Autronica Autroprime 2 Configuration Handbook

Page 1
116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03
Configuration Handbook
Autroprime Interactive Fire Detection System
116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03
Release 2
Page 2
Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03,
Autronica Fire and Security AS
Page 2
COPYRIGHT ©
This publication, or parts thereof, may not be reproduced in any form, by any method, for any purpose.
Autronica Fire and Security AS and its subsidaries assume no responsibility for any errors that may appear in the publication, or for damages arising from the information in it. No information in this publication should be regarded as a warranty made by Autronica Fire and Security AS. The information in this publication may be updated without notice.
Product names mentioned in this publication may be trademarks. They are used only for identification.
Page 3
Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03,
Autronica Fire and Security AS
Page 3
Table of Contents
1.Introduction ....................................................................... 8
1.1 About the Handbook ......................................................................... 8
1.2 The Reader ....................................................................................... 8
1.3 Reference Documentation ................................................................ 8
1.4 Ready-to-use in a Pre-configured State ............................................ 9
1.5 Saving a Configuration and Restarting the System .......................... 9
1.6 Configuration Examples .................................................................... 9
2.Service Commands .......................................................... 10
2.1 Site-specific Configuration ................................................................ 10
2.2 Access Level 3 – Service Menu ........................................................ 10
2.3 Service Menu .................................................................................... 10
2.4 Entering the Service Menu ................................................................ 12
3.System Settings ................................................................ 14
3.1 Menu Selections - Overview ............................................................. 14
3.2 Save Configuration ............................................................................ 14
3.3 Restart System .................................................................................. 15
3.4 Day Mode Operation Times .............................................................. 16
3.4.1Viewing Existing Day Mode Operation Times......................... 17
3.4.2Adding new Day Mode Operation Times ................................ 17
3.5 Service Mode Password ................................................................... 18
3.6 Date and Time ................................................................................... 18
3.7 Set Operator Panel Connection ........................................................ 19
3.8 Sound Patterns .................................................................................. 20
3.9 Automatic Resound ........................................................................... 22
3.10Detection Zone (DZ) Delay Timers ................................................... 22
3.11Detection Zone (DZ) Global Dependency ......................................... 23
3.12Battery Parameters ........................................................................... 23
3.13Panel Name ....................................................................................... 24
3.14Language .......................................................................................... 24
3.15FARE and FWRE Disablement ......................................................... 25
3.16Mains Power Fault Indication ............................................................ 25
3.17Printer Setup ..................................................................................... 26
3.18Configuration Check .......................................................................... 26
3.19System S hutdown ............................................................................ 27
3.20Restore Factory Settings ................................................................... 28
4.Loop Operation ................................................................. 29
4.1 Accessing the Menu Selections ........................................................ 29
4.2 Enable ............................................................................................... 30
4.3 Disable .............................................................................................. 30
4.4 Change Disable Time Span .............................................................. 31
Page 4
Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03,
Autronica Fire and Security AS
Page 4
4.5 Show Polluted Detectors ................................................................... 31
4.6 Show Low Current Units ................................................................... 32
5.Unit Configuration ............................................................ 33
5.1 Menu Selections - Overview ............................................................. 33
5.2 Detection Zones ................................................................................ 34
5.2.1Accessing the Menu Selections .............................................. 34
5.2.2Configure Properties for a Detection Zone ............................. 35
5.2.3Connect to Alarm Zone ........................................................... 36
5.2.4Connect to Output ................................................................... 36
5.2.5Connect to Disable Input Device ............................................ 37
5.2.6Connect to Local Alarm Delay Unit ......................................... 37
5.2.7Connect to Panel .................................................................... 37
5.2.8Disconnect from Alarm Zone .................................................. 38
5.2.9Disconnect from Output .......................................................... 38
5.2.10Disconnect from Disable Input Device .................................... 38
5.2.11Disconnect from Local Alarm Delay Unit ................................ 38
5.2.12Disconnect from Panel ............................................................ 39
5.2.13Show Member Points .............................................................. 39
5.2.14Show Connected Units ........................................................... 39
5.3 Alarm Zones ...................................................................................... 40
5.3.1Accessing the Menu ................................................................ 40
5.3.2Configure Properties for an Alarm Zone ................................. 41
5.3.3Connect to Neighbour Alarm Zone ......................................... 41
5.3.4Disconnect from Neighbour Alarm Zone................................. 42
5.3.5Show Member Fire Alarm Devices ......................................... 42
5.3.6Show Neighbour Alarm Zones ................................................ 42
5.3.7Show Activating Detection Zones ........................................... 43
5.4 Points................................................................................................. 44
5.4.1Accessing the Menu ................................................................ 44
5.4.2Configure Properties for a Point ............................................. 45
5.4.3Move to Detection Zone (/Create New) .................................. 46
5.4.4Connect to Output ................................................................... 47
5.4.5Connect to Activation Group (/Create New) ........................... 48
5.4.6Disconnect from Output .......................................................... 49
5.4.7Disconnect from Activation Group .......................................... 49
5.4.8Show Connected Units ........................................................... 50
5.5 Fire Alarm Devices ............................................................................ 51
5.5.1Accessing the Menu ................................................................ 51
5.5.2Configure Properties for a Fire Alarm Device ......................... 52
5.5.3Move to Alarm Zone ................................................................ 52
5.5.4Show Connected Units ........................................................... 53
5.6 Loop Outputs ..................................................................................... 54
5.6.1Accessing the Menu ................................................................ 54
5.6.2Configure Properties for a Loop Output .................................. 55
5.6.3Connect to Output ................................................................... 56
5.6.4Connect to Activation Group ................................................... 56
5.6.5Disconnect from Output .......................................................... 57
5.6.6Disconnect from Activation Group .......................................... 57
5.6.7Show Activating Detection Zones ........................................... 58
5.6.8Show Activating Points ........................................................... 58
5.6.9Show Activating Inputs ............................................................ 59
5.6.10Show Activating Groups .......................................................... 59
5.6.11Show Activating Outputs ......................................................... 60
5.6.12Show Connected Units ........................................................... 60
5.7 Local Outputs .................................................................................... 61
5.7.1Accessing the Menu ................................................................ 61
5.7.2Configure Properties for a Local Output ................................. 62
Page 5
Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03,
Autronica Fire and Security AS
Page 5
5.7.3Connect to Output ................................................................... 63
5.7.4Connect to Activation Group ................................................... 63
5.7.5Disconnect from Output .......................................................... 64
5.7.6Disconnect from Activation Group .......................................... 64
5.7.7Show Activating Detection Zones ........................................... 65
5.7.8Show Activating Points ........................................................... 65
5.7.9Show Activating Inputs ............................................................ 66
5.7.10Show Activating Groups .......................................................... 66
5.7.11Show Activating Outputs ......................................................... 67
5.7.12Move to Alarm Zone ................................................................ 67
5.7.13Show Connected Units ........................................................... 68
5.8 Loop Inputs ........................................................................................ 69
5.8.1Accessing the Menu ................................................................ 69
5.8.2Configure Properties for a Loop Input ..................................... 70
5.8.3Connect to Output ................................................................... 71
5.8.4Connect to Alarm Zone ........................................................... 71
5.8.5Disconnect from Output .......................................................... 71
5.8.6Disconnect from Alarm Zone .................................................. 72
5.8.7Show Connected Units ........................................................... 72
5.9 Local Inputs ....................................................................................... 73
5.9.1Accessing the Menu ................................................................ 73
5.9.2Configure Properties for a Local Input .................................... 74
5.9.3Connect to Output ................................................................... 75
5.9.4Connect to Alarm Zone ........................................................... 75
5.9.5Disconnect from Output .......................................................... 75
5.9.6Disconnect from Alarm Zone .................................................. 76
5.9.7Show Connected Units ........................................................... 76
5.10Loop I/O Carriers ............................................................................... 77
5.10.1Description .............................................................................. 77
5.10.2Accessing the Menu ................................................................ 78
5.10.3Configure Properties for a Loop IO Carrier ............................. 79
5.10.4Show All Carrier Units ............................................................. 79
5.10.5Show Carrier Points ................................................................ 80
5.10.6Show Carrier Inputs ................................................................ 80
5.10.7Show Carrier Outputs ............................................................. 81
5.11Mimic Panels ..................................................................................... 82
5.11.1Accessing the Menu ................................................................ 82
5.11.2Configure Properties for a Mimic Panel .................................. 82
5.11.3Configure Mimic Inputs and Outputs ...................................... 83
5.12Activation Groups .............................................................................. 84
5.12.1Accessing the Menu ................................................................ 84
5.12.2Configure Properties for an Activation Group ......................... 85
5.12.3Connect to Output ................................................................... 85
5.12.4Disconnect from Output .......................................................... 86
5.12.5Show Member Points .............................................................. 86
5.12.6Show Connected Units ........................................................... 87
5.13External Interfaces ............................................................................ 87
5.13.1Accessing the menu ................................................................ 87
5.13.2Serial Port Settings ................................................................. 88
5.13.3TCP/IP Port Settings ............................................................... 88
5.13.4ESPA ....................................................................................... 89
5.13.5MODBUS ................................................................................ 92
5.13.6VDR ......................................................................................... 96
5.13.7Remote Access ....................................................................... 97
5.14Detection Loops ................................................................................ 100
5.15Operator Panels ................................................................................ 101
Page 6
Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03,
Autronica Fire and Security AS
Page 6
6.Unit Test ............................................................................ 102
6.1 Menu Selections - Overview ............................................................. 102
6.2 Testing Detection Zones ................................................................... 102
6.3 Testing Alarm Zones ......................................................................... 103
6.4 Testing Fire Alarm Devices ............................................................... 104
6.5 Testing Loop Outputs ........................................................................ 105
6.6 Testing Local Outputs ....................................................................... 106
6.7 Testing Mimic Panels ........................................................................ 107
7.System Topology .............................................................. 108
7.1 Menu Selections - Overview ............................................................. 108
7.2 Show Properties ................................................................................ 108
7.3 Show Topology .................................................................................. 109
7.4 Show All Faults .................................................................................. 109
7.5 Clear Loop Config. – Restart System ............................................... 110
7.6 Deactivate ......................................................................................... 111
7.7 Activate .............................................................................................. 111
8.Export and Import ............................................................. 112
8.1 Menu Selections - Overview ............................................................. 112
8.2 USB Output ....................................................................................... 112
8.3 Export Log ......................................................................................... 113
8.4 Select Configuration & Restart System ............................................. 114
8.5 Backup Current Configuration ........................................................... 114
8.6 Export Configuration.......................................................................... 115
8.7 Import Configuration .......................................................................... 116
9.Configuration Examples ................................................... 117
9.1 Before you Start ................................................................................ 117
9.2 Example 1: Basic Configuration Example ......................................... 118
9.2.1Site information – Excel Sheet ................................................ 120
9.2.2Buttons .................................................................................... 120
9.2.3Initial Startup – Default Configuration ..................................... 121
9.2.4Save Configuration / Restart System ...................................... 121
9.2.5Site-specific Configuration – Example 1 ................................. 122
9.2.6Step 1: Create Detection Zones and Connect Points ............. 123
9.2.7Add a Site-specific Name to each Point (if needed) ............... 124
9.2.8Step 2: Connect the new Detection Zones to the Alarm
Zone ........................................................................................ 125
9.2.9Step 3: Save Configuration / Restart System ......................... 125
9.3 Example 2: Configuration with several alarm zones and
control functions ................................................................................ 126
9.3.1Site-specific Configuration – Example 2 ................................. 128
9.3.2Step 1: Create Detection Zones and Connect Points ............. 129
9.3.3Add a Site-specific Name to each Point (if needed) ............... 130
9.3.4Step 2: Connect Fire Alarm Devices to new alarm
zones (5.5.3) ........................................................................... 131
9.3.5Step 3: Connect already configured detection zones to
a new alarm zone (Alarm Zone 1). (5.2.3) .............................. 131
9.3.6Step 4: Connect the new detection zones to a new
alarm zone (Alarm Zone 2). (5.2.3) ......................................... 132
9.3.7Step 5: Define Alarm Zone 1 and Alarm Zone 2 as
Neighbour Alarm Zones (5.3.3) .............................................. 132
Page 7
Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03,
Autronica Fire and Security AS
Page 7
9.3.8Step 6: Connect a point in Detection Zone 6 to the
Parent Alarm Zone (5.2.3) ...................................................... 133
9.3.9Step 7: Configure outputs for ventilation control and
door control (5.4.4 and 5.2.4) ................................................. 133
9.3.10Step 8: Save Configuration / Restart System ......................... 134
10.Other Functions ................................................................ 135
10.1Clipboard Functions .......................................................................... 135
10.1.1Copy ........................................................................................ 135
10.1.2Cut ........................................................................................... 135
10.1.3Paste ....................................................................................... 136
10.1.4View Content ........................................................................... 136
10.2Capital and Small Letters –Toggle functionality ................................ 137
11.Configuration Tool ............................................................ 138
11.1Introduction ........................................................................................ 138
11.2Setup Wizard ..................................................................................... 138
11.3Starting the Configuration Tool ......................................................... 140
11.4Help File ............................................................................................ 141
12.Appendix ........................................................................... 142
12.1Alarm Organization............................................................................ 142
12.1.1Detection Zones with Different Properties .............................. 142
12.1.2The Actioning of Alarm Zones................................................. 142
12.1.3Immediate Action Detection Zones ......................................... 143
12.1.4Dependency Action Detection Zones ..................................... 143
12.1.5Delayed Action Detection Zones ............................................ 144
12.1.6Delayed Dependency Detection Zones .................................. 145
12.1.7SOLAS Detection Zones ......................................................... 146
12.1.8Silent, Small and Large Alarm – Overview ............................. 146
13.Reader’s Comments ......................................................... 149
Page 8
Introduction
Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03,
Autronica Fire and Security AS
Page 8
1. Introduction
1.1 About the Handbook
This document describes in detail how to configure site-specific installations of the Autroprime Interactive Fire Detection System by means of the operating buttons on the panel.
1.2 The Reader
This handbook is intended for technicians and service personnel who are responsible for the site-configuration of the Autroprime system. We assume that the reader is familiar with the manoeuvre and utility buttons which are described in detail in the Operator’s Handbook.
1.3 Reference Documentation
The table below shows an overview of the complete technical documentation that is available in several languages:
Documents Part number File name
System Description 116-P-APRIME2-SYSTEM/XGB aprime2system_xgb Getting Started 116-P-APRIME2-GESTAR/EGB aprime2gestar_egb Installation Handbook 116-P-APRIME2-INSTAL/DGB aprime2instal_dgb Connecting Loop Units 116-P-CONNECTLOOPUNIT/DGB connectloopunit_dgb Configuration Handbook 116-P-APRIME2-CONFIG/EGB aprime2config_egb Operator’s Handbook 116-P-APRIME2-OPERAT/FGB aprime2operat_fgb User Guide 116-P-APRIME2-USERGU/LGB aprime2usergu_lgb Wall Chart 116-P-APRIME2-WALLC/LGB aprime2wallc_lgb Menu Structure 116-P-APRIME2-MENUS/MGB aprime2menus_mgb Datasheet; Fire Alarm Control Panel BS-200 116-P-BS200/CGB bs200_cgb Datasheet; Fire Alarm Control Panel BS-200M
116-P-BS200M/CGB bs200m_cgb
Datasheet; Fire Alarm Control Panel BS-200L
116-P-BS200L/CGB bs200l_cgb
Datasheet; Repeater Panel BS-211 116-P-BS211/CGB bs211_cgb Datasheet; Information Panel BV-210 116-P-BV210/CGB bv210_cgb Datasheet; Fire Brigade Panel BU-210 116-P-BU210/CGB bu210_cgb Datasheet; Mimic Driver BUR-200 116-P-BUR200/CGB bur200_cgb
Page 9
Introduction
Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03,
Autronica Fire and Security AS
Page 9
1.4 Ready-to-use in a Pre-configured State
Autroprime is provided to the user in a pre-configured state, in this
state the panel is set to recognize detectors and other loop units connected to the detection loops and the availability of routing equipment, etc. As such, the system is fully functional and ready-to­use simply by turning ON the power, but not configured to respond in any non-default way. A functional verification of the panel is run to assure the panel itself is fully functional.
By default the system has one Detection Zone and one Alarm Zone. A point in alarm will activate all Fire Alarm Devices and Fire Alarm Routing Equipment.
Site-specific configuration can be performed by means of the panel buttons. Refer to chapter 2.1, Site-specific Configuration.
