exhausted kitchen air and for easier and safer access
to the lter medium for cleaning and/or replacement.
Refer to drawing before proceding to step 4.
4. Suspend hood from adequate roof supports using 1/2”
threaded rods with nuts and washers.
5. Level hood left to right and front to back.
6.
Brackets are provided for hoods which are to be installed
end to end or back to back. Bolt brackets together using
3/8” bolt through holes provided. (See Fig. 6 at right)
7. Install C channel where the ends of the hood meet and install T moldings on front face of hoods where they join. High temperature silicone can be used to install C channel and T moldings.
7. Brackets are provided at the top front of the hood and the top of the make-up air plenum box. Bolt brackets
together using 3/8” bolt through holes provided. (See
Fig. 6)
Fig 6
8. Install C channel where the ends of the hood meet
and install T moldings on front face of hoods where they join. High temperature silicone can be used to install C channel and T moldings.
9. For make-up air hoods, the supply collar with built-in
UL listed re damper and air volume damper must be
installed per instructions on collar.
10. Provide a removable service door in supply duct near
re damper.
OM-VMR 7
8 OM-VMR
IV. ELECTRICAL CONNECTIONS
A.VCW Control Panel [Refer to fig. 7]
1.Typical field connection terminals for VCW Control Panel are shown in fig. 7. For custom features such as sequential wash, time delay, etc. refer to AVTEC shop drawing in back of this manual.
2.Terminals No. 1 and No. 2 are for the 120vac Power Supply. Terminal No. 1 is Hot and Terminal No. 2 is Neutral.
3.Terminals No. 3 and No. 4 are 120vac power for the Water Solenoid and Detergent Pump. These terminals are "hot" whenever the Water Wash Solenoid and the Detergent Pump is scheduled to be "ON" or when there is a fire condition. Terminal No. 5 provides power for a pump/prime switch with a momentary closed/normally open contact. This switch is helpful in checking the performance of the pump as well as in priming the pump.
B.Programmable Automatic Wash Sequence
[PAWS] Control Panel
1.Typical Field Connections for the PAWS Control Panel are shown on [figs. 10, 11, and 12]. Note that all options and connections may not be included on your system.
2.Terminal Block #1 [TB-1] has three [3]
terminals and is located on the right-hand side of the Input/Output [I/O] Board. Terminal #1 [uppermost] is for the Hot lead of the power supply and is protected by a fuse located within the panel. Terminal #2 [center] is for the Neutral lead of the power supply. Terminal #3 [lowermost] is used to ground the Input/Output Board to the Control Panel Housing.
Terminal No. 4 is Hot and Terminals No. 2 & 3 are Neutral.
3.Terminals No. 3 and No. 6 carry 120vac whenever the fans are scheduled to be ON. They are used to activate the fan contactor[s]. In the event of a fire situation, power is removed from Terminal 5 which provides power for Terminal No. 6. Terminal No. 6 is the Hot lead and Terminal No. 3 is Neutral.
7.giF
OM-VMR 9
4.Terminal Block #2 [TB-2] has three [3] pairs of terminals and is located at the upper right corner of the Input/Output Board. The first pair of terminals are for the number one wash valve solenoid. This will be the only wash output active in a P-10-__ or P-15-__ Control Panel. The second pair of terminals are for the number two wash valve solenoid. The third pair of terminals are for the number three wash valve solenoid.
5.Terminal Block #3 [TB-3] has three [3] pairs of terminals. It will not be present on P-10-__ or P­15-__ Control Panels. The first pair of terminals are for wash valve solenoid number four. The second pair of terminals are for the number five wash valve solenoid. The third pair of terminals are for the number six wash valve solenoid.
6.Terminal Block #4 [TB-4] has three [3] pairs of terminals. It will not be present on P-10-__ or P­15-__ Control Panels. The first pair of terminals are for the number seven wash valve solenoid. The second pair of terminals are for the number eight wash valve solenoid.
7.Terminal Block #5 [TB-5] has three [3] pairs of terminals. The first pair provides power for the detergent pump. The second pair provides power for the PAWS Alarm/Trouble horn. [The third pair provides power for the vent fan contactors. [see figs. #8a & 8b]
Note that the maximum output is one-and-one­half [1-1/2] amperes. If the total inrush current for all contactors will exceed this limit, an intermediate relay must be used.
8.Terminal Block #9 [TB-9] has three [3] pairs of terminals and is located at the lower left corner of the Input/Output Board. The first pair of terminals are for connection to the optional supervised shut-off valve. If the panel is not equipped with this option, a jumper wire must be installed. The second pair of terminals are for connection to the Manual Fire Switch. The third pair of terminals are for connection to the automatic fire switch contacts terminals are for connection to the automatic fire switch contacts.
Fig 8a
Fig 8b
10 OM-VMR
9.Terminal Block #11 [TB-11] has three [3] pairs of terminals. The first pair of terminals are low voltage connections for the detergent low level probe. The probe should be installed in the detergent container so that it does not protrude above the top of the detergent pump inlet strainer. [fig. #9] This is intended to prevent cavitation of the pump and will advise when the tank needs to be refilled. The probe rods may be cut to facilitate a neat and effective installation.
Fig 9
10.Terminal Block #12 [TB-12] has three [3] pairs of terminals. The first pair of terminals are for connection to the optional battery.
OM-VMR 11
Loading...
+ 25 hidden pages