Auto-Zone Control Systems Zoning Design User Manual

ZoningZoning
Zoning
ZoningZoning
Design GuideDesign Guide
Design Guide
Design GuideDesign Guide
Zone
Zone
8500 NW River Park Drive Parkville , MO 64152 PH: (816) 505-1100 FX: (816) 505-1101 E-mail: mail@wattmaster.com
Visit our website at www.wattmaster.com
WattMaster Controls assumes no responsibility for errors, or omissions. This document is subject to change without notice. All rights reserved.
Table Of Contents
How Auto-Zone Works ..........................................................................................................5
Why Should I Use Auto-Zone?..............................................................................................6
What Is Unique About Auto-Zone? ....................................................................................6-8
Zoning Systems Versus True VAV Systems .......................................................................... 9
Basics Of Designing A Zoning System................................................................................ 10
Design Considerations ................................................................................................... 11-12
Zoning Design Procedures.............................................................................................13-21
System Installation .........................................................................................................22-26
Application Notes ................................................................................................................27
Table Of Figures & Tables
Figure 1-1: Auto-Zone Plus System Overview .................................................................... 5
Figure 1-2: Zones Affected By Outdoor Load...................................................................13
Figure 1-3: Zone Layout With External Zones Only ......................................................... .14
Figure 1-4: Zones With North And South Exposures ....................................................... .14
Figure 1-5: Zoning And Constant Volume Units ................................................................14
Figure 1-6: Round Bypass Damper.................................................................................. .16
Figure 1-7: Rectangular Bypass Damper & Kit ................................................................ .16
Figure 1-8 Preferred Sensor Location ..............................................................................1 7
Figure 1-9: Acceptable Sensor Location ........................................................................... 17
Figure 1-10: Least Desirable Sensor Location .................................................................... 17
Figure 1-11: Pressure Dependent Damper .........................................................................1 8
Figure 1-12: Pressure Independent Damper.......................................................................1 8
Figure 1-13: WattMaster Communications Wire ................................................................. 23
Figure 1-14: Auto-Zone Basic System Communications Loop Wiring ................................2 4
Figure 1-15: Auto-Zone Plus System Communications Loop Wiring .................................. 24
Figure 1-16: Transformer & Wire Sizing Considerations.....................................................26
Table 1-1: Round Damper Selection Data.......................................................................... 19
Table 1-2: Rectangular Damper Selection Data .................................................................2 0
How Auto-Zone Works
Zoning Design Guide
The Auto-Zone control system converts single-zone constant volume rooftop packaged or split system HVAC units into variable air volume/variable tempera­ture multiple zone systems. The microprocessor based Zone Manager calculates the heating and cooling re­quirements for each zone based on real time informa­tion received from each Zone Controller/Damper. The Zone Manager then directs the HVAC unit to provide the appropriate amount of heating, cooling, and venti­lation to satisfy each zone’s requirements. A bypass damper controlled, by a static air pressure sensor, modu­lates a bypass damper to maintain constant duct pres­sure.
The Auto-Zone system uses a unique 3 tier approach to controlling the system:
Voting Zones
System Demand
Priority
This 3 tier system works in an integrated fashion to maintain proper control of the equipment and effective control of comfort in the zone.
First the zone must initiate a vote to the HVAC unit. This occurs when a zone becomes more than 1 degree off setpoint. At this time a vote is placed for heating or cooling. Next the controller evaluates the total cooling demand or heating demand within the entire building to see which requirement is more critical. Finally, the system looks for any priority conditions, which would take precedence over other zones. All three of these elements working together provide accurate and stable control of comfort.
Additional control features are taken into account to provide a very effective control of the system. Some of these include priority override, supply air temperature limits, outside air temperature lockouts, and min./max. control over damper position.
Substantial savings can be realized using the Auto-Zone Zoning system instead of having to install multiple roof­top units to accommodate multiple zone requirements. The Auto-Zone Zoning system is versatile and can be used with any packaged roof top unit or split system. It controls a variety of terminal unit functions including single duct pressure dependent, pressure independent, series fan and parallel fan terminals.
CONNECT TO OTHER ZONE MANAGERS
120/9 VAC
TRANSFORMER
AVOID
DIRECT
SUNLIGHT
NETWORK COMM LOOP
AC LINE VOLTAGE
COMPUTER (OPTIONAL)
RemoteLink
CONTROLS
REMOTE LINK
(OPTIONAL MODEM)
2 CONDUCTOR
24 GA.
OUTSIDE AIR SENSOR
24 VAC
GROUND
COMMLINKII
CONTROLS
COMM LINK II
INTERFACE
( OPTIONAL )
CONTROL CABLE
SUPPLY AIR
TEMPERATURE
SENSOR
2 CONDUCTOR
ZONE MANAGER
LOCAL COMM LOOP
120/24 VAC
TRANSFORMER
24 GA.
SYSTEM MANAGER
FAN
0
1
4
7
c.
e
D
*
H
C
F
E
O
I
A
L
O
MIXED
T
T
L
I
I
AIR
E
N
N
R
G
G
OUTSIDE AIR
EXHAUST AIR
RETURN AIR
MODULATING
3 CONDUCTOR
24 GA.
LO
BYPASS DAMPER
STATIC PRESSURE SENSOR & PICKUP TUBE
HI
2 CONDUCTOR
24 GA.
RETURN AIR SENSOR
CONNECT TO OTHER ZONE CONTROLLERS OR CV UNITS
SUPPLY AIR DUCT
MODULATING
DAMPER
ZONE
CONTROLLER
V
C
e
n
o
Z
-
o
t
u
A
N
O
M
M
P
8
3
:
2
0
8
9
/
0
2
/
7
D
E
I
P
U
C
C
O
S
M
R
A
L
A
O
N
SYSTEM
MANAGER
m
r
la
A
sc
E
u
n
e
M
2
3
n
o
ti
a
ic
n
u
m
m
o
C
e
d
i
r
r
e
v
O
6
5
8
9
s
u
in
M
r
te
n
E
r
a
le
C
0
.
C
N
I
S
L
O
R
T
N
O
C
R
E
T
S
A
M
T
T
A
W
ZONE 1
TEMPERATURE SENSOR
MODULATING
DAMPER
ZONE
CONTROLLER
WARMER
NORMAL
COOLER
OVR
ZONE 2
TEMPERATURE SENSOR
W/OVERRIDE AND SETPOINT ADJUST
UP TO 16 ZONES
Figure 1-1: Auto-Zone Plus System Overview
Auto-Zone Systems 5
Zoning Design Guide
Why Should I Use Auto-Zone?
Auto-Zone is a proven system with a long history of successful installations. Our systems have been refined over the years with the help of feedback from people in the field who work and live with these systems on a daily basis. Our success is greatly due to the fact that we have implemented changes and enhancements based
on real world experience not from tinkering with equip­ment in an isolated lab environment. This real world approach provides engineers, contractors, and end us­ers with a zone control system that is efficient, reliable, and most importantly, keeps the customers comfortable!
What Is Unique About Auto-Zone?
Auto-Zone is unique because it has many features not found on other systems. These features include
Non-Proprietary Design
Auto-Zone will work on any manufacturers HVAC equipment that will accept a standard thermostat con­nection. This protects the end user from being locked in to one source for service and support. In addition, Auto­Zone Systems include very comprehensive documenta­tion, which was written in a format specifically for a “non-controls technician”. Because the manuals are so user friendly, it prevents the end user from being “locked-in” to one contractor for service. Any new con­tractor needs only a copy of the system manual to have as much technical information as any previous contrac­tor.
Pre-Engineered Software
System design, software, and documentation has already been done for you. This eliminates the costly expense usually associated with conventional DDC systems, making the Auto-Zone system more competitive and easier to install and operate.
One System for Zoned or Single Zone Systems
Not only does Auto-Zone provide a networked zone control system for one or multiple zoned HVAC units, you can also connect individual single zone units to the system eliminating the need to use programmable ther­mostats.
Easy to Configure
Since Auto-Zone components are grouped into pack­ages, configuring a system has been simplified. This reduces the chance of ordering errors and makes sys­tem layout effortless!
User Friendly Set Up
Since the Auto-Zone comes with menu driven, fill in the blank programming, system setup is simple. The system manual takes you step by step through the set up process. Default parameter values are programmed into permanent memory so the system can be opera­tional at start-up. Specialized training is not required.
6 Auto-Zone Systems
Zoning Design Guide
True Network Communications
The Auto-Zone uses a three wire, RS-485 loop for com­munication between all controllers in the system. This provides a very reliable form of communication with flexibility of installation. The loop can be wired in a “daisy chain” or “star” configuration. Many other zon­ing systems utilize “home run” wiring that requires all communication cables to be brought back to a central point adding additional cost to the project and compli­cating wiring.
High Integrity Communications
Many communicating control systems are susceptible to electrical interference. One major manufacturer of zoning systems recommends that their communication cable should not be strapped to conduit because of po­tential interference. The Auto-Zone Systems have a communication bus that is almost immune to any noise problems that may be found in most commercial facili­ties.
Microprocessor Controllers
All controllers in the Auto-Zone have an on board microprocessor. This is what gives the Auto-Zone its powerful features and capabilities not found in other systems.
Stand Alone Systems
All Auto-Zone Systems are true stand-alone and do not require a computer to operate. Unit controllers main­tain their own 7 day time clock, 365 day holiday sched­uling, and setpoints within each controller.
Menu Driven Operators’ Interface
All Auto-Zone systems have an operators’ keypad and display terminal. This gives you access to system sta­tus and parameter values without the need for a com­puter. The 4 line by 20 character display is backlighted making it easy to read even in low light environments. Menu driven programming makes the system extremely user friendly. In addition, the interface panel is pass­word protected to keep unauthorized users from access­ing the system.
Communications Via Optional Modem
The Remote Link is used for achieving remote commu­nications with the Auto-Zone system. It connects to the
CommLink II communications interface and a local phone line. With the Remote Link, the Auto-Zone sys­tem can be monitored and controlled from a remote lo­cation, using a computer and the ZoneView AZ or Plus software packages.