1.5 Saving a Configuration and Restarting the System
Note that you always have to save a configuration and restart the system;
after an initial startup (part of the start-up procedure) each time a configuration has been changed.
This menu selections are found in the Service Menu/System Settings (see chapter 2).
1.6 Configuration Examples
Chapter 9 in this handbook deals with two configuration examples, one basic configuration example and an example with several alarm zones and control functions. These examples shows how to perform typical configurations of a medium-sized installation (to simplify the understanding of the configuration principle, the basic configuration example deals with one loop and 8 points only).
Page 10
Service Commands
Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03,
Autronica Fire and Security AS
Page 10
2. Service Commands
2.1 Site-specific Configuration
Site-specific configuration can be performed by means of the panel buttons (configuration level 2), typically including:
naming and assigning detectors/manual call points to Detection
Zones
naming and defining the number and type of Detection Zones
(Immediate Action, Dependency Action, Delayed Action, Delayed Dependency Action, SOLAS)
assigning Fire Alarm Devices to Alarm Zones specifying the Detections Zones that can activate selected Alarm
Zones
configuring “conditions” for outputs, for example, coincidence
action; meaning that at least two detectors in the same detection zone must be in alarm state before actions are initiated
assigning Detection Zones to disable devices (BW-200)
All these options and many more are available in the Service menu.
2.2 Access Level 3 – Service Menu
From the operator panel you can perform service commands. To use the Service Commands, access level 3 is required.
Access Level Access Remedy Description
3 Password restricted Accessible by persons trained and authorized to do
reconfiguration of site specific data and maintenance according to the manufacturer’s published instruction.
4 Mechanical tool Accessible by persons doing repair work and changing
firmware.
2.3 Service Menu
The entire Service Menu is shown on the next page.
Page 11
Service Commands
Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03,
Autronica Fire and Security AS
Page 11
Access Level 1: No key or password requ ired
Access Level 2: Access by key
Access Level 3: Password restricted
Menu St ructur e English
Enter Service Mo de
Service
System Settings Loop Opera t ion Unit Configuration Unit Test System Topology Export and Import
Save Configuration Restart System Day Mode Operation Times Service Mode Password Date and Time Set Ope ra tor P ane l Conne cti on Sound P atte rns Automatic Resound DZ Delay Timers DZ Global Depe ndency Battery Parameters Panel Name Language FARE and FWRE Disa blement Mai ns P ower Fault I ndic ation Printer Setup Configur atio n C heck Sys tem S hutdown Restore Factory Settings
Enable Units Disable Units Change Disable Time Span Show P ollute d Dete ctor s Show Low Cur re nt Units
Detec tion Zone s Alar m Zones Points Fire Alarm Devices Loop Outputs Local Outputs Loop Inputs Local Inputs Loop I/O Ca rr ier s Mimic Panels Activ ati on Groups External Interfaces Detec tion Loops Operator Panels
Detec tion Zone s Alar m Zones Fire Alarm Devices Loop Outputs Local Outputs Mimic Panels
Show Topolog y Show All Faul ts Clear Loop Config. –Restart System Deactivate/Activate
Expor t Log Select Configuration & Restart System Back up Cur re nt Configu r ati o n Expor t Confi gura tio n Import C onfigu r atio n
Exit Service Mode
(Functions)
116-P-APRIME2-MENUS/MGB, 2012-01-10
(Applicable only if Mimic Panels are used)
Connect to Alarm Zone Connect to Output Connect to Disable I nput De vice Connect to Loc al Alarm Delay Unit Connect to Panel (special panel only) Disc on nect from Alar m Zone Disconnect from Output Disconnect from Disable Input Device Disconnect from Local Alarm Delay Unit Disconnect from Panel (special panel only) Show Member P o i nts Show Connected Units
Connect to Neighbour Alarm Zone Disc on nect from Neighbour Al arm Zone Show Member Fire Alarm Devices Show Neighbour Alarm Zones Show Activating Detection Zo nes
Move to De te ction Zone (/Cre ate New) Connect to Output Connect to Acti vation Group (/Create New) Disconnect from Output Disconnect from Activat ion Group Show Connected Units
Move to Alarm Zone Show Connected Units
Connect to Output Connect to Acti vation Group Disconnect from Output Disconnect from Activat ion Group Show Activating Detection Zo nes Show Activa ti ng P oi nts Show Activa ti ng I nputs Show Activa ti ng G r oups Show Activa ti ng O utputs
Move to Alarm Zone (applies to FAD only)
Show Connected Units
Connect to Output Connect to Alarm Zone Disconnect from Output Disc on nect from Alar m Zone Show Connected Units
Show All Carrier Unit s Show Carrie r Points Show Carrier Inputs Show Carrier Outputs
Configure Show Mimic I nputs Show Mimic O utputs
Connect to Output Disconnect from Output Show Member P o i nts Show Connected Units
(Not applicable to FAD, FARE and FWRE:)
(Not applicable to FARE and FWRE:)
Serial Port Settings TCP/IP Port Sett ings ESPA MODBUS VDR Remote Access
Configure ESPA Settings Configure ESPA Events Configure ESPA Receivers Table Send ESPA Test Event
Configure MODBUS Settings Congigure Status Registers Configure Command Regist ers Set Testb it to 0 Set Testb it to 1 Assi gn Uni que MODBUS Index es
Configure V DR S ettings Send VDR Test Event
Server an d W eb Access User Manageme nt Clients Clien t Proxy Server
Page 12
Service Commands
Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03,
Autronica Fire and Security AS
Page 12
2.4 Entering the Service Menu
First, to enter the Menu Mode from operation mode or the panel’s
idle state, press and hold down the Enter button
for a few
seconds.
The following will appear in the display:
Use the arrow down button to scroll down and select Enter
Service Mode.
Press Enter twice, then use the alphanumeric keypad and type
the password that has been selected during commissioning (4 characters).
To accept the password, press Enter once more. The menu selections Service and Exit Service now appear in the
display.
Page 13
Service Commands
Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03,
Autronica Fire and Security AS
Page 13
To enter the Service menu, use the arrow down button to scroll down and select Service, then press the Enter.
Page 14
System Settings
Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03,
Autronica Fire and Security AS
Page 14
3. System Settings
3.1 Menu Selections - Overview
All system settings are global settings, meaning that the settings affect the entire system. From the Service Menu, perform the following: Press Enter to select System Settings.
The following menu selections appear:
Save Configuration (chapter 3.2) Restart System (chapter 3.3) Day Mode Operation Times (chapter 3.4) Service Mode Password (chapter 3.5) Date and Time (chapter 3.6) Set Operator Panel Connection (chapter 3.7) Sound Patterns (chapter 3.8) Automatic Resound (chapter 3.9) Detection Zone Delay Timers (chapter 3.10) Detection Zone Global Dependency (chapter 3.11) Battery Parameters (chapter 3.12) Panel Name (chapter 3.13) Language (chapter 3.14) FARE and FWRE Disablement (chapter 3.15) Mains Power Fault Indication (chapter 3.16) Printer Setup (chapter 3.17) Configuration Check (chapter 3.18) System Shutdown (chapter 3.19) Restore Factory Settings (chapter 3.20)
The following chapters describe the menus in detail (following the sequence of the System Settings Menu).
3.2 Save Configuration
Each time a configuration has been changed, this command should be run. The changes will not become effective until a Restart System command is performed.
From the Service Menu, perform the following:
Press Enter to select System Settings. Press Enter twice to select Save Configuration. Type a new Site Name, or accept the existing one by pressing the
arrow down button.
Type a new Operator Name, or accept the existing one by
pressing the arrow down button.
Press Enter to type a new Site Configuration Version then press
Enter, or accept the existing one by pressing the arrow down button.
Press Enter to type a new Description then press Enter, or accept
the existing one by pressing the arrow down button.
To confirm, press Enter.
Page 15
System Settings
Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03,
Autronica Fire and Security AS
Page 15
3.3 Restart System
Note that you always have to save a configuration (chapter 3.2) and restart the system in order to activate a configuration:
each time a configuration has been changed after an initial startup (part of the start-up procedure)
From the Service Menu, perform the following:
Press Enter to select System Settings. Press the arrow down button to select Restart System, then press
Enter.
If the system is to be restarted after a configuration has been
changed, the following message will appear:
”System configuration data has been changed. If the system is restarted without saving configuration data, the changes will be lost. Save data before restarting?” o Use the left arrow button to select Accept, then press Enter
twice.
o Type a new Site Name, or accept the existing one by pressing
the arrow down button.
o Type a new Operator Name, or accept the existing one by
pressing the arrow down button.
o Press Enter to type a new Site Configuration Version then
press Enter, or accept the existing one by pressing the arrow down button.
o Press Enter to type a new Description then press Enter, or
accept the existing one by pressing the arrow down button.
o To confirm, press Enter.
After a short period the message “Configuration has been saved” will appear.
o Press the left arrow button, then press Enter to confirm.
If the system is to be restarted after an intitial startup, the
following message will appear: “Restart of the system will perform a controlled shutdown before restart. This may take a while, depending on the system size.” o Use the left arrow button to select Accept, then press Enter to
confirm. The message ”System is now shutting down…” will appear,
and a bar will appear at the bottom showing the progress of the reboot.
Page 16
System Settings
Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03,
Autronica Fire and Security AS
Page 16
3.4 Day Mode Operation Times
By default the entire system is set to Night Mode, meaning that the system is set to immediate output actioning.
The system menu Day Mode Operation Times allows you to configure settings for automatic delay of the activation of outputs to Fire Alarm Devices (FAD) and/or Fire Alarm Routing Equipment (FARE) at certain periods.
The settings will only affect points that have been set to “Override Delay and Dependency NO” in detection zones configured as Delayed Action Detection Zones or Delayed Dependency Detection Zones.
To achieve this, you simply choose the days in the week when you want the system to automatically enable the delays, plus the exact duration of the disablement in hours and minutes (the start time and end time).
A maximum of 14 settings are available (for example, 7 days; 2 intervals per day, or, for example, 14 intervals for one specific day).
Note that overlapping settings are not possible.
From the Service Menu, perform the following:
Press Enter to select System Settings. Press the arrow down button to select Day Mode Operation
Times, then press Enter twice.
Use the left/right arrow button to select among the following days:
o Unspecified o Every day o Monday to Friday o Saturday, Friday, Thursday, Wednesday, Tuesday, Monday,
Sunday.
Press Enter. Use the alphanumeric keypad to specify the start time*
(hours:minutes), then press Enter.
Specify the end time* (hours:minutes), then press Enter. * Note that if an invalid input is given, a message indicating this will
appear in the display. It is recommended that all settings (for example, settings for 4
different days) are done before the settings finally are confirmed. To view existing Day Mode Operation Times, refer to chapter 3.4.1.
To add new Day Mode Operation Times to existing ones at a later point of time, refer to chapter 3.4.2.
Press and hold down the Function button
a few seconds
(“Long press to accept or cancel”).
To confirm the new settings (Accept), press Enter.
Page 17
System Settings
Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03,
Autronica Fire and Security AS
Page 17
3.4.1 Viewing Existing Day Mode Operation Times
To view existing Day Mode Operation Times, do as follows:
o If you have left the Day Mode Operation Times menu (if you
have not, go directly to the next step), return to the System Settings menu, press the arrow down button to select Day Mode Operation Times, then press Enter.
o In the Day Mode Operation Times menu, scroll downwards
using the arrow down button several times (pressing the arrow down button 3 times will reveal the next setting, pressing 3 times more will reveal the next setting, etc.).
3.4.2 Adding new Day Mode Operation Times
To add a new Day Mode Operation Time at a later point, provided
that there are available settings (maximum 10), do as follows: o In the System Settings menu, press the arrow down button to
select Day Mode Operation Times, then press Enter twice.
o Scroll downwards using the arrow down button several times
until “Unspecified “ is shown (pressing the arrow down button 3 times will reveal the next setting, pressing 3 times more will reveal the next setting, etc.).
The number of times you have to press the arrow down button before “Unspecified” is shown in the display depends on the number of settings that already are defined.
For example, if there is 1 previous setting, you have to press the arrow down button 3 times before “Unspecified” is shown. If there are 2 previous settings, you have to press the arrow down button 6 times before “Unspecified” is shown.
o When “Unspecified” is shown in the display, use the left/right
arrow button to select among the days that are available, and continue as described in chapter 3.4.
Page 18
System Settings
Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03,
Autronica Fire and Security AS
Page 18
3.5 Service Mode Password
This menu allows you to change the Service Mode Password. A total of 4 characters must be used.
From the Service Menu, perform the following:
Press Enter to select System Settings. Press the arrow down button to select Service Mode Password,
then press Enter twice.
Type the new password, then press Enter. Type the new password once more, then press Enter. To confirm the new password, press Enter once more.
The message “Please wait…” will appear in the display and the new password will take effect within a couple of seconds.
3.6 Date and Time
This menu allows you to set/change the date and time.
From the Service Menu, perform the following:
Press Enter to select System Settings. Press the arrow down button to select Date and Time, then press
Enter twice.
To change the time, overwrite the time (hours, minutes, seconds),
then press Enter.
To change the date, overwrite the date (day, month, year), then
press Enter.
To confirm the new settings, press Enter once more.
Page 19
System Settings
Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03,
Autronica Fire and Security AS
Page 19
3.7 Set Operator Panel Connection
This command allows the operator to specify how the operator panel is connected.
If the panel is to be operated as a standalone panel (and the
panel is connected accordingly, i.e. J7), the menu selection Operator Panel must be selected (default).
If the panel is to be connected to a panel bus, the menu selection
Auxiliary terminal block (J4) must be selected.
From the Service Menu, perform the following:
Press Enter to select System Settings. Press the arrow down button to select Operator Panel
Connection, then press Enter twice.
Use the arrow left/right button to select;
J7, Operator Panel (default) if the panel is to operate as a standalone panel or; J4, Auxiliary terminal block if the panel is to be connected to a panel bus.
To confirm the chosen settings, press Enter twice.
IMPORTANT NOTE: The default panel connection setting (Service Menu/System
Settings/“Set Operator Panel connection”) is set to “J7, Operator Panel” (connector J7). Likewise, the cables from the integrated operator panel BS-210 are connected to connector J7.
All panels delivered from our factory are thus prepared for operating as a standalone cabinet with an integrated BS-210 and with no external panel bus.
If an external panel bus with additional panels is to be connected to the cabinet or the operator panel BS-210 is to be placed outside the cabinet, the panel connection setting and cabling (communication cables) must be changed during installation/commissioning in order to achieve redundancy and fault monitoring of the panel bus.
Page 20
System Settings
Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03,
Autronica Fire and Security AS
Page 20
3.8 Sound Patterns
The standard setup of the system provides the following default sound patterns in the following prioritized order:
Sound signal Default sound patterns Default Prolong Signal (the
last bit)
Custom-defined Pattern 1 0000000000000000 0 seconds General Alarm Pattern 0101010101010101 2 seconds Evacuate Pattern 1100110011001100 0 seconds Alert Pattern 1000000010000000 0 seconds Custom-defined Pattern 2 0000000000000000 0 seconds Custom-defined Pattern 3 0000000000000000 0 seconds
Pattern Activation Detection zones are connected to alarm zones (Main Alarm Zones). An alarm signal from the detection zones activates the EVACUATE pattern in these alarm zones. Neighbour Alarm zones may be connected to the Main Alarm Zones. The Neighbour Alarm Zones will have the ALERT pattern activated.
The remaining patterns may be activated from an input signal configured as “Activate all Alarms” (refer to 5.9.2). Be aware of the priority given in the table above.
The following settings are available for each sound pattern: The Sound Pattern is set by choosing a predefined 16 bit number
(binary) which determines the pattern (for example, the Alert Pattern, including the following bits; 1000000010000000). The one-digits correspond to ON, and the zero-digits correspond to OFF.
Prolong Signal: It is possible to prolong the last signal (i.e. the last bit) for a chosen sound pattern from 1 to a maximum of 99 seconds.
Sound Level: It is possible to choose between High, Medium or Low sound level. (Not applicable for BBL-100 and BBL-100/IP).
Sound Tone: It is possible to choose between Continuous or Slow Whoop. (Not applicable for BBL-100 and BBL-100/IP).
Page 21
System Settings
Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03,
Autronica Fire and Security AS
Page 21
Example: 7 short signals and one long signal, used as a standard evacuation signal onboard ships.