Memory Backup
Instead of batteries, which have to be replaced, Auto­Zone utilizes super capacitors to provide power for memory backup during power outages. The major ad­vantages to this approach is that super capacitors are more reliable than batteries and they recharge in a mat­ter of seconds instead of hours. T ypical memory backup is good for a minimum of 10 days.
Modulating, Heavy Duty Actuators with Real Time Feedback
All Auto-Zone actuators utilize true modulating con­trol unlike many systems, which are two position. This gives the system-improved control, which translates, to better comfort levels. Our actuators are also rated for 2-½ million cycles, making our actuators some of the most reliable in the industry. One other critical feature is the real time feedback. Many other systems have no feedback at all. They blindly estimate the travel time of their actuator, which, in the real world, is not a very repeatable estimate. To help correct the problems in­herent with this approach, they recycle all the actuators in the system once or twice a day . They may save a few dollars by not including feedback but they sacrifice sys­tem performance. Not so with Auto-Zone.
Commercial Grade – Insulated Round Zone Dampers
Auto-Zone only uses commercial grade zone dampers, not cheap, flimsy, “light commercial” or “residential” style dampers like many other manufacturers. Our round damper is ARI certified and comes from the factory fully insulated. Why? When many zone dampers are installed they are improperly insulated or not insulated at all. This can cause problems with the damper “sweat­ing” from condensation. With factory insulated zone dampers, we eliminate a common problem for the con­tractor while insuring the end user will not have prob­lems with condensation dripping down onto the ceil­ing.
Auto-Zone Systems 7
Zoning Design Guide
What Is Unique About Auto-Zone?
Rectangular Dampers
Auto-Zone uses only top of the line, aluminum air foil rectangular control dampers. No other zone system on the market today utilizes a damper of this quality and performance!
Patented Flush Mount Room Sensors
Our flush mount room sensors are so unique, they are patented (U.S. Patent No. 4,659,236). Even though part of the sensor is recessed into the wall to provide an attractive yet tamper proof flush mounting, internal wall temperatures do not influence the sensor. A special plate on the face of the sensor accurately senses space tem­perature. Even though the attractive off white plastic housing is a preferred color, the sensor housing can be painted or wallpapered to blend with room decor with­out affecting sensor performance. The sensors are of­fered in four different configurations:
Sensor
Sensor w/override
hundreds. ZoneView is not copy protected so it can be installed on multiple PC’s’ without additional expense. Just some of its many features include but are not lim­ited to:
Pre-designed status screens for all controllers
Alarm dial out capability
Programming of all system parameters
Trend logging to Excel™ spreadsheets
Alarm Handling
Custom graphics capability
Sensor w/setpoint adjustment
Sensor w/setpoint adjustment & override
Modular Connections
Many Auto-Zone auxiliary devices are connected to the controllers via modular plugs like the ones used on tele­phones. This simplifies installation and eliminates the possibility of wiring errors. The devices, which utilize this method, are damper actuators for zone and bypass control, auxiliary relay boards, and static pressure/air flow sensors. There is one interesting side note about the auxiliary relay board and airflow sensors. These devices are typically used on the zone controllers in the Auto-Zone Basic & Plus systems. When the system is powered up, it automatically looks to see if these de­vices are connected to the controller. If they are, the controller automatically reconfigures itself to utilize these devices and activates the appropriate set up screens back at the operators interface. Pretty neat don’t you think!
FREE! Windows™ Graphics Software
Each Auto-Zone system can be monitored on site or remotely using a PC and our ZoneView Plus™ Win­dows 98 software. This full-featured package is very user friendly and can be used to monitor one system or
Open Protocol System
Auto-Zone is an open protocol based system allowing other manufacturers to develop direct interfaces to the communications loop. This gives you the ability to in­tegrate the Auto-Zone system into products from other vendors. Our engineering staff will be glad to assist any vendor in this process.
8 Auto-Zone Systems
Zoning Design Guide
Zoning Systems Versus True VAV Systems
General
Even though there are some similarities between zone control systems and Variable Air Volume (VAV) sys­tems, there are some major differences. In many cases systems will be called VAV when in fact they are really a zoning system or are referred to as a zoning system when they are really a VAV system. Always make sure that you do not try to adapt a zoning system to a VAV design system. Understanding the differences will help you to prevent misapplication of the Auto-Zone zoning system. In the paragraphs that follow we will try to ex­plain the differences, advantages and disadvantages of each and explain their operation.
V AV Systems
These systems consist of an HVAC unit that is gener­ally a cooling only unit and VAV terminal units located in the downstream ductwork that are used to control the amount of constant temperature air delivered to the various building zones. Sometimes the HV AC unit may have gas or electric heat, but it is typically sized and applied for morning warm-up purposes. The HV AC unit is designed to vary the volume of air that is supplied to the duct system by using either inlet vanes or an elec­tronic variable frequency drive. These devices modu­late to control the air flow through the supply fan in response to the static pressure in the duct system. VAV systems typically use high velocity VAV terminal units to distribute the air to the zones. As the various VAV terminal units in the different zones open and close to supply the constant temperature air to the spaces, the HVAC unit varies the volume of constant temperature air based on the static pressure in the ductwork. The HV AC unit is designed to maintain a constant cold sup­ply air temperature regardless of the air flow volume in the system. The HVAC unit cycles it’s cooling stages to maintain a constant predetermined supply air tem­perature. It typically runs continuously based on a sched­ule. For perimeter zones requiring heat, reheat coils (electric or hot water) located in the terminal units are used to supply heated air to the space. Many times fan powered terminal boxes are used and in many cases also incorporate electric or hot water heating coils to provide perimeter zone heating. In summary a true V AV system uses a variable volume fan supplying constant temperature air to the system with variable volume ter­minal units used to control the volume of constant tem­perature air delivered to the space. Generally these sys­tems use pressure independent damper control.
Auto Zone Systems
The Auto-Zone zoning system is completely different in operation and design from the VAV system previ­ously discussed. One of the major differences between the zoning system and a true VAV system is that the HVAC unit used on a zoning system utilizes a constant volume fan. Air volume control of the zoning system is achieved by bypassing air from the HVAC unit supply duct back into the HVAC unit return air duct on the unit inlet. This bypass air is controlled based on a static pres­sure sensor located in the supply air duct downstream of the unit supply air discharge. The bypass damper modulates open and closed based on the static pressure in the duct. The temperature at the HV AC unit dischar ge varies in relation to the demand from the zones. Typi­cally the HVAC units used for the zoning system will have both heating and cooling capabilities. The fan sup­plies a constant volume of cold or hot air to the duct system and which is fed to the individual zones by modu­lating zone dampers. Each zone controller relays its heat­ing or cooling demand to the HVAC unit controller. The HVAC unit controller determines its mode of operation (heating, cooling or vent mode) depending on the de­mand from the zone controllers. The unit controller uti­lizes a voting system to determine the correct mode of operation. Each zone controller determines (based on its heating and cooling setpoints) whether or not to use the air being supplied by the HVAC unit. For example, one of the zones is calling for cooling when the tem­perature in the duct is above the zones cooling setpoint. This zone will move to its minimum cooling position to prevent warm air being introduced into the space. With the zoning system the zone dampers are generally pressure dependent. Pressure independent operation is available but is not very common. Reheat and/or fan powered terminal units can be used but aren’t commonly part of the typical zoning system.
Conclusion
In many cases VAV systems go over budget because of the increased cost of a VAV, HVAC unit and the expen­sive VAV controls associated with the system. Many times the system can be redesigned to a zoning system using Auto-Zone controls with a significant cost sav­ings and equal or better performance and comfort than the VAV system would provide. Be sure to follow the instructions in this design guide for your zoning sys­tem.
Auto-Zone Systems 9
Zoning Design Guide
Basics of Designing A Zoning System
This is a summary of the key items you need to con­sider for the design and layout of a successful zoning system.
It is important that you study the design guide for a more in depth understanding of proper system design.
By following the design guide and these tips you can eliminate many unnecessary headaches that occur when the basic rules of zoning are not followed. Always con­tact WattMaster Controls if you have any questions.
Always group zones with similar load profiles on the same HVAC unit.
Never mix perimeter zones with interior zones on the same HVAC unit.
Each zoned HVAC unit should have a minimum of 3 to 4 zones. Any less and you should consult the factory.
If you have electric reheat coils mounted on VAV boxes, it is recommended that a fan powered box be used. Consult the factory for further details concerning this application.
If there is an economizer on the HVAC unit, it is highly recommended, though not required, that the Zone Manager control the economizer.
Pressure Independent Zones must always use round dampers or VAV boxes, never rectangular - no exceptions!
Never attempt to use a zone control system on a true VAV application. See “ Zoning Systems Versus True VAV Systems” on page 9 of this guide for detailed information.
Each zoned HVAC unit can support a maximum of 16 voting zones. Any zones and you should contact the factory.
When using auxiliary heat for individual zones, perimeter heat such as baseboard is always preferred and more economical to operate than a fan terminal unit with reheat.
more
Bypass dampers should always be sized for 60%-70% of the HVAC units rated CFM.
Even though the Auto-Zone system has certain features to help protect your equipment, safety devices associated with the HVAC unit.
never override or disconnect any
10 Auto-Zone Systems
Design Considerations
Zoning Design Guide
Load Diversity
A zoning system is designed to improve tenant comfort by dynamically rebalancing the air distribution when used with a typical constant volume rooftop heating/ cooling unit. If zones with extremely different load con­ditions are serviced by a single rooftop unit, the result will be poor control and excessive wear due to cycling of the equipment.
It is especially important to avoid mixing interior zones (which require cooling all year) with exterior zones (which may require constant heat during winter months). If you must mix zones under these conditions, consider using either VAV boxes with heat or separate external heat on perimeter zones. Auto-Zone Zoning systems offer a variety of methods to control additional zone heat to help you avoid problems.
Group similar loads on an individual unit and use more than one zoned unit if required. Any special loads can be handled by using separate constant volume units.
The Auto-Zone Plus system offers the designer consid­erable flexibility by allowing both multiple-zoned units and single-zone units to be connected within a single simple system.
Cooling - Partial Load Conditions
The engineer must be aware of several potential prob­lems when applying a zoning system for cold weather operation.
on utilities and provide comfort under conditions when it is not possible to operate the mechanical cooling sys­tem.