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1
From the Service Menu, perform the following:
Press Enter to select System Settings. Press the arrow down button to select Sound Patterns, then press
Enter.
Scroll downwards to select the desired Sound Pattern, then press
Enter twice.
To change the pattern, use the Cancel button to delete the bits,
then type the new ones and press Enter. To change the bit values, use the arrow down/up buttons.
To prolong the last signal, type the seconds (from 1 to 99), then
press Enter.
To select the Sound Level (High, Medium or Low), use the arrow
left/right button, then press Enter.
To define the Sound Tone (Continuous or Slow Whoop), use the
arrow left/right button, then press Enter.
To confirm the new settings, press Enter once more.
bits
0=OFF
1=ON
Page 22
System Settings
Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03,
Autronica Fire and Security AS
Page 22
3.9 Automatic Resound
During normal operation: When pressing the Silence button in the event of an alarm, all fire alarm devices (FADs) will be deactivated. The red Fire Alarm indication lamp will switch from a pulsing to a steady light. At this stage, the resound timer will start. The resound timer will restart on each operation of the Silence button.
Holding the Silence button down for more than 7 seconds will activate the Resound function (this message appears in the information field).
The alarm zones are by default automatically resounded to their alarm states on timeout (configurable) of the Silence resound timer.
The menu selection Automatic Resound allows you to determine whether an automatic resound is possible or not. By default, automatic resound is off (No) and the time delay is set to 12 minutes.
From the Service Menu, perform the following:
Press Enter to select System Settings. Press the arrow down button to select Automatic Resound, then
press Enter twice.
To select YES, press the right arrow button, then press Enter. To change the Time Delay, use the Cancel button to delete it,
then type the new one and press Enter.
To confirm the new settings, press Enter once more.
3.10 Detection Zone (DZ) Delay Timers
During normal operation, when the operator panel receives a fire alarm signal from a point in a Delayed Action detection zone (configurable), the actioning of outputs to Fire Alarm Devices (FAD) can be delayed. Also the actioning of outputs to Fire Alarm Routing Equipment (FARE) can be delayed with the exception of manual call points.
The delay is divided into two (configurable) delay periods, Initial delay, T1 and Prolonged Delay, T2.
The default value for T1 is 60 seconds The default value for T2 is 120 seconds. The maximum delay (T1 plus T2) is 10 minutes (600 seconds).
The (T1) delay period is started when a Fire Alarm signal from a point is received. Acti ons will be initiated after the T1 delay period has expired. Pressing the Prolong Delay button, will terminate T1 and the delay period T2 will start.
From the Service Menu, perform the following:
Press Enter to select System Settings. Press the arrow down button to select Detection Zone Delay
Timers, then press Enter twice.
To change the delay timers, use the Cancel button to delete the
present T1 Delay Timer (seconds), then type the new one and press Enter.
Repeat this procedure for the T2 Delay Timer, then press Enter.
Page 23
System Settings
Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03,
Autronica Fire and Security AS
Page 23
To confirm the new settings, press Enter once more.
3.11 Detection Zone (DZ) Global Dependency
This menu selection allows you to turn on Detection Zone Global Dependency, meaning that an alarm in a detecion zone will require a second alarm from another point, in any detection zone, before the detection zone activates any output.
A fire alarm signal from a single detector will initiate no actions, i.e. there will be no actioning of outputs to;
Fire Alarm Devices (FAD) Fire Alarm Routing Equipment (FARE) Fire Protection Equipment (FPE)
From the Service Menu, perform the following:
Press Enter to select System Settings. Press the arrow down button to select DZ Global Dependency,
then press Enter.
The following message appears: “If enabled, an alarm in a DZ will require alarm from another point, in any DZ, before the DZ activates any output. Turn on DZ Global Dependency?”
To answer YES, press Enter, then press the right arrow button,
and press Enter once more.
To confirm the new setting, press Enter once more.
3.12 Battery Parameters
This menu allows you to specify the following:
the minimum charge voltage the battery low voltage limit the maximum charge current the maximum resistance limit
From the Service Menu, perform the following:
Press Enter to select System Settings. Press the arrow down button to select Battery Parameters, then
press Enter twice.
Press the right arrow button to select the minimum charge voltage
(default 21000mV, minimum 20000mV, maximum: 31000mV), then press Enter.
Press the right arrow button to select the battery low voltage limit
(default 21000mV, minimum 17900mV, maximum: 31000mV), then press Enter.
Press the right arrow button to select the maximum charge
current (default 1500mA, minimum 1000mA, maximum: 2000mA), then press Enter.
Press the right arrow button to select the maximum resistance
limit (default 800mOhm, minimum 200mOhm, maximum: 5000 mOhm), then press Enter.
To confirm the new setting, press Enter once more.
Page 24
System Settings
Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03,
Autronica Fire and Security AS
Page 24
3.13 Panel Name
This menu allows you to change the Panel Name.
From the Service Menu, perform the following:
Press Enter to select System Settings. Press the arrow down button to select Panel Name, then press
Enter twice. The current Panel Name will appear.
Press Enter, then overwrite the Name. The Panel Type will
appear in the display.
To confirm the new Name, press Enter. Use the Cancel button to leave this menu selection.
3.14 Language
This menu allows you to change the language. Autroprime supports the following languages (listed in alphabetical
order):
Danish Dutch English Finnish German French Hungarian Icelandic Italian Norwegian Polish Portuguese (Brazilian) Russian Spanish Swedish
From the Service Menu, perform the following:
Press Enter to select System Settings. Press the arrow down button to select Language, then press
Enter twice.
To select the desired language, use the left arrow button to the
language appears in the display, then press Enter.
To change the date, overwrite the date (day, month, year), then
press Enter.
To confirm the new language, press Enter once more.
The message “Please wait…” will appear in the display, meaning that the selected language file is now being imported. The import of the new language file may take a couple of minutes.
Page 25
System Settings
Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03,
Autronica Fire and Security AS
Page 25
3.15 FARE and FWRE Disablement
This menu selection allows you to disable Fire Alarm Routing Equipment (FARE) and Fault Warning Routing Equipment (FWRE) when the system is in access level 2 or 3. In this way, the outputs to Fire Alarm Routing Equipment (FARE) and Fault Warning Routing Equipment (FWRE) will – assuming that this setting has been chosen -always be disabled during service (in access level 2 and 3).
Note that the disablement will only have effect on the system when the system is in access level 2 or 3.
From the Service Menu, perform the following:
Press Enter to select System Settings. Press the arrow down button to select FARE and FWRE
Disablement, then press Enter twice.
To disable FARE in access level 2 and 3, use the right arrow
button to select YES, then press Enter.
To disable FWRE in access level 2 and 3, use the right arrow
button to select YES, then press Enter.
To confirm the settings, press Enter once more.
3.16 Mains Power Fault Indication
This menu selection allows you to specify a delay period (in minutes) before a Power Fault indication is shown in the event of a power outage or electrical power failure.
According to EN 54 regulations, this delay period can be a maximum of 30 minutes.
If you have specified a delay, it is possible to choose whether or not you want to disable the outputs to Fire Warning Routing Equipment as well.
From the Service Menu, perform the following:
Press Enter to select System Settings. Press the arrow down button to select Mains Power Fault
Indication, then press Enter twice.
Type the desired number of minutes (Delay Fault Indication), then
press Enter.
Use the right arrow button to choose whether you want to disable
the outputs to Fire Warning Routing Equipment (YES/NO), then press Enter.
To confirm the settings, press Enter once more.
Page 26
System Settings
Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03,
Autronica Fire and Security AS
Page 26
3.17 Printer Setup
The menu selection allows you to enable printing of alarm events. Whenever any alarm events occur, the system will automatically printout these events.
In addition, you can initiate a printer test instantly to verify that the communication with the printer is established.
The printer’s operational status is monitored once every hour, and a fault message is presented in the panel display whenever any printer fault is detected.
The printer should use its factory default parameters. Refer to the printer user's guide.
From the Service Menu, perform the following:
Press Enter to select System Settings. Press the arrow down button to select Printer Setup, then press
Enter twice.
Use the right or left arrow button to choose whether you want to
enable printing of alarm events (YES/NO), then press Enter.
Use the right or left arrow button to choose whether you want to
reverse print direction (YES/NO)
Use the right or left arrow button to choose whether you want to
initiate an instant printer test (YES/NO), then press Enter.
To confirm the settings, press Enter once more.
3.18 Configuration Check
The menu selection allows you to check the consistency of the running configuration.
The default value is YES, meaning that if the configuration contains at least one Detection Zone that does not activate any Alarm Zone, a fault messages will appear.
Selecting YES will result in the following behaviour: After system startup, the fault message ”DZ does not activate any AZ” will appear if one or several Detection Zones are not connected to an Alarm Zone. The fault message can be acknowledged and a reset can be performed, but the fault message will reappear if the fault still exists.
Selecting NO will result in the following behaviour: No fault messages will appear if one or several Detection Zones are not connected to an Alarm Zone.
From the Service Menu, perform the following:
Press Enter to select System Settings. Press the arrow down button to select Configuration Check, then
press Enter twice.
Use the right arrow button to choose YES or NO, then press
Enter.
To confirm the settings, press Enter once more.
Page 27
System Settings
Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03,
Autronica Fire and Security AS
Page 27
3.19 System S hutdown
This menu selection allows you to bring the panel to a safe state when the intention is to subsequently switch the power off by disconnecting the mains power cable.
From the Service Menu, perform the following:
Press Enter to select System Settings. Press the arrow down button to select System Shutdown. Press Enter, and the following message will appear in the display:   The following message will appear in the display: ”System
Shutdown will do a controlled shutdown of the services. When state System Fault is entered, it is safe to power off the system.”
To execute the command, use the left arrow button, then press
Enter.
Page 28
System Settings
Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03,
Autronica Fire and Security AS
Page 28
3.20 Restore Factory Settings
This menu selection allows you to restore factory settings. Note that all configuration data will be deleted, and the system will
return to its pre-configured state (factory settings). After the command “Restore Factory Settings” is run, the fault
message “Missing Configuration File” will appear in the display, which is normal.
The command “Save Configuration” and “Restart System” must then be run. When these two commands are executed, the configuration file including the factory settings will take effect, and the fault message will no longer be shown.
From the Service Menu, perform the following:
Press Enter to select System Settings. Press the arrow down button to select Restore Factory Settings. Press Enter, and the following message will appear in the display:
”All configuration data will be deleted and the system restarted. Are you sure you want to continue?”
To execute the command, use the left arrow button, then press
Enter. The following message will appear in the display: “Please Wait….
System is now shutting down.”
Page 29
Loop Operation
Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03,
Autronica Fire and Security AS
Page 29
4. Loop Operation
4.1 Accessing the Menu Selections
From the Service Menu, perform the following:
Use the arrow down button to scroll downwards to
Loop Operation, then press Enter.
All loops are listed in the display. Use the arrow up/down buttons to select the detection loop in
question.
To view properties for the selected detection loop, press Enter.
The following information is shown:
o Name o Limit for maximum loop current o Measured loop current o Loop resistance – wire o Loop resistance + wire
To access available functions for a selected detection loop, press
the Function button
, or use, if necessary, the multiselect feature to select several detection loops by pressing the Select button
to mark the detection zones that are to be
configured, and then press the Function button .
The following menu selections will appear:
o Enable (chapter 4.2) o Disable (chapter 4.3) o Change Disable Time Span (chapter 4.4) o Show Polluted Detectors (chapter 4.5) o Show Low Current Units (chapter 4.6)
Scroll with the arrow up/down buttons to select the desired menu,
then follow the instructions in the relevant chapter.
Page 30
Loop Operation
Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03,
Autronica Fire and Security AS
Page 30
4.2 Enable
This menu selection allows you to enable detection loops that are currently disabled. To execute the command, access level 3 is required.
From the Service Menu, perform the following:
After pressing the Function button for the selected detection
loop(s), select Enable (the first menu selection), then press Enter.
To confirm the enablement, press Enter once more. The display will return to the list of loops.
4.3 Disable
During service a technician is able to disable one or several loops. To execute the command, access level 3 is required.
From the Service Menu, perform the following:
After pressing the Function button for the selected detection
loop(s), use the arrow down button to select Disable, then press Enter twice.
Enter the hours and minutes, then press Enter. To confirm the disablement, press Enter once more.
The display will return to the list of loops.
Page 31
Loop Operation
Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03,
Autronica Fire and Security AS
Page 31
4.4 Change Disable Time Span
This menu selection allows a technician to change the disable time span.
From the Service Menu, perform the following:
After pressing the Function button for the selected detection
loop(s), use the arrow down button to select Change Disable Time Span, then press Enter twice.
Enter the hours and minutes, then press Enter. To confirm the new disable time span, press Enter once more.
The display will return to the list of loops.
4.5 Show Polluted Detectors
This menu selection allows you to specify a limit (default 80) for black and white dust pollution. All units exceeding the specified limit will be listed in the display.
The menu also allows you to reset the compensation level for units exceeding the limit.
From the Service Menu, perform the following:
After pressing the Function button for the selected detection
loop(s), use the arrow down button to select Show Polluted Detectors, then press Enter twice.
Use the alpanumeric keypad to specify a limit for dust pollution,
then press Enter.
To confirm the setting, press Enter once more. All points that exceed the specified limit are listed. To reset the compensation level for a point exceeding the
specified limit, select the point, then press the Function button
.
Select Reset Compensation Level, then press Enter. To confirm the setting, press Enter once more.
Page 32
Loop Operation
Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03,
Autronica Fire and Security AS
Page 32
4.6 Show Low Current Units
The command allows you to identify low current loop units (100mA, 150mA, 200mA and 250mA) that are not intended to be on a high current loop (300mA, 350mA and 400mA).
An attempt to increase the loop current to 300mA, 350mA or 400mA for a selected detection loop (command: Service/Unit Configuration/Detection Loop) will be rejected by the system if low current units are on this detection loop (a fault message “Low current loop unit detected” will tell you that there are one or several low current loop units on the high current detection loop).
From the Service Menu, perform the following:
After pressing the Function button for the selected detection
loop(s), use the arrow down button to select Show Low Current Units, then press Enter twice.
All low current units are listed.
Page 33
Unit Configuration
Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03,
Autronica Fire and Security AS
Page 33
5. Unit Configuration
5.1 Menu Selections - Overview
The Unit Configuration menu includes the following menu selections:
Detection Zones (chapter 5.2) Alarm Zones (chapter 5.3) Points (chapter 5.4) Fire Alarm Devices (chapter 5.5) Loop Outputs (chapter 5.6) Local Outputs (chapter 5.7) Loop Inputs (chapter 5.8) Local Inputs (chapter 5.9) Loop I/O Carriers (chapter 5.10) Mimic Panels (BUR-200), (chapter 5.11)
(Menu selection available only if Mimic Panels are connected).
Activation Groups (chapter 5.12) External Interfaces (chapter 5.13) Detection Loops (chapter 5.14) Operator Panels (chapter 5.15)
Page 34
Unit Configuration
Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03,
Autronica Fire and Security AS
Page 34
5.2 Detection Zones
5.2.1 Accessing the Menu Selections
From the Service Menu, perform the following:
Use the arrow down button to scroll downwards to
Unit Configuration, then press Enter twice.
Use the arrow up/down buttons to select the detection zone that
is to be configured.
To view or change properties for the selected detection zone
(name and alarm organization), refer to Configure Properties for a Detection Zone (chapter 5.2.2).
To access available functions for a selected detection zone,
press the Function button
, or use, if necessary, the multiselect feature to select several detection zones by pressing the Select button
to mark the detection zones that are to be
configured, and then press the Function button .
The following menu selections will appear:
o Connect to Alarm Zone (chapter 5.2.3) o Connect to Output (chapter 5.2.4) o Connect to Disable Input Device (chapter 5.2.5) o Connect to Local Alarm Delay Unit (chapter 5.2.6) o Connect to Panel* (chapter 5.2.7) o Disconnect from Alarm Zone (chapter 5.2.8) o Disconnect from Output (chapter 5.2.9) o Disconnect from Disable Input Device (chapter 5.2.10) o Disconnect from Local Alarm Delay Unit (chapter 5.2.11) o Disconnect from Panel* (chapter 5.2.12) o Show Member Points (chapter 5.2.13 ) o Show Connected Units (chapter 5.2.14)
Scroll with the arrow up/down buttons to select the desired menu,
then follow the instructions in the relevant chapter.
* Menu selection available only if a “Mimic” panel is connected.
Page 35
Unit Configuration
Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03,
Autronica Fire and Security AS
Page 35
5.2.2 Configure Properties for a Detection Zone
The following properties apply:
view/change the name of a detection zone change the alarm organization, i.e. the detection zone type
(Immediate Action, Dependency Action, Delayed Action, Delayed Dependency Action, SOLAS).
Note that the default Detection Zone will always have the detection zone type “Immediate Action”, i.e. it cannot be changed.
The system provides the following types of detection zones with different properties:
Immediate Action detection zone Dependency Action detection zone Delayed Action detection zone Delayed Dependency detection zone SOLAS (Safety of Life at Sea) detection zone
The property of a detection zone as well as the type of point (detector or manual call point) will determine how the system responds to the signal - with respect to action. For information on alarm organization and the different types of detection zones, refer to Appendix.
From the Detection Zones Menu (5.2.1), perform the following:
After selecting the detection zone in question by means of the
arrow down/up buttons, press Enter twice.
Type a new Name then press Enter, or accept the existing one by
pressing the arrow down button.
If the detection zone is the default detection zone, press Enter to
confirm the setting.
If the detection zone in question is not the default detection zone,
you can select among 5 different detection zone types (alarm organization).
Use the left or right arrow button to select the detection zone
type, then press Enter.
To confirm the setting, press Enter once more.
Page 36
Unit Configuration
Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03,
Autronica Fire and Security AS
Page 36
5.2.3 Connect to Alarm Zone
This menu allows you to connect a detection zone to an existing alarm zone.
From the Detection Zones Menu (5.2.1), perform the following:
After pressing the Function button for the selected detection
zone(s), select Connect to Alarm Zone (the first menu selection), then press Enter.
Use the arrow down button to select an existing alarm zone. Press Enter to connect the detection zone to this alarm
zone.
To confirm the setting, press Enter once more.
5.2.4 Connect to Output
This menu allows you to connect a detection zone to an output.
From the Detection Zones Menu (5.2.1), perform the following:
After pressing the Function button for the selected detection
zone(s), use the arrow down button to select Connect to Output, then press Enter. Only local outputs of the type General Output will be listed.
Use the arrow down button to select the output, then press Enter
twice.
Use the arrow left/right buttons to select the Detection Activation
State (Prealarm, Small Alarm, Large Alarm, Silent Alarm), then press Enter.
To confirm the setting, press Enter once more.
Page 37
Unit Configuration
Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03,
Autronica Fire and Security AS
Page 37
5.2.5 Connect to Disable Input Device
This menu allows you to connect a detection zone to a Disable Input Device (DID).
From the Detection Zones Menu (5.2.1), perform the following:
After pressing the Function button for the selected detection
zone(s), use the arrow down button to select Connect to Disable Input Device, then press Enter twice.
Use the arrow button to select the Disable Input Device, then
press Enter.
To confirm the setting, press Enter once more.
5.2.6 Connect to Local Alarm Delay Unit
This menu allows you to connect a detection zone to a Local Alarm Delay Unit.
From the Detection Zones Menu (5.2.1), perform the following:
After pressing the Function button for the selected detection
zone(s), use the arrow down button to select Connect to Local Alarm Delay Unit, then press Enter twice.
Use the arrow button to select the Local Alarm Delay Unit, then
press Enter.
To confirm the setting, press Enter once more.
5.2.7 Connect to Panel
This menu allows you to connect a detection zone to a “Larmlagring” Panel. Note that the menu selection is available only if a such panel is connected to the system.
From the Detection Zones Menu (5.2.1), perform the following:
After pressing the Function button for the selected detection
zone(s), use the arrow down button to select Connect to Panel, then press Enter twice.
Use the arrow button to select the Panel, then press Enter. To confirm the setting, press Enter once more.
Page 38
Unit Configuration
Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03,
Autronica Fire and Security AS
Page 38
5.2.8 Disconnect from Alarm Zone
This menu allows you to disconnect a detection zone from an alarm zone.
From the Detection Zones Menu (5.2.1), perform the following:
After pressing the Function button for the selected detection
zone(s), use the arrow down button to select Disconnect from Alarm Zone, then press Enter twice.
Use the arrow down/up button to select the alarm zone to be
disconnected, then press Enter.
To confirm the setting, press Enter once more.
5.2.9 Disconnect from Output
This menu allows you to disconnect a detection zone from an output.
From the Detection Zones Menu (5.2.1), perform the following:
After pressing the Function button for the selected detection
zone(s), use the arrow down button to select Disconnect from Output, then press Enter twice.
Use the arrow down/up button to select the output to be
disconnected, then press Enter.
To confirm the setting, press Enter once more.
5.2.10 Disconnect from Disable Input Device
This menu allows you to disconnect a detection zone from a Disable Input Device (DID).
From the Detection Zones Menu (5.2.1), perform the following:
After pressing the Function button for the selected detection
zone(s), use the arrow down button to select Disconnect from Disable Output Device, then press Enter twice.
Use the arrow down/up button to select the device to be
disconnected, then press Enter.
To confirm the setting, press Enter once more.
5.2.11 Disconnect from Local Alarm Delay Unit
This menu allows you to disconnect a detection zone from a Local Alarm Delay Unit.
From the Detection Zones Menu (5.2.1), perform the following:
After pressing the Function button for the selected detection
zone(s), use the arrow down button to select Disconnect from Local Alarm Delay Unit, then press Enter twice.
Use the arrow down/up button to select the device to be
disconnected, then press Enter.
To confirm the setting, press Enter once more.
Page 39
Unit Configuration
Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03,
Autronica Fire and Security AS
Page 39
5.2.12 Disconnect from Panel
This menu allows you to disconnect a detection zone from a “Larmlagring” Panel. Note that the menu selection is available only if a such panel is connected to the system.
From the Detection Zones Menu (5.2.1), perform the following:
After pressing the Function button for the selected detection
zone(s), use the arrow down button to select Disconnect from Panel, then press Enter twice.
Use the arrow down/up button to select the panel to be
disconnected, then press Enter.
To confirm the setting, press Enter once more.
5.2.13 Show Member Points
This menu allows you to view a list of all points belonging to a selected detection zone.
From the Detection Zones Menu (5.2.1), perform the following:
After pressing the Function button for the selected detection
zone(s), use the arrow down button to select Show Member Points, then press Enter.
To view detailed information for a selected point, use the arrow
down/up button to select the point, then press Enter.
The following information will appear:
o the point’s name/type o information on whether the point is set to override delay and
dependency or not (YES/NO)
o the point’s performance class day settings o the point’s operation class day settings o the point’s performance class night settings o the point’s operation class night settings
5.2.14 Show Connected Units
This menu allows you to view all connections related to a selected detection zone, i.e. what the detection zone activates (for example, alarm zone, outputs, etc.).
From the Detection Zones Menu (5.2.1), perform the following:
After pressing the Function button for the selected detection
zone(s), use the arrow down button to select Show Connected Units, then press Enter.
To view detailed information (name, parent alarm zone and
immediate activation status) for all connections related to a selected detection zone, use the arrow down/up button to select an alarm zone, then press Enter.
Page 40
Unit Configuration
Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03,
Autronica Fire and Security AS
Page 40
5.3 Alarm Zones
5.3.1 Accessing the Menu
From the Service Menu, perform the following:
Use the arrow down button to scroll downwards to
Unit Configuration, then press Enter.
Use the arrow down button to select Alarm Zones, then press
Enter once more.
Use the arrow up/down buttons to select the alarm zone that
is to be configured.
To view or change properties for the selected alarm zone
(name), refer to Configure Properties for an Alarm Zone (chapter
5.3.2).
To access available functions for a selected alarm zone, press
the Function button
, or use, if necessary, the multiselect feature to select several alarm zones by pressing the Select button
to mark the alarm zones that are to be configured,
and then press the Function button .
The following menu selections will appear:
o Connect to Neighbour Alarm Zone (chapter 5.3.3) o Disconnect from Neighbour Alarm Zone (chapter 5.3.4) o Show Member Fire Alarm Devices (chapter 5.3.5) o Show Neighbour Alarm Zones (chapter 5.3.6) o Show Activating Detection Zones (chapter 5.3.7)
Scroll with the arrow up/down buttons to select the desired menu,
then follow the instructions in the relevant chapter.
Page 41
Unit Configuration
Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03,
Autronica Fire and Security AS
Page 41
5.3.2 Configure Properties for an Alarm Zone
To configure properties for an alarm zone, it is assumed that fire alarm devices (FADs) have already been connected to an alarm zone (the menu selection Fire Alarm Device).
From the Alarm Zones Menu (5.3.1), perform the following:
After selecting the alarm zone in question by means of the arrow
down/up buttons, press Enter twice.
Type a new Name, or accept the existing one by pressing the
arrow down button.
Press Enter. Use the left or right arrow button to select a Parent Alarm Zone,
then press Enter.
Use the right or left arrow buttons to choose whether you want
Immediate Activation or not (YES/NO), then press Enter.
To confirm the setting, press Enter once more. * Parent Alarm Zone (default alarm zone):
The top-level Alarm Zone is called the Parent Alarm Zone. A system consists of a Parent Alarm Zone, usually with several “sub-level” alarm zones in an hierarchy. Each “sub level”-alarm zone is related to a specific area of, for example, a building. If an alarm occurs in a Parent Alarm Zone, all Fire Alarm Devices (FADs) within the Parent Alarm Zone, plus all FADs belonging to all “sub-level”-alarm zones will be activated.
5.3.3 Connect to Neighbour Alarm Zone
This menu allows you to define a neighbour alarm zone for a selected alarm zone, or define the neighbourhood relation between alarm zones.
From the Alarm Zones Menu (5.3.1), perform the following:
After pressing the Function button for a selected alarm zone,
select Connect to Neighbour Alarm Zone (the first menu selection), then press Enter.
From the list of alarm zones, select an alarm zone that is to be
defined as a neighbour alarm zone, then press Enter.
To confirm the setting, press Enter once more. If you want to define another alarms zone as neighbour alarm
zone to the selected alarm zone, repeat the procedure above.
Page 42
Unit Configuration
Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03,
Autronica Fire and Security AS
Page 42
5.3.4 Disconnect from Neighbour Alarm Zone
This menu allows you to disconnect neighbourhood relations between alarm zones.
From the Alarm Zones Menu (5.3.1), perform the following:
After pressing the Function button for the selected alarm zone(s),
use the arrow down button to select Disconnect Neighbour Alarm Zone, then press Enter.
A list will appear, listing all alarm zones that have neighbourhood
relations.
Select the alarm zone that is to be disconnected, then press
Enter.
To confirm the setting, press Enter once more.
5.3.5 Show Member Fire Alarm Devices
This menu allows you to view all Fire Alarm Devices (FADs) belonging to an alarm zone.
From the Alarm Zones Menu (5.3.1), perform the following:
After pressing the Function button for the selected alarm zone(s),
use the arrow down button to select Show Member Fire Alarm Devices, then press Enter.
A list of all Fire Alarm Devices (FADs) will appear in the display. Use the arrow down button to select the FAD in question, then
press Enter.
The name of the FAD and the unit function will appear in the display.
5.3.6 Show Neighbour Alarm Zones
This menu allows you to view the neighbour alarm zones for a selected alarm zone.
From the Alarm Zones Menu (5.3.1), perform the following:
After pressing the Function button for the selected alarm zone(s),
use the arrow down button to select Show Neighbour Alarm Zones, then press Enter.
A list of all Neighbour Alarm Zones will appear in the display. Use the arrow down button to select the Neighbour Alarm Zone
in question, then press Enter.
The name of the Neighbour Alarm Zone and the unit function will appear in the display.
Page 43
Unit Configuration
Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03,
Autronica Fire and Security AS
Page 43
5.3.7 Show Activating Detection Zones
This menu allows you to view all detection zones that activate a selected alarm zone.
From the Alarm Zones Menu (5.3.1), perform the following:
After pressing the Function button for the selected alarm zone(s),
use the arrow down button to select Show Activating Detection Zones, then press Enter.
A list of all Detection Zones will appear in the display. Use the arrow down button to select the Detection Zone in
question, then press Enter.
The name of the Detection Zone and the alarm organization will appear in the display.
Page 44
Unit Configuration
Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03,
Autronica Fire and Security AS
Page 44
5.4 Points
5.4.1 Accessing the Menu
From the Service Menu, perform the following:
Use the arrow down button to scroll downwards to
Unit Configuration, then press Enter.
Use the arrow down button to select Points, then press Enter
once more.
Use the arrow up/down buttons to select the point that
is to be configured.
To view or change properties for the selected point, refer to
Configure Properties for a Point (chapter 5.4.2).
To access available functions for a selected point, press the
Function button
, or use, if necessary, the multiselect feature to select several points by pressing the Select button to mark the points that are to be configured, and then press the Function button
.
The following menu selections will appear:
o Move to Detection Zone (/Create New) (chapter 5.4.3) o Connect to Output (chapter 5.4.4) o Connect to Activation Group (/Create New) (chapter 5.4.5) o Disconnect from Output (chapter 5.4.6) o Disconnect from Activation Group (chapter 5.4.7) o Show Connected Units (chapter 5.4.8)
Scroll with the arrow up/down buttons to select the desired menu,
then follow the instructions in the relevant chapter.
Page 45
Unit Configuration
Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03,
Autronica Fire and Security AS
Page 45
5.4.2 Configure Properties for a Point
The following properties can be changed:
name of a point override delay and dependency
In an alarm situation, the actioning of outputs will be delayed when; the detection zone has been defined as a Delayed Action detection zone (configurable) and the point(s) in this Delayed Action detection zone has not been set to Override Delay and Dependency, i.e. set to No.
performance class day setting (Normal 1, Normal 2; Industrial);
depends on the type of detector
operation class day setting (depends on the type of point;
MultiSensor with heat, MultiSensor only, Heat only)
performance class night setting (Normal 1, Normal 2; Industrial) operation class night setting (MultiSensor with heat, MultiSensor
only, Heat only)
From the Points Menu (5.4.1), perform the following:
After selecting the point in question by means of the arrow
down/up buttons, press Enter twice.
Type a new Name then press Enter, or accept the existing one by
pressing the arrow down button.
Use the left or right arrow button to select Yes or No (Override
Delay and Dependency or not), then press Enter.
Use the left or right arrow button to select the desired
performance class day setting, then press Enter.
Use the left or right arrow button to select the desired
operation class day setting, then press Enter.
Use the left or right arrow button to select the desired
performance class night setting, then press Enter.
Use the left or right arrow button to select the desired
operation class night setting, then press Enter.
To confirm the setting, press Enter once more.
Page 46
Unit Configuration
Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03,
Autronica Fire and Security AS
Page 46
5.4.3 Move to Detection Zone (/Create New)
This menu allows you to:
move (connect) a selected point to an existing detection zone create a new detection zone for a selected point and, at the same
time, connect this point to the new detection zone
When creating a new detection zone, the alarm organization for the new detection zone is determined (refer to Detection Zone / Configure Properties, chapter 5.2.2).
From the Points Menu (5.4.1), perform the following:
After pressing the Function button for the selected point(s), select
Move to Detection Zone (/Create New), (the first menu selection), then press Enter.
To connect the selected point to a new detection zone:
o With the uppermost menu selection highlighted, press Enter
twice.
o Type a name for the new detection zone, then press Enter. o Use the left or right arrow button to select the desired
alarm organization, then press Enter.
o To confirm the setting, press Enter once more.
To move (connect) the selected point to an existing detection
zone: o Use the arrow down button to select the detection zone that
is to be connected to the point, then press Enter.
o To confirm the setting, press Enter once more.
Page 47
Unit Configuration
Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03,
Autronica Fire and Security AS
Page 47
5.4.4 Connect to Output
This menu allows you to connect a selected point to an output. The following settings can be done:
Point State:
meaning which alarm level (pre-alarm or alarm) the point must have before the output is activated.
Activate on Point Disable (Yes/No):
Yes: meaning that the output is activated if the selected point is disabled. No: meaning that the output is not activated if the selected point is disabled.
Activate on Point Fault (Yes/No):
Yes: meaning that the output is activated if there is a fault on the selected point. No: meaning that the output is not activated if there is a fault on the selected point.
From the Points Menu (5.4.1), perform the following:
After pressing the Function button for the selected point(s), use
the arrow down button to scroll downwards to Connect to Output, then press Enter.
A list of all available outputs will appear in the display. Use the arrow up/down button to select the output that
is to be connected to the selected point, then press Enter twice.