2.) Low Supply Air Temperatures. Under lightly loaded conditions much of the supply air may be by­passed back into the return air side of the HVAC unit. This bypassing will result in the lowering of the supply air temperature, which may result in the supply air tem­perature reaching the low temperature safety limit. If the supply air low temperature safety limit is exceeded, the control system will “cut off” the mechanical cool­ing to protect it from damage. Excessive cycling of the mechanical system will result if this condition persists. Comfort may also suffer if the system cannot run long enough to satisfy cooling demands.
A number of things can be done to reduce this problem. Some of these things depend upon the type of installa­tion.
A void oversizing the unit. Do your all load calculations carefully. Since the zoning system directs the heating or cooling to the zones which require it, you may find that you can use a smaller unit in many cases. Oversizing is the number one cause of excessive low supply air temperature cycling.
Use an economizer. Although this is not a cure-all, it greatly improves operation during cool weather when cooling loads are minimal. Using an economizer also improves ventilation and lowers operating costs.
1.) Low Ambient T emperature Lockout. During very cold weather it is common for mechanical systems to have “low temperature lockouts” which protect equip­ment from damage if operated under these conditions. Auto-Zone also provides user programmed lockouts for protection purposes, although mechanical safeties should always be used as the final stage of protection.
If the rooftop unit services interior zones with thermal loads, which require cooling when outside temperatures are below the safe operating limits for your equipment, you should seriously consider installing an economizer on your rooftop unit. The Auto-Zone control system is designed to take advantage of an economizer if it is installed. The use of an economizer will save money
Increase cooling minimum airflow. Increase your cool­ing minimum airflow or damper position settings to al­low more air during cooling operation. Be careful to avoid minimum settings that are so high they may cause over cooling of the spaces.
Bypass the air into the ceiling plenum. If you have a system without ducted return, bypass the air into the ceiling plenum instead of into the return air intake. Be careful if you use this method since you may get “dump­ing” of cold air from your return air grilles. This method works best with plenum returns. Do not use this method
with ducted returns.
Auto-Zone Systems 11
Zoning Design Guide
Design Considerations
Increase your static pressure setpoint. This will help reduce the amount of air being bypassed. Be aware of increased noise levels and the cost of operation if you use excessive static pressures. This will not work if you are using pressure independent zone controllers, since they will maintain a constant flow of air to the zones regardless of duct static pressure. This technique will likely cause over cooling of the spaces due to increased
airflow at minimum positions.
Warning:
If the fan system has the capability of producing static pressures which could damage ductwork you must pro­vide a manual reset, high pressure limit switch (Dwyer 1900-5-MR or equal) to cut off the fan system in the event of high duct static. Do not use your Auto-Zone Zoning system as a safety device!
Heating - Partial Load Conditions
Heating difficulties are less common than cooling dif­ficulties. They are similar in nature, however, and the cures are generally the same. Again, a number of things can be done to reduce the effects of this problem.
Increase heating minimum airflow. Increase your heat­ing minimum airflow or damper position settings to allow more air during heating operation. Be careful to avoid minimum settings that are so high they may cause over heating of the spaces.
method works best with plenum returns. Do not use
this method with ducted returns
Use auxiliary heat . Use an auxiliary heat source in either your VAV boxes or use baseboard heaters.
Auto-Zone has a number of auxiliary heat control op­tions which provide solutions to most problems. Refer to the Auxiliary Heat Control Options topic near the end of this section.
Override Conditions
After-hours overrides can produce aggravated partial load conditions in both the heating and cooling modes. A single zone being overridden for after-hours use most commonly causes the problem. This causes the rooftop equipment to operate for only one zone. The Auto-Zone system offers an improved solution to this common problem by allowing a single override to trigger a group of zones via a “global” override. This allows the sys­tem to operate with sufficient load to reduce cycling caused by light load conditions.
Building Pressurization
If you are using an economizer, building pressurization must be addressed. Failure to properly handle building pressurization may result in doors remaining open when the economizer is operating. Pressurization problems can render economizer operation useless. The follow­ing suggestions will help to avoid potential problems.
Increase the static pressure. Set the static pressure setpoint to be as high as practical. Increasing static pres­sure does not help if you are using pressure indepen­dent control operation.
A void oversizing the unit. Do your all load calculations carefully. Since the zoning system directs the heating or cooling to the zones which require it, you may find that you can use a smaller unit in many cases.
Bypass the air into the ceiling plenum. If you have a system without ducted return, bypass the air into the ceiling plenum instead of into the return air intake. This
Use powered exhaust. A power exhaust fan(s) must be used when the system utilizes ducted returns. The re­turn duct pressure drop will cause most barometric re­lief dampers to function poorly or not at all. Auto-Zone has the ability to control a powered exhaust whenever the economizer is operating.
Use a separate building pressure control. Use a con­trol that operates a relief fan or dampers to relieve build­ing pressure
12 Auto-Zone Systems
Zoning Design Procedures
Zoning Design Guide
General
There are six basic steps to designing an Auto-Zone Zoning system:
1.) Determining the number and location of zones
2.) Sizing the central unit
3.) Duct Considerations
4.) Room air motion and diffuser selection
5.) Bypass damper sizing
6.) Sizing the zone dampers
Step #1 - Determining The Number And Location Of Zones
A single air handler unit can have no more than sixteen zones and no fewer than 3 zones. If the number of zones exceeds sixteen then more than one Zone Manager will be required.
on the wall, ceiling and floor material and location within the building (e.g. top or middle floor), a typical floor of a building usually has several distinct tempera­ture or control zones that are affected uniquely by the outdoor load. These zones are depicted in Figure 1-2. Depending on the size of the building and partition lay­out, some of these zones may overlap or be insignifi­cant from a zoning standpoint. For example, Zone 11 could be multiple conference or computer rooms where additional zoning would be required, or it could be as small as a corridor where no zoning is required. Simi­larly, zones 7 and 8 could have no external windows and no partitions between them and could be consid­ered a single zone. Some zones could be divided into multiple offices with full partitions between them, thus requiring separate Zone Controllers because of differ­ent internal loads, but the same external load.
Generally, the greater the number of individual Zone Controllers, the greater the comfort. The designer will have to look at the specific building, balancing the costs of multiple zones with the added comfort possible with multiple zones, to match the owner’s requirements.
The primary precaution to be taken in applying the Auto­Zone Zoning System is to select the zoning so that no zone will be at maximum (design) heating (or cooling) load when any other zone requires the opposite tem­perature air to satisfy its load. For example, depending

Figure 1-2: Zones Affected by the Outdoor Load

It is important to recognize that there are purely inter­nal zones, such as Zone 11 in Figure 1-2, which may contain separate offices/conference/computer rooms. These internal zones could easily have high cooling re­quirements while external zones (1,2,3, etc.) could be at or near design heating load. This is a misapplication
of the Auto-Zone, zoning (or any heating/cooling change-over) system. The interior zones with cooling
only loads should be served by a separate single zone rooftop HVAC unit (that could be zoned between mul­tiple rooms with a similar load profile). Supplemental heat could be added to the perimeter zones and con­trolled with the auxiliary heat control board from the Zone Controller. System performance will generally be compromised and frequent change-over from the heat­ing to the cooling mode will occur during the heating season if purely internal zones are combined on the same air-conditioning unit serving perimeter zones. The ex­posure to the sun has a large affect on the loading of the building. With the building zoned as shown below, for the best control, zones 6, 7, 8, 9 and 10 should be put on one HVAC unit, and zones 1, 2, 3, 4 and 5 on an­other HV AC unit. Zone 1 1 should be on a separate single zone constant volume HVAC unit.
Auto-Zone Systems 13
Zoning Design Guide
Zoning Design Procedures
Here is another example of the building’s exposure af­fecting the zoning. Figure 1-3 below
shows a building layout with 7 zones, it has 3 zones with an eastern ex­posure, 4 zones with a western exposure and two each north and south exposures. This building can be con­trolled from a single, constant volume air handler. All of the zones have exterior surfaces and there are no totally internal zones, so they will have similar load requirements.

  
Figure 1-4: Zones With North And South Exposures.
Figure 1-3: Zone Layout With External Zones Only.
Figure 1-4 shows a building with 7 zones, 4 of the zones
have a north exposure and the other 3 have a south ex­posure. Since there is a big difference in the affect on the building between north and south exposures, this situation should use two zoned HVAC units.
Figure 1-5 shows a combination manufacturing facility and office area. The space temperature in the individual zones numbered 1 through 7, would all be controlled by a single HVAC unit. A single constant volume HVAC unit would be used for each of the zones 8 through 12.




Figure 1-5: Zoning And Constant Volume Units
14 Auto-Zone Systems
Zoning Design Guide
Step #2 - Sizing the Central Unit
Because the zones are controlled with variable air vol­ume, it is unlikely that all zones will be at design load at the same time. The zoning allows for the diversity of loads to be taken into account and will often provide better comfort with a smaller HVAC unit.
In sizing the system, the individual zone loads should be calculated using any dependable load estimating pro­gram. Because of diversity, the central unit should be selected for the instantaneous peak load, not the sum of the peak loads, as would be done with a constant vol­ume single zone system. Consider the following when sizing the central unit.
Size the peak cooling load based on the
month day hour of the greatest total building system load
Heating should be sized for the lowest design
temperature with an additional margin for morning “pickup”. This margin is generally recommended to be 20 to 25 percent of base design.
Step #3 - Duct Design Considerations
The Auto-Zone system uses a typical low pressure duct design. T o reduce noise problems duct pressures should not exceed 1 inch W.C.
Primary trunk ducts should not be “undersized.” This is especially true for “pressure dependent” systems. Pressure dependent refers to the typical Auto-Zone, Zone Controller without the airflow sensor. W ith larger trunk ducts, it is easier to assure relatively constant pres­sure to each zone. Runs should be as short as possible, and the trunk duct system kept as symmetrical as pos­sible to facilitate system balancing. Wherever possible, run the trunk ducts above corridors and locate the zone dampers above corridors to reduce the noise in the space and facilitate service of the units. Trunk ducts should be sized for no more than 0.1 inch W.C. drop per 100 feet., and a maximum duct velocity of 2000 FPM.
Note For pressure independent terminal units
with velocity sensors and conventional “VAV” boxes properly selected for “quiet” operation, this 2000 FPM rule can be exceeded by up to 50 percent. The designer, however, should be very experienced in VAV system design before considering modification of this general rule.
T ypical VAV systems with pressure independent termi­nals use the static regain method for sizing ducts. The typical Auto-Zone Zoning system is a low-pressure, pressure dependent system that utilizes conventional unitary air-conditioning units. These systems should use the equal-friction method of sizing the ducts, and use the maximum loss of 0.1 inch per 100 feet as described above.
Step #4 - Air Motion/Diffuser Selection
Air motion is a consideration for occupant comfort. The selection of diffusers for an Auto-Zone Zoning system requires more care than a constant volume system due to varying flow of air into the zones. Slot diffusers are recommended due to their superior performance at low airflows. Because the zone airflow is variable volume, lower cost round or rectangular diffusers that were sat­isfactory for constant volume may prove unsatisfactory with an Auto-Zone Zoning system. These diffusers may result in “dumping” of the cold air at low flows in the cooling mode, and insufficient room air motion at low air flows in the heating mode. Although high air mo­tion in the heating mode can be undesirable, a slot dif­fuser with a high induction ratio generally helps to re­duce room air “stratification” when the heating comes from a ceiling diffuser . Linear slot diffusers should be properly selected for the airflow and “throw” suited to the specific installation or zone.
Additional factors to consider in diffuser selection is sound level and throw at design flow. Generally, mul­tiple diffusers will result in lower sound levels in the space, but this must be balanced with the additional hardware and installation costs. It is commonly recom-
Auto-Zone Systems 15
Zoning Design Guide
Zoning Design Procedures
mended that slot diffusers be located near the perim­eter or outside wall with the airflow directed into the room. Consult your diffuser supplier or catalog for proper diffuser sizing and location.
Series fan boxes may be used instead of zone dampers where higher induction rates are desirable. If the heat loss on perimeter walls is high, such as large areas of glass, the use of Series Fan Boxes may be indicated to maintain higher induction rates to offset “downdrafts.” If the heat loss is greater than 275 BTUH/LINEAR FOOT, you should use high quality slot diffusers next to the outer wall with the airflow directed inward to counteract downdrafts during heating. Serious downdraft problems occur when heat losses exceed 400 BTUH/linear foot and both high induction diffusers and series fan boxes are recommended.
Step #5 - Bypass Damper Sizing
The function of the bypass damper is to allow a con­stant volume air handling unit to be used with variable volume zone dampers. The bypass damper modulates on a signal from a duct static pressure sensor to “by­pass” air from the supply duct back into the return air duct. If the duct static pressure exceeds the adjustable
setpoint, then the damper opens to bypass more air, and if the static pressure drops below the setpoint, it closes to bypass less air. Using a load calculation program, the bypass damper should be sized to give you the maximum CFM of air to be bypassed, typically 60 to 70 percent of the HVAC units rated capacity.
T o size the damper, select a damper from the table based on calculated bypass CFM and a maximum velocity between 1750-2250 FPM. When determining the by­pass duct size, be sure to take into account any transi­tion fittings and associated pressure drops. (See Tables 1-1 & 1-2: Damper Sizing Charts)
Whenever possible, use a single bypass damper and round duct for the bypass. If space limitations or total airflow requires it, multiple bypass dampers can be con­trolled in parallel or a rectangular damper may be used. For proper control of the Bypass Damper, the static pres­sure sensor location is very important. Refer to Fig- ures 1-8 Thru 1-10 for proper sensor installation loca­tion information and guidelines.
Figure 1-6: Round Bypass Damper
Figure 1-7: Rectangular Bypass Damper & Kit
16 Auto-Zone Systems
Fan
RA Sensor
SA Sensor
Return Air Duct
Supply Air Duct
SP Pickup
Bypass Damper
SP Sensor
Fan
Zoning Design Guide
SA Sensor
Bypass Damper
SP Pickup
Supply Air Duct
RA Sensor
Return Air Duct
SP Sensor
3D Min.2DMin.
Figure 1-8: Preferred Sensor Location
If the trunk ducts are properly sized for minimum pres­sure drop, the location of the static pickup probe is not particularly critical. It should ideally be located at right angles to the airflow in a straight section of the supply duct approximately 2/3 the distance of the total length of the supply duct. Also the probe should be located not less than 3 duct diameters downstream and 2 duct diameters upstream of any elbow or takeoff. See Fig-
ure 1-8.
Fan
RA Sensor
Return Air Duct
Supply Air Duct
Tubing To Be Equal Length And Size
SP Pickups
Bypass Damper
SA Sensor
SP Sensor
Figure 1-10: Least Desirable Sensor Location If the supply duct comes directly from the unit and im-
mediately splits in opposite directions, the pressure pickup should be located ahead of the split, or as close to it as possible, even if the bypass damper(s) are lo­cated downstream of the split.
Step #6 - Sizing the Zone Damper
Use a load program to determine the peak load for each zone. These calculations will be used in selecting the appropriate zone damper sizes.
Using the maximum acceptable velocity for a branch duct (typically 1000-1500 FPM for minimal noise), find the smallest damper that will deliver the required CFM as determined by the load program.
Locate the branch velocity used in the duct design pro­gram on the left hand column of the damper sizing chart (T able 1-1). Move across the chart and find the damper which will provide the acceptable CFM to meet your specific zone requirements.
Note Compare the damper size selected against
Figure 1-9: Acceptable Sensor Location
Since the “ideal” location is often difficult to find in an installation, a location in the main trunk where the tip is not in a “negative pressure area” (e.g. just downstream of the inside curve of an elbow) or an area where the tube opening is directly impacted by the velocity of the supply air. See Figure 1-9.
One additional damper may be slaved together for large zones. See zone wiring diagram for details. This should be reserved for situations when it is not practical to use a single large damper . Round zone dampers can be speci­fied to be either pressure dependent or independent.
the duct size to determine if the next size up or down will provide acceptable performance without requiring a transi­tion fitting.
Auto-Zone Systems 17
Zoning Design Guide
Zoning Design Procedures
Pressure Dependent Dampers
With pressure dependent (PD) dampers, the minimum and maximum airflow is set based on damper position. During the final commissioning of the system, each zone is typically balanced with a flow hood and the min/max position is fixed either mechanically or the preferred method, in the controller software. Since this min/max setting is based only on position, as the static pressure fluctuates it will cause the actual airflow at the zone damper to increase or decrease. Therefore the name, pressure dependent since the airflow is dependent on the static pressure. Pressure dependent dampers are available in round or rectangular configurations. See Figure 1-1 1 for a diagram of a typical pressure depen­dent zone damper.
dent operation. Pressure independent operation is avail­able for round zone dampers only. Pressure indepen­dent rectangular dampers are not available. See Figure 1-12 for a diagram of a typical pressure independent zone damper.
When pressure independent dampers are used they must be field calibrated so the CFM of airflow for the mini­mum and maximum airflow setpoints will be correct. This should be done by the field technician during the commissioning portion of the system installation. The K-factor is the amount of airflow in CFM that the spe­cific damper will produce with 1” W .C. duct static pres­sure on the damper flow sensor. This K-factor is used by the controller software to maintain the correct mini­mum or maximum airflow setpoint regardless of the static pressure at the flow sensor. The K-factor and the minimum and maximum damper CFMs can be entered at the Zone Manager on Basic systems, or using the System Manager on Auto-Zone Plus systems. K-fac­tors can also be entered using a personal computer with the ZoneView computer front end software installed. The K-factors for each damper size are listed in Table 1-1: Round Air Damper Selection. Once the correct K­factors and minimum and maximum damper CFM setpoints are entered, the damper will modulate to try to maintain these CFM airflows during damper opera­tion. If zone dampers or fan terminal units manufac­tured by others are used, the correct K-factors must be obtained from the equipment manufacturer.
Figure 1-11: Pressure Dependent Damper
Pressure Independent Dampers
When using pressure independent (PI) dampers this minimum and maximum is set based on actual CFM of airflow through the damper. Airflow is measured using a pickup tube mounted in the zone damper and an elec­tronic air flow sensor. Using this method you always know the actual airflow through each zone damper in­stead of just the damper percentage open. The mini­mum and maximum settings are based on this actual airflow reading. As the static pressure fluctuates, the flow sensor reads the variation and automatically repo­sitions the damper to maintain the minimum or maxi­mum flow setpoints. Since the minimum or maximum airflow is maintained independently of the static pres­sure available in the duct it is called pressure indepen-
Figure 1-12: Pressure Independent Damper
18 Auto-Zone Systems
Zoning Design Guide
Round Damper Blade Assembly
1/2" Foil Faced Insulation
AIRF
FLOW
LO IR A
W
Bypass & Slave Dampers Zone Dampers
Damper Round Duct Size
CFM @ 1” Velocity Pressure
Air Flow Probe “K” Factor- For Pressure
Independent Applications Only
(Area Ft
2
)
Round Damper Blade Assembly
Zone Controller
1/2" Foil Faced Insulation
Actuator
Control Enclosure (Cover Removed)
Bypass & Slave Interface
Table 1-1: Round Damper Selection Data
6
(0.188)
474 950 1417 2120 2908 3700
8
(0.338)
10
(0.532)
L
F IR A
W
12
(0.769)
W
A
O
I R F
L
O
Actuator
Control Enclosure (Cover Removed)
14
(1.050)
16
(1.375)
Velocity Through Zone Damper
FPM
750 - Zone
141
(0.03)
1000 - Zone
188
(0.05)
1250 - Zone
235
(0.07)
1500 - Zone
282
(0.09)
1750 – Bypass Only
329
(0.12)
2000 – Bypass Only
376
(0.15)
2250 – Bypass Only
423
(0.18)
WattMaster reserves the right to change specifications without notice
Rectangular Dampers
Auto-Zone rectangular dampers are high quality alu­minum construction with opposed/air foil designed blades for superior control and have both blade and jamb seals for tight shut off. The dampers are installed using a mounting flange. The purpose for the flange mount­ing is to allow as much unrestricted free space within the duct as possible.