Use the left or right arrow button to set the Point State, then
press Enter.
Use the left or right arrow button to set Yes or No for Activate on
Point Disable, then press Enter.
Use the left or right arrow button to set Yes or No for Activate on
Point Fault, then press Enter.
To confirm the setting, press Enter once more.
Page 48
Unit Configuration
Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03,
Autronica Fire and Security AS
Page 48
5.4.5 Connect to Activation Group (/Create New)
This menu allows you to:
connect a selected point to an existing activation group create a new activation group for a selected point and, at the
same time, connect this point to the new activation group
When creating a new activation group, the following settings are determined: Activate group on Unit State:
meaning which alarm level the points within this activation group will react to (pre-alarm, alarm, fault and disablement).
Activation Group Dependency:
meaning how many points within this activation group must be in alarm state before actions are initiated (1-5 and All).
Refer also to chapter 5.12 Activation Groups.
From the Points Menu (5.4.1), perform the following:
After pressing the Function button for the selected point(s), use
the arrow down button to scroll downwards to Connect to Activation Group (/Create New), then press Enter.
To connect the selected point to a new activation group:
o With the uppermost menu selection highlighted, press Enter
twice.
o Type a name for the new activation group, then press Enter. o Use the left or right arrow button to select the desired
unit state (Prealarm/Alarm), then press Enter.
o Use the left or right arrow button to determine how many points
within this activation group that must be in alarm state before actions are initiated (1-5 and All).
o To confirm the setting, press Enter once more.
To move (connect) the selected point to an existing detection
zone: o Use the arrow down button to select the activation group
that is to be connected to the point, then press Enter.
o To confirm the setting, press Enter once more.
Page 49
Unit Configuration
Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03,
Autronica Fire and Security AS
Page 49
5.4.6 Disconnect from Output
This menu allows you to disconnect a selected point from an existing output.
From the Points Menu (5.4.1), perform the following:
After pressing the Function button for the selected point(s), use
the arrow down button to scroll downwards to Disconnect from Output, then press Enter.
In the display you will now see a list of all outputs that are connected to the selected point .
To disconnect the selected point from an output, use the arrow
down button to select the output, then press Enter.
To confirm the setting, press Enter once more.
5.4.7 Disconnect from Activation Group
This menu allows you to disconnect a selected point from an existing activation group.
From the Points Menu (5.4.1), perform the following:
After pressing the Function button for the selected point(s), use
the arrow down button to scroll downwards to Disconnect from Activation Group, then press Enter.
A list of the activation groups the selected point is connected to will appear in the display.
To disconnect the selected point from an activation group, use
the arrow down button to select the activation group, then press Enter.
To confirm the setting, press Enter once more.
Page 50
Unit Configuration
Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03,
Autronica Fire and Security AS
Page 50
5.4.8 Show Connected Units
This menu allows you to view units that are activated by the selected point (detection zones, outputs etc.).
From the Points Menu (5.4.1), perform the following:
After pressing the Function button for the selected point(s), use
the arrow down button to scroll downwards to Show Connected Units, then press Enter.
A list will appear in the display, showing all detection zones, outputs etc. that are activated by the selected point.
Page 51
Unit Configuration
Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03,
Autronica Fire and Security AS
Page 51
5.5 Fire Alarm Devices
5.5.1 Accessing the Menu
From the Service Menu, perform the following:
Use the arrow down button to scroll downwards to
Unit Configuration, then press Enter.
Use the arrow down button to select Fire Alarm Device, then
press Enter once more.
Use the arrow up/down buttons to select the Fire Alarm Device
that is to be configured.
To view or change properties for the selected Fire Alarm Device,
refer to Configure Properties for a Fire Alarm Device (chapter
5.5.2).
To access available functions for a selected Fire Alarm Device,
press the Function button
, or use, if necessary, the multiselect feature to select several Fire Alarm Devices by pressing the Select button
to mark the Fire Alarm Devices
that are to be configured, and then press the Function button .
The following menu selections will appear:
o Move to Alarm Zone (chapter 5.5.3) o Show Connected Units (chapter 5.5.4)
Scroll with the arrow up/down buttons to select the desired menu,
then follow the instructions in the relevant chapter.
Page 52
Unit Configuration
Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03,
Autronica Fire and Security AS
Page 52
5.5.2 Configure Properties for a Fire Alarm Device
The following properties can be changed:
name of a Fire Alarm Device (FAD) the “unit function” for local outputs that are assigned the unit
function Fire Alarm Device (FAD). (Refer to the Local Outputs menu).
From the Fire Alarm Devices Menu (5.5.1), perform the following:
After selecting the FAD in question by means of the arrow
down/up buttons, press Enter twice.
Type a new Name and press Enter, or accept the existing one by
pressing the arrow down button.
To confirm the setting, press Enter once more. If a local output (that is assigned unit function FAD) is selected,
and not a FAD, use the arrow left/right buttons to select among the following unit functions:
o Fire Alarm Device o General Output o RESET Out o Silence Alarm Output o Silence Out o Small Alarm Output o FWRE o FARE
Press Enter. To confirm the setting, press Enter once more.
5.5.3 Move to Alarm Zone
This menu allows you to connect a selected Fire Alarm Device to an existing alarm zone or create a new alarm zone, and at the same time connect the new alarm zone to the Fire Alarm Device.
From the Fire Alarm Devices Menu (5.5.1), perform the following:
After pressing the Function button for the selected FAD(s), select
Move to Alarm Zone (the first menu selection), then press Enter.
Use the arrow button to select an existing alarm zone, or select
the menu Create New Alarm Zone. o If an existing alarm zone is selected, press Enter twice to
connect the detection zone to this alarm zone.
o If a new alarm zone is to be created, select Create New
Alarm Zone, press Enter twice, type the name, then press Enter.
o Use the left/right arrow buttons to select the Parent Alarm
Zone”, then press Enter twice to confirm.
Page 53
Unit Configuration
Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03,
Autronica Fire and Security AS
Page 53
5.5.4 Show Connected Units
This menu allows you to view the alarm zone that belongs to a selected Fire Alarm Device (FAD). The name of the alarm zone, and this alarm zone’s parent alarm zone will appear in the display.
From the Fire Alarm Devices Menu (5.5.1), perform the following:
After pressing the Function button for the selected FAD(s), use
the arrow down button to select Show Connected Units, then press Enter.
In the display you will now see the alarm zone that belongs to the selected Fire Alarm Device.
Press Enter.to view the name of the alarm zone.
Page 54
Unit Configuration
Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03,
Autronica Fire and Security AS
Page 54
5.6 Loop Outputs
5.6.1 Accessing the Menu
From the Service Menu, perform the following:
Use the arrow down button to scroll downwards to
Unit Configuration, then press Enter.
Use the arrow down button to select Loop Outputs, then
press Enter once more.
Use the arrow up/down buttons to select the Loop Output
that is to be configured (if any).
To view or change properties for the selected Loop Output, refer
to Configure Properties for a Loop Output (chapter 5.6.2).
To access available functions for a selected loop output, press
the Function button
, or use, if necessary, the multiselect feature to select several loop outputs by pressing the Select button
to mark the loop outputs that are to be configured,
and then press the Function button .
The following menu selections will appear: (Menu selections not applicable to FAD, FARE and FWRE):
o Connect to Output (chapter 0) o Connect to Activation Group (chapter 5.6.4) o Disconnect from Output (chapter 5.6.5) o Disconnect from Activation Group (chapter 5.6.6) o Show Activating Detection Zones (chapter 5.6.7) o Show Activating Points (chapter 5.6.8) o Show Activating Inputs (chapter 5.6.9) o Show Activating Groups (chapter 5.6.10) o Show Activating Outputs (chapter 5.6.11)
(Menu selection applies to FAD only):
o Move to Alarm Zone
(Menu selection not applicable to FARE, FWRE):
o Show Connected Units (chapter 5.6.12)
Scroll with the arrow up/down buttons to select the desired menu,
then follow the instructions in the relevant chapter.
Page 55
Unit Configuration
Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03,
Autronica Fire and Security AS
Page 55
5.6.2 Configure Properties for a Loop Output
The properties for a loop output depends on the type of output.
From the Loop Outputs Menu (5.6.1), perform the following:
After selecting the Loop Output in question by means of the arrow
down/up buttons, press Enter twice.
Type a new Name, or accept the existing one by pressing the
arrow down button.
Press Enter, then use the arrow left/right buttons to select among
the unit functions that are available for the selected Loop Output (see overview below).
Press Enter. To confirm the setting, press Enter once more.
Unit functions for different types of loop outputs: Door Unit
o Name o Function o Activation Group Dependency (how many Activation Groups
must be in alarm before the output is activated, the default value is 1, see example below)
o Supervisory o Supervisory Text o Activation o Activation Timer o Monitoring Timer
Standard Control Unit
o Name o Function o Supervisory
Example. Door Control in engine room scenario
1. Monitoring Timer
If a door's position has been changed, for example, from open to closed (or visa versa), an indication of the door’s status (open / ajar / closed) will be given within a certain period (seconds). The Monitoring Timer determines this period.
2. Activation Timer If a command is sent to close a door (regardless of whether the door is open or closed), a technical alarm will be activated if the door is not closed within a certain period (seconds). The Activation Timer determines this period.
3. Activation
Monitoring Timer
If a door is closed because a “close” command is sent, it can be opened and it can stay open / ajar for a certain period (seconds). If the door is not closed within this period, a technical alarm will be activated. The Activation Monitoring Timer determines this period (supervisory).
Output
Act. Group 2
Act. Grou
p
1
Page 56
Unit Configuration
Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03,
Autronica Fire and Security AS
Page 56
5.6.3 Connect to Output
This menu allows you to determine, for a selected loop output, which outputs that are to be activated on the activation of this loop output. In the example below, loop output 1 will on activation, activate output 2 and 3.
Note that the menu selection does not apply to Fire Alarm Devices (FAD), Fire Alarm Routing Equipment (FARE) and Fire Warning Routing Equipment (FWRE).
From the Loop Outputs Menu (5.6.1), perform the following:
After pressing the Function button for the selected Loop
Output(s), select Connect to Output (the first menu selection),
then press Enter. A list of all available outputs will appear in the display. Use the arrow up/down button to select the output(s) that
is to be activated on the activation of the loop output, then press
Enter. To confirm the setting, press Enter once more.
5.6.4 Connect to Activation Group
This menu allows you to connect a selected loop output to an Activation Group by which it will be activated.
Note that the menu selection does not apply to Fire Alarm Devices (FAD), Fire Alarm Routing Equipment (FARE) and Fire Warning Routing Equipment (FWRE).
From the Loop Outputs Menu (5.6.1), perform the following:
After pressing the Function button for the selected Loop
Output(s), use the arrow down button to scroll downwards to
Connect to Activation Group, then press Enter. A list of all available activation groups will appear in the display. Use the arrow up/down button to select the activation group that
is to be connected to the loop output, then press Enter. To confirm the setting, press Enter once more.
Loop Output 1
Output 3
Output 2
Page 57
Unit Configuration
Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03,
Autronica Fire and Security AS
Page 57
5.6.5 Disconnect from Output
This menu allows you to disconnect a selected loop output from an output, meaning that the selected loop output will, on activation, not activate the output. In the example below, loop output 1 will on activation, no longer activate output 3 (only output 2).
Note that the menu selection does not apply to Fire Alarm Devices (FAD), Fire Alarm Routing Equipment (FARE) and Fire Warning Routing Equipment (FWRE).
From the Loop Outputs Menu (5.6.1), perform the following:
After pressing the Function button for the selected Loop
Output(s), use the arrow down button to scroll downwards to
Disconnect from Output, then press Enter. In the display you will now see a list of all outputs that are connected
to the selected loop output. To disconnect the selected loop output from an output, use the
arrow down button to select the output, then press
Enter. To confirm the setting, press Enter once more.
5.6.6 Disconnect from Activation Group
This menu allows you to disconnect a selected loop output from an Activation Group.
Note that the menu selection does not apply to Fire Alarm Devices (FAD), Fire Alarm Routing Equipment (FARE) and Fire Warning Routing Equipment (FWRE).
From the Loop Outputs Menu (5.6.1), perform the following:
After pressing the Function button for the selected Loop
Output(s), use the arrow down button to scroll downwards to
Disconnect from Activation Group, then press Enter. In the display you will now see a list of all activation groups that are
connected to the selected loop output. To disconnect the selected loop output from an activation group,
use the arrow down button to select the activation group, then
press Enter. To confirm the setting, press Enter once more.
Loop Out
p
ut 1
Output 3
Output 2
Page 58
Unit Configuration
Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03,
Autronica Fire and Security AS
Page 58
5.6.7 Show Activating Detection Zones
This menu allows you to view all detection zones that are connected to the selected loop output.
Note that the menu selection does not apply to Fire Alarm Devices (FAD), Fire Alarm Routing Equipment (FARE) and Fire Warning Routing Equipment (FWRE).
From the Loop Outputs Menu (5.6.1), perform the following:
After pressing the Function button for the selected Loop
Output(s), use the arrow down button to scroll downwards to
Show Activating Detection Zones, then press Enter. In the display you will now see a list of all detection zones that are
connected to the selected loop output.
5.6.8 Show Activating Points
This menu allows you to view all points that are connected to the selected loop output.
Note that the menu selection does not apply to Fire Alarm Devices (FAD), Fire Alarm Routing Equipment (FARE) and Fire Warning Routing Equipment (FWRE).
From the Loop Outputs Menu (5.6.1), perform the following:
After pressing the Function button for the selected Loop
Output(s), use the arrow down button to scroll downwards to
Show Activating Points, then press Enter. In the display you will now see a list of all points that are connected
to the selected loop output.
Page 59
Unit Configuration
Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03,
Autronica Fire and Security AS
Page 59
5.6.9 Show Activating Inputs
This menu allows you to view all inputs that are connected to the selected loop output.
Note that the menu selection does not apply to Fire Alarm Devices (FAD), Fire Alarm Routing Equipment (FARE) and Fire Warning Routing Equipment (FWRE).
From the Loop Outputs Menu (5.6.1), perform the following:
After pressing the Function button for the selected Loop
Output(s), use the arrow down button to scroll downwards to
Show Activating Inputs, then press Enter. In the display you will now see a list of all inputs that are connected
to the selected loop output.
5.6.10 Show Activating Groups
This menu allows you to view all activating groups (groups; meaning “Activation Groups”) the selected loop output is connected to.
Note that the menu selection does not apply to Fire Alarm Devices (FAD), Fire Alarm Routing Equipment (FARE) and Fire Warning Routing Equipment (FWRE).
From the Loop Outputs Menu (5.6.1), perform the following:
After pressing the Function button for the selected Loop
Output(s), use the arrow down button to scroll downwards to
Show Activating Groups, then press Enter. In the display you will now see a list of all activation groups that are
connected to the selected loop output.
Page 60
Unit Configuration
Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03,
Autronica Fire and Security AS
Page 60
5.6.11 Show Activating Outputs
This menu allows you to view all outputs that are connected to the selected loop output.
Note that the menu selection does not apply to Fire Alarm Devices (FAD), Fire Alarm Routing Equipment (FARE) and Fire Warning Routing Equipment (FWRE).
From the Loop Outputs Menu (5.6.1), perform the following:
After pressing the Function button for the selected Loop
Output(s), use the arrow down button to scroll downwards to
Show Activating Outputs, then press Enter. In the display you will now see a list of all outputs that are connected
to the selected loop output.
5.6.12 Show Connected Units
This menu allows you to view all connections that are connected to the selected loop output (and that activate the selected loop output).
Note that the menu selection does not apply to Fire Alarm Routing Equipment (FARE) and Fire Warning Routing Equipment (FWRE).
From the Loop Outputs Menu (5.6.1), perform the following:
After pressing the Function button for the selected Loop
Output(s), use the arrow down button to scroll downwards to
Show Connections, then press Enter. In the display you will now see a list of all connections that are
connected to the selected loop output.
Page 61
Unit Configuration
Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03,
Autronica Fire and Security AS
Page 61
5.7 Local Outputs
5.7.1 Accessing the Menu
From the Service Menu, perform the following:
Use the arrow down button to scroll downwards to
Unit Configuration, then press Enter. Use the arrow down button to select Local Outputs, then
press Enter once more. Use the arrow up/down buttons to select the Local Output
that is to be configured. To view or change properties for the selected Local Output, refer
to Configure Properties for a Local Output (chapter 5.7.2). To access available functions for a selected local output, press
the Function button
, or use, if necessary, the multiselect feature to select several local outputs by pressing the Select button
to mark the local outputs that are to be configured,
and then press the Function button .
The following menu selections will appear: Menu selections not applicable to FAD, FARE and FWRE:
o Connect to Output (chapter 5.7.3) o Connect to Activation Group (chapter 5.7.4) o Disconnect from Output (chapter 5.7.5) o Disconnect from Activation Group (chapter 5.7.6)
Menu selectoins applicable to Open Collector Outputs (general output 1 and 2):
o Show Activating Detection Zones (chapter 5.7.7) o Show Activating Points (chapter 5.7.8) o Show Activating Inputs (chapter 5.7.9) o Show Activating Groups (chapter 5.7.10) o Show Activating Outputs (chapter 5.7.11)
Menu selections applicable to Monitored Outputs (1 and 2):
o Move to Alarm Zone (chapter 5.7.12)
(Menu selection applicable to FAD only)
o Show Connected Units (chapter 5.7.13)
(Menu selection not applicable to FARE and FWRE)
Scroll with the arrow up/down buttons to select the desired menu,
then follow the instructions in the relevant chapter.
Page 62
Unit Configuration
Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03,
Autronica Fire and Security AS
Page 62
5.7.2 Configure Properties for a Local Output
The following properties can be changed:
the name of the local output the “unit function” for a local output – applies only to the standard
outputs on the main board’s terminal block J1.
Terminal Output hardware type Default function
J1.12 Monitored Output 1 +24V FAD 1 J1.13 Monitored Output 1 0V FAD 1 J1.14 Monitored Output 2 +24V FAD 2 J1.15 Monitored Output 2 0V FAD 2 J1.16 Open Collector Output 1 General Output 1 J1.17 Open Collector Output 2 General Output 2 J1.18 Auxiliary +24V Out Intended used for Open collector J1.19 Relay Output 1 Com
FARE
J1.20 Relay Output 1 NO J1.21 Relay Output 1 NC J1.22 Relay Output 2 Com
FWRE
J1.23 Relay Output 2 NO J1.24 Relay Output 2 NC
From the Local Outputs Menu (5.7.1), perform the following:
After selecting the Local Output in question by means of the
arrow down/up buttons, press Enter twice.
Type a new Name, or accept the existing one by pressing the
arrow down button.
Press Enter, then use the arrow left/right arrow buttons to select
among the following unit functions:
o Fire Alarm Device:
equipment giving warning of fire, for example, a sounder or visual indicator.
o Disable Out:
output that is activated when there are disablements in the system
o General Output:
output that is activated according to the configured events, for example, Pre Alarm, Alarm, Input Activated etc.
o RESET Out:
output activated for approx. 2 seconds when the Reset button is operated.
o Silent Alarm Output:
output dedicated to be activated at Silent Alarm regardless of alarm origin
o Silence Out:
output activated for approx. 2 seconds when the Silence button is operated
o Small Alarm Output:
output dedicated to be activated at Small Alarm regardless of alarm origin
o Fire Alarm Routing Equipment (FARE):
equipment routing an alarm signal from control and indicating equipment to a Fire Alarm Receiving Station.
o Fault Warning Routing Equipment (FWRE):
equipment routing a fault warning signal from control and indicating equipment to a fault warning receiving station.
Press Enter. To confirm the setting, press Enter once more.
Page 63
Unit Configuration
Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03,
Autronica Fire and Security AS
Page 63
5.7.3 Connect to Output
This menu allows you to connect a selected local output to an output. The menu selection applies to open collector 1 and 2.
Note that the menu selection does not apply to Fire Alarm Devices (FAD), Fire Alarm Routing Equipment (FARE) and Fire Warning Routing Equipment (FWRE).
From the Local Outputs Menu (5.7.1), perform the following:
After pressing the Function button for the selected Local
Output(s), select Connect to Output (the first menu selection), then press Enter.
A list of all available outputs will appear in the display. Use the arrow up/down button to select the output that
is to be connected to the selected local output, then press Enter.
To confirm the setting, press Enter once more.
5.7.4 Connect to Activation Group
This menu allows you to connect a selected local output to an Activation Group. The menu selection applies to open collector 1 and 2.
Note that the menu selection does not apply to Fire Alarm Devices (FAD), Fire Alarm Routing Equipment (FARE) and Fire Warning Routing Equipment (FWRE).
From the Local Outputs Menu (5.7.1), perform the following:
After pressing the Function button for the selected Local
Output(s), use the arrow down button to scroll downwards to Connect to Activation Group, then press Enter.
A list of all available activation groups will appear in the display. Use the arrow up/down button to select the activation group that
is to be connected to the local output, then press Enter.
To confirm the setting, press Enter once more.
Page 64
Unit Configuration
Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03,
Autronica Fire and Security AS
Page 64
5.7.5 Disconnect from Output
This menu allows you to disconnect a selected local output from an existing output. The menu selection applies to onboard General Outputs only.
Note that the menu selection does not apply to Fire Alarm Devices (FAD), Fire Alarm Routing Equipment (FARE) and Fire Warning Routing Equipment (FWRE).
From the Local Outputs Menu (5.7.1), perform the following:
After pressing the Function button for the selected Local
Output(s), use the arrow down button to scroll downwards to Disconnect from Output, then press Enter.
In the display you will now see a list of all outputs that are connected to the selected local output.
To disconnect the selected local output from an output, use the
arrow down button to select the output, then press Enter.
To confirm the setting, press Enter once more.
5.7.6 Disconnect from Activation Group
This menu allows you to disconnect a selected local output from an existing Activation Group (refer to chapter 5.12). The menu selection applies to onboard General Outputs only.
Note that the menu selection does not apply to Fire Alarm Devices (FAD), Fire Alarm Routing Equipment (FARE) and Fire Warning Routing Equipment (FWRE).
From the Local Outputs Menu (5.7.1), perform the following:
After pressing the Function button for the selected Local
Output(s), use the arrow down button to scroll downwards to Disconnect from Activation Group, then press Enter.
In the display you will now see a list of all Activation Groups that are connected to the selected local output.
To disconnect the selected local output from an Activation Group,
use the arrow down button to select the activation group, then press Enter.
To confirm the setting, press Enter once more.
Page 65
Unit Configuration
Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03,
Autronica Fire and Security AS
Page 65
5.7.7 Show Activating Detection Zones
This menu allows you to view all detection zones that are connected to the selected local output. The menu selection applies to onboard General Outputs only.
Note that the menu selection does not apply to Fire Alarm Devices (FAD), Fire Alarm Routing Equipment (FARE) and Fire Warning Routing Equipment (FWRE).
From the Local Outputs Menu (5.7.1), perform the following:
After pressing the Function button for the selected Local
Output(s), use the arrow down button to scroll downwards to Show Activating Detection Zones, then press Enter.
In the display you will now see a list of all detection zones that are connected to the selected local output.
Use the arrow up/down button to select a detection zone, then
press Enter.
The name of the detection zone and unit function will appear in the display.
5.7.8 Show Activating Points
This menu allows you to view all points that are connected to the selected local output. The menu selection applies to onboard General Outputs only.
Note that the menu selection does not apply to Fire Alarm Devices (FAD), Fire Alarm Routing Equipment (FARE) and Fire Warning Routing Equipment (FWRE).
From the Local Outputs Menu (5.7.1), perform the following:
After pressing the Function button for the selected Local
Output(s), use the arrow down button to scroll downwards to Show Activating Points, then press Enter.
In the display you will now see a list of all points that are connected to the selected local output.
Use the arrow up/down button to select a point, then press Enter. The point’s properties will appear in the display.
Page 66
Unit Configuration
Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03,
Autronica Fire and Security AS
Page 66
5.7.9 Show Activating Inputs
This menu allows you to view all inputs that are connected to the selected local output. The menu selection applies to onboard General Outputs only.
Note that the menu selection does not apply to Fire Alarm Devices (FAD), Fire Alarm Routing Equipment (FARE) and Fire Warning Routing Equipment (FWRE).
From the Local Outputs Menu (5.7.1), perform the following:
After pressing the Function button for the selected Local
Output(s), use the arrow down button to scroll downwards to Show Inputs, then press Enter.
In the display you will now see a list of all inputs that are connected to the selected local output.
Use the arrow up/down button to select an input, then press
Enter.
The input’s properties will appear in the display.
5.7.10 Show Activating Groups
This menu allows you to view all activation groups (groups; meaning “Activation Groups”) that are connected to the selected local output. The menu selection applies to onboard General Outputs only.
Note that the menu selection does not apply to Fire Alarm Devices (FAD), Fire Alarm Routing Equipment (FARE) and Fire Warning Routing Equipment (FWRE).
From the Local Outputs Menu (5.7.1), perform the following:
After pressing the Function button for the selected Local
Output(s), use the arrow down button to scroll downwards to Show Activation Groups, then press Enter.
In the display you will now see a list of all activation groups that are connected to the selected local output.
Use the arrow up/down button to select the Activation Group,
then press Enter.
The following information will appear in the display (for information on unit state and coincidence, refer to chapter 5.4.4):
o the name of the Activation Group o the Unit State o the Coincidence
Page 67
Unit Configuration
Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03,
Autronica Fire and Security AS
Page 67
5.7.11 Show Activating Outputs
This menu allows you to view all outputs that are connected to the selected local output. The menu selection applies to onboard General Outputs only.
Note that the menu selection does not apply to Fire Alarm Devices (FAD), Fire Alarm Routing Equipment (FARE) and Fire Warning Routing Equipment (FWRE).
From the Local Outputs Menu (5.7.1), perform the following:
After pressing the Function button for the selected Local
Output(s), use the arrow down button to scroll downwards to Show Outputs, then press Enter.
In the display you will now see a list of all outputs that are connected to the selected local output.
Use the arrow up/down button to select an output, then press
Enter.
The output’s properties will appear in the display.
5.7.12 Move to Alarm Zone
This menu allows you to connect a selected Local Output (applies only to local outputs related to Fire Alarm Devices) to an alarm zone or create a new alarm zone, and at the same time connect the new alarm zone to the Local Output (Fire Alarm Device).
Note that the menu selection applies to Fire Alarm Devices (FAD) only.
From the Local Outputs Menu (5.7.1), perform the following:
After pressing the Function button for the selected Local
Output(s), use the arrow down button to select Move to Alarm Zone, then press Enter.
Use the arrow button to select an existing alarm zone, or select
the menu Create New Alarm Zone. o If an existing alarm zone is selected, press Enter twice to
connect the local output to this alarm zone.
o If a new alarm zone is to be created, select Create New
Alarm Zone, press Enter twice, type the name, then press Enter.
o Use the left/right arrow buttons to select the Parent Alarm
Zone, then press Enter twice to confirm.
Page 68
Unit Configuration
Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03,
Autronica Fire and Security AS
Page 68
5.7.13 Show Connected Units
This menu allows you to view all connections that are connected to the selected local output. The menu selection applies to onboard General Outputs only.
Note that the menu selection does not apply to Fire Alarm Routing Equipment (FARE) and Fire Warning Routing Equipment (FWRE).
From the Local Outputs Menu (5.7.1), perform the following:
After pressing the Function button for the selected Local
Output(s), use the arrow down button to scroll downwards to Show Connections, then press Enter.
In the display you will now see a list of all connections that are connected to the selected local output.
Use the arrow up/down button to select a connection, then press
Enter.
In the display you will now see the name and unit function.
Page 69
Unit Configuration
Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03,
Autronica Fire and Security AS
Page 69
5.8 Loop Inputs
5.8.1 Accessing the Menu
From the Service Menu, perform the following:
Use the arrow down button to scroll downwards to
Unit Configuration, then press Enter.
Use the arrow down button to select Loop Inputs, then
press Enter once more.
Use the arrow up/down buttons to select the Loop Input
that is to be configured.
To view or change properties for the selected Loop Input, refer
to Configure Properties for a Loop Input (chapter 5.8.2).
To access available functions for a selected loop input, press the
Function button
, or use, if necessary, the multiselect feature to select several loop inputs by pressing the Select button to mark the loop inputs that are to be configured, and then press the Function button
.
The following menu selections will appear:
o Connect to Output (chapter 5.8.3) o Connect to Alarm Zone (chapter 5.8.4) o Disconnect from Output (chapter 5.8.5) o Disconnect from Alarm Zone (chapter 5.8.6) o Show Connected Units (chapter 5.8.7)
Scroll with the arrow up/down buttons to select the desired menu,
then follow the instructions in the relevant chapter.
Page 70
Unit Configuration
Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03,
Autronica Fire and Security AS
Page 70
5.8.2 Configure Properties for a Loop Input
The following properties can be changed:
the name of the loop input supervisory (Yes/No);
If Yes is selected, the inputs that are defined for technical alarms will be activated during normal operation, meaning that an indication of an event will appear in the display (supervisory text) on the activation of the loop input. The panel will be in Supervisory Condition.
From the Loop Inputs Menu (5.8.1), perform the following:
After selecting the Loop Input in question by means of the
arrow down/up buttons, press Enter twice.
Type a new Name, or accept the existing one by pressing the
arrow down button.
Press Enter. Use the left/right arrow buttons to select Supervisory:Yes or No,
then press Enter.
To confirm the setting, press Enter once more.
Page 71
Unit Configuration
Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03,
Autronica Fire and Security AS
Page 71
5.8.3 Connect to Output
This menu allows you to connect a selected loop input to an output.
From the Loop Inputs Menu (5.8.1), perform the following:
After pressing the Function button for the selected loop input(s),
select Connect to Output (the first menu selection), then press Enter.
A list of all available outputs will appear in the display. Use the arrow up/down button to select the output that
is to be connected to the selected loop input, then press Enter.
To confirm the setting, press Enter once more.
5.8.4 Connect to Alarm Zone
This menu allows you to connect a selected loop input to an alarm zone. In this way, the system will be able to activate Fire Alarm Devices (FADs) in the alarm zone.
From the Loop Inputs Menu (5.8.1), perform the following:
After pressing the Function button for the selected loop input(s),
use the arrow down button to scroll downwards Connect to Alarm Zone (the first menu selection), then press Enter.
A list of all alarm zones will appear in the display. Use the arrow up/down button to select the alarm zone that
is to be connected to the selected loop input, then press Enter.
To confirm the setting, press Enter once more.
5.8.5 Disconnect from Output
This menu allows you to disconnect a selected loop input from an existing output.
From the Loop Inputs Menu (5.8.1), perform the following:
After pressing the Function button for the selected loop input(s),
use the arrow down button to scroll downwards to Disconnect from Output, then press Enter.
In the display you will now see a list of all outputs (if any) that are connected to the selected loop input.
To disconnect the selected loop input from an output, use the
arrow down button to select the output, then press Enter.
To confirm the setting, press Enter once more.
Page 72
Unit Configuration
Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03,
Autronica Fire and Security AS
Page 72
5.8.6 Disconnect from Alarm Zone
This menu allows you to disconnect a selected loop input from an alarm zone.
From the Loop Inputs Menu (5.8.1), perform the following:
After pressing the Function button for the selected loop input(s),
use the arrow down button to scroll downwards to Disconnect from Alarm Zone, then press Enter.
In the display you will now see a list of all alarm zones (if any) that are connected to the selected loop input.
To disconnect the selected alarm zone from the loop input, use
the arrow down button to select the input, then press Enter.
To confirm the setting, press Enter once more.
5.8.7 Show Connected Units
This menu allows you to view all connections that are connected to the selected loop input.
From the Loop Inputs Menu (5.8.1), perform the following:
After pressing the Function button for the selected loop input(s),
use the arrow down button to scroll downwards to Show Connected Units, then press Enter.
In the display you will now see a list of all connections (if any) that are connected to the selected loop input.
Use the arrow up/down button to select a connection, then press
Enter.
In the display you will now see the name and unit function of the connections that are connected to the selected loop input.
Page 73
Unit Configuration
Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03,
Autronica Fire and Security AS
Page 73
5.9 Local Inputs
5.9.1 Accessing the Menu
From the Service Menu, perform the following:
Use the arrow down button to scroll downwards to
Unit Configuration, then press Enter.
Use the arrow down button to select Local Inputs, then
press Enter once more.
Use the arrow up/down buttons to select the Local Input
that is to be configured.
To view or change properties for the selected Local Input, refer
to Configure Properties for a Local Input (chapter 5.9.2).
To access available functions for a selected local input, press the
Function button
, or use, if necessary, the multiselect feature to select several local inputs by pressing the Select button to mark the local inputs that are to be configured, and then press the Function button
.
The following menu selections will appear:
o Connect to Output (chapter 5.9.3) o Connect to Alarm Zone (chapter 5.9.4) o Disconnect from Output (chapter 5.9.5) o Disconnect from Alarm Zone (chapter 5.9.6) o Show Connected Units (chapter 5.9.7)
Scroll with the arrow up/down buttons to select the desired menu,
then follow the instructions in the relevant chapter.
Page 74
Unit Configuration
Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03,
Autronica Fire and Security AS
Page 74
5.9.2 Configure Properties for a Local Input
The following properties can be changed:
the name of the local input
the unit function for a local input
supervisory (YES/NO) supervisory text hardware type
From the Local Inputs Menu (5.9.1), perform the following:
After selecting the Local Input in question by means of the
arrow down/up buttons, press Enter twice.
Type a new Name, or accept the existing one by pressing the
arrow down button.
Press Enter, then use the arrow left/right arrow buttons to select
among the following unit functions: o Day/Night Input:
input used for Day/Night Mode
o User Configurable Input:
input to be used for Supervisory function or general output activation
o Morse Input:
input that activates onboard Fire Alarm Devices (local outputs) similar to a morse key
o Mute FAD Input:
input that turns all FADs off while active
o Reset In Input:
input used as an external System Reset (similar to operating the Reset button)
o Silence In Input:
input used as an external silence of Fire Alarm Devices (similar to operating the Silence button)
o FARE Feedback:
input used as an acknowledge signal from the Fire Alarm receiving station, activates a separate LED on the panel
o Activate All Alarms*:
input used to activate all Fire Alarm Devices with a selectable sound pattern
o FWRE:
It is possible to use a monitored input for the FWRE function. This requires a special electrical connection using, for example, an optocoupler. Only available if no other input/output is configured as FWRE.
Press Enter, use arrow left/right arrow buttons to select
Supervisory YES or NO (where applicable), then press Enter.
Type a Supervisory text (where applicable), then press Enter. State the hardware type, then press Enter. To confirm the setting, press Enter once more.
* NOTE: If “Activate All Alarms” is selected, do as follows: press Enter after this selection is highlighted, press the arrow down button several times until you can press Enter to accept and return to the menu level above. Now you must select the same Loop Input again, then press the arrow down button once. The selections “Supervisory” and “Supervisory Text” are no longer shown, and are replaced by the selection “Sound Patterns”. Now you will be able to select one of several sound patterns (see chapter 1.1).
Page 75
Unit Configuration
Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03,
Autronica Fire and Security AS
Page 75
5.9.3 Connect to Output
This menu allows you to connect a selected local input to an output.
From the Local Inputs Menu (5.9.1), perform the following:
After pressing the Function button for the selected local input(s),
select Connect to Output (the first menu selection), then press Enter.
A list of all available outputs will appear in the display. Use the arrow up/down button to select the output that
is to be connected to the selected local input, then press Enter.
To confirm the setting, press Enter once more.
5.9.4 Connect to Alarm Zone
This menu allows you to connect a selected local input to an alarm zone.
From the Local Inputs Menu (5.9.1), perform the following:
After pressing the Function button for the selected local input(s),
use the arrow down button to scroll downwards to Connect to Alarm Zone, then press Enter.
A list of all available alarm zones will appear in the display. Use the arrow up/down button to select the alarm zone that
is to be connected to the selected local input, then press Enter.
To confirm the setting, press Enter once more.
5.9.5 Disconnect from Output
This menu allows you to disconnect a selected local input from an existing output.
From the Local Inputs Menu (5.9.1), perform the following:
After pressing the Function button for the selected local input(s),
use the arrow down button to scroll downwards to Disconnect from Output, then press Enter.
In the display you will now see a list of all outputs that are connected to the selected local input.
To disconnect the selected local input from an output, use the
arrow down button to select the output, then press Enter.
To confirm the setting, press Enter once more.
Page 76
Unit Configuration
Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03,
Autronica Fire and Security AS
Page 76
5.9.6 Disconnect from Alarm Zone
This menu allows you to disconnect a selected local input from an alarm zone.
From the Local Inputs Menu (5.9.1), perform the following:
After pressing the Function button for the selected local input(s),
use the arrow down button to scroll downwards to Disconnect from Alarm Zone, then press Enter.
In the display you will now see a list of all alarm zones that are connected to the selected local input.
To disconnect the selected local input from an alarm zone, use
the arrow down button to select the alarm zone, then press Enter.
To confirm the setting, press Enter once more.
5.9.7 Show Connected Units
This menu allows you to view all connections that are connected to the selected local input.
From the Local Input Menu (5.9.1), perform the following:
After pressing the Function button for the selected local input(s),
use the arrow down button to scroll downwards to Show Connected Units, then press Enter.
In the display you will now see a list of all connections that are connected to the selected local input.
Use the arrow up/down button to select a connection, then press
Enter.
In the display you will now see the name and unit function of the connections that are connected to the selected local input.
Page 77
Unit Configuration
Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03,
Autronica Fire and Security AS
Page 77
5.10 Loop I/O Carriers
5.10.1 Description
The loop units BN-303, BN-304, BN-305 and BN-306 are defined as Loop I/O Carriers.
A Loop I/O Carrier is a loop unit hosting one or several I/O subunits. The Loop I/O Carrier itself and all the input/outputs are assigned
separate loop unit IDs. The Loop I/O Carrier’s dipswitch setting determines which function is
assigned to the inputs/outputs. A Loop I/O Carrier may only have one function, which falls into one of the following categories: Point
Inputs with function Prealarm and/or Alarm and/or Fault, all latching, except BN-30x/E Prealarm
Input
Inputs are either On or Off Inputs may also give “Supervisory Alarm” (configurable)
Output
Outputs are either On or Off
Outputs may also give "Supervisory Alarm" (configurable). Outputs configured to function K, L or M are either Steady On or Off.
These units are also using sensor inputs (used for monitoring of the output). The sensor inputs are either On, Off, or Undetermined.
The subunits of a Loop I/O carrier are also present in the listing of units of menu commands Points, Loop Inputs and Loop Outputs.
Page 78
Unit Configuration
Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03,
Autronica Fire and Security AS
Page 78
5.10.2 Accessing the Menu
From the Service Menu, perform the following:
Use the arrow down button to scroll downwards to
Unit Configuration, then press Enter.
Use the arrow down button to select Loop IO Carriers, then
press Enter once more.
Use the arrow up/down buttons to select the Loop IO Carrier
that is to be configured.
To view or change properties for the selected Loop IO Carrier,
refer to Configure Properties for a Loop IO Carrier (chapter 5.10.3).
To access available functions for a selected Loop IO Carrier,
press the Function button
, or use, if necessary, the multiselect feature to select several Loop IO Carriers by pressing the Select button
to mark the ones that are to be configured,
and then press the Function button
.
The following menu selections will appear:
o Show All Carrier Units (chapter 5.10.4) o Show Carrier Points (chapter 5.10.5) o Show Carrier Inputs (chapter 5.10.6) o Show Carrier Outputs (chapter 5.10.7)
Scroll with the arrow up/down buttons to select the desired menu,
then follow the instructions in the relevant chapter.
Page 79
Unit Configuration
Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03,
Autronica Fire and Security AS
Page 79
5.10.3 Configure Properties for a Loop IO Carrier
The name of the Loop IO Carrier can be changed.
From the Loop IO Carriers Menu (chapter 5.10.2), perform the following:
After selecting the Loop IO Carrier in question by means of the
arrow down/up buttons, press Enter twice.
Type a new Name, or accept the existing one by pressing the
arrow down button.
Press Enter to view the Function/Switch. Press Enter, then type a new Unit Function, or accept the existing
one by pressing the arrow down button.
Press Enter, then type another Production Number, or accept the
existing one by pressing the arrow down button.
Press Enter, then state the hardware type, or accept the existing
one by pressing the arrow down button.
To confirm the setting, press Enter once more.
5.10.4 Show All Carrier Units
This menu allows you to view all Carrier Units. It not possible to change unit properites of the listed points, inputs or outputs.The command only helps the operator to show what type of I/O subunits the selected carrer is hosting.
To change properites of the Carrier's subunits, use one of the commands corresponding to the unit type.
From the Loop IO Carriers Menu (chapter 5.10.2), perform the following:
After pressing the Function button for the selected Loop IO
Carrier(s), use the arrow down button to scroll downwards to Show All Carrier Units, then press Enter.
In the display you will now see a list of all Carrier Units. "Show all Carrier Units" creates a list of units independent of the IO
Carrier configuration (i.e. dip switch setting).
Page 80
Unit Configuration
Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03,
Autronica Fire and Security AS
Page 80
5.10.5 Show Carrier Points
This menu allows you to view Carrier Points.
From the Loop IO Carriers Menu (chapter 5.10.2), perform the following:
After pressing the Function button for the selected Loop IO
Carrier(s), use the arrow down button to scroll downwards to Show Carrier Points, then press Enter.
In the display you will now see a list of all Carrier Points. Use the arrow up/down button to select a Carrier Point, then
press Enter.
In the display you will now see the relevant properties.
5.10.6 Show Carrier Inputs
This menu allows you to view Carrier Inputs.
From the Loop IO Carriers Menu (chapter 5.10.2), perform the following:
After pressing the Function button for the selected Loop IO
Carrier(s), use the arrow down button to scroll downwards to Show Carrier Inputs, then press Enter.
In the display you will now see a list of all Carrier Inputs. Use the arrow up/down button to select a Carrier Input, then
press Enter.
In the display you will now see the relevant properties.
Page 81
Unit Configuration
Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03,
Autronica Fire and Security AS
Page 81
5.10.7 Show Carrier Outputs
This menu allows you to view Carrier Outputs.
From the Loop IO Carriers Menu (chapter 5.10.2), perform the following:
After pressing the Function button for the selected Loop IO
Carrier(s), use the arrow down button to scroll downwards to Show Carrier Outputs, then press Enter.
In the display you will now see a list of all Carrier Outputs. Use the arrow up/down button to select a Carrier Output, then
press Enter.
In the display you will now see the relevant properties.
Page 82
Unit Configuration
Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03,
Autronica Fire and Security AS
Page 82
5.11 Mimic Panels
This menu selection is available only if Mimic Panels (Mimic Driver BUR-200) are connected to the system.
5.11.1 Accessing the Menu
From the Service Menu, perform the following:
Use the arrow down button to scroll downwards to
Unit Configuration, then press Enter.
Use the arrow down button to select a Mimic Panels, then
press Enter once more.
To view or change properties for the selected mimic panel, refer
to Configure Properties for a Mimic Panel (chapter 5.11.2), or;
To access available functions for the selected Mimic Panel, press
the Function button Continue following the instructions in chapter 5.11.3)
5.11.2 Configure Properties for a Mimic Panel
From the Mimic Panels Menu (5.11.1), perform the following:
After selecting the mimic panel in question by means of the
arrow down/up buttons, press Enter twice.
Type a new Name, or accept the existing one by pressing the
arrow down button.
Press Enter To confirm the setting, press Enter once more.
Page 83
Unit Configuration
Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03,
Autronica Fire and Security AS
Page 83
5.11.3 Configure Mimic Inputs and Outputs
From the Mimic Panels Menu (5.11.1), perform the following:
After pressing the Function button for the selected mimic panel(s),
the command Mimic Boards (Mimic Drivers, BUR-200) will appear, then press Enter.
To access available functions for the Mimic Board, press
the Function button
The following alternatives will appear: Mimic Input Units Mimic Output Units
Use the arrow down button to select either Mimic Input Units or
Mimic Output Units, then press the Function button
once
more.
The following commands will appear:
Connect to Output Connect to Alarm Zone Disconnect from Output Disconnect from Alarm Zone Show Connected Units
Page 84
Unit Configuration
Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03,
Autronica Fire and Security AS
Page 84
5.12 Activation Groups
Points and general outputs can be assigned to Activation Groups (configurable). An Activation Group can be configured to trigger an output in the event of an alarm. An output unit connected to this output will then initiate a signal to activate external equipment, as for example, doors, sprinkler systems, ventilation valves, horns and fire lights.
5.12.1 Accessing the Menu
From the Service Menu, perform the following:
Use the arrow down button to scroll downwards to
Unit Configuration, then press Enter.
Use the arrow down button to select Activation Groups, then
press Enter once more.
Use the arrow up/down buttons to select the Activation Group
that is to be configured.
To view or change properties for the selected Activation Group,
refer to Configure Properties for an Activation Group (chapter
5.12.2).
To access available functions for a selected activation group,
press the Function button
, or use, if necessary, the multiselect feature to select several activation groups by pressing the Select button
to mark the activation groups that are to be
configured, and then press the Function button .
The following menu selections will appear:
o Connect to Output (chapter 5.12.3) o Disconnect from Output (chapter 5.12.4) o Show Member Points (chapter 5.12.5) o Show Connected Units (chapter 5.12.6)
Scroll with the arrow up/down buttons to select the desired menu,
then follow the instructions in the relevant chapter.
Page 85
Unit Configuration
Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03,
Autronica Fire and Security AS
Page 85
5.12.2 Configure Properties for an Activation Group
The following properties can be changed:
the name of the local output Activate group on Unit State:
meaning which alarm level the points within this activation group will react to (pre-alarm, alarm, fault and disablement).
Activation Group Dependency:
meaning how many points within this activation group that must be in alarm state before actions are initiated (1-5 and All).
From the Activation Groups Menu (5.12.1), perform the following:
After selecting the Activation Group in question by means of the
arrow down/up buttons, press Enter twice.
Type a new Name, or accept the existing one by pressing the
arrow down button.
Press Enter, then use the left or right arrow button to select the
desired unit state (pre-alarm, alarm, fault and disablement), then press Enter.
Use the left or right arrow button to determine how many points
within this activation group that must be in alarm state before actions are initiated (1-5 and All).
To confirm the setting, press Enter once more.
5.12.3 Connect to Output
This menu allows you to connect a selected Activation Group to an output.
From the Activation Groups Menu (5.12.1), perform the following:
After pressing the Function button for the selected activation
group(s), select Connect to Output (the first menu selection), then press Enter.
A list of all available outputs will appear in the display. Use the arrow up/down button to select the output that
is to be connected to the selected Activation Group, then press Enter.
To confirm the setting, press Enter once more.
Page 86
Unit Configuration
Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03,
Autronica Fire and Security AS
Page 86
5.12.4 Disconnect from Output
This menu allows you to disconnect a selected local input from an existing Activation Group.
From the Activation Groups Menu (5.12.1), perform the following:
After pressing the Function button for the selected activation
group(s), use the arrow down button to scroll downwards to Disconnect from Output, then press Enter.
In the display you will now see a list of all outputs that are connected to the selected Activation Group.
To disconnect the selected local input from an Activation Group,
use the arrow down button to select the output, then press Enter.
To confirm the setting, press Enter once more.
5.12.5 Show Member Points
This menu allows you to view all points that are connected to the selected Activation Group.
From the Activation Groups Menu (5.12.1), perform the following:
After pressing the Function button for the selected activation
group(s), use the arrow down button to scroll downwards to Show Connections, then press Enter.
In the display you will now see a list of all connections that are connected to the selected Activation Group.
Use the arrow up/down button to select a connection, then press
Enter.
Page 87
Unit Configuration
Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03,
Autronica Fire and Security AS
Page 87
5.12.6 Show Connected Units
This menu allows you to view all outputs (or units that will be activated by the group) that are connected to the selected Activation Group.
From the Activation Groups Menu (5.12.1), perform the following:
After pressing the Function button for the selected activation
group(s), use the arrow down button to scroll downwards to Show Connections, then press Enter.
In the display you will now see a list of all connections that are connected to the selected Activation Group.
Use the arrow up/down button to select a connection, then press
Enter.
In the display you will now see the name and unit function.
5.13 External Interfaces
5.13.1 Accessing the menu
From the Service Menu, perform the following:
Use the arrow down button to scroll downwards to
Unit Configuration, then press Enter.
Use the arrow down button to select External Interfaces, then
press Enter once more.
A list of all related interfaces will appear in the display, including:
o Serial Port Settings (chapter 5.13.2) o TCP/IP Port Settings (chapter 5.13.3) o ESPA (chapter 5.13.4) o MODBUS (5.13.5) o VDR (chapter 5.13.6) o Remote Access (chapter 5.13.7)
Use the arrow up/down buttons to select the External Interface
that is to be configured, then follow the instructions in the relevant chapter.
Page 88
Unit Configuration
Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03,
Autronica Fire and Security AS
Page 88
5.13.2 Serial Port Settings
This menu selection allows you to define all serial port settings. Note that ESPA and Voice Data Recorder (VDR) require the use of
the serial port. MODBUS can use either the serial or ethernet port.
From the External Interfaces Menu (5.13.1), perform the following:
Select Serial Port Settings (the first menu selection), then press
Enter twice.
Use the arrow left/right button to select “Bits per second”, then
press Enter.
Use the arrow left/right button to select “Word Length”, then
press Enter.
Use the arrow left/right button to select “Parity”, then press Enter. Use the arrow left/right button to select “Stop Bits”, then press
Enter.
Use the arrow left/right button to select “Hardware Interface”,
then press Enter.
To confirm the setting, press Enter once more.
TCP/IP Port Settings
This menu selection allows you to define all Ethernet(TCP/IP) port settings.
MODBUS can use either the serial or ethernet port.
From the External Interfaces Menu (5.13.1), perform the following:
Use the arrow down button to select TCP/IP Port Settings, then
press Enter twice.
Use the arrow left/right button to select “Own IP Address”, then
press Enter.
Use the arrow left/right button to select “Gateway IP Address”,
then press Enter.
Use the arrow left/right button to select “Subnet Mask”, then
press Enter.
To confirm the setting, press Enter once more.
Page 89
Unit Configuration
Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03,
Autronica Fire and Security AS
Page 89
5.13.4 ESPA
This menu selection includes the following submenus:
Configure Settings (chapter 5.13.4.1) Configure Events (chapter 5.13.4.2) Configure Receivers (chapter 5.13.4.3) Send Test Event (chapter 5.13.4.4)
Note that ESPA always requires the use of the serial port.
5.13.4.1 Configure Settings
This menu selection allows you to configure ESPA settings.
From the External Interfaces Menu (5.13.1), perform the following:
Use the arrow down button to select ESPA, then press Enter. Select Configure Settings (the uppermost menu), then press
Enter twice.
Type a new Name, or accept the existing one by pressing the
arrow down button.
Press Enter, use the arrow left/right buttons to select the port
(not in use or serial), then press Enter.
  Use the arrow left/right buttons to select whether you want to
restore factory settings or not (No/Yes), then press Enter. o If No is selected, the next menu selection will be shown and
all following values must be selected.
o If Yes is selected, default values will be used.
Use the arrow left/right buttons to select the display size (default
128), then press Enter.
Use the arrow left/right buttons to select the line length
(default 12), then press Enter.
Use the arrow left/right buttons to select the alphabet type (7 bits,
8 bits, or GSM), then press Enter.
Use the arrow left/right buttons to select the fault detail (Yes/No),
then press Enter.
Use the arrow left/right buttons to select whether you want to
prepare for a startup message, then press Enter.
To confirm the settings, press Enter once more.
Page 90
Unit Configuration
Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03,
Autronica Fire and Security AS
Page 90
5.13.4.2 Configure Events
This menu selection allows you to configure event properties.
From the External Interfaces Menu (5.13.1), perform the following:
Use the arrow down button to select ESPA, then press Enter. Use the arrow down button to select Configure Events, then
press Enter and you can define a text, the number of beeps and transmissions for the following events:
o Alarm o Prealarm o Fault o Supervisory o Startup o Test
Select Alarm (the uppermost menu), then press Enter twice. Type a freely chosen text, then press Enter. Enter the number of beeps (refer to the paging system’s
specifications), then press Enter.
Enter the number of transmissions (normally 2 transmissions for
normal calls and 3 transmissions for alarms), then press Enter.
To confirm the settings, press Enter once more. Configure the properties for all other events as described above.
5.13.4.3 Configure Receivers
This menu selection allows you to configure user properties.
From the External Interfaces Menu (5.13.1), perform the following:
Use the arrow down button to select ESPA, then press Enter. Use the arrow down button to select Configure Receivers, then
press Enter.
You can now define the properties for 10 differenet users. Select User 1 (the uppermost selection), then press Enter twice.
Enter the user name, then press Enter. Enter the receiver number, then press Enter. Use the left and right arrow button to select the events that are to
be displayed, including one of the following selections:
o no events o all events o alarm o alarm + prealarm o alarm + prealarm + supervisory
To confirm the settings, press Enter once more. Configure the properties for all other users as described above.
Page 91
Unit Configuration
Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03,
Autronica Fire and Security AS
Page 91
5.13.4.4 Send Test Event
This command is used for test purposes.
From the External Interfaces Menu (5.13.1), perform the following:
Use the arrow down button to select ESPA, then press Enter. Use the arrow down button to select Send Test Event, then press
Enter.
The following message will appear: “Text Message Transmitted”.
o A text message is transmitted to verify that there is a proper
communication between Autroprime and the paging system.
Page 92
Unit Configuration
Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03,
Autronica Fire and Security AS
Page 92
5.13.5 MODBUS
This menu selection includes the following submenus:
Configure Settings (chapter 5.13.5.1) Configure Status Registers (chapter 5.13.5.2) Configure Command Registers (chapter 5.13.5.3) Set Testbit to 0 (chapter 5.13.5.4) Set Testbit to 1 (chapter 5.13.5.5) Assign Unique MODBUS Indexes (chapter 5.13.5.6)
MODBUS can use either the serial or ethernet port.
5.13.5.1 Configure Settings
This menu selection allows you to configure MODBUS settings.
From the External Interfaces Menu (5.13.1), perform the following:
Use the arrow down button to select MODBUS, then press Enter. Select Configure Settings, then press Enter twice.
Type a new Name, or accept the existing one by pressing the
arrow down button.
Press Enter, use the arrow left/right buttons to select the port
(not in use, serial or TCP/IP), then press Enter.
If Ethernet is selected, use the arrow left/right buttons to select
the TCP/IP Address, then press Enter (not in use when serial is selected).
If Ethernet is selected, use the arrow left/right buttons to select
the Port Number, then press Enter (not in use when serial is selected).
Use the arrow left/right buttons to select the mode (slave or
master), then press Enter.
Use the arrow left/right buttons to select whether you want to
restore factory settings or not (Yes/No), then press Enter.
Select the default slave 1, or use the alphanumeric keypad to type
another slave address, then press Enter.
Select the default slave ID (12) (normally not changed), or use the
alphanumeric keypad to type another slave ID, then press Enter.Use the arrow left/right buttons to select Handshake (Yes/No), then press Enter.
Use the arrow left/right buttons to select Report Fault (Yes/No),
then press Enter.
Select the Fault Timer (default 10 seconds), or use the
alphanumeric keypad to type another Fault Timer, then press Enter.
To confirm the settings, press Enter once more.
Page 93
Unit Configuration
Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03,
Autronica Fire and Security AS
Page 93
5.13.5.2 Configure Status Registers
This menu selection allows you to configure Status Registers. The Status Register is either the Input Register or the Holding
Register. This depends on whether the Modbus mode is configured as Slave or Master.
Modbus Master - Holding Register: The Start Address for the Status Register is in the range 40001 to
45000. Modbus Slave – Input Register:
The Start Address for the Status Register is in the range 30001 to
35000.
From the External Interfaces Menu (5.13.1), perform the following:
Use the arrow down button to select MODBUS, then press Enter. Use the arrow down button to select Configure Status Registers,
then press Enter twice.
Type the Start Address, then press Enter. Type the Number of Registers, then press Enter. To confirm the settings, press Enter once more.
5.13.5.3 Configure Command Registers
This menu selection allows you to configure command registers. The Command Register is identical to the Holding Register. Only the
Start Address (first Register Number) is specified, and the Command Register consists of 3 Registers where only the the Start Address (first Register Number) is defined.
Note that when using Modbus Master, make sure that the range for the Command Register and Status Register does not overlap. See example below.
Register Type Register Number
Range of Command Register
40001 40002 40003
Range of Status Register
40004 40xxx 40004 + number of registers -1
Page 94
Unit Configuration
Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03,
Autronica Fire and Security AS
Page 94
From the External Interfaces Menu (5.13.1), perform the following:
Use the arrow down button to select MODBUS, then press Enter. Use the arrow down button to select Configure Command
Registers, then press Enter twice.
Type the Start Address, then press Enter. To confirm the setting, press Enter once more.
5.13.5.4 Set Testbit to 0
This command is used for test purposes.
From the External Interfaces Menu (5.13.1), perform the following:
Use the arrow down button to select MODBUS, then press Enter. Use the arrow down button to select Set Testbit to 0, then press
Enter.
The following message will appear: “Test finished”.
Page 95
Unit Configuration
Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03,
Autronica Fire and Security AS
Page 95
5.13.5.5 Set Testbit to 1
This command is used for test purposes.
From the External Interfaces Menu (5.13.1), perform the following:
Use the arrow down button to select MODBUS, then press Enter. Use the arrow down button to select Set Testbit to 1, then press
Enter.
The following message will appear: “Test message transmitted”.
5.13.5.6 Assign Unique MODBUS Indexes
This command is used for test purposes.
From the External Interfaces Menu (5.13.1), perform the following:
Use the arrow down button to select MODBUS, then press Enter. Use the arrow down button to select Assign Unique MODBUS
Indexes, then press Enter.
To confirm the setting, press Enter once more.
Page 96
Unit Configuration
Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03,
Autronica Fire and Security AS
Page 96
5.13.6 VDR
This menu selection allows you to define all settings for the Voyage Data Recorder (VDR), including the following submenus:
Configure Settings (chapter 5.13.6.1) Send Test Event (chapter 5.13.6.2)
Note that the Voyage Data Recorder (VDR) requires the use of the serial port.
5.13.6.1 Configure Settings
This menu selection allows you to configure VDR settings.
From the External Interfaces Menu (5.13.1), perform the following:
Use the arrow down button to select VDR, then press Enter. Select Configure Settings (the uppermost selection), then press
Enter twice.
Type a new Name, or accept the existing one by pressing the
arrow down button.
Press Enter, use the arrow left/right buttons to select the port
(not in use or serial), then press Enter.
Use the arrow left/right buttons to select whether you want to
restore factory settings or not (Yes/No), then press Enter.
Use the arrow left/right buttons to select Log Volume Mini
(Yes/No), then press Enter. If Yes is selected, the amount of information which is sent to the VDR will be limited; only information on alarms and door control will be sent.
Use the arrow left/right buttons to select Alive Time (default 4
minutes), then press Enter. Alive Time determines how often a message is sent to the VDR to ensure that there is a proper communication between the system and the VDR.
Use the arrow left/right buttons to select Update Time
(default 120 minutes), then press Enter. Update Time determines how often the VDR receives a full update of all fire alarms and fault statuses.
To confirm the settings, press Enter once more.
5.13.6.2 Send Test Event
This command is used for test purposes.
From the External Interfaces Menu (5.13.1), perform the following:
Use the arrow down button to select VDR, then press Enter. Use the arrow down button to select Send Test Event, then press
Enter
The following message will appear: “Test message transmitted”.
Page 97
Unit Configuration
Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03,
Autronica Fire and Security AS
Page 97
5.13.7 Remote Access
Autroprime can be configured to act as a TCP/IP network node, allowing Autroprime to communicate with WWW based applications for monitoring and control (chapter 5.13.7.1) or, for example, an AutroMaster Integrated Safety and Emergency Management System (chapter 5.13.7.2, 5.13.7.3 and 5.13.7.4).
5.13.7.1 Server and Web Access
Server and Web Access must be configured in order to allow external WWW clients access Autroprime.
From the External Interfaces Menu (5.13.1), perform the following:
Select Remote Access, then press Enter twice. Select Server and Web Access, then press Enter. Use the arrow left/right button to select Server Access Level (Off,
Monitoring or Monitoring and Control), then press Enter.
Monitoring is to be selected if you want the external system to
only receive information from Autroprime.
Monitoring and Control is to be selected if you want
Autroprime to both receive information from and transmit information to an external system (for example AutroMaster).
Use the arrow left/right button to select Web Application Access
Level (Off, Monitoring or Monitoring and Control), then press Enter.
Monitoring is to be selected if you want the Web application
to only receive information from Autroprime.
Monitoring and Control is to be selected if you want
Autroprime to both receive information from and transmit information to a Web Application.
Use the arrow left/right button to select Select Access Time
Unlimited (NO or YES)
If YES is selected, the Client or Web application will have
continuous access.
If NO is selected, the Autroprime system will close the
communication with a PC Web-application or Client after a time span given by Time Limitation.
Select Time Limitation (hours) if applicable. Press Enter. To confirm, press Enter once more.
Page 98
Unit Configuration
Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03,
Autronica Fire and Security AS
Page 98
5.13.7.2 User Management
Autroprime can be configured as a Client being able to access and communicate with a server-based application, for example, AutroMaster ISEMS. The required configuration is performed in the User Management menu (plus the Clients menu, described in next chapter).
From the External Interfaces Menu (5.13.1), perform the following:
Select Remote Access, then press Enter. Use the arrow down button to select User Management, then
press Enter twice.
Press Enter, then type a User Name, then press Enter Type a Password (minimum 8 characters), then press Enter To confirm, press Enter once more.
5.13.7.3 Clients
Autroprime can be configured as a Client being able to access and communicate with a server-based application, for example, AutroMaster ISEMS. The required configuration is performed in the Clients menu (plus the User Management menu described in previous chapter).
From the External Interfaces Menu (5.13.1), perform the following:
Select Remote Access, then press Enter.. Use the arrow down button to select Clients, then press Enter
(maximum 4 Clients can be defined)
Use the arrow down button to select one of the 4 Clients, then
press Enter twice.
Type a Client name, then press Enter. Type the User, then press Enter. Use the arrow left/right button to select Account Status, then
press Enter.
Select Active to activate this client. Select Suspended to deactivate this client.
Use the arrow left/right button to select Client Access Level (Off,
Monitoring or Monitoring and Control), then press Enter.
Monitoring is to be selected if you want Autroprime to only
receive information from the Client.
Monitoring and Control is to be selected if you want
Autroprime to both receive information from and transmit information to the Client.
Use the arrow left/right button to set the External Server Address
(for example,10.62.63.79:10002), then press Enter.
To confirm, press Enter once more.
Page 99
Unit Configuration
Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03,
Autronica Fire and Security AS
Page 99
5.13.7.4 Client Proxy Server
If the network is using a Proxy Server, the Client Proxy Server must be defined in the following menu:
From the External Interfaces Menu (5.13.1), perform the following:
Select Remote Access, then press Enter. Use the arrow down button to select Client Proxy Server, then
press Enter twice.
If a proxy server is to be connected, type the Proxy Server
Address (for example, 10.64.1.46:8080), then press Enter.
To confirm, press Enter once more.
Page 100
Unit Configuration
Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03,
Autronica Fire and Security AS
Page 100
5.14 Detection Loops
This menu selection allows you to:
define the name of a detection loop override the system calculated preset current set a different limit for the maximum possible loop current for a
selected detection loop. The following different default settings are possible: 100mA,
150mA, 200mA, 250mA, 300mA, 350mA and 400mA.
Note that the high current settings 300mA, 350mA and 400mA are only available with BSA-200A or BSD-200A (revision A required). Due to limitations of the power supply, the system will not allow configuration of a total loop current exceeding 1200 mA.
When the system is powered up, or the loop driver is enabled, the system will automatically calculate and set a current limit which is optimized for each loop individually, depending on the number and type of loop units. If the operator has configured a maximum loop current value being higher than the system preset value, this value will not be changed by the system.
In some cases the system may allow the operator to override the system preset loop current and decrease the maximum loop current to a value being 50 mA lower the preset loop current. This should only be used if the system reports a fault on the loop resistance being too high. Overriding and decreasing the preset loop current with 50 mA may be sufficient to avoid this fault.
The maximum power consumption is determined by the following
parameters:
o the number of loop units o the loop unit type, i.e. the specified maximum current for the
loop unit type
From the Service Menu, perform the following:
Use the arrow down button to scroll downwards to
Unit Configuration, then press Enter.
Use the arrow down button to select Detection Loops, then
press Enter.
Use the arrow up/down buttons to select the Detection Loop
that is to be configured, then press Enter twice.
Type a new Name, or accept the existing one by pressing
the arrow down button.
Press Enter, use the arrow left/right button to select (if allowed by
the system) if the preset loop current shall be overrided, then press Enter.
Press Enter, use the arrow left/right button to set the limit for
maximum loop current, then press Enter.
To confirm, press Enter once more.
Loading...