Many companies utilize slide-in type dampers which
Airflow Through Zone Damper - CFM
inches W.C . With Air Damper Full Open)
(P
S
254
(0.02)
338
(0.03)
423
(0.04)
507
(0.06)
592
(0.08)
676
(0.10)
761
(0.13)
399
(0.01)
532
(0.02)
665
(0.03)
798
(0.04)
931
(0.06)
1064
(0.07)
1197
(0.09)
577
(0.02)
769
(0.03)
961
(0.04)
1154
(0.05)
1346
(0.06)
1538
(0.07)
1730
(0.09)
788
(0.01)
1050
(0.02)
1313
(0.03)
1575
0.04) 1838
(0.05)
2100
(0.07)
2363
(0.08)
1031
(0.01)
1375
(0.01)
1718
(0.02)
2062
(0.03)
2405
(0.04)
2749
(0.05)
3094
(0.06)
can cause air flow problems. These slide-in dampers require that the damper frame be inside the duct. Imag­ine an 8 x 10 rectangular duct using a slide in damper with a frame thickness of 1”. The frame alone would reduce the opening to 6 x 8.
Another possible problem encountered with rectangu­lar dampers is the blade width. Many damper manufac­turers supply dampers with 6” or 8” dampers blades. This can become a major problem, for example, if the
Auto-Zone Systems 19
Zoning Design Guide
Zoning Design Procedures
damper has a height of 10. In this case the damper would utilize an 8 blade and a 2 blade stop or dam would be installed across the base of the damper. Tak­ing into consideration the blade stop and the frame, a 10 x 10 damper would have a reduced opening of 6 x 8 inside the duct. Many contractors have experienced low air flow problems on projects only to discover this hid­den problem of the dampers actually creating the re­striction. Auto-Zone utilizes a variety of blade widths in order to accommodate the size of the damper instead of the damper trying to accommodate the size of the blade.
Table 1-2: Rectangular Damper Selection Data
Rectangular Dampers
Damper
Height
B
Damper
Width
A
8 410
10 510
12 560
14 660
16 750
18 770
20 850
22 930
24 950
26 990
28 1070
30 1020
32 1090
34 1150
36 1060
8 10 12 14 16 18 20 22 24 26 28 30 32 34 36
Airflow Data with Full Open Damper – CFM @ 1000 FPM Velocity
For airflow CFM at other velocities use these multipliers: 750 FPM = 0.75, 1250 FPM = 1.25, 1500 FPM = 1.5, 2000 = 2.0, 2250 = 2.25
530
640
740
850
(0.16)
(0.10)
(0.07)
(0.05)
(0.04)
590
690
800
910
(0.10)
(0.07)
(0.05)
(0.03)
(0.03)
650
730
850
970
(0.07)
(0.05)
(0.03)
(0.02)
(0.02)
770
880
1030
1180
(0.05)
(0.03)
(0.02)
(0.02)
(0.01)
890
1030
1200
1370
(0.04)
(0.03)
(0.02)
(0.01)
(0.01)
980
1180
1380
1580
(0.03)
(0.03)
(0.01)
(0.01)
(0.01)
1090
1330
1550
1770
(0.03)
(0.02)
(0.01)
(0.01)
(0.01)
1210
1480
1730
1980
(0.02)
(0.01)
(0.01)
(0.01)
(0.01)
1290
1630
1900
2170
(0.02)
(0.01)
(0.01)
(0.02)
(0.01)
(0.01)
(0.01)
(0.01)
(0.01)
1390
(0.01)
1500
(0.01)
1550
(0.01)
1660
(0.01)
1770
(0.01)
1790
(0.01)
(0.01)
1780
2080
(0.01)
(0.01)
1930
2250
(0.01)
2080
2430
(0.01)
2230
2600
(-)
2380
2780
(-)
2520
2670
(-)
WattMaster reserves the right to change specifications without notice
(-)
2380
(-)
2570
(-)
(-)
2780
(-)
(-)
2970
(-)
(-)
3180
(-)
(-)
3090
(-)
(-)
(PS - inches W.C. @ 1000 FPM Velocity)
970
(0.03)
1030
(0.02)
1090
(0.01)
1330
(0.01)
1540
(0.01)
1780
(0.01)
1990
(0.01)
2230
2440
2680
2890
3130
3340
3580
3510
1080
(0.03)
1150
(0.02)
1210
(0.01)
1480
(0.01)
1710
(0.01)
1980
(0.01)
2210
2480
(-)
2710
(-)
2980
(-)
3210
(-)
3480
(-)
3710
(-)
3980
(-)
3930
(-)
1190
(0.02)
1260
(0.01)
1330
(0.01)
1630
(0.01)
1880
(0.01)
2180
2430
(-)
2730
(-)
2980
(-)
3280
(-)
3530
(-)
3830
(-)
4080
(-)
4370
(-)
4350
(-)
1300
(0.02)
1380
(0.01)
1460
(0.01)
1760
(0.01)
2060
(-)
2350
(-)
(-)
(-)
(-)
(-)
(-)
(-)
(-)
(-)
(-)
(-)
2650
(-)
2950
(-)
3250
(-)
3550
(-)
3850
(-)
4150
(-)
4450
(-)
4750
(-)
5040
(-)
1410
(0.02)
1500
(0.01)
1580
(0.01)
1910
(0.01)
2230
2550
2870
3200
3520
3850
4170
4500
4820
1520
(0.01)
1610
(0.01)
1700
(0.01)
2060
2400
(-)
2750
(-)
3090
(-)
3450
(-)
3790
(-)
4150
(-)
4500
(-)
4850
(-)
(-)
NA NA NA NA NA NA
NA NA NA NA NA NA
1630
(0.02)
1730
(0.01)
1820
(0.01)
2210
(-)
2570
(-)
2950
(-)
3310
(-)
3700
(-)
4060
(-)
4450
(-)
4820
(-)
(-)
NA NA NA NA NA
1740
(0.01)
1840
(0.01)
1940
2360
(-)
2740
(-)
3150
(-)
3530
(-)
3950
(-)
4330
(-)
4750
(-)
(-)
NA NA NA NA
1850
(0.01)
2000
(0.01)
2060
(-)
(-)
(-)
(-)
(-)
(-)
(-)
(-)
NA NA NA
(-)
2510
(-)
2910
(-)
3350
(-)
3750
(-)
4200
(-)
4600
(-)
NA NA
1970
(0.01)
2080
(0.01)
2190
(-)
2640
(-)
3090
(-)
3540
(-)
3990
(-)
4440
(-)
4880
(-)
20 Auto-Zone Systems
Zoning Design Guide
Auxiliary Heat Control Options
The Auto-Zone Zoning system offers the user a variety of methods to deal with zone heating requirements. In order to control zone heat, an optional Relay Expan­sion Board is required. When deciding how to handle zone heating requirements the user should consider the following:
Does the rooftop unit have heat?
Are you using fan-powered boxes with reheat?
Is auxiliary heat such as baseboard or radiant
ceiling panels used?
If the zone has some type of heat, the user must con­sider how the heat is to be used. Typical questions that should be asked:
Q: Should the zone heat be used as a first stage where
it will become active before a heating demand is created at the rooftop unit?
A: This mode is useful if you expect to have both
heating and cooling demands at the same time. The zone will use its own heat and allow the rooftop unit to continue to provide cooling for other zones. This mode is also useful if the roof top unit does not have any heating capabilities.
Q: Is the zone heat only to be used as a second stage,
where it will be activated only if the roof top unit cannot maintain the space temperature, such as during very cold weather?
A: In this mode of operation the rooftop will examine
the heating and cooling demands and try to satisfy all of the zones by switching between heating and cooling as required. The zone heat will only be activated if the zone temperature falls below a selected limit.
Relay Expansion Board Outputs
The following describes the operation of each of the relays on the optional relay expansion board. The user can choose the appropriate relays for any given appli­cation.
Relay #1 - Parallel Fan
If the Zone is in cooling or vent mode, the parallel fan can activate anytime the zone temperature drops 0.5° F below the heating setpoint. It deactivates when the tem­perature rises above the heating setpoint.
Relay #2 - Box Heat
If the zone is in cooling or vent mode then the box heat can activate anytime the zone temperature drops 1.5° F below the heating setpoint. It deactivates when the tem­perature rises to within 1.0° F of the heating setpoint. Box heat is not allowed to activate in the heating mode when there is hot air being supplied by the air handling unit. This output was intended to allow zone reheat while the Zone Manager is satisfying cooling demands in other zones.
Relay #3 - Aux. Heat
In the occupied mode, the aux heat can activate any­time the zone temperature is 0.5° F below the aux heat setpoint. It deactivates when the temperature rises 0.5° F above the aux heat setpoint. In the unoccupied mode, the aux heat uses the unoccupied heating setpoint with the same deadband values mentioned above. This pre­vents the zone from maintaining the same aux heat setpoint at night that it does during the daytime. The Parallel Fan and Box Heat are prevented from coming on until the aux heat is energized.
This output was intended to allow zone heating to aug­ment the normal heating mode and also to allow a zone an attempt to satisfy its own heating needs before cre­ating a heating demand at the Zone Manager.
Q: Should the zone heat be locked out if the rooftop
unit is supplying warm air?
A: Many times it is desirable to use the rooftop
heating whenever possible and only use zone heat when the rooftop unit is in cooling. This mode of operation will lockout zone heat if the rooftop is delivering heated air.
Relay #4 - Series Fan
The series fan runs anytime the main fan is running. This includes occupied and unoccupied modes. The fan can only start running when the zone damper is closed, so it determines that the damper is closed before start­ing the fan.
Auto-Zone Systems 21
Zoning Design Guide
System Installation
Mounting Of Controllers
All Auto-Zone Round Dampers or Rectangular Damper Kits have the required controllers, actuators etc. fac­tory mounted in an indoor rated control enclosure. If you wish to use another manufacturers dampers for zon­ing control you must purchase Zone or Bypass Pack­ages from WattMaster. These are furnished without a mounting enclosure. Most local codes require these components be mounted in an enclosure. If yours does not require this it is still strongly recommended that you do mount them in an enclosure. Components that are not in an enclosure are in danger of being damaged, and are susceptible to dirt and moisture contamination. You may furnish your own enclosure or one is avail­able from WattMaster. The part number for the WattMaster enclosure is EE000075-01. This is an in­door rated enclosure. If the zone mounting location is susceptible to water damage, watertight enclosures can be purchased at any local electrical supply. Mounting location for the controllers should not violate any lo­cal, state or national codes.
device. Possible problems you may encounter using common transformers to power multiple devices are:
If polarity is not maintained between devices,
shorting of the transformer will occur resulting in damage to the electronics.
When using one transformer to power multiple
devices it is possible to lose most or all of your system if the transformer fails.
It is important when powering multiple devices
from one transformer that total VA load and wiring voltage drops be taken into account for proper sizing of the transformer and wire. (See Table 3 on page 23)
It is therefore recommended that in most installations individual transformers be installed for each device. This will greatly reduce the possibility of errors and possible damage to the system.
System Wiring
Wiring requirements for Auto-Zone systems can be bro­ken down into four main categories:
1.) Power Wiring
2.) Communications Wiring
3.) Controller Wiring
4.) Sensor Wiring
Each category should be thoroughly understood and implemented in order to have a trouble free installa­tion.
Power Wiring
All Auto-Zone devices are powered by 24 VAC. It is possible to power the system using one or more com­mon transformers or individual transformers for each
Power wiring should always be done in accordance with any local, state, or national codes.
It is also important to note that THE HVAC UNITS
FACTORY TRANSFORMER SHOULD NEVER BE USED TO POWER Auto-Zone devices! Normally
transformers on typical HVAC units are sized to only handle the load of the units factory installed controls. A separate transformer must be used.
Communication Loops
The Auto-Zone system utilizes two different commu­nications loops. The Basic system uses a 9600 Baud RS-485 communications loop (Local Loop) only. The Plus system uses two different communications loops. It has a 9600 Baud RS-485 communications loop (Lo­cal Loop) like the Basic system but also has an RS-485 19200 baud communication loop (Network Loop) that connects the Zone Managers together and connects the CommLink II communications interface.
22 Auto-Zone Systems
Zoning Design Guide
W attMaster requires that all communication wire be 18 gauge minimum, two wire shielded cable, Belden #82760 or equivalent. W attMaster offers AZWR series communications cable for this purpose. The 18 gauge color coded and labeled wire is available for the local loop and the network loop communications wiring. The local loop wire is supplied in 1000 ft. spools and is la­beled Local Loop with a green candy stripe. The network loop wire is supplied in 500 ft. spools and is labeled Network Loop with a red candy stripe.
Local Loop Wire
Figure 1-13: WattMaster Communications Wire
The loop is best connected in a daisy chain configura­tion, meaning the loop is connected from one control­ler to another. It is not necessary to sequentially ad­dress the zone controllers in relation to their location on the loop.
Even though the daisy chain configuration is preferred, the star configuration can also be used. If required, a combination of the two can also be used. Remember, the best communications loop wiring is the one which utilizes the minimum number of ends while using the shortest wiring path.
Communication Wiring terminals on most Auto-Zone controllers are marked “T”, “R” and SHLD (Note: instead of SHLD the CommLink is marked “G” and the Basic Zone Manager is marked SH). All wiring should be connected T to T , R to R and SHLD to SHLD throughout the entire loop system. Communication wire
Network Loop Wire
should be color coded to facilitate error free wiring. The communication loops will not work if any of the wires are reversed or otherwise landed incorrectly . Com­munications loops can be run up to a maximum of ap­proximately 4000 ft. in total length. If your system ex­ceeds this length, please consult the WattMaster fac­tory for more information regarding extended commu­nication loop lengths and solutions.
Caution: Unless the communications loop
is installed in conduit, be careful to position the cable away from high noise devices like fluorescent lights, transformers, VFDs, etc. Conduit is not required for com­munications loop wiring unless required by local codes.
Tip: Incorrect wiring of the communications
loop is the most common mistake made during installation. Before beginning installation, write down the wire color used on each terminal connection and consistently maintain that color code. It is recommended that a continuous wire run be made between devices. Anytime a splice is made in the cable you increase your chance of problems. If a splice must be made, should be soldered and wrapped or if soldering is not possible use butt splice crimp connectors and wrap tightly with electrical tape.
Caution: Make sure when you are inserting
Never use wire nuts! Cable
wires into the terminal blocks that strands of wire do not stick out and touch the adjacent terminals. If adjacent wires touch each other or another terminal, shorting and subsequent damage to the circuit board could result
Auto-Zone Systems 23
Zoning Design Guide
COMM
LINK
II
COMM
LINK
II
System Installation
Computer
(Optional)
C
O M
M LINK
II
L O
C
O
O
M
P
M
O D
P
E M
WCLI
AT
T M
A S
T E R
O
N T R
O
S,N C
CommLink II
(Optional)
S
y c
h r
o
n o
u s
D
a
t a
L i n
k
SIG
DET
RDY
SND
REC
PWR
CO
NTROLS
Remote Link
(Optional)
RS485 Loop
24VAC
RS485 Loop
HVAC Unit
Zone Manager
UTO-ZONE
A
AUTOZONE
WEDJANUARY11 2001
OCCUPIED
Zone Controllers Occupy Addresses 1 through 16.
Zone
Controller #1
RAM
R
R
8K
32K
34
18
FLOW
CX4
CX3
CX8
U4
U3
U 8
RN1 1
M
V
B31920P
74H
S6264L-70P
4.00F AZ
9936
C
ZO
573N
S
D5
N
C
E
094
C
R 27
CX9
U9
C
C
LM
13
9
C 66
RAM
EPROM
C8
2
C 14
80C55
R22
2
D5
A
V
D
R
P.U.
J
EF
C
R32
10
X
R23
1
P
6W
T'STA
ILIPS
R
-5-1
R24
2
U11
T
M
8
/3
H
52 5
0S
R
=1
P
C
1
0C
94
R
1
50
9
8
9
2
1
S
0
IP
06
IL
FD
CB
C
H P
P
50
D
15
C
E
X
W
R25
U
5
D
D7
5
O
ADDRE
G
SS
ADD
CX10
9
1
U
3C
6
2
R
4
C
75176
8
6
4
O
S
M
C
U
C
8
W
X
M
10
3
1
6
16 32
LD3
P
C
TOKEN
C
O
5
4
W
R
NET
10
E
R
R26
R
1
R14
0
3
V 1
250
D4
LD
LD
R
F1
2
1
21
R
C
9
6
562
Y S
R
101
E
REC
SCAN
R
R
R
V
fTimesNew
.2
12
1
10
1
L1
fTimesNew
Roman|b0|i0|
Roman|b0|i0|c0|p18;
c0|p18;OMRON
G5L-114P-PS 24VDC CONTACT:
MDL
Q
VR1
UL/CSA5A250VAC
D
K
2
1
1
D3
T
C7
fTimesNew
7824
7824C
R
24VAC
fTimesNew
15
Roman|b0|i0|
9936
Roman|b0|i0|c0|p18;
M
64A
c0|p18;OMRON
G5L-114P-PS
MC340
24VDC CONTACT:
Q
U
R16
D
UL/CSA5A250VAC
3
7
R17
2
K2
GND
R5 R6 R7
P J1
P J2
V2
CX1
U 1
TC U 32K
2V
16L8
R1 R2 R3
CX2
Q 1
B
7 4H 3 19
U
C
C
2
1
20 2 59
PS C 2
R4
S IO N
TO R
E XP A N
AC T U A
Controller #16
D5
5 62 R E V . 2
24VAC 24VAC
Zone
RAM
R
R
8K
32K
3
1
FLOW
4
8
CX4
CX3
CX1
CX8
U4
U3
U 8
U
RN1
1
TC
1
M
V
B
74
U
S
4.00F
31
AZ
32K
62
H
9 93
92
C
64
ZO
57
6
0P
L-7
2V
3N
S
N
C
0P
E
094
C
R 27
16L8
CX9
U9
R1
C
C
LM
1
9
R2
3
C 66
RAM
EPROM
C
R3
2
8 C 1
80C55
R22
4
CX2
2
D5
AD
VR
Q
P.U.
1
J
E
C1
F
R32
X
0
R23
B
7
1
P
4H 3 19
6W
U
C
C
2
1
20
T'STA
2
ILIPS
R
-5-1
59
R24
2
U
T
PS
M
8
/3
H
52
1
C
5
0S
1
R
=1
2
P
C
1
0C
94
R
1
50
9
8
9
2
1
S
0
IP
06
IL
FD
CB
C
H P
P
50
D
1
R4
5
C
E
X
W
R25
R5
U
5
D
D7
5
O
ADDRE
R6
G
SS
ADD
R7
CX10
P
9
1
U
3C
J1
S
E
6
2
R
IO
XP
4
C
7
8
6
N
4
51
O
A
SW
N
M
C
U
C
76
8
X
M
10
3
1
6
16
32
LD3
P
C
TOKEN
C
O
5
4
W
R
P
NET
10
E
J2
R
R26
R
TO
AC
1
R
0
3
1
V
R
T
4
1
250
U
D4
A
LD
LD
R
F1
2
1
2 1
R
C
9
6 Y S 10
REC
SCAN
R
R
R
fTimesNew
1
12
1
10
1
L
fTimesNew
Roman|b0|i0|
1
Roman|b0|i0|c0|p18;
c0|p18;OMRON
G5L-114P-PS 24VDC CONTACT:
MDL
Q
VR1
UL/CSA5A250VAC
D
K
2
1
1
D3
T
C7
fTimesNew
7824
7824C
R
24VAC
fTimesNew
15
Roman|b0|i0|
9936
Roman|b0|i0|c0|p18;
M
64A
c0|p18;OMRON
G5L-114P-PS
MC340
24VDC CONTACT:
Q
U
R16
D
UL/CSA5A250VAC
3
7
R17
2
K2
GND
V2
Figure 1-14: Auto-Zone Basic System Communication Loop Wiring
Zone Controllers Occupy Addresses 1 through 16. CV Controllers And Other Add On Devices, Occupy Addresses 18 trough 30
Computer
(Optional)
RS485 Network Loop
24VAC
HVAC Unit #1
Zone Manager
19200 Baud
9600 Baud
C
O M
M
L
I N K
I I
L O
C
O
O
M
P
M
O D
P
E M
WCLI
AT T
M A S
T E R
O N
T R O
S,N
C
CommLink II
SychronousDataLink
SIG
DET
RDY
SND
REC
PWR
CON
T
ROLS
Remote Link
(Optional)
Network Loop To Other Zone Managers
24VAC
RS485 Local Loop #2
RS485 Local Loop #1
HVAC Unit #2 Zone Manager
The Loop Does Not Have To Follow The Board Address Sequence
Zone
Controller #1
RAM
R34
R18
8K
32K
FLOW
CX4
CX3
CX8
U4
U3
U 8
RN1
1
M
V
B
74H
S
4.00F
31920PS
A
6264L-70P 9936
ZZ
C 573N
O
D5
N
C
E
094
C
R 2 7
CX9
U9
C
C
LM
13
9
C 6
RAM
62
EPROM
C
8 C 14
80C55
R22
2
D5
A
V
D
R
P.U.
J
EF
C
R32
10
X1
S
R23
P
6W
-1
T'STA
ILIP
R
R24
28
U
T
2-5
M S
1
1/3 55
1
R
C
40
PH
C
0=
19
R
1
80
99
20
65
1
S
B
D
IP IL
F
C
C
00
H P
P
5
D
15
C
E
X
W
R25
U
5
D
D7
5
O
ADDRE
G
SS
ADD
CX10
P
93C
1
U
J1
6
2
R
46
C
75176
8
4
O
S
M
C
U
C
8
W
X6
M
10
3
1
16
32
LD3
P
C
TOKEN
C
O
5
4
W
R
P
NET
100
E
J2
R
R26
R
13 R 14
V 1
250
D4
L
L
D
D
R
F1
2
1
21
R
C
9
6
562
YS
R
101
EV
REC
SCAN
R
R
R
fTimesNew
.2
12
1
10
1
L1
fTimesNew
Roman|b0|i0|
Roman|b0|i0|c0|p18;
c0|p18;OMRON
G5L-114P-PS 24VDC CONTACT:
MDL
Q
VR1
UL/CSA5A250VAC
D
K
2
1
1
D3
T
C7
fTimesNew
7824
7824C
R
24VAC
fTimesNew
15
Roman|b0|i0|
9936
Roman|b0|i0|c0|p18;
M
64A
c0|p18;OMRON
G5L-114P-PS
MC340
24VDC CONTACT:
Q
U
R16
D
UL/CSA5A250VAC
3
7
R17
2
K 2
GND
V2
24VAC
Zone
Controller #1
RAM
R
R
8K
32K
34
18
FLOW
CX4
CX3
CX8
U4
U3
U 8
RN1
1
M
V
B31920P
74HC
S
4.00F AZZ
6264L-70PC 9936
573N
O
S
D5
N
C
E
094
R 27
CX9
U9
C
C
LM
13
9
C 66
RAM
EPROM
C
2
8
C14
80C55
R22
2
D5
AD
VR
P.U.
J
E
C
F
R32
10
X
R23
1
P
6W
T'STA
ILIPS
R
-5-1
R24
2
U
T
M
8
/3
H
52
1
5
0S
1
R
=1
P
C11
19
0C
94
R
50
9
2
S
B8
0
IP
06
IL
FD
C
C
H P
P
50
D
15
C
E
X5
W
R25
U
D
D7
5
O
ADDRE
G
SS
ADD
CX10
P
93C
1
U
J1
6
2
R8
46
C
75176
4
O
S
M
C
U
C
8
W
X
M
10
3
1
6
16 32
LD3
P
C
TOKEN
C
O
5
4
W
R
PJ2
NET
100
ER
R
R26
13 R 14
V1
250
D4
LD
LD
R
F1
2
1
21
R
C
9
6
562
Y
S101 R E
REC
SCAN
R12
R11
R10
V
fTimesNew
.2
L1
fTimesNew
Roman|b0|i0|
Roman|b0|i0|c0|p18;
c0|p18;OMRON
G5L-114P-PS 24VDC CONTACT:
MDL
Q
VR1
UL/CSA5A250VAC
D
K1
2
1
D3
T
C7
fTimesNew
7824
7824C
R
24VAC
fTimesNew
15
Roman|b0|i0|
9936
Roman|b0|i0|c0|p18;
M
64A
c0|p18;OMRON
G5L-114P-PS
MC340
24VDC CONTACT:
Q
U7
D
R16
UL/CSA5A250VAC
3
R17
2
K 2
GND
V2
24VAC
Zone
Controller #16
RAM
R
R
8K
32K
3
1
FLOW
8
4
CX4
CX1
U 1
TC U 32K
2V
16L8
R1 R2 R3
CX2
Q 1
B31920P
74H
U
C
C
2
1
259
S C 2
R4
R5 R6 R7
SIO
EX P N A N
TOR
AC TU A
CX3
CX1
CX8
U4
U3
U 8
U
RN1
1
TC
1
M
V
B
7
U
S
4H
4.00F
31
A
32K
62 9
ZZ
93
92
C
64
57
6
0P
L-7
2V
O
3N
S
D5
N
C
0P
E
094
C
R 2 7
16L8
CX9
U9
R1
C
C
LM
1
9
R2
3
C 6
RAM
62
EPROM
C
R3
8
C1
80C55
R22
4
CX2
2
D5
AD
VR
Q
P.U.
1
J
E
C
F
R32
10
X
S
R23
B
7
1
P
4H 3 19
6W
U
C
C
2
1
-1
20
T'STA
2
ILIP
R
59
R24
28
U
T
2-5
P
M S
11
S
C
1/3 55
R
2
C
40
PH
C
0=
19
R
1
80
99
20
65
1
S
B
D
IP IL
F
C
C
00
H P
P
5
D
15
R4
C
E
X
W
R25
R5
U
5
D
D7
5
O
ADDRE
R6
G
SS
ADD
R7
CX10
P
9
1
U
3C
J1
S
6
2
R
IO
4
C
7
8
6
N
4
51
O
S
M
C
U
C
76
8
W
X
M
10
3
1
6
16 32
LD3
P
C
TOKEN
C
O
5
4
W
R
P
NET
1
E
J
R
R26
00
2
R
TO
1
R
3
1
V
R
4
1
250
D4
L
L
D
D
R
F1
2
1
21
R
C
9
6
5
Y
62
S
R
10
E
REC
SCAN
R
R
R
V
fTimesNew
1
.2
12
1
10 1
L
fTimesNew
Roman|b0|i0|
1
Roman|b0|i0|c0|p18;
c0|p18;OMRON
G5L-114P-PS 24VDC CONTACT:
MDL
Q
VR1
UL/CSA5A250VAC
D
K
2
1
1
D3
T
C7
fTimesNew
7824
7824C
R
24VAC
fTimesNew
15
Roman|b0|i0|
9936
Roman|b0|i0|c0|p18;
M
64A
c0|p18;OMRON
G5L-114P-PS
MC340
24VDC CONTACT:
Q
U
R16
D
UL/CSA5A250VAC
3
7
R17
2
K 2
GND
V2
24VAC
Zone
Controller #16
RAM
R
R
8K
32K
3
1
FLOW
4
8
CX4
CX1
U 1
TC U 32K
2V
16L8
R1 R2 R3
CX2
Q 1
B
74H
31920P
U2
C1
C 259
S C 2
R4
R5 R6 R7
S
E IO
XPAN N
TOR
A C TU A
CX3
CX1
CX8
U4
U3
U 8
U
RN1
1
TC
1
M
V
B
74
U
S
4.00F
31
AZZ
32K
62
H
99
92
C
64 36
57
0P
L-70
2V
O
3N
S
D5
N
C
P
E
094
C
R 27
16L8
CX9
U9
R1
C
C
LM
9
1
R2
3
C 66
RAM
EPROM
C
R3
2
8 C 1
80C55
R22
4
CX2
2
D5
A
V
Q
D
R
P.U.
1
J
E
C
F
R32
1
X
0
R23
B
7
1
P
4H
31
6W
U
C
9
C
2
1
20
T'STA
2
ILIPS
R
-5-1
59
R24
2
U
T
PS
M
8
/3
H
52
1
C
5
0S
1
R
=1
2
P
C
19
0C
94
R
1
50
9
2
1
S
B8
0
IP
06
IL
FD
C
C
H P
P
50
D
1
R4
5
C
E
X
W
R25
R5
U5
5
D
D7
O
ADDRE
R6
G
SS
ADD
R7
CX10
P
9
1
U
3C
J1
SIO
6
2
R
4
C
7
8
6
N
4
51
O
SW
M
C
U
C
76
8
X
M
1
3
1
6
0
16
32
LD3
P
C
TOKEN
C
O
5
4
W
R
P
NET
10
ER
J2
R
R26
TO
1
R
0
3
1
V
R
4
1
250
D4
LD
LD
R
F1
2
1
2 1
R
C
9
6
5
Y
62
S
R
10
E
REC
SCAN
R
R
R
V
fTimesNew
1
.
12
1
10
2
1
L
fTimesNew
Roman|b0|i0|
1
Roman|b0|i0|c0|p18;
c0|p18;OMRON
G5L-114P-PS 24VDC CONTACT:
MDL
Q
VR1
UL/CSA5A250VAC
D
K
2
1
1
D3
T
C7
fTimesNew
7824
7824C
R
24VAC
fTimesNew
15
Roman|b0|i0|
9936
Roman|b0|i0|c0|p18;
M
64A
c0|p18;OMRON
G5L-114P-PS
MC340
24VDC CONTACT:
Q
U
D
R16
UL/CSA5A250VAC
3
7
R17
2
K 2
GND
V2
24VAC
Constant Volume
(Addresses Start At 18)
COMM
T
SHLD
R
LD4
REC.
E XP A N
A C TU A
12V AIN
1
AIN
2
AIN
3
AIN
4
AIN
5 GND
GND
AOUT
PRESSURE
SENSOR
To Any Other
CV Controllers
Or Add On Devices
Constant Volume
(Addresses Start At 18)
COMM
T
SHLD
R
LD4
REC.
EX P A N
AC T U A
12V AIN
1 AIN
2 AIN
3 AIN
4 AIN
5 GND
GND
AOUT
PRESSURE
SENSOR
To Any Other
CV Controllers
Or Add On Devices
Controller
RAM
EPROM
485 COMM
ADDRESS ADD
G
DO
EW
0-5 VDC
YS101564
0-1
VDC
Controller
RAM
EPROM
485 COMM
ADDRESS ADD
DOG
EW
0-5 VDC
YS101564
0-1
VDC
32K 8K
COMM
TEST
24VAC
32K 8K
COMM
TEST
24VAC
RELAY
OUTPUT COM 1-3 OUT
1 OUT
2 OUT
3 OUT
OUT
4 OUT
5 COM 4-5
4-5
PWR
GND
24VAC
RELAY
OUTPUT COM 1-3 OUT
1 OUT
2 OUT
3 OUT
OUT
4 OUT
5 COM 4-5
4-5
PWR
GND
24VAC
Figure 1-15: Auto-Zone Plus System Communication Loop Wiring
24 Auto-Zone Systems
Zoning Design Guide
Controller Wiring
All controller wiring should be in accordance with all local, state, and national codes. It is recommended that all wire be a minimum of 18 AWG unless otherwise specified in the charts below. Controller connections and wire sizing is as follows:
Zone Manager
24 VAC Supply Voltage (25 VA)
(2) Conductors - Determine minimum wire size from Figure 1-16 on page 26.
Communications Loop
(2) Conductors 18 gauge minimum twisted pair with shield (WattMaster communication wire, Belden #82760 or equal)
Supply Air Temperature Sensor
(2) Conductors 24 gauge minimum
Return Air Temperature Sensor
(2) Conductors 24 gauge minimum
Outside Air Sensor
(2) Conductors 24 gauge minimum
Supply Static Pressure Sensor
(2) Conductors 24 gauge minimum
Bypass Damper
(4) Conductors 24 gauge minimum
HVAC Unit Control Wiring
(6) Conductors 24 gauge minimum R (Common), G (Fan), Y1 (Cool 1), Y2 (Cool 2), W1 (Heat 1), W2 (Heat 2)
For Auto-Zone Plus System With Optional Staging Expansion Board up to an additional (8) conductors Y3 through Y6, W3 Through W6
System Manager
24 VAC Supply Voltage (25 VA)
(2) Conductors - Determine minimum wire size from Figure 1-16 on page 26.
Communications Loop
(2) Conductors 18 gauge minimum twisted pair with shield (WattMaster communication wire, Belden #82760 or equal)
Zone Controller
24 VAC Supply Voltage (10 VA)
(2) Conductors - Determine minimum wire size from Figure 1-16 on page 26.
Communications Loop
(2) Conductors 18 gauge minimum twisted pair with shield (WattMaster communication wire, Belden #82760 or equal)
Room Sensor
(2) Conductors 24 gauge minimum
(3) Conductors if using optional slide
Sensor Wiring
Auto-Zone temperature sensors utilize a type III ther­mistor element that is one of the most commonly used sensors in the building controls industry. Sensor wire should be a minimum of 24 gauge however larger wire such as 18 gauge is commonly used.
Conventional thermostat cable is acceptable in most commercial and institutional installations. In some in­stallations which have the potential for high electrical noise, such as broadcast facilities (radio, TV , etc.), heavy industrial (machinery, welding equipment, etc.), and medical (x-ray, scanning, etc.), it is advisable to use shielded cable on sensors which are located in or close to these environments. The same cable used for the com­munication bus can be used in these situations.
Sensor requirements are:
Supply Air Sensor
(2) Conductors 24 gauge minimum
Return Sensor
(2) Conductors 24 gauge minimum
Outside Air Sensor
(2) Conductors 24 gauge minimum
Room Sensor
(2) Conductors 24 gauge minimum
(3) Conductors if using optional slide adjust
Auto-Zone Systems 25
Zoning Design Guide
System Installation
Some installers like to use one large 24VAC transformer to power several controllers. This is allowable as long as polarity is maintained to each controller on the transformer circuit.
recommends using a separate transformer for each controller in order to eliminate the potential for damaging controllers due to incorrect polarity.
Using separate transformers also allows redundancy in case of a transformer failure. Instead of having 8 controllers inoperative because of a malfunctioning transformer you have only 1 controller off line. If the installer does decide to use a large transformer to supply power to several controllers, the following transformer and wire sizing information is presented to help the installer correctly supply 24VAC power to the controllers.
Following is a typical example to help the installer to correctly evaluate transformer and wiring designs.
Each Zone Controller with actuator requires 10 VA @ 24VAC power. In the examples below we have a total of 8 Zone Controllers.
8 Zone Controllers @ 10VA each................ 8 x 10VA = 80VA.
The above calculation determines that our transformer will need to be sized for a minimum of 80VA if we are to use one transformer to power all the controllers.
Next we must determine the maximum length of run allowable for the wire gauge we wish to use in the installation. Each wire gauge below has a voltage drop per foot value we use to calculate total voltage drop.
18ga wire.................................0.00054 = voltage drop per 1’ length of wire
16ga wire.................................0.00034 = voltage drop per 1’ length of wire
14ga wire.................................0.00021 = voltage drop per 1’ length of wire
For our example we will use 18 gauge wire. WattMaster recommends 18 gauge as a minimum wire size for all power wiring.
Next use the voltage drop per foot value for 18 gauge wire from the list above and multiply by the total VA load of the 8 controllers to be installed.
0.00054 (Voltage drop per foot for 18 gauge wire) x 80VA controller load = Volts/Ft.
WattMaster controllers will operate efficiently with a voltage drop no greater than 2 Volts. Divide the total allowable voltage drop of 2 Volts by the number you arrived at above and you have the maximum number of feet you can run the 18 gauge wire with an 80VA transformer with no more than a 2 Volt drop at the farthest controller from the transformer..
Parallel circuiting of the wiring instead of wiring all 8 controllers in series allows for longer wire runs to be used with the same size wire (as shown in our examples below). transformer size, multiple transformers, circuiting, etc., when laying out an installation. No matter what layout scheme is decided upon, it is mandatory that the farthest controller on the circuit is supplied with a minimum of 22 Volts.
It is often necessary for the installer to calculate and weigh the cost and installation advantages and disadvantages of wire size,
Warning:
If polarity is not maintained, severe damage to the controllers may result. WattMaster Controls
2 (Volts total allowable voltage drop)
0.0432 (Voltage drop per 1 ft. @ 80VA load)
=
0.0432
46.30 feet
24VAC Power - Transformer & Wire Sizing Considerations
ZONE
CONTROLLER
B
A
ZONE
CONTROLLER
120 / 24VAC
ZONE
CONTROLLER
ZONE
CONTROLLER
Distance A to B cannot exceed 46.30 Ft.
ZONE
CONTROLLER
ZONE
CONTROLLER
ZONE
CONTROLLER
ZONE
CONTROLLER
ZONE
CONTROLLER
BC
ZONE
CONTROLLER
ZONE
CONTROLLER
ZONE
CONTROLLER
Distance from A to B cannot exceed 92.60 Ft. Distance from A to C cannot exceed 92.60 Ft.
CONTROLLER
CONTROLLER
CONTROLLER
CONTROLLER
A
ZONE
ZONE
ZONE
ZONE
120 / 24VAC
Component Power Requirements
System Manager ........ ..............25VA GPC Controller.... .....................20VA
Zone Manager..........................25VA
Wetbulb Module .......................20VA
Zone Controller ........................10VA Lighting Panel Controller ..........25VA
CV Controller............................20VA
Zone Relay Expansion Board ...10VA
CV-C Controller................. .......20VA Staging Expansion Board .........20VA
Optimal Start Scheduler ...........25VA
Figure 1-16: Transformer And Wire Sizing Considerations
ZONE
CONTROLLER
ZONE
CONTROLLER
ZONE
CONTROLLER
BCDE
ZONE
CONTROLLER
ZONE
CONTROLLER
ZONE
CONTROLLER
A
120 / 24VAC
Distance from A to B cannot exceed 185.20 Ft. Distance from A to C cannot exceed 185.20 Ft. Distance from A to D cannot exceed 185.20 Ft. Distance from A to E cannot exceed 185.20 Ft.
JOB NAME
FILENAME
WIRSIZ1.CDR
DATE:
11/30/99
PAGE
1
DESCRIPTION:
Wire & Transformer Sizing
CONTROLS
DRAWN BY:
Auto-Zone
B. CREWS
ZONE
CONTROLLER
ZONE
CONTROLLER
26 Auto-Zone Systems
Application Notes:
Zoning Design Guide
Zoning 30 And 40 Ton Units
When using large HVAC units for zoning applications, several rules must be considered to prohibit potential problems.
Because of the large air flow capacities of the 30 and 40 ton units, great care must be taken in sizing zone and bypass dampers.
Use these guidelines to help keep you out of trouble.
Always use the Auto-Zone Plus system even if you only have one unit that you are zoning.
Generally you should use constant volume units in your zoning system design. If your units are to be equipped with variable frequency drives or inlet vanes, please consult WattMaster Controls for assistance.
The OE340-10-AGSTG relay expansion card is usually required for each Zone Manager controlling two or more stages of cooling.
Bypass dampers should be sized for 60 to 70% of the rated CFM of the unit. Because of the large air volumes involved, rectangular dampers should be used instead of round dampers. Consult the rectangular damper sizing guide (Table 1-2 on page 25), for CFM ratings.
Large units should always have a minimum of 6 zones due to the high air flow capacities.
To prevent excessive noise in the system, zone damper total minimum airflow settings should be equal to or preferably greater than 30% of the units rated CFM.
As an added precaution, we recommend a high duct static safety switch be installed (Dwyer Model 1900­5-MR or equal) to prevent over pressurization of the ductwork.
Auto-Zone Systems 27
Form: WM-AZA-ZDG-01B Printed in the USA October 2001 All rights reserved Copyright 2001
WattMaster Controls Inc. • 8500 NW River Park Drive Parkville MO 64152 Phone (816) 505-1100 E-mail: mail@wattmaster.com Fax (816) 505-1101
Loading